72 50 35 45 81 Type Rated current In (A) Breaking capacity (kA) Recommended sections of the condmuocutonrtsin (g/mm 2 ) Packing/Box (pcs) Catalogue number Curve C Catalogue number Curve B C41N / 2A 2 4.5 1.0 12 / 240 41460 41460B C41N / 4A 4 4.5 1.0 12 / 240 41461 41461B C41N / 6A 6 4.5 1.0 12 / 240 41451 41451B C41N / 10A 10 4.5 1.5 12 / 240 41452 41452B C41N / 16A 16 4.5 2.5 12 / 240 41453 41453B C41N / 20A 20 4.5 2.5 12 / 240 41454 41454B C41N / 25A 25 4.5 4.0 12 / 240 41455 41455B C41N / 32A 32 4.5 6.0 12 / 240 41456 41456B C41N / 40A 40 4.5 10.0 12 / 240 41457 41457B C41N / 50A 50 4.5 10.0 12 / 240 41458 41458B C41N / 63A 63 4.5 16.0 12 / 240 41459 41459B 17 CIRCUIT BREAKERS Miniature circuit breakers (MCB) C40N 16 CIRCUIT BREAKERS Miniature circuit breakers C45, C60 TERMINAL NON-FLAMMABLE COVER JUMP KNUCKLE HANDLE LOCK KNACKLE MOVABLE CONTACT ARC CHAMBER STATIC CONTACT MAXIMUM CURRENT RELEASE AUXILIARY CONTACT (accessory) UNDER VOLTAGE RELEASE (accessory) SHUNT RELEASE (accessory) 1 2 3 4 5 6 7 8 9 10 11 12 Characteristics Circuit breakers are automatically-operated electrical switches, designed to protect elec- trical circuits from damage caused by overload or short circuit. They can also be used as devices for commutation and control of electrical circuits. They differ in the following characteristics: * Operating voltage: 230, 400V * Number of poles: 1, 2, 3, 4 * Breaking curve: - curve B – breaks between 3 and 5 In, used for low voltage short circuit currents (long circuits and generators) - curve C – breaks between 5 and 10 In, used for protection of main power supply cables and conventional consumers - curve D – breaks between 10 and 20 In, used for protection of industrial consumers with high initial current flow (electric motors) * Breaking capacity: 4.5, 6, 10kA 10 7 11 12 9 8 6 5 4 3 2 1 Functions: - protection of the electrical circuits from overload or short circuits of the outer circuit - it can be used as a device for commutation and control of electrical circuits - in combination with auxiliary devices it allows remote control, commutation or indication of the protected circuit - for mounting in housing and industrial buildings - for mounting at a distance from the transformer post from 150 to 850 m - allows protection of consumers generating short circuit currents up to 6000 A Technical data: * Rated voltage: 230/400V; 50/60Hz * Breaking capacity (cycle O-CO) in accordance with standard EN 60 898-1: 6000A * Rated breaking capacity Ics= 75% Icu * Isolating voltage:≥2000V * Electrical wear resistance (number of cycles): 4000 * Mechanical (number of cycles): 20000 * Class of current limiting:3 * IP code: IP>20 * Breaking curve: B curve – the overload and short-circuit protection is activated at 3-5 ln. Used for protection of big length cables and power generators. C – the maximum current release breaks between 5 and 10 In; used to protect main power supply cables and conven- tional consumers * Joining terminal: flat (tunnel) screw terminal with composition 1.5 coldly draw-plated plane Q235 – A * Plastic box – not keeping the burning material nylon PA66, UV rays wear resistance * Box permitivity strength: >18MV/m * Abnormal heating wear resistance and fire of the outer parts: 960°C / 3s * Maximum current release containing: - copper coil - composition: pure copper T2 type - resistance: from 0.6 to 180m - welding effort: <150 000 N/mm - bimetal plate – composition: 5J158 to TB180 depending on the current - thickness: 0.6mm (up to 40A) and 0.8mm (up to 63A) - magnetic core – composition: coldly draw-plated metal wire (1Gr18Ni9) - thickness: 1.15 to 2.24μm - drawing effort: from 200 to 400N/mm - contact head of the movable contact – composition: silver graphite CAg(5) - dimension 3x3x0.8 (up to 40A) and 4x4x0.8 (up to 63A) - static contact – composition: pure copper T2Y2 - composition of the contact head: silver graphite CAg(5) * Power supply (conducting) - power supply busbar 1P63, 3P63 - rigid conductors up to 25 mm - flexible conductors up to 16 mm * Tightening moment:1.33Nm Mounting: * vertical * DIN-rail * for mounting in housing or industrial environment without serious interference * ambient temperature: -5°C to + 40°C±2° C Documents corresponding to the product: Standard EN60898-1 EN 60947-2 С4xN constructive series number of poles (1;2;3;4) rated current breaking curve С C x
