Top Banner
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com MARK ROHDE NO. 1465 S T A T E O F N E W M E X I C O R E G I S T E R E D A R C H I T E C T Copyright © RMKM Architecture, P.C. 2018 SHEET TITLE SHEET NUMBER PROJECT MODELED BY RMKM PROJECT NO. SCALE DESIGN PHASE PROJECT MANAGER G-000 NEW ART BUILDING AiM #3035 NMSU LAS CRUCES, NM COVER SHEET A01508 RMKM Replacement of Dan W. Williams Hall CONSTRUCTION DOCUMENTS 1/5/2018 MYO SHEET LIST SHEET NO. SHEET NAME M-801B BASE BID & BID LOT 1 1ST LEVEL SPACE PRESSURIZATION PLAN - STUDIO WING M-802B BASE BID 2ND LEVEL SPACE PRESSURIZATION PLAN - STUDIO WING M-901 MECHANICAL 3D REPRESENTATIONS MECHANICAL CONTROLS MI-001 MECHANICAL CONTROLS LEGEND MI-601 MECHANICAL CONTROLS DIAGRAMS MI-602 MECHANICAL CONTROLS DIAGRAMS MI-603 MECHANICAL CONTROLS DIAGRAMS MI-604 MECHANICAL CONTROLS DIAGRAMS MI-605 SEQUENCE OF OPERATIONS MI-606 SEQUENCE OF OPERATIONS (CONT.) ELECTRICAL E-001 ELECTRICAL LEGEND ES-101 ELECTRICAL DEMO SITE PLAN ES-102 ELECTRICAL SITE PLAN EL-101A BASE BID & BID LOT 1 1ST LEVEL LIGHTING FLOOR PLAN - GALLERY WING EL-101B BASE BID & BID LOT 1 1ST LEVEL LIGHTING FLOOR PLAN - STUDIO WING EL-102B BASE BID 2ND LEVEL LIGHTING FLOOR PLAN - STUDIO WING EP-101A BASE BID & BID LOT 1 1ST LEVEL POWER FLOOR PLAN - GALLERY WING EP-101B BASE BID & BID LOT 1 1ST LEVEL POWER FLOOR PLAN - STUDIO WING EP-102B BASE BID 2ND LEVEL POWER FLOOR PLAN - STUDIO WING EP-121A BASE BID 1ST LEVEL ELECTRICAL ROOF PLAN - GALLERY WING EP-122B BASE BID 2ND LEVEL ELECTRICAL ROOF PLAN - STUDIO WING FA-101A BASE BID & BID LOT 1 1ST LEVEL FIRE ALARM FLOOR PLAN - GALLERY WING FA-101B BASE BID & BID LOT 1 1ST LEVEL FIRE ALARM FLOOR PLAN - STUDIO WING FA-102B BASE BID 2ND LEVEL FIRE ALARM FLOOR PLAN - STUDIO WING E-501 ELECTRICAL DETAILS E-601A ELECTRICAL DIAGRAMS E-601B ELECTRICAL DIAGRAMS E-602 GROUNDING DIAGRAM E-603 LIGHTING CONTROL DIAGRAMS E-604 ELECTRICAL LIGHTING DIAGRAMS E-701 ELECTRICAL LUMINAIRE SCHEDULES E-702 ELECTRICAL LUMINAIRE SCHEDULES E-703 ELECTRICAL PANEL SCHEDULES E-704 ELECTRICAL PANEL SCHEDULES E-705 ELECTRICAL PANEL SCHEDULES E-706 ELECTRICAL PANEL SCHEDULES E-707 ELECTRICAL PANEL SCHEDULES E-708 ELECTRICAL PANEL SCHEDULES E-801 LABORATORY EQUIPMENT ELECTRICAL SCHEDULE TECHNOLOGY T-001 TECHNOLOGY LEGEND TS-102 TECHNOLOGY SITE PLAN T-101A BASE BID & BID LOT 1 1ST LEVEL TECH SYSTEMS FLOOR PLAN - GALLERY WING T-101B BASE BID & BID LOT 1 1ST LEVEL TECH SYSTEMS FLOOR PLAN - STUDIO WING T-102B BASE BID 2ND LEVEL TECH SYSTEMS FLOOR PLAN - STUDIO WING T-401 ENLARGED TECHNOLOGY PLANS T-501 TECHNOLOGY DETAILS T-502 TECHNOLOGY DETAILS T-503 AUDIO-VISUAL DETAILS T-601 TECHNOLOGY DIAGRAMS SHEET LIST SHEET NO. SHEET NAME FX-102B BASE BID 2ND LEVEL & PENTHOUSE FIRE PROTECTION FLOOR PLAN - STUDIO WING FX-501 FIRE PROTECTION DETAILS FX-601 FIRE PROTECTION DIAGRAMS PLUMBING P-001 PLUMBING LEGEND PS-102 PLUMBING SITE PLAN PL-101A BASE BID & BID LOT 1 1ST LEVEL WASTE & VENT FLOOR PLAN - GALLERY WING PL-101B BASE BID & BID LOT 1 1ST LEVEL WASTE & VENT FLOOR PLAN - STUDIO WING PL-102B BASE BID 2ND LEVEL WASTE & VENT FLOOR PLAN - STUDIO WING PL-122B BASE BID PENTHOUSE LEVEL WASTE & VENT FLOOR PLAN PP-101A BASE BID & BID LOT 1 1ST LEVEL PRESSURE PIPING FLOOR PLAN - GALLERY WING PP-101B BASE BID & BID LOT 1 1ST LEVEL PRESSURE PIPING FLOOR PLAN - STUDIO WING PP-102B BASE BID 2ND LEVEL & PENTHOUSE PRESSURE PIPING FLOOR PLANS - STUDIO WING PG-101B BASE BID & BID LOT 1 1ST LEVEL PIPED GASES FLOOR PLAN - STUDIO WING PG-102B BASE BID 2ND LEVEL PIPED GASES FLOOR PLAN - STUDIO WING P-401 ENLARGED PLUMBING PLANS P-501 PLUMBING DETAILS P-502 PLUMBING DETAILS P-503 PLUMBING DETAILS P-701 PLUMBING SPECIFICATIONS P-702 PLUMBING SCHEDULES MECHANICAL M-001 MECHANICAL LEGEND MS-101 MECHANICAL DEMOLITION SITE PLAN MS-102 MECHANICAL SITE PLAN MH-101A BASE BID & BID LOT 1 1ST LEVEL HVAC FLOOR PLAN - GALLERY WING MH-101B BASE BID & BID LOT 1 1ST LEVEL HVAC FLOOR PLAN - STUDIO WING MH-102B BASE BID 2ND LEVEL HVAC FLOOR PLAN - STUDIO WING MH-121A BASE BID 1ST LEVEL MECHANICAL ROOF PLAN - GALLERY WING MH-122B BASE BID 2ND LEVEL MECHANICAL ROOF PLAN - STUDIO WING MP-101A BASE BID & BID LOT 1 1ST LEVEL MECHANICAL PIPING FLOOR PLAN - GALLERY WING MP-101B BASE BID & BID LOT 1 1ST LEVEL MECHANICAL PIPING FLOOR PLAN - STUDIO WING MP-102B BASE BID 2ND LEVEL MECHANICAL PIPING FLOOR PLAN - STUDIO WING M-301 MECHANICAL SECTIONS M-302 MECHANICAL SECTIONS M-401 ENLARGED MECHANICAL PLANS M-402 ENLARGED MECHANICAL PLANS M-403 ENLARGED MECHANICAL PLANS M-501 MECHANICAL DETAILS M-502 MECHANICAL DETAILS M-503 MECHANICAL DETAILS M-504 MECHANICAL DETAILS M-505 MECHANICAL DETAILS M-601 MECHANICAL DIAGRAMS M-602 MECHANICAL DIAGRAMS M-603 MECHANICAL DIAGRAMS M-604 MECHANICAL DIAGRAMS M-701 MECHANICAL SCHEDULES M-702 MECHANICAL SCHEDULES M-703 