Top Banner

of 96

Noh Aspe Asse Ppt

Apr 14, 2018

Download

Documents

Adel Suker
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 7/30/2019 Noh Aspe Asse Ppt

    1/96

    Cleveland ASPE

    February 13, 2008

    ResidentialSprinkler &

    Preaction SystemDesign

  • 7/30/2019 Noh Aspe Asse Ppt

    2/96

    Residential Sprinklers

  • 7/30/2019 Noh Aspe Asse Ppt

    3/96

    Residential Sprinklers

    Large residential construction growth over the last decade

    Building Code Changes

    Efforts of Organizations

    Home Fire Sprinkler Coalition

    NFSA

    AFSA

    NFPA

    Education to Home Builders and Local Officials

    Minimum Discharge Density Changes by UL and NFPA

  • 7/30/2019 Noh Aspe Asse Ppt

    4/96

    Residential Sprinklers

    Residential, unique to standard or quick response sprinklers

    Control Mode Sprinkler

    ESFR (Early Suppression Fast Response)

    Residential???

  • 7/30/2019 Noh Aspe Asse Ppt

    5/96

    Residential Sprinklers

    Residential Sprinklers: Installed to provide an increased

    level of life safety for the occupant. Residential sprinklers

    are designed to prevent flashover, keeping the living space

    survivable for a minimum amount of time.

  • 7/30/2019 Noh Aspe Asse Ppt

    6/96

    Residential Sprinklers

    Residential sprinklers are tested to a separate UL standard.

    The testing procedure verifies the thermal sensitivity and

    water distribution characteristics.

    UL 1626, Residential Sprinklers for Fire Protection Service

    It is not a design document, It is a standard published andused by UL to evaluate the performance of a residential

    sprinkler.

    Plunge Test Room Test

  • 7/30/2019 Noh Aspe Asse Ppt

    7/96

    Residential Sprinklers

    The scope of UL 1626 is defined within the document as:

    These requirements cover residential sprinklers intended for

    installation on sprinkler systems for fire protection service.

    Requirements for the installation and use of residential

    sprinklers for the Installation of Sprinkler Systems, NFPA 13,

    and Installation of Sprinkler Systems in One- and Two-FamilyDwellings and Mobil Homes, NFPA 13D and Residential

    Occupancies up to and Including Four Stories in Height

    Sprinkler Systems, NFPA 13R.

  • 7/30/2019 Noh Aspe Asse Ppt

    8/96

    Sensitivity Oven Plunge Test

    STANDARD RESPONSE

    100 Sec. Plunge Test

    3 Min. 51 Sec. Room FireTest

    QUICK RESPONSE

    14 Sec. Plunge Test

    75 Sec. Room Fire Test

    RESIDENTIAL

    14 Sec. Plunge

    Requires a Special Room

    Fire Test

  • 7/30/2019 Noh Aspe Asse Ppt

    9/96

    Residential Sprinklers

    Residential Sprinklers are required to pass special fire tests.

    The objective of residential sprinklers is to provide safety to

    the occupant and allow safe egress in a fire.

    In a residential fire test, the temperature cannot exceed 600 F

    3 below the ceiling where the thermocouples are installed.

    The maximum temperature at 5-3 above the floor is 200 F.The temperature 5-3 above the floor shall not exceed 130 F

    for any continuous 2 minute period.

    The maximum ceiling material temperature behind the

    finished ceiling surface shall not exceed 500F.

  • 7/30/2019 Noh Aspe Asse Ppt

    10/96

    Residential Sprinklers

    A special room is used to test residential sprinklers that simulates

    a residential occupancy. (2) residential sprinklers are located in

    the room for their coverage area. For a pendent sprinkler, theseareas of coverage are 12x12, 14x14, 16x16, 18x18, and 20x

    20. For sidewall sprinklers, these areas of coverage are typically

    14x14, 16x16, 16x18, 16x20, 16x22, 18x18 and 20x20.

    The (2) sprinklers are installed at the coverage area that a listing

    is desired at. A third sprinkler is located near an open door. The

    sprinkler at the door is not connected to water filled piping. If the

    sprinkler at the door activates at any time during the test, the testis considered a failure.