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
72
50
35
45
81
Type Rated current In (A)
Breaking capacity (kA)
Recommendedsections of the
condmuocutonrtsin (g/mm2)Packing/Box (pcs) Catalogue number
Circuit breakers are automatically-operated electrical switches, designed to protect elec-trical circuits from damage caused by overload or short circuit. They can also be used as devices for commutation and control of electrical circuits. They differ in the following characteristics:* Operating voltage: 230, 400V* Number of poles: 1, 2, 3, 4* Breaking curve:- curve B – breaks between 3 and 5 In, used for low voltage short circuit currents (long circuits and generators)- curve C – breaks between 5 and 10 In, used for protection of main power supply cables and conventional consumers- curve D – breaks between 10 and 20 In, used for protection of industrial consumers with high initial current flow (electric motors)* Breaking capacity: 4.5, 6, 10kA
10
7
11 12
9
8
6
54 3
21
Functions:- protection of the electrical circuits from overload or short circuits of the outer circuit- it can be used as a device for commutation and control of electrical circuits- in combination with auxiliary devices it allows remote control, commutation or indication of the protected circuit- for mounting in housing and industrial buildings- for mounting at a distance from the transformer post from 150 to 850 m- allows protection of consumers generating short circuit currents up to 6000 ATechnical data:* Rated voltage: 230/400V; 50/60Hz* Breaking capacity (cycle O-CO) in accordance with standard EN 60 898-1: 6000A* Rated breaking capacity Ics= 75% Icu* Isolating voltage:≥2000V* Electrical wear resistance (number of cycles): 4000* Mechanical (number of cycles): 20000* Class of current limiting:3* IP code: IP>20* Breaking curve:B curve – the overload and short-circuit protection is activated at 3-5 ln. Used for protection of big length cables and power generators.C – the maximum current release breaks between 5 and 10 In; used to protect main power supply cables and conven-tional consumers* Joining terminal: flat (tunnel) screw terminal with composition 1.5 coldly draw-plated plane Q235 – A* Plastic box – not keeping the burning material nylon PA66, UV rays wear resistance* Box permitivity strength: >18MV/m* Abnormal heating wear resistance and fire of the outer parts: 960°C / 3s* Maximum current release containing:- copper coil - composition: pure copper T2 type- resistance: from 0.6 to 180m- welding effort: <150 000 N/mm- bimetal plate – composition: 5J158 to TB180 depending on the current- thickness: 0.6mm (up to 40A) and 0.8mm (up to 63A)- magnetic core – composition: coldly draw-plated metal wire (1Gr18Ni9)- thickness: 1.15 to 2.24μm- drawing effort: from 200 to 400N/mm- contact head of the movable contact – composition: silver graphite CAg(5)- dimension 3x3x0.8 (up to 40A) and 4x4x0.8 (up to 63A)- static contact – composition: pure copper T2Y2- composition of the contact head: silver graphite CAg(5)* Power supply (conducting)- power supply busbar 1P63, 3P63- rigid conductors up to 25 mm- flexible conductors up to 16 mm* Tightening moment:1.33NmMounting:* vertical* DIN-rail* for mounting in housing or industrial environment without serious interference* ambient temperature: -5°C to + 40°C±2° C
Documents corresponding to the product:Standard EN60898-1EN 60947-2
С4xN constructive seriesnumber of poles (1;2;3;4)
rated currentbreaking curve С
C x
72
50
35
45
81
Type Rated current In (A)
Breaking capacity (kA)
Recommendedsections of the
condmuocutonrtsin (g/mm2)Packing/Box (pcs) Catalogue number