MECHANICAL SCHEDULES M-704 MECHANICAL SCHEDULES M-801A BASE BID & BID LOT 1 1ST LEVEL SPACE PRESSURIZATION PLAN - GALLERY WING SHEET LIST SHEET NO. SHEET NAME ARCHITECTURAL A-101A BASE BID & BID LOT 1 1ST LEVEL FLOOR & DIMENSION PLANS - GALLERY WING A-101B BASE BID & BID LOT 1 1ST LEVEL FLOOR & DIMENSION PLANS - STUDIO WING A-102 BASE BID & BID LOT 1 2ND LEVEL FLOOR & DIMENSION PLANS - STUDIO WING A-111A BASE BID & BID LOT 1 1ST LEVEL REFLECTED CEILING PLANS - GALLERY WING A-111B BASE BID & BID LOT 1 1ST LEVEL REFLECTED CEILING FLOOR PLAN - STUDIO WING A-112 BASE BID 2ND LEVEL & PENTHOUSE REFLECTED CEILING PLAN A-121 BASE BID & BID LOT 1 1ST LEVEL ROOF PLANS - GALLERY WING A-122 BASE BID 2ND LEVEL & PENTHOUSE ROOF PLANS AE-100A EQUIPMENT INVENTORY AE-100B EQUIPMENT INVENTORY AE-101A EQUIPMENT & CASEWORK PLAN 1ST LEVEL - GALLERY WING AE-101B EQUIPMENT & CASEWORK PLAN 1ST LEVEL - STUDIO WING AE-102 EQUIPMENT & CASEWORK PLAN 2ND LEVEL- STUDIO WING A-200 BASE BID BUILDING ELEVATIONS A-201 BASE BID & BID LOT 1 BUILDING ELEVATIONS A-301 BUILDING SECTIONS A-302 BUILDING SECTIONS A-303 BUILDING SECTIONS A-304 BUILDING SECTIONS A-310 WALL SECTIONS A-311 WALL SECTIONS A-312 WALL SECTIONS A-313 WALL SECTIONS A-314 WALL SECTIONS A-315 WALL SECTIONS A-401 ENLARGED PLANS & ELEVATIONS A-410 INTERIOR ELEVATIONS - HALLS A-411 INTERIOR ELEVATIONS - HALLS A-420 STAIR & ELEVATOR ENLARGED PLANS, SECTIONS AND DETAILS A-421 VERTICAL CIRCULATION SECTIONS A-423 STAIR ENLARGED PLAN, SECTIONS & DETAILS A-501 SECTION DETAILS A-502 SECTION DETAILS A-503 SECTION DETAILS A-511 PLAN DETAILS A-512 PLAN DETAILS A-513 PLAN DETAILS A-514 PLAN DETAILS A-515 PLAN DETAILS & PIVOT WALL ENLARGED PLANS & DETAILS A-600 DOOR SCHEDULE & DETAILS A-601 EXTERIOR FRAME TYPES & GLAZING SCHEDULES A-602 EXTERIOR FRAME TYPES & GLAZING SCHEDULES A-603 EXTERIOR FRAME & GLAZING SCHEDULES A-610 ROOM FINISH SCHEDULES & DETAILS A-622 CASEWORK ELEVATIONS A-623 CASEWORK ELEVATIONS A-624 CASEWORK ELEVATIONS A-625 CASEWORK SECTIONS & DETAILS A-626 CASEWORK SECTIONS & DETAILS A-701 PARTITION TYPE LEGEND & DETAILS FIRE PROTECTION FX-001 FIRE PROTECTION LEGEND FX-101A BASE BID & BID LOT 1 1ST LEVEL FIRE PROTECTION FLOOR PLAN - GALLERY WING FX-101B BASE BID & BID LOT 1 1ST LEVEL LEVEL FIRE PROTECTION FLOOR PLAN - STUDIO WING SHEET LIST SHEET NO. SHEET NAME GENERAL G-000 COVER SHEET G-001 ABBREVIATIONS, SYMBOLS, & SPECIAL INSPECTIONS G-100A OVERALL 1ST & 2ND LEVEL FLOOR PLANS G-100B OVERALL ROOF PLAN G-101 CODE PLAN - FIRST LEVEL G-102 CODE PLAN - SECOND & PENTHOUSE LEVELS G-105 TYPICAL MOUNTING HEIGHTS CIVIL C-001 GENERAL NOTES, VICINITY MAP, F.I.R.M. AND LEGEND C-101 SITE PAVING PLAN - BASE BID C-101A SITE PAVING PLAN - ALTERNATE C-102 GRADING PLAN - BASE BID C-102A GRADING PLAN - ALTERNATE C-103 PAVING AND DRAINAGE SECTIONS AND DETAILS C-104 WATER AND SANITARY SEWER PLAN - BASE BID C-104A WATER AND SANITARY SEWER PLAN - ALTERNATE C-105 WATER AND SANITARY SEWER SECTIONS AND DETAILS LANDSCAPE L-100 IRRIGATION PLAN L-101 IRRIGATION NOTES, DETAILS, SCHEDULE L-200 LANDSCAPE PLAN L-201 LANDSCAPE NOTES, DETAILS, SCHEDULE ARCHITECTURAL SITE AS-100 SITE SURVEY AS-101 DEMOLITION ARCHITECTURAL SITE PLAN AS-102 ARCHITECTURAL SITE PLAN AS-103 SITE DETAILS AS-104 SITE DETAILS STRUCTURAL S001 STRUCTURAL GENERAL NOTES S101-A FOUNDATION PLANS - GALLERY WING S101-B FOUNDATION PLAN - STUDIO WING S102-A LEVEL 2 FLOOR & LOW ROOF FRAMING PLAN - GALLERY WING S102-B LEVEL 2 FRAMING - STUDIO WING S103-B LEVEL 2 ROOF & PENTHOUSE FLOOR FRAMING - STUDIO WING S104-A HIGH ROOF FRAMING PLAN S201 BRACED FRAME ELEVATIONS S202 BRACED FRAME ELEVATIONS S203 BRACED FRAME DETAILS S301 SECTIONS & DETAILS S302 SECTIONS & DETAILS S303 SECTIONS & DETAILS S304 SECTIONS & DETAILS S305 SECTIONS & DETAILS S306 SECTIONS & DETAILS S401 ENLARGED STAIR FRAMING PLANS - SECTIONS AND DETAILS S701 TYPICAL DETAILS S702 TYPICAL DETAILS S703 TYPICAL DETAILS NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO 100% CONSTRUCTION DOCUMENTS 05 JANUARY 2018 OWNER PROJECT DIRECTORY A & E TEAM PROJECT DIRECTORY TEAM MEMBER CONTACT PHONE ARCHITECT: RMKM ARCHITECTURE, P.C. MILDRED ORTIZ 505.243.5454 STRUCTURAL ENGINEERING: RME ABQ STRUCTURAL ENGINEERS JIM KREIS 505.889.3004 CIVIL ENGINEERING: HIGH MESA CONSULTING GROUP J. GRAEME MEANS 505.345.4250 MEPT ENGINEERING: BRIDGERS & PAXTON CONSULTING ENGINEERS ABBAS SHIRIAN 505.883.4111 LANDSCAPE ARCHITECT: RICHARD BORKOVETZ LANDSCAPE ARCHITECTURE RICHARD BORKOVETZ 505.266.8506 CONSTRUCTION COST ESTIMATING: BALIS & COMPANY JON BALIS 505.883.7990 PROJECT MANAGER: ROBERT HERRERA ASSISTANT DIRECTOR: JOSE LOERA EXECUTIVE DIRECTOR: ALTON LOONEY VICINITY MAP PROJECT LOCATION: 1308 University Ave Las Cruces, NM NEW ART BUILDING PROJECT LOCATION NO. ISSUE DATE 1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
27

NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

Jun 04, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

MARKROHDE

NO. 1465

ST

ATE

OF NEW MEXI C

O

RE

GI S

TER E D ARCHI T

EC

T

Copyright © RMKM Architecture, P.C. 2018

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

G-000

NEW ARTBUILDINGAiM #3035

NMSU LAS CRUCES, NM

COVER SHEET

A01508

RMKM

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS1/5/2018

MYO

SHEET LISTSHEET NO. SHEET NAMEM-801B BASE BID & BID LOT 1 1ST LEVEL SPACE PRESSURIZATION PLAN - STUDIO WINGM-802B BASE BID 2ND LEVEL SPACE PRESSURIZATION PLAN - STUDIO WINGM-901 MECHANICAL 3D REPRESENTATIONS

MECHANICAL CONTROLSMI-001 MECHANICAL CONTROLS LEGENDMI-601 MECHANICAL CONTROLS DIAGRAMSMI-602 MECHANICAL CONTROLS DIAGRAMSMI-603 MECHANICAL CONTROLS DIAGRAMSMI-604 MECHANICAL CONTROLS DIAGRAMSMI-605 SEQUENCE OF OPERATIONSMI-606 SEQUENCE OF OPERATIONS (CONT.)

ELECTRICALE-001 ELECTRICAL LEGENDES-101 ELECTRICAL DEMO SITE PLANES-102 ELECTRICAL SITE PLANEL-101A BASE BID & BID LOT 1 1ST LEVEL LIGHTING FLOOR PLAN - GALLERY WINGEL-101B BASE BID & BID LOT 1 1ST LEVEL LIGHTING FLOOR PLAN - STUDIO WINGEL-102B BASE BID 2ND LEVEL LIGHTING FLOOR PLAN - STUDIO WINGEP-101A BASE BID & BID LOT 1 1ST LEVEL POWER FLOOR PLAN - GALLERY WINGEP-101B BASE BID & BID LOT 1 1ST LEVEL POWER FLOOR PLAN - STUDIO WINGEP-102B BASE BID 2ND LEVEL POWER FLOOR PLAN - STUDIO WINGEP-121A BASE BID 1ST LEVEL ELECTRICAL ROOF PLAN - GALLERY WINGEP-122B BASE BID 2ND LEVEL ELECTRICAL ROOF PLAN - STUDIO WINGFA-101A BASE BID & BID LOT 1 1ST LEVEL FIRE ALARM FLOOR PLAN - GALLERY WINGFA-101B BASE BID & BID LOT 1 1ST LEVEL FIRE ALARM FLOOR PLAN - STUDIO WINGFA-102B BASE BID 2ND LEVEL FIRE ALARM FLOOR PLAN - STUDIO WINGE-501 ELECTRICAL DETAILSE-601A ELECTRICAL DIAGRAMSE-601B ELECTRICAL DIAGRAMSE-602 GROUNDING DIAGRAME-603 LIGHTING CONTROL DIAGRAMSE-604 ELECTRICAL LIGHTING DIAGRAMSE-701 ELECTRICAL LUMINAIRE SCHEDULESE-702 ELECTRICAL LUMINAIRE SCHEDULESE-703 ELECTRICAL PANEL SCHEDULESE-704 ELECTRICAL PANEL SCHEDULESE-705 ELECTRICAL PANEL SCHEDULESE-706 ELECTRICAL PANEL SCHEDULESE-707 ELECTRICAL PANEL SCHEDULESE-708 ELECTRICAL PANEL SCHEDULESE-801 LABORATORY EQUIPMENT ELECTRICAL SCHEDULE

TECHNOLOGYT-001 TECHNOLOGY LEGENDTS-102 TECHNOLOGY SITE PLANT-101A BASE BID & BID LOT 1 1ST LEVEL TECH SYSTEMS FLOOR PLAN - GALLERY WINGT-101B BASE BID & BID LOT 1 1ST LEVEL TECH SYSTEMS FLOOR PLAN - STUDIO WINGT-102B BASE BID 2ND LEVEL TECH SYSTEMS FLOOR PLAN - STUDIO WINGT-401 ENLARGED TECHNOLOGY PLANST-501 TECHNOLOGY DETAILST-502 TECHNOLOGY DETAILST-503 AUDIO-VISUAL DETAILST-601 TECHNOLOGY DIAGRAMS