  • 7/30/2019 Noh Aspe Asse Ppt

    11/96

    UL 1626 Residential Sprinkler Test

  • 7/30/2019 Noh Aspe Asse Ppt

    12/96

  • 7/30/2019 Noh Aspe Asse Ppt

    13/96

  • 7/30/2019 Noh Aspe Asse Ppt

    14/96

    Residential Sprinklers

    Residential sprinklers are required to meet minimum

    wall wetting characteristics. 28 is the maximum distance down

    from the ceiling on the wall that a residential pendent andsidewall sprinkler must wet the wall.

    Sidewall sprinklers must direct 5% of their discharge upon

    the wall on which they are installed.

    These wall wetting characteristics mean that a residential sprinkler

    must discharge or spray in a very flat pattern. Obstructions such

    as sloped ceilings, beams, ceiling fans, and lights can inhibit theperformance of residential sprinklers and must be avoided.

  • 7/30/2019 Noh Aspe Asse Ppt

    15/96

  • 7/30/2019 Noh Aspe Asse Ppt

    16/96

    Residential Sprinklers

    The minimum design criteria for residential sprinklers per UL

    And NFPA 13D and NFPA 13R is to provide a minimum

    .05 gpm per sq. ft. over the area of protection.

    NFPA 13 requires that the minimum design criteria for

    residential sprinklers or residential occupancies be a .10

    gpm per sq. ft.

    Each residential sprinkler must pass the special fire tests and

    wall wetting requirements before they are listed as residential

    sprinklers.

  • 7/30/2019 Noh Aspe Asse Ppt

    17/96

    NFPA 13D Occupancies

  • 7/30/2019 Noh Aspe Asse Ppt

    18/96

    NFPA 13D One and Two Family Dwellings and

    Manufactured Homes

    NFPA 13D is the design and installation standard for

    single and two family dwellings, or in other words a home

    that is a single structure.

    The sprinkler design for this type of occupancy is for (2)

    residential sprinklers to discharge at the minimum flow rate

    and pressure of its UL listing.

    Water supply capacity is generally an issue for these system

    designs, so it may be prudent to utilize more residential

    sprinklers in a system at smaller spacings to lower the watersupply requirement.

  • 7/30/2019 Noh Aspe Asse Ppt

    19/96

    NFPA 13 R Occupancies

  • 7/30/2019 Noh Aspe Asse Ppt

    20/96

    NFPA 13R Residential Occupancies up to and Including

    Four Stories in Height

    Generally these NFPA 13R occupancies

    are apartments, dormitories, hotels, motels

    The residential sprinkler design criteria for the residentialdwelling requires that (4) residential sprinklers are designed

    to operate at their listed flow rate and pressure for the area

    of coverage to be protected.

    Public areas such as corridors, require a design per NFPA

    13, meaning the water supply needs to adequate for a NFPA

    13 installation.

  • 7/30/2019 Noh Aspe Asse Ppt

    21/96

    NFPA 13 Residential Occupancies

  • 7/30/2019 Noh Aspe Asse Ppt

    22/96

    NFPA 13 Residential Occupancies that are not NFPA 13D

    Or NFPA 13R

    These occupancies are buildings that are greater than (5)

    stories, typical of high rise apartment buildings, large hotel

    resorts, etc.

    The design requirement per NFPA 13 is for a minimum .10

    gpm per sq ft or the residential sprinklers listing for the

    area, which ever is greater.

    Water supply requirements are higher for NFPA 13 residential

    occupancies because the water flow is providing protection

    to the structure as well as life safety.

  • 7/30/2019 Noh Aspe Asse Ppt

    23/96

    Residential Sprinklers

    Due to the minimum flow rate requirements for residential

    sprinklers there are many different K factors for residential

    sprinklers to address different coverage areas and differentcode requirements, (NFPA 13D and NFPA 13R versus NFPA

    13 residential occupancies)

    The K factors step up from smaller areas of coverage of NFPA13D, to moderate and large areas of coverage of NFPA 13R,

    to very large water demands of NFPA 13. These specific K

    Factors allow for the most efficient use of water and pressure.