Functions:- protection of the electrical circuits from overload or short circuits of the outer circuit- it can be used as a device for commutation and control of electrical circuits- in combination with auxiliary devices it allows remote control, commutation or indication of the protected circuit- for mounting in industrial buildings with high contamination level of the electric system- for mounting at a distance from the transformer post from 150 to 850 m- allows protection of consumers generating short circuit currents up to 6000 ATechnical data:* Rated voltage: 230/400V; 50/60Hz* Breaking capacity (cycle O-CO) in accordance with standard EN 60 898-1: 6000A* Rated breaking capacity Ics= 75% Icu* Isolating voltage:≥2000V* Electrical wear resistance (number of cycles): 000* Mechanical (number of cycles): 0000* Class of current limiting:3* IP code: IP>20* Breaking curve:B – the maximum current release breaks between 3 and 5 In; used to protect long circuits and generatorsC – the maximum current release breaks between 5 and 10 In; used to protect main power supply cables andconventional consumers* Joining terminal: Combined screw clamp made of 1.5 cold extruded Q235-A material with additional coating* Plastic box – not keeping the burning material nylon PA66, UV rays wear resistanceStatus indicator* Box permitivity strength: >18MV/m* Abnormal heating wear resistance and fire of the outer parts: 960°C / 3sHeat resistance of internal non-electrical components: 850°С / 10 s* Maximum current release containing:- copper coil - composition: pure copper T2 type- resistance: from 0.6 to 180m- welding effort: <150 000 N/mm- bimetal plate – composition: 5J158 to TB180 depending on the current- thickness: 0.6mm (up to 40A) and 0.8mm (up to 63A)- magnetic core – composition: coldly draw-plated metal wire (1Gr18Ni9)- thickness: 1.15 to 2.24μm- drawing effort: from 200 to 400N/mm- contact head of the movable contact – composition: silver graphite CAg(5)- dimension 3x3x0.8 (up to 40A) and 4x4x0.8 (up to 63A)- static contact – composition: pure copper T2Y2- composition of the contact head: silver graphite CAg(5)* Power supply (conducting)- power supply busbar 1P63, 3P63- rigid conductors up to 25 mm- flexible conductors up to 16 mm* Tightening moment:1.33NmMounting:* vertical* DIN-rail* for mounting in housing or industrial environment without serious interference* ambient temperature: -5°C to + 40°C±2° C
Documents corresponding to the product:Standard EN60898-1
С6xN constructive seriesnumber of poles (1;2;3;4)
rated currentbreaking curve С
C x
Type Rated current In (A)
Breaking capacity (kA)
Recommendedsections of the
condmuocutonrtsin (g/mm2)Packing/Box (pcs) Catalogue number
Functions:- protection of the electrical circuits from overload or short circuits of the outer circuit- it can be used as a device for commutation and control of electrical circuits- in combination with auxiliary devices it allows remote control, commutation or indication of the protected circuitTechnical data:* Rated voltage: 230/400V; 50/60Hz* Breaking capacity (cycle O-CO) in accordance with standard EN 60 898-1: 10000A* Rated breaking capacity Ics= 75% Icu* Isolating volatage:≥2000V, 1 min at impulse wave 1.2/50μs* Electrical wear resistance (number of cycles):≥4000* Mechanical wear resistance (number of cycles):≥20000* Class of current limiting:3* IP code: IP>20* Breaking curve: C* Joining terminal: flat (tunnel) screw terminal with composition 1.5 coldly draw-plated plane Q235 – A* Plastic box – not keeping the burning material nylon PA66, UV rays wear resistance* Box permitivity strength: >18MV/m* Abnormal heating wear resistance and fire of the outer parts: 960°C / 3s* Power supply (conducting)- power supply busbar- rigid conductors up to 25- flexible conductors up to 35* Tightening moment:1.33NmMounting:* vertical* DIN-rail* possibility for labeling* for mounting in industrial environment* ambient temperature: -5°C to + 40°C±2° C
Documents corresponding to the product:Standard EN60898-1EN 60947-2
С100L constructive seriesnumber of poles (1;3)
rated currentbreaking curve С
C x
(C curve)
1000
5000
2000
1000
500
200
100
50
20
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.01
0.005
0.002
0.001
0.5 1 2 3 4 5 7 10 20 30 50 70 100 200 i/in
t(s)
Electromagneticrelease
Thermal release
(D )curve
1000
5000
2000
1000
500
200
100
50
20
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.01
0.005
0.002
0.001
0.5 1 2 3 4 5 7 10 20 30 50 70 100 200 i/in
t(s)
Thermal release