SHEET LISTSHEET NO. SHEET NAMEFX-102B BASE BID 2ND LEVEL & PENTHOUSE FIRE PROTECTION FLOOR PLAN - STUDIO

WINGFX-501 FIRE PROTECTION DETAILSFX-601 FIRE PROTECTION DIAGRAMS

PLUMBINGP-001 PLUMBING LEGENDPS-102 PLUMBING SITE PLANPL-101A BASE BID & BID LOT 1 1ST LEVEL WASTE & VENT FLOOR PLAN - GALLERY WINGPL-101B BASE BID & BID LOT 1 1ST LEVEL WASTE & VENT FLOOR PLAN - STUDIO WINGPL-102B BASE BID 2ND LEVEL WASTE & VENT FLOOR PLAN - STUDIO WINGPL-122B BASE BID PENTHOUSE LEVEL WASTE & VENT FLOOR PLANPP-101A BASE BID & BID LOT 1 1ST LEVEL PRESSURE PIPING FLOOR PLAN - GALLERY WINGPP-101B BASE BID & BID LOT 1 1ST LEVEL PRESSURE PIPING FLOOR PLAN - STUDIO WINGPP-102B BASE BID 2ND LEVEL & PENTHOUSE PRESSURE PIPING FLOOR PLANS - STUDIO

WINGPG-101B BASE BID & BID LOT 1 1ST LEVEL PIPED GASES FLOOR PLAN - STUDIO WINGPG-102B BASE BID 2ND LEVEL PIPED GASES FLOOR PLAN - STUDIO WINGP-401 ENLARGED PLUMBING PLANSP-501 PLUMBING DETAILSP-502 PLUMBING DETAILSP-503 PLUMBING DETAILSP-701 PLUMBING SPECIFICATIONSP-702 PLUMBING SCHEDULES

MECHANICALM-001 MECHANICAL LEGENDMS-101 MECHANICAL DEMOLITION SITE PLANMS-102 MECHANICAL SITE PLANMH-101A BASE BID & BID LOT 1 1ST LEVEL HVAC FLOOR PLAN - GALLERY WINGMH-101B BASE BID & BID LOT 1 1ST LEVEL HVAC FLOOR PLAN - STUDIO WINGMH-102B BASE BID 2ND LEVEL HVAC FLOOR PLAN - STUDIO WINGMH-121A BASE BID 1ST LEVEL MECHANICAL ROOF PLAN - GALLERY WINGMH-122B BASE BID 2ND LEVEL MECHANICAL ROOF PLAN - STUDIO WINGMP-101A BASE BID & BID LOT 1 1ST LEVEL MECHANICAL PIPING FLOOR PLAN - GALLERY

WINGMP-101B BASE BID & BID LOT 1 1ST LEVEL MECHANICAL PIPING FLOOR PLAN - STUDIO WINGMP-102B BASE BID 2ND LEVEL MECHANICAL PIPING FLOOR PLAN - STUDIO WINGM-301 MECHANICAL SECTIONSM-302 MECHANICAL SECTIONSM-401 ENLARGED MECHANICAL PLANSM-402 ENLARGED MECHANICAL PLANSM-403 ENLARGED MECHANICAL PLANSM-501 MECHANICAL DETAILSM-502 MECHANICAL DETAILSM-503 MECHANICAL DETAILSM-504 MECHANICAL DETAILSM-505 MECHANICAL DETAILSM-601 MECHANICAL DIAGRAMSM-602 MECHANICAL DIAGRAMSM-603 MECHANICAL DIAGRAMSM-604 MECHANICAL DIAGRAMSM-701 MECHANICAL SCHEDULESM-702 MECHANICAL SCHEDULESM-703 MECHANICAL SCHEDULESM-704 MECHANICAL SCHEDULESM-801A BASE BID & BID LOT 1 1ST LEVEL SPACE PRESSURIZATION PLAN - GALLERY WING

SHEET LISTSHEET NO. SHEET NAMEARCHITECTURALA-101A BASE BID & BID LOT 1 1ST LEVEL FLOOR & DIMENSION PLANS - GALLERY WINGA-101B BASE BID & BID LOT 1 1ST LEVEL FLOOR & DIMENSION PLANS - STUDIO WINGA-102 BASE BID & BID LOT 1 2ND LEVEL FLOOR & DIMENSION PLANS - STUDIO WINGA-111A BASE BID & BID LOT 1 1ST LEVEL REFLECTED CEILING PLANS - GALLERY WINGA-111B BASE BID & BID LOT 1 1ST LEVEL REFLECTED CEILING FLOOR PLAN - STUDIO WINGA-112 BASE BID 2ND LEVEL & PENTHOUSE REFLECTED CEILING PLANA-121 BASE BID & BID LOT 1 1ST LEVEL ROOF PLANS - GALLERY WINGA-122 BASE BID 2ND LEVEL & PENTHOUSE ROOF PLANSAE-100A EQUIPMENT INVENTORYAE-100B EQUIPMENT INVENTORYAE-101A EQUIPMENT & CASEWORK PLAN 1ST LEVEL - GALLERY WINGAE-101B EQUIPMENT & CASEWORK PLAN 1ST LEVEL - STUDIO WINGAE-102 EQUIPMENT & CASEWORK PLAN 2ND LEVEL- STUDIO WINGA-200 BASE BID BUILDING ELEVATIONSA-201 BASE BID & BID LOT 1 BUILDING ELEVATIONSA-301 BUILDING SECTIONSA-302 BUILDING SECTIONSA-303 BUILDING SECTIONSA-304 BUILDING SECTIONSA-310 WALL SECTIONSA-311 WALL SECTIONSA-312 WALL SECTIONSA-313 WALL SECTIONSA-314 WALL SECTIONSA-315 WALL SECTIONSA-401 ENLARGED PLANS & ELEVATIONSA-410 INTERIOR ELEVATIONS - HALLSA-411 INTERIOR ELEVATIONS - HALLSA-420 STAIR & ELEVATOR ENLARGED PLANS, SECTIONS AND DETAILSA-421 VERTICAL CIRCULATION SECTIONSA-423 STAIR ENLARGED PLAN, SECTIONS & DETAILSA-501 SECTION DETAILSA-502 SECTION DETAILSA-503 SECTION DETAILSA-511 PLAN DETAILSA-512 PLAN DETAILSA-513 PLAN DETAILSA-514 PLAN DETAILSA-515 PLAN DETAILS & PIVOT WALL ENLARGED PLANS & DETAILSA-600 DOOR SCHEDULE & DETAILSA-601 EXTERIOR FRAME TYPES & GLAZING SCHEDULESA-602 EXTERIOR FRAME TYPES & GLAZING SCHEDULESA-603 EXTERIOR FRAME & GLAZING SCHEDULESA-610 ROOM FINISH SCHEDULES & DETAILSA-622 CASEWORK ELEVATIONSA-623 CASEWORK ELEVATIONSA-624 CASEWORK ELEVATIONSA-625 CASEWORK SECTIONS & DETAILSA-626 CASEWORK SECTIONS & DETAILSA-701 PARTITION TYPE LEGEND & DETAILS