  • 7/30/2019 Noh Aspe Asse Ppt

    24/96

    Preaction

    Systems

  • 7/30/2019 Noh Aspe Asse Ppt

    25/96

    Preaction Systems

    Are: Fixed fire

    protection systems with

    CLOSED sprinklers

    connected to pipingpressurized with air or

    nitrogen (generally for

    supervision) with a

    dependable water supply

    controlled by a normally

    closed Deluge Valve

    activated by a releasesystem

  • 7/30/2019 Noh Aspe Asse Ppt

    26/96

    Preaction Systems

    Are Recommended :

    For hazards where fast

    application of water infire conditions is

    important.

    (Non and Single

    Interlocked Pre-Action)

  • 7/30/2019 Noh Aspe Asse Ppt

    27/96

    Preaction Systems

    Are Recommended :

    To prevent water

    damage due tomechanical damage to

    system piping.

    (Single and Double

    Interlocked Pre-Action)

  • 7/30/2019 Noh Aspe Asse Ppt

    28/96

    Preaction Systems

    Are Recommended :

    Where water entering

    the system piping couldharm the system, such

    as a freezer.

    (Double Interlocked Pre-

    Action)

  • 7/30/2019 Noh Aspe Asse Ppt

    29/96

    PREACTION SYSTEMS

    The building block of a pre-action

    system is the deluge valve and trim.

    Additions to the deluge valve and trim

    will be a riser check valve, an airsupply, and closed head sprinkler

    piping.

  • 7/30/2019 Noh Aspe Asse Ppt

    30/96

    Deluge Systems

    Deluge valve with

    Conventional Trim

    (PORV)

  • 7/30/2019 Noh Aspe Asse Ppt

    31/96

    Deluge Systems

    Deluge valve with

    Conventional Trim

    (PORV)

  • 7/30/2019 Noh Aspe Asse Ppt

    32/96

    Preaction Systems

    Basic components of preactionsystems before release or interlock

    are addressed

    Preaction Components

    Deluge valve

    Valve trim

    Riser Check valveSystem piping

    Air supply

  • 7/30/2019 Noh Aspe Asse Ppt

    33/96

    Sprinkler Heads

    Allowed toBe Installed

    On Preaction Systems

  • 7/30/2019 Noh Aspe Asse Ppt

    34/96

    Dry Barrel Sprinkler

    Upright Sprinkler

    Horizontal SidewallSprinkler

  • 7/30/2019 Noh Aspe Asse Ppt

    35/96

    OR

  • 7/30/2019 Noh Aspe Asse Ppt

    36/96

    A pendent sprinkler installed on a return bend, where the sprinklerAnd the sprinkler line supplying it are in a heated area