Electromagneticrelease
Type Number of poles
Rated current In (A)
Breaking capacity (kA) Packing/Box (pcs) Catalogue number
Curve CCatalogue number
Curve D
C100M 1P 80 10 9 / 180 41180 41180D
C100M 1P 100 10 9 / 180 41190 41190D
C100M 1P 125 10 9 / 180 41195 41190D
Type Number of poles
Rated current In (A)
Breaking capacity (kA) Packing/Box (pcs) Catalogue number
Curve CCatalogue number
Curve D
C100M 2P 80 10 6 / 120 41280 41281
C100M 2P 100 10 6 / 120 41290 41291
Type Number of poles
Rated current In (A)
Breaking capacity (kA) Packing/Box (pcs) Catalogue number
Curve CCatalogue number
Curve D
C100M 3P 80 10 4 / 60 41380 41381
C100M 3P 100 10 4 / 60 41390 41391
Type Number of poles
Rated current In (A)
Breaking capacity (kA) Packing/Box (pcs) Catalogue number
Functions:- protection of the electrical circuits from overload or short circuits of the outer circuit- it can be used as a device for commutation and control of electrical circuits- in combination with auxiliary devices it allows remote control, commutation or indication of the protected circuitTechnical data:* Rated voltage: 230/400V; 50/60Hz* Breaking capacity (cycle O-CO) in accordance with standard EN 60 898-1: 10000A* Rated breaking capacity Ics= 75% Icu* Isolating volatage:≥2000V* Electrical wear resistance (number of cycles):≥4000* Mechanical wear resistance (number of cycles):≥20000* Class of current limiting:3* IP code: IP>20* Breaking curve: C,D* Joining terminal: flat (tunnel) screw terminal with composition 1.5 coldly draw-plated plane Q235 – A* Plastic box – not keeping the burning material nylon PA66, UV rays wear resistance* Box permitivity strength: >18MV/m* Abnormal heating wear resistance and fire of the outer parts: 960°C / 3s* Maximum current release containing:- copper coil - composition: pure copper T2 type- resistance: from 148 to 230m- welding effort: <400 N/- bimetal plate – composition: TB180/0.5- thickness: 0.8mm- magnetic core – composition: coldly draw-plated metal wire (1Gr18Ni9)- thickness: 1.15 to 2.24μm- drawing effort: 20N/mm2
- contact head of the movable contact – composition: silver graphite CAg(5)- dimension 6x6x1- static contact – composition: pure copper T2Y2- composition of the contact head: silver graphite CAg(5)* Power supply (conducting)- power supply busbar- rigid conductors up to 50- flexible conductors up to 35* Tightening moment:1.33NmMounting:* vertical* DIN-rail* possibility for labeling* for mounting in industrial environment* ambient temperature: -5°C to + 40°C±2° C
Documents corresponding to the product:Standard EN60898-1EN 60947-2
С100M constructive seriesnumber of poles (1;2;3;4)
rated currentbreaking curve С, D
D x
78
45
18
36
72
65
49
5
Type Rated current In (A)
Breaking capacity (kA)
Recommendedsections of the
condmuocutonrtsin (g/mm2)Packing/Box (pcs) Catalogue number
Curve C
61DC / 1A 1 6 1.0 12 / 240 41164
61DC / 2A 2 6 1.0 12 / 240 41165
61DC / 4A 4 6 1.0 12 / 240 41166
61DC / 6A 6 6 1.0 12 / 240 41167
61DC / 10A 10 6 1.5 12 / 240 41168
61DC / 16A 16 6 2.5 12 / 240 41169
61DC / 20A 20 6 2.5 12 / 240 41170
61DC / 25A 25 6 4.0 12 / 240 41171
61DC / 32A 32 6 6.0 12 / 240 41172
61DC / 40A 40 6 10.0 12 / 240 41173
61DC / 50A 50 6 10.0 12 / 240 41174
61DC / 63A 63 6 16.0 12 / 240 41175
Type Rated current In (A)
Breaking capacity (kA)
Recommendedsections of the
condmuocutonrtsin (g/mm2)Packing/Box (pcs) Catalogue number
Curve C
62DC / 2A 2 6 1.0 6 / 120 41176
62DC / 4A 4 6 1.0 6 / 120 41177
62DC / 6A 6 6 1.0 6 / 120 41178
62DC / 10A 10 6 1.5 6 / 120 41179
62DC / 16A 16 6 2.5 6 / 120 41181
62DC / 20A 20 6 2.5 6 / 120 41182
62DC / 25A 25 6 4.0 6 / 120 41183
24 25
CIRCUIT BREAKERS CIRCUIT BREAKERSMiniature circuit breakers (MCB) C60DC series Miniature circuit breakers (MCB) C60DC series