FIRE PROTECTIONFX-001 FIRE PROTECTION LEGENDFX-101A BASE BID & BID LOT 1 1ST LEVEL FIRE PROTECTION FLOOR PLAN - GALLERY WINGFX-101B BASE BID & BID LOT 1 1ST LEVEL LEVEL FIRE PROTECTION FLOOR PLAN - STUDIO

WING

SHEET LISTSHEET NO. SHEET NAMEGENERALG-000 COVER SHEETG-001 ABBREVIATIONS, SYMBOLS, & SPECIAL INSPECTIONSG-100A OVERALL 1ST & 2ND LEVEL FLOOR PLANSG-100B OVERALL ROOF PLANG-101 CODE PLAN - FIRST LEVELG-102 CODE PLAN - SECOND & PENTHOUSE LEVELSG-105 TYPICAL MOUNTING HEIGHTS

CIVILC-001 GENERAL NOTES, VICINITY MAP, F.I.R.M. AND LEGENDC-101 SITE PAVING PLAN - BASE BIDC-101A SITE PAVING PLAN - ALTERNATEC-102 GRADING PLAN - BASE BIDC-102A GRADING PLAN - ALTERNATEC-103 PAVING AND DRAINAGE SECTIONS AND DETAILSC-104 WATER AND SANITARY SEWER PLAN - BASE BIDC-104A WATER AND SANITARY SEWER PLAN - ALTERNATEC-105 WATER AND SANITARY SEWER SECTIONS AND DETAILS

LANDSCAPEL-100 IRRIGATION PLANL-101 IRRIGATION NOTES, DETAILS, SCHEDULEL-200 LANDSCAPE PLANL-201 LANDSCAPE NOTES, DETAILS, SCHEDULE

ARCHITECTURAL SITEAS-100 SITE SURVEYAS-101 DEMOLITION ARCHITECTURAL SITE PLANAS-102 ARCHITECTURAL SITE PLANAS-103 SITE DETAILSAS-104 SITE DETAILS

STRUCTURALS001 STRUCTURAL GENERAL NOTESS101-A FOUNDATION PLANS - GALLERY WINGS101-B FOUNDATION PLAN - STUDIO WINGS102-A LEVEL 2 FLOOR & LOW ROOF FRAMING PLAN - GALLERY WINGS102-B LEVEL 2 FRAMING - STUDIO WINGS103-B LEVEL 2 ROOF & PENTHOUSE FLOOR FRAMING - STUDIO WINGS104-A HIGH ROOF FRAMING PLANS201 BRACED FRAME ELEVATIONSS202 BRACED FRAME ELEVATIONSS203 BRACED FRAME DETAILSS301 SECTIONS & DETAILSS302 SECTIONS & DETAILSS303 SECTIONS & DETAILSS304 SECTIONS & DETAILSS305 SECTIONS & DETAILSS306 SECTIONS & DETAILSS401 ENLARGED STAIR FRAMING PLANS - SECTIONS AND DETAILSS701 TYPICAL DETAILSS702 TYPICAL DETAILSS703 TYPICAL DETAILS

NMSU NEW ART BUILDINGLAS CRUCES, NEW MEXICO

100% CONSTRUCTION DOCUMENTS 05 JANUARY 2018

OWNER PROJECT DIRECTORY

A & E TEAM PROJECT DIRECTORYTEAM MEMBER CONTACT PHONEARCHITECT: RMKM ARCHITECTURE, P.C. MILDRED ORTIZ 505.243.5454

STRUCTURALENGINEERING: RME ABQ STRUCTURAL ENGINEERS JIM KREIS 505.889.3004

CIVILENGINEERING: HIGH MESA CONSULTING GROUP J. GRAEME MEANS 505.345.4250

MEPTENGINEERING: BRIDGERS & PAXTON CONSULTING ENGINEERS ABBAS SHIRIAN 505.883.4111

LANDSCAPEARCHITECT: RICHARD BORKOVETZ LANDSCAPE ARCHITECTURE RICHARD BORKOVETZ 505.266.8506

CONSTRUCTIONCOST ESTIMATING: BALIS & COMPANY JON BALIS 505.883.7990

PROJECT MANAGER: ROBERT HERRERAASSISTANT DIRECTOR: JOSE LOERA

EXECUTIVE DIRECTOR: ALTON LOONEY

VICINITY MAP

PROJECT LOCATION:1308 University AveLas Cruces, NM

NEW ART BUILDINGPROJECT LOCATION

NO. ISSUE DATE1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

Page 2: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

UP

P

P

P P R/FR/F R/F

P

F

F

P

/1

FA

102-

A

/1

FA

102 -

A

EXTERIORYARD

140

ELEVATOR/STAIRLOBBY

200F

DIGITALOUTPUT

221

GRADUATESTUDIO

220A

GRADUATESTUDIO

220B

GRADUATESTUDIO

220C

GRADUATESTUDIO

220D

GRADUATESTUDIO

220E

GRADUATESTUDIO

220F

GRADUATESTUDIO

220G

GRADUATESTUDIO

220H

HALLH201E

FACULTYSTUDIO

(SAFETY)242

GRAD STUDIOHUDDLE

240

FILM LOADING222D

GANG DARKRM

222B

PHOTO DOC. &STORAGE

210

PHOTOSTUDIO

222

FILMPROCESSING

RM222E

DESIGNSTUDIO

224

WOMENSR223A

MENSR223B

HALLH201F

STUDY/RESOURCE RM

229TR

T225AELEC. RM

M225B

COMPUTERLAB231

TECHNOLOGYLAB233

JEWELRYFACULTYSTUDIO

234

JANITORJ227

WASH OUT224A DARKROOM

224B

ETCHING RM224C

PAINTINGSTUDIO

230

STILL LIFESTORAGE

230ADRESSING

230BDRESSING

232A

DRAWINGSTUDIO

232

STUDENTCOLLABORATION

236

HALLH201G

DWG/PAINTINGFACULTYSTUDIO

238A

PHOTO.FACULTYSTUDIO

238B

DESIGNFACULTYSTUDIO

238C

CONFERENCERM235

DESIGNFACULTYSTUDIO

238D

FILM LOADING222C

C F G

8

2

ED

3

5

7

10

9

11

4

6.1

9.5

6.6

D.8 E.5 E.8 F.4 G.4

2.3

2.6

2.7

5.1

B.8

11.2

6

D.3

2.4

E.6 F.7 H

2.2

10.9

9.6

8.9

2.9

3.5

4.4

5.3

6.4

6.9

7.8

8.8

E.4D.45 D.9D.4

2.65

4.5

FS TS

1

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

1/8" = 1'-0"