    Ceiling

  • 7/30/2019 Noh Aspe Asse Ppt

    37/96

    Deluge Valve

    Deluge

  • 7/30/2019 Noh Aspe Asse Ppt

    38/96

    Priming chamber

    Discharge or

    outlet chamberInlet chamber

    Deluge

    Valves

  • 7/30/2019 Noh Aspe Asse Ppt

    39/96

    Deluge Valves

    Held Closed by water pressure in priming chamber

    Priming Chamber controlled by release system

    When release system operates, priming chamber relieved of

    Priming pressure, allowing deluge valve to open

    Deluge

  • 7/30/2019 Noh Aspe Asse Ppt

    40/96

    Deluge

    Valves Priming Deluge Valve Priming ChamberWith water

    Note: Priming Supply

    Provided upstream of

    Control valve

    Deluge Deluge valve primed closed with

  • 7/30/2019 Noh Aspe Asse Ppt

    41/96

    Deluge

    Valves

    g p

    Water supply control valve open

    Supply water pressure

    Deluge Release System Operates

  • 7/30/2019 Noh Aspe Asse Ppt

    42/96

    Deluge

    Systems

    y p

    Draining water from priming

    chamber

    Deluge Pressure in priming chamber is

  • 7/30/2019 Noh Aspe Asse Ppt

    43/96

    g

    Valves

    p g

    Reduced, allowing clapper to open

    Deluge

  • 7/30/2019 Noh Aspe Asse Ppt

    44/96

    g

    Valves

    Water flows into discharge

    Chamber, out to sprinkler

    System piping & discharge

    outlets

    DelugeDel ge al e remains open

  • 7/30/2019 Noh Aspe Asse Ppt

    45/96

    g

    ValvesDeluge valve remains open

    Until system is manually shut-down

  • 7/30/2019 Noh Aspe Asse Ppt

    46/96

    Model E Deluge Valve

    Model F Deluge Valve

    Model F Deluge Valve

    Model E deluge valves

    Available 1 , 2, 3,

    4, and 6

    Model F deluge valves

    Available 1 , 2, 2 ,3, 4, 6, 8 Vertical and Horizontal

  • 7/30/2019 Noh Aspe Asse Ppt

    47/96

    Halar Coating

    Corrosion Resistant Trim

    Brass or Stainless Steel

  • 7/30/2019 Noh Aspe Asse Ppt

    48/96

    Preaction

    Systems

    PREACTION SYSTEM TYPES

  • 7/30/2019 Noh Aspe Asse Ppt

    49/96

    PREACTION SYSTEM TYPES

    Interlock and Release

    Non-Interlocked Preaction

    -Electric or pneumatic releaseSingle Interlocked Preaction

    -Electric Release

    -Pneumatic Release

    Double Interlocked Preaction

    -Pneumatic/Pneumatic

    -Electric/Pneumatic

    -Electric/Electric

  • 7/30/2019 Noh Aspe Asse Ppt

    50/96

    SINGLE INTERLOCKED

    PREACTION

  • 7/30/2019 Noh Aspe Asse Ppt

    51/96

    Single Interlock Operation

    Activation of the Release System will cause theDeluge Valve to trip open.

    Water will enter the closed sprinkler piping.

    When (if) a sprinkler operates,Water will flow from the open sprinkler

    immediately.

    -Similar to a WET system!

  • 7/30/2019 Noh Aspe Asse Ppt

    52/96

    Single-Interlocked Pre-action Systems

    Air Supply Considerations

    Minimum Pressure: No minimum

    Maximum to Fill system: 30 minutes

    Water Delivery time to Inspectors Test: Notmeasured

    May not be required if less than 20 sprinklers on

    system

    Preaction Systems

  • 7/30/2019 Noh Aspe Asse Ppt

    53/96

    RELEASE SYSTEMS FOR

    SINGLE INTERLOCKED

    PREACTION

    y

    Electric or

    Pneumatic

  • 7/30/2019 Noh Aspe Asse Ppt

    54/96

    SINGLE INTERLOCKEDPREACTION

    PNEUMATIC RELEASE

    PNEUMATIC RELEASE

  • 7/30/2019 Noh Aspe Asse Ppt

    55/96

    PNEUMATIC RELEASE

    -Sometimes referred to as dry pilot lines

    -Resemble hydraulic release

    -Utilize same release devices as hydraulic release-Are filled with pressurized air or nitrogen

    -Important to keep release line free of moisture

    -Used in areas subject to freezing

    -Pneumatic actuator or pneumatic bypass held closed with air-Pneumatic actuator or pneumatic bypass is holding priming

    water in priming chamber of deluge valve

    Preaction

  • 7/30/2019 Noh Aspe Asse Ppt

    56/96

    Systems

    Single Interlocked

    Preaction

    Pneumatic Release

    = Direction of Air Flow

  • 7/30/2019 Noh Aspe Asse Ppt

    57/96

    SINGLE INTERLOCKEDPREACTION

    ELECTRIC RELEASE

    Preaction

    S t Single Interlocked

  • 7/30/2019 Noh Aspe Asse Ppt

    58/96

    Systems Single Interlocked

    Preaction ElectricRelease

    = Direction of

    Air flow

  • 7/30/2019 Noh Aspe Asse Ppt

    59/96

    DOUBLE INTERLOCKED

    PREACTION

    Double Interlock Operation

  • 7/30/2019 Noh Aspe Asse Ppt

    60/96

    The Release System must activate ..-(an alarm will sound)

    -AND,

    -Pressure in the sprinkler piping must be reduced-(due to a sprinkler opening in fire conditions)

    To trip open the Deluge Valve.

    In fire conditions,

    - After the release system operates and the sprinkler

    opens, water needs to travel from the Deluge Valve

    to the open sprinkler.There may be a time delay similar to a Dry System.