Functions:- for lowering constant current voltaic arc and use of the breaker at constant current consumer protection- protection of the electrical circuits from overload or short circuit of the outer circuit at alternating current and constantcurrent power supply circuits- for commutation and control of electrical circuits- in combination with auxiliary alternating current devices for remote control, commutation or indication of theprotected circuit- for mounting in industrial buildings- for protection of consumers generating short circuit currents to 6000 A at alternating current power supplyTechnical data:* Rated voltage: 240V; AC/DC* Breaking capacity (cycle O -CO) in accordance with standard EN 60 898- 1: 6000A* Rated breaking capacity Ics=75% Icu* Insulating voltage: ≥2000V* Electrical wear resistance (number of cycles): ≥4000* Mechanical wear resistance (number of cycles): ≥20000* Class of current limiting: 3* IP code: IP>20* Breaking curve: C – the maximum current release breaks between 5 and 10 In; used to protect power supply cables and conventional consumers* Joining terminal: flat (tunnel) screw terminal with composition 1.5 coldly draw-plated plane Q235 – A* Plastic box – not keeping the burning material nylon PA66, UV rays wear resistance* Box permitivity strength: >18MV/m* Abnormal heating wear resistance and fire of the outer parts: 960°C / 3s* Maximum current release containing:- copper coil - composition: pure copper T2 type- resistance: from 0.6 to 180m- welding effort: <150 000 N/mm- bimetal plate – composition: 5J158 to TB180 according to the current- thickness: 0.6mm (up to 40A) and 0.8mm (up to 63A)- magnetic core – composition: coldly draw-plated metal wire (1Gr18Ni9)- thickness: 1.15 to 2.24μm- drawing effort: from 200 to 400N/mm- contact head of the movable contact – composition: silver graphite CAg(5)- dimension 3x3x0.8 (up to 40A) and 4x4x0.8 (up to 63A)- static contact – composition: pure copper T2Y2- composition of the contact head: silver graphite CAg(5)- metal magnetic plate for lowering the constant current arc* Conducting:- power supply busbar 1P63- rigid conductors up to 25 mm- flexible conductors up to 16 mm* Tightening moment: 1.33NmMounting* vertical* DIN-rail* for mounting in housing or industrial environment without serious current interference* Ambient temperature: -5°C to + 40°C±2° C
Documents corresponding to the product:Standard EN60898-1EN 60898-2
С60xDC constructive seriesnumber of poles (1;2)
rated currentbreaking curve С
C x
Type Rated current In (A)
Breaking capacity (kA)
Recommendedsections of the
condmuocutonrtsin (g/mm2)Packing/Box (pcs) Catalogue number
Curve C
DP1N / 6 6 4.5 1.0 12 / 240 41006
DP1N / 10 10 4.5 1.5 12 / 240 41010
DP1N / 16 16 4.5 2.5 12 / 240 41016
DP1N / 20 20 4.5 2.5 12 / 240 41020
DP1N / 25 25 4.5 4.0 12 / 240 41025
DP1N / 32 32 4.5 6.0 12 / 240 41032
Type Rated voltage Type breaker Packing/Box (pcs) Catalogue number
ELMARK MN 2 60 230V С60 12 / 240 41909
Type Rated voltage Type breaker Packing/Box (pcs) Catalogue number
ELMARK MX 60 230V С60 12 / 240 41902
Type Rated voltage Type breaker Packing/Box (pcs) Catalogue number
ELMARK OF 60 230V С60 12 / 240 41901
ELMARK SD100 230V C100M 12 / 240 41909
27
CIRCUIT BREAKERSAuxiliary devices for circuit breakers
Functions:- protection of the electrical circuits from overload or short circuit of the outer circuit- it can be used as a device for commutation and control of electrical circuits- it breaks simultaneously the lead and the neutral conductor as the heat protection is only at the lead conductorTechnical data:* Rated voltage: 230V; 50/60Hz* Breaking capacity (cycle O-CO) in accordance with standard EN 60 898-1: 4500 A* Rated breaking capacity Ics = 50% Icu* Insulating voltage: ≥2000V* IP code: IP>20* Breaking curve: C – the maximum current release breaks between 5 and 10 In; used to protect main power supplycables and conventional consumersConnecting:* Joining terminal: flat (tunnel) screw terminal* Power supply (conducting):- power supply busbar DP1N- flexible or rigid conductor* Mounting: on DIN-rail
Circuit breakers DP1N (1P+N) - SIGMA design
Combined voltage circuit-breaker МN2Functions:- when the voltage is reduced below 170V operation is initiated and the automatic switch is turned off- when the voltage is increased above 270V operation is initiated and the automatic switch is turned off- allows manual turning on of the switch after powering is restored- indication of the position of the deviceTechnical characteristics:* Rated voltage: 230/400V; 50/60Hz* Insulation voltage: ≥2000V* Protection ratio: IP>20Connection method:* Double connector: flat (tunnel) screw connector* Feeding (conducting):- flexible conductors up to 1.5mm2