FA-102B

NEW ARTBUILDINGNMSU LAS CRUCES, NM

BASE BID 2ND LEVEL FIRE ALARM FLOORPLAN - STUDIO WING

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB

OU

1/8" = 1'-0"FA-102B

1 BASE BID 2ND LEVEL FIRE ALARM FLOOR PLAN - STUDIO WING

NORTH

KEY PLAN

GALLERY

WING

STUDIO

WING EXTERIOR

YARD

MA

TC

H L

INE

RECEIVING

BID LOT 1

0' 8' 16' 32' 64'

1. COORDINATE FLOW AND TAMPER SWITCH LOCATION IN CEILING SPACE WITH PLUMBING DRAWINGS. PROVIDE INDICATOR LIGHT TO INDICATE LOCATION OF FLOW AND TAMPER SWITCHES THAT ARE ABOVE THE CEILING.

A. SEE SHEET E-604 FOR FIRE ALARM RISER DIAGRAM.B. ALL STROBES IN CORRIDORS AND COMMON AREAS WILL FLASH AT THE

SAME TIME.C. COORDINATE ALL DEVICES WITH ARCHITECTURAL AT WHITEBOARDS AND

PANEL LOCATIONS.D. REFER TO SPECIFICATION 28 3111 FOR VOICE EVACUATION SYSTEM

REQUIREMENTS AND ADDITIONAL INFORMATION. E. SEE SPECIFICATION SECTION 013100 FOR COORDINATION DRAWING

REQUIREMENTS.

GENERAL SHEET NOTES

KEYNOTES

IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASICREPRESENTATION OF THE FIRE ALARM SYSTEM. DEVICES INDICATED ONTHESE DOCUMENTS ARE IN NO WAY IMPLIED TO BE COMPREHENSIVE OF

THE FINAL DESIGN. IT IS THE RESPONSIBILITY OF THE FIRE ALARMCONTRACTOR TO PROVIDE A DESIGN/BUILD FIRE ALARM SYSTEM BASEDUPON A THOROUGH REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE

RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR TO ENSURE THAT THEFIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE REQUIREMENTS OFTHE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY

PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSTEMSIMPACTING THE FIRE ALARM SYSTEM. NO CHANGE ORDERS SHALL BE

APPROVED FOR THE BASE SCOPE OF WORK.

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:06:09-07'00'

Page 3: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

2" GRAVEL AT BOTTOM

WIDE SWEEP BEND

POLYMER CONCRETESTACKABLE BOX,WITH OPEN BOTTOM

EXTEND CONDUITS4" ABOVE BOTTOM,(2" ABOVE GRAVEL)

TYPE SIZE BOX

A 48WX48LX48D

COVER

PULL BOX SCHEDULE

B

6" DEEP LAYER OF CRUSH STONE BASE (3/4" CLEANCRUSHED STONE - 2B CLEAN)

BACK FILL

12-18" DEEPSEE SCHEDBELOW

PG4848BA48 PG4848HH0017

C 11Wx18Lx18D

D 12Wx12Lx12D

PC1118BA18 PC1118HAXX-17

PC1212BA12 PC1212HAXX-17

24W-36L-30D PG2436BA30 PG2436CA0017

- ALL PULL BOXES ARE TYPE "A" UNLESS NOTED OTHERWISE- COVER TO BE SECURED WITH MIN. OF TWO TAMPER-PROOF

FIVE-SIDED-HEAD STAINLESS STEEL BOLTS.- BOX WITH NO BASE.- LID TO DISPLAY "ELECTRIC" (QUAZITE OPTION #17)- BASIS OF DESIGN QUAZITE "PC" STYLE BOX.- BOX AND LID COLOR TO BE "LIGHT TAN".

NOTE:

CEILING

HANGER WIRES (TYP.)CEILING SYSTEM

MEMBERS. SUSPEND FROM EACHBUILDING FRAMING OR STRUCTURALNO. 12 GAUGE WIRE HANGER TO

END OF FIXTURE.

SUSPENSIONSYSTEM (TYP.)

18" BELOW CEILING

(TYP.)HANGER WIRES

CORNERS OF FIXTURE.

NO. 12 GAUGE WIRE HANGER TOBUILDING FRAMING OR STRUCTURALMEMBERS). SUSPEND FROM ALL FOUR

CEILING SYSTEM

LAY-IN LUMINAIRE

SEISMIC FIXTURE CLAMPS: REQUIRED AT ALL (4) LUMINAIRE CORNERS WITH (2) #10 SELF-TAPPING SCREWS. AGI SEISMIC PRODUCTS OR EQUAL. AC 184 COMPLIANT.

(TYP.)HANGER WIRESCEILING SYSTEM

BOLT CONNECTION WITHCOMPRESSION SPADE LUGFITTING (TYPICAL)

TO SERVICE ENTRANCE GROUND

2700V INSULATORS

STAND-OFFS

COPPER BUS BAR(REFER TO DIAGRAM ANDKEYED NOTE ON SHEET E602.)

DUCTBANK SIDEVIEW

RED CONCRETE

WARNING TAPE

WARNING TAPE

GRADE12"

30"MIN.

ONLY ONE CONDUIT SHOWN FOR CLARITY.

4"3"

3" 3"

3"

12"

SIMILAR FOR LOCATIONSWHERE MORE OR LESS CONDUITS ARE REQUIRED

PROVIDE CONCRETE DUCT BANK FOR PROTECTION ATDRIVEWAYS, STREETS, PARKING AREAS, OR OTHER LOCATIONS

WHERE VEHICULAR USE IS PRESENT.

CONDUIT SIZED AS INDICATED ON PLANS AND/OR FEEDER SCHEDULE

COUPLING

RED CONCRETEENCASED DUCT

RGS CONDUIT SIZE WHERE APPLICABLE

PVC CONDUIT SIZEWHERE APPLICABLE

TRENCHING

3"

SPARE

#4/0 GROUND

4" CONDUIT (TYP.)

3"3"

FINISHED GRADE OR SURFACE. REPAIRSURFACES TO MATCH EXISTING.

UNDISTURBED EARTH.

COMPACTED TO 90% RELATIVE DENSITY.FREE FROM LARGE ROCKS AND DEBRIS.(COMPACTED IN 6" LAYERS).