    Double-Interlocked Preaction Systems

  • 7/30/2019 Noh Aspe Asse Ppt

    61/96

    y

    Air Supply Considerations

    Minimum Pressure: 7 psi

    Maximum to Fill system: 30 minutes

    Water Delivery time to Inspectors Test:

    Systems greater than 750 gallons capacity- 1 min.Systems 500 to 750 gallons- 1 min. unless a QOD is

    installed

    Preaction Systems

  • 7/30/2019 Noh Aspe Asse Ppt

    62/96

    Electric,

    Pneumatic, or

    Both

    RELEASE SYSTEMS FOR

    DOUBLE INTERLOCKED

    PREACTION

  • 7/30/2019 Noh Aspe Asse Ppt

    63/96

    DOUBLE INTERLOCKEDPREACTION

    PNEUMATIC/PNEUMATIC

  • 7/30/2019 Noh Aspe Asse Ppt

    64/96

    = Direction of Air

    Flow

    Double Interlocked

    Preaction

    Pneumatic/PneumaticRelease

  • 7/30/2019 Noh Aspe Asse Ppt

    65/96

    DOUBLE INTERLOCKEDPREACTION

    ELECTRIC/PNEUMATIC

    Preaction

  • 7/30/2019 Noh Aspe Asse Ppt

    66/96

    Systems

    = Direction of Air Flow

    Double Interlocked Electric/Pneumatic

  • 7/30/2019 Noh Aspe Asse Ppt

    67/96

    DOUBLE INTERLOCKEDPREACTION

    ELECTRIC / ELECTRIC

    Preaction

    Systems

    Electric Release Device

    And air supervisory switch

    C d t l

  • 7/30/2019 Noh Aspe Asse Ppt

    68/96

    Systems Cross zoned at panel

    Double Interlocked Preaction - Electric/Electric Release

    = Direction of Air Flow

  • 7/30/2019 Noh Aspe Asse Ppt

    69/96

    Viking

    SureFire

    PreactionSystems

    SureFire

  • 7/30/2019 Noh Aspe Asse Ppt

    70/96

    Fail Safe Preaction SystemsFail safe pre-action systems are pre-action systems that

    will operate when there is a loss of AC and DC power.

    Some municipalities have fail-safe pre-action

    requirements. In general, pneumatic release pre-action

    systems are listed and approved fail-safe pre-action

    systems.

    You should check with the manufacturer if they have a

    listed or approved fail-safe electric release pre-action

    system option.

    SureFire Pre-action

    Systems

  • 7/30/2019 Noh Aspe Asse Ppt

    71/96

    Systems

    Are Recommended :

    Where operation of the

    fire protection system inthe absence of electric

    power or power outage

    is a concern.

    Viking SureFire

    Release Trim Module To pressurized

    system piping

  • 7/30/2019 Noh Aspe Asse Ppt

    72/96

    system piping

    Solenoid valves are described by their position

    when non-powered:

    1) Normally OpenWhen non-powered the solenoid valve is

    open

    2) Normally Closed

    When non-powered the solenoid valve isclosed

    Pneumatic Actuator

    Viking SureFire

    Release Trim Module

  • 7/30/2019 Noh Aspe Asse Ppt

    73/96

    ReleaseSystems

    24vdc Electric solenoid

    (normally open)

    24vdc Electric solenoid

    (normally closed)

  • 7/30/2019 Noh Aspe Asse Ppt

    74/96

    TotalPac2 &

    TrimPac

  • 7/30/2019 Noh Aspe Asse Ppt

    75/96

    Pneumatic Release

  • 7/30/2019 Noh Aspe Asse Ppt

    76/96

    Electric Release

  • 7/30/2019 Noh Aspe Asse Ppt

    77/96

    Electric/Pneumatic

    Release

  • 7/30/2019 Noh Aspe Asse Ppt

    78/96

  • 7/30/2019 Noh Aspe Asse Ppt

    79/96

    TrimPac LabelsTrimPac is effixed with labels that indicate what type ofrelease is installed in the TrimPac trim, where the controlling

    stainless steel hoses are to be installed, and where pressure

    switches are to be installed.