* Tightening moment of the screw: 1.33NmMounting:* vertical, by means of two pins attached to the rivets of the circuit-breaker, while the operating mechanism is con-nected to the switching off mechanism of the circuit breaker after the sealing lid is demounted
Shunt release MX (independent release)Functions:- remote circuit breaker switching off at voltage feed- allows manual switching on of the breaker at voltage recovery- indication of the device’s locationTechnical data:* Rated voltage: 230V; 50/60Hz* Isolating voltage: ≥2000V* IP code: IP>20Connecting:* Joining terminal: flat (tunnel) screw terminal* Power supply (conducting):- flexible conductors up to 1.5mm2
* Tightening moment: 1.33Nm* The power supply of the release is accomplished at the outlet of the breakerMounting:* vertical, clamps with two pins to the breaker’s rivets and the executive mechanism is joined up to the switching mechanism of the breaker after dismounting the seal cover
Auxiliary contact OFFunctions:-at circuit breaker switching off it sends a signal to the control or signalization system-indication of the location of the auxiliary contact and the breakerTechnical data:* Rated voltage: 230V* Isolating voltage: ≥2000V* Ingress protecting rating: IP>20Connecting:* Joining terminal: flat (tunnel) screw terminal* Power supply (conducting): - flexible conductors up to 1.5mmMounting:* vertical, clamps with two pins to breaker’s rivets, and the executive mechanism is joined up to the switching mecha-nism of the breaker after dismounting the seal cover
Type designation:МN - constructive seriesnumber of poles - 1Documents correspondingto the product:Standard EN60898-1
Type designation:МX - constructive seriesnumber of poles - 1Documents correspondingto the product:Standard EN60898-1
Type designation:OF - constructive seriesnumber of poles - 1Documents correspondingto the product:Standard EN60898-1
CIRCUIT BREAKERSIsolating switches ISS2 125…800A series
28
CIRCUIT BREAKERSSwitch disconnectors ISS 63…100A series
Functions:- switching on/off heavy loaded electrical circuits- breaking of electrical circuits- can be used as a main breakerTechnical data:* Rated voltage: 230/400V; 50/60Hz* Joining terminal: flat (tunnel) screw terminal* Connecting: power supply busbar, rigid or flexible conductors* Tightening moment: 1.33Nm* Isolating voltage: ≥500V* Electrical wear resistance (number of cycles): ≥10000* Mechanical wear resistance (number of cycles): ≥20000* IP code: IP>20* Mounting: DIN-rail* Plastic material of UV rays* Ambient temperature: -20°C + 55°C
Documents correspondingto the product:Standard EN 60947-3 and IEC947-3
The series three- and four-pole load isolating switch ISS2 xxx are produced for mounting in main electrical boards for disconnection of the circuits, switching on of generators because of the fact they are not affected by the frequency variations. High mechanical strength and resistance to circulation. Simple and secure management. There is a possibility for the products to be produced with an window for visible disconnection.Functions:- switching on and off of electrical circuits under load- disconnection of electrical circuits- used as main circuit-breaker- resistant to high voltages, to short circuits in the protected circuit- it has no protective functionTechnical features:* Rated voltage: not higher than 660V; 50/60Hz* Double connector: screw connection* Connection: solid or flexible conductors* Insulation voltage: ≥1000V* Resistance to impulse voltage: 8000V* Electrical endurance (number of cycles): ≥5 000* Mechanical endurance (number of cycles): ≥10 000* Protection ratio: IP>20* Mounting method: to a surface by means of bolts* Plastic resistant to UV raysPlastic resistant to UV rays* Ambient temperature: -20°÷40ºС
Note: ISS2-xxx in – load circuit-breaker for mounting in the interior of a board ISS2 -xxx out – load circuit-breaker with an extended lever for mounting on the front panel of the board
Documents correspondingto the product:Standard EN 60947-1EN 60947-3 and IEC 60947-6