WARNING TAPE. (DETECTABLE)

PVC SCHEDULE 40 CONDUIT. NUMBERAND SIZE PER ONE-LINE DIAGRAM.FEEDER RUNS WILL BE GALVANIZED RIGIDSTEEL (GRS) FOR BENDS AND WHERETHEY ENTER A BUILDING.

CONCRETE DUCTBANK. CONCRETE TO BECOLORED RED.

6" SAND BED.

42"

MIN

.

24" MIN.

*

2

3

1

4

5

6

7

1

2

3

4

5

6

7

12"

SPARE4"4"4"

G

G

GG

GROUND LUG

BUSH CONDUIT ENDS

#6 BARE COPPER BONDED TO REBAR AND CONNECTED TOPOLE GROUND LUG

FINISH GRADE

BRANCH CIRCUIT INPVC CONDUIT. SEEELECTRICAL SITE PLANFOR ROUTING.

FIXTURE POLE AND BASEPLATE FURNISHED ASINTEGRAL PART OF PIXTURE

CHAMFER AND FINISHAS DIRECTED BYARCHITECT

4 #7 REBAR OPPOSITEEACH OTHER

GALVANIZED BOLTS FURNISHEDAS PART OF FIXTURE.QUANTITY AS REQUIRED BYMANUFACTURER. INSTALLBOLTS PER MANUFACTURER'SBOLT PATTERN

BRANCH CIRCUIT INPVC CONDUIT. SEEFOR ROUTING.

#3 REBAR TIESAT 12" O.C. 30"

6'-0

"

2'-0

"

MIN

.

6"

TO FIXTURE. LIGHTING FIXTURE IS EXISTING AND WILL BE REUSED IN NEW POLE.

G

G

GG

GROUND LUG

BUSH CONDUIT ENDS

#6 BARE COPPER BONDED TO REBAR AND CONNECTED TOPOLE GROUND LUG

FINISH GRADE

BRANCH CIRCUIT INPVC CONDUIT. SEEELECTRICAL SITE PLANFOR ROUTING.

TO FIXTURE. LIGHTING FIXTURE IS EXISTING AND WILL BE REUSED IN NEW POLE.

FIXTURE POLE AND BASEPLATE FURNISHED ASINTEGRAL PART OF PIXTURE

CHAMFER AND FINISHAS DIRECTED BYARCHITECT

4 #7 REBAR OPPOSITEEACH OTHER

GALVANIZED BOLTS FURNISHEDAS PART OF FIXTURE.QUANTITY AS REQUIRED BYMANUFACTURER. INSTALLBOLTS PER MANUFACTURER'SBOLT PATTERN

BRANCH CIRCUIT INPVC CONDUIT. SEEFOR ROUTING.

#3 REBAR TIESAT 12" O.C. 30"

6'-0

"

2'-0

"

MIN

.

DEVICE AND OUTLET BOX TYPES PER PLANS

CORD INSULATIONAND CONDUCTORSPER PLANS

CORD REEL

BALL STOP

CHANNEL

THREADED ROD ORAPPROVED EQUIVALENT

CORD GRIP

7'-0" AFF(MIN)

SUSPENDEDCEILING

CORD & PLUG

NEMA 5-20RTWISTLOCK CEILING OUTLET

ASSEMBLY TO CONSIST OF THE FOLLOWING COMPONENTS(BASIS OF DESIGN):- HUBBELL #HBLC40123--REEL W/MOUNTING BASE AND 12/3 WIRE LEADS- HUBBELL #3059H--PORTABLE OUTLET BOX- HUBBELL #3061H--LIFTING COVER WITH GFCI DEVICE PLATE- HUBBELL #074011335--STAINLESS STEEL CORD GRIP

BACK TO BACK DUPLEX RECEPTACLE (4 OUTLETS TOTAL)

VACANCY/OCCUPANCYSENSOR

SWITCHED OUTLET SHALL BE COLOR CODED: LIGHT BROWN

SWITCHED OUTLET SHALL BE COLOR CODED: LIGHT BROWN

GENERAL NOTE:1. AT LEAST 50% OF ALL 120V, 20A RECEPTACLES MUST BE AUTOMATICALLY CONTROLLED PER

ASHRAE 90.1: SECTION 8.4.2. THIS STANDARD ONLY APPLIES TO PRIVATE OFFICES, AND COMPUTER CLASSROOMS.

2. BOTH A TIME CLOCK AND OCCUPANCY SENSOR TO CONTROL RECEPTACLE'S SWITCHED OUTLETS. DURING “ON” HOURS ALL SWITCHED RECEPTACLES WILL REMAIN ON. DURING CLOCK OFF HOURS, SWITCHED RECEPTACLES WILL ONLY BE ON WHEN ROOM IS OCCUPIED. DURING “OFF” HOURS RECEPTACLES WILL SHUT OFF AFTER 20 MINUTES OF ROOM VACANCY.

3. SPLIT-WIRE RECEPTACLES SHALL BE USED THROUGH-OUT THE DESIGNATED SPACES. THIS INCLUDES WALL MOUNTED, FLOOR MOUNTED AND CEILING MOUNTED RECEPTACLES AS NOTED IN PLANS. COMPUTER PC SHALL BE CONNECTED TO UNSWITCHED RECEPTACLE FOR CONTINUOUS POWER.

4. COORDINATE WITH NMSU TIME CLOCK SETTINGS FOR THESE DEVICES.

(TIME CLOCK DIALOG)

REFER TO E-603

RELAYPACK

ELEVATION

SECTION "A-A"

RIGID STEEL 3/4"CONDUIT FOR WIRING

RIGID STEEL CONDUITFOR SUPPORT PER

N.E.C. ART. 314

CAST METAL"WHILE-IN-USE"WATERPROOF

COVER(S) &RECEPTACLE(S)

CAST METAL, 2-GANG,NEMA 3R JUNCTION BOXWITH THREADED HUBS

12"

MA

X

3/4" CONDUIT

NOTE: REFER TO STRUCTURAL AND ARCHITECTURAL DRAWINGS FORSECURELY ATTATCHING TO ROOF STRUCTURE AND FLASHING

2-GANG JUNCTION BOX

ELEVATION

SECTION "A-A"

RIGID STEEL 3/4"CONDUIT FOR WIRING

RIGID STEEL 2" STRUT SUPPORT

PERN.E.C. ART. 314

DISCONNECT. REFER TO PLANS

FOR SIZE.