    TrimPac has access doors for an emergency release and for

    the alarm test valve. TrimPac has viewports for priming watersupply and water supply pressure.

  • 7/30/2019 Noh Aspe Asse Ppt

    80/96

  • 7/30/2019 Noh Aspe Asse Ppt

    81/96

  • 7/30/2019 Noh Aspe Asse Ppt

    82/96

  • 7/30/2019 Noh Aspe Asse Ppt

    83/96

  • 7/30/2019 Noh Aspe Asse Ppt

    84/96

  • 7/30/2019 Noh Aspe Asse Ppt

    85/96

  • 7/30/2019 Noh Aspe Asse Ppt

    86/96

    TotalPac2

    TotalPac 2 3 New Offerings

  • 7/30/2019 Noh Aspe Asse Ppt

    87/96

    Skid Remote Controlled Self Contained

    Skid Units

  • 7/30/2019 Noh Aspe Asse Ppt

    88/96

    Same Base as Cabinet

    - No Enclosure- Includes non-wired switches and non-wired

    solenoid

    - No air supply

    - 1 6

    Skid Units

  • 7/30/2019 Noh Aspe Asse Ppt

    89/96

    Skid Unit is used as a building block for

    Remote Controlled and Self Contained unitsAvailable in: Pre-action

    Deluge

    HP Dry

    Standard DryWet Systems

    Cycling Systems

    All units serialized

    Remote Controlled Units

  • 7/30/2019 Noh Aspe Asse Ppt

    90/96

    Remote Controlled Units

    Available in same systems as skidAll switches wired to terminal block

    Four Air Supply Options

    All units serialized

    Self Contained Units

  • 7/30/2019 Noh Aspe Asse Ppt

    91/96

    Self Controlled Units

    Available in same systems as skidAll switches and panel wired to

    terminal block

    Four Air Supply Options

    All units serialized

    Self Contained Units

  • 7/30/2019 Noh Aspe Asse Ppt

    92/96

    Control Area:

    Release Control Panel BoardEmergency Batteries

    Air Compressor Isolation

    Switch

    Sprinkler Head Storage Tray

    Self Contained Units

  • 7/30/2019 Noh Aspe Asse Ppt

    93/96

    Two Swinging Doors to System

    Area to allow for easier access

    More Room to work on system

    If maintenance is required

    Supervised sprinkler

    piping system

    Shut-Off Valve (D4)

    Supervised sprinkler

    piping system

    Shut-Off Valve (D4)

    Other Available Options

  • 7/30/2019 Noh Aspe Asse Ppt

    94/96

    FM-072Q-0-09A.dwg

    Sight-GlassAssembly (D5)

    Point flashlight here

    Supervised Water Supply

    Control Valve (D1)

    Deluge (A1) or

    Flow Control Valve (A2)

    Riser Check

    Valve (D2)

    Main Drain Valve

    (D3)

    FM-072Q-0-09A.dwg

    Sight-GlassAssembly (D5)

    Point flashlight here

    Supervised Water Supply

    Control Valve (D1)

    Deluge (A1) or

    Flow Control Valve (A2)

    Riser Check

    Valve (D2)

    Main Drain Valve

    (D3)

    Supervised Water Supply

    Control Valve (D1)

    Deluge (A1) or

    Flow Control Valve (A2)

    FM-072Q-0-1

    0A.dwg

    Riser Check

    Valve (D2)

    To FIRE DEPT.

    CONNECTION

    (by contractor)

    Grooved Tee

    Connection

    Supervised Water Supply

    Control Valve (D1)

    Deluge (A1) or

    Flow Control Valve (A2)

    FM-072Q-0

    -10A.dwg

    Riser Check

    Valve (D2)

    To FIRE DEPT.

    CONNECTION

    (by contractor)

    Grooved Tee

    Connection

    System Isolation ValveAnd Site Glass

    Fire Dept. Conn.

    Semi-Flanged Units

    TotalPac 2 3 New Offerings

  • 7/30/2019 Noh Aspe Asse Ppt

    95/96

    Skid Remote Controlled Self Contained

  • 7/30/2019 Noh Aspe Asse Ppt

    96/96

    Questions?