12"

MA

X

3/4" CONDUIT

NOTE: REFER TO STRUCTURAL AND ARCHITECTURAL DRAWINGS FORSECURELY ATTATCHING TO ROOF STRUCTURE AND FLASHING

2-GANG JUNCTION BOX

A

A

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

NO SCALE

E-501

NEW ARTBUILDINGNMSU LAS CRUCES, NM

ELECTRICAL DETAILS

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB

OU

SCALE: NO SCALE1 LINEAR DIRECT-INDIRECT SUPPORT DETAIL

SCALE: NO SCALE2 LUMINAIRE SUPPORT DETAIL

SCALE: NO SCALE3 MAIN GROUNDING ELECTRODE BUS BARSCALE: NO SCALE6 DUCTBANK DETAILS - PRIMARY POWER

SCALE: NO SCALE5 208V SECONDARY DUCT BANK DETAILSCALE: NO SCALE8 POLE BASE DETAIL (PARKING LOT LIGHTS)

SCALE: 1/8" = 1'-0"4 PULL BOX/HAND HOLE DETAIL

SCALE: NO SCALE9 POLE BASE DETAIL (WALKWAY LIGHTS)

SCALE: NO SCALE7 POWER CORD REEL DETAILSCALE: N.T.S.10 PLUG LOAD CONTROL

SCALE: NO SCALE12 RECEPTACLE ROOF MOUNTING DETAIL

SCALE: NO SCALE11 UNISTRUT MOUNTED DISCONNECT DETAIL

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:25:29-07'00'

Page 4: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

"S25-133"

1 2 3 4

4

TO LOAD BREAK SECTIONALIZER

100E

20E

SP

AR

E

100E

TO WILLIAMS VAULT

TO HILTON HALL

23.9 KV

208Y/120

EX. T25-423750 kVA(H & SS)

EX. H & SS

EX

EX. 3#4/0 W/ 1/3 NEUTRAL

AND #1/0 GND

23.9 KV

208Y/120

6

"J1"

1000/3P

EX. 1200A, 208Y/120V, 50 KAIC

EX. (3) - 4#500 KCMIL(3) 4" CONDUIT

EX. WILLIAMS HALL EX. ANNEX(NORMAL)

800 Y 50 Y

EX. EX.EX. EX.

METERED DEMAND LOAD:

140KW @ .895 PF = 156.5 KVA

1000 Y

9

NEC DEMAND LOAD: 192.5 KVA

"T1" XFMR BY NMSU

1600 YEX.

4

1600/3P4

15

EX. FIRE PUMP

4

250 YEX.

4

4

4

1 2 3

600/

3P

800/

3P

SP

AC

E

1000

/3P

4

50/3

P

11

EX. SITE POLE

LUMINAIRES

EX

12

14

EX. NMSU EMERGENCY SYSTEM @ BUSINESS VAULT (4160Y / 2400V)

2.4KV

240/120V

50/3P

PANEL "EM" - 480Y/277V, 3PH, 4W 100A

50/3P

M

100/3P

EX

NEW XFMR"T3"

NMSU 25 KV SYSTEM(NEW WORK)

NMSU "CONTINUOUS LIGHTING"

EMERGENCY SYSTEM(NEW WORK)

WORK WITHIN DASHED LINES IS BY NMSU. SHOWN HERE FOR REFERENCE ONLY.

50/3P 20/3P

SP

AC

E

SP

AC

E

PANEL "EM1" PANEL "EM2"

EX. MSB

"DB1" - FREE-STANDING GEAR

600 Y

"J3""J2"

"HH-1"

"HH-2" "HH-3"

"J4"

4

125/

3P

1000

/3P

EX. ANNEX(EMERG.)

EX. ANNEX

AIC RATING: 14 kAIC

208Y/120V, 3PH, 4W 1000A, AIC RATING: 22 kAIC

PHASE IIIPHASE I

1

1

1

1

125 Y

125 Y

8

8

8

"D1"100E

50 Y 50 Y

XXA

P5-350

EXIST. BUSINESS ADM VAULT SWITCH: "S5-200"

1 2 3 4

65A

P5-355

4

2

2

TO GARDINER VAULT

TO BUSINESS ADMINISTRATION

15A

EX. SWITCH

EX. NMSU EMERGENCY SYSTEM (4160Y / 2400V)

208Y/120V

2.4KV

120/240V

50/2P

EX. PANEL "E"

50/2P

M

100/2P

EX. ANNEX(EMERG.)

EX. WILLIAMS HALL

85A

1#2 15kV1#2 600V(1) 2" CONDUIT

3#1, 1#6 GND IN(1) 1-1/4" CONDUIT

EX

EX. XFMR25 kVA

50A

/2P

EX.3#4, 1#10 GND IN(1) 1" CONDUIT

EX. T5-815(3) 50 kVA

1000/3P

5KV

EX. ANNEX(NORMAL)

5 KV

208Y/120

EX. T5-810300 kVA

1200A, 208Y/120V, 50 KAIC

3#2 15kV1#2 600V(1) 4" CONDUIT

(3) - 4#500 KCMIL(3) 4" CONDUIT

EX.

500 KCMIL SET

EX. WILLIAMS HALL

800/3PEX

800A, 208Y/120V

EXISTING ABOVE-GRADE ELECTRICAL VAULT. EQUIPMENT SHOWN WITHIN DASHED LINES IS INSIDE OF VAULT

208V120/240V

10 KVA 3#6, 1#10 GND IN3/4" CONDUIT

3#4, 1#10 GND IN1" CONDUIT

50A

/2P

EX. PANEL "E1"NEC DEMAND

LOAD: 3.96 KVA

3#4, 1#10 GND IN(1) 1" CONDUIT

EX. ATS80A/3P

SINGLE- PHASE

NMSU 5 KV SYSTEM(EXISTING/DEMO WORK)

NMSU "CONTINUOUS LIGHTING"

EMERGENCY SYSTEM(EXISTING/DEMO WORK)

2

2

2

2

22

2

2 2

2

2 22 2

2

2

2

3

4

4

4

4

5

NEC DEMAND LOAD: 13.96

KVA

EX. EMERGENCY PANEL

NEC DEMAND LOAD: 10 KVA

15

2

METERED DEMAND LOAD:

140KW @ .895 PF = 156.5 KVA

EX. SITE POLE

LUMINAIRES

EX

12

13

EX. PANEL (AT SCULPTURE YARD)

2

800/3P 400/3P 125/3P EX EX

22

2

"J3"

2

PHASE II

PHASE II

7

2

2

5 "J1"

EX.EX.

25

40

35

30

45

50

60

70

90

80

125

100

200

175

225

250

150

300

350

450

400

700

600

800

1000

500

1200

1600

2500

2000

3000

NOTE:

NOTESDESIGNATION

THREE PHASE THREE WIRE & GROUND FEEDER

FEEDER SCHEDULE

20

4000

CONDUCTORS GROUND CONDUIT

(6) 3-600 KCMIL

(8) 3-500 KCMIL

(10) 3-600 KCMIL

(5) 3-600 KCMIL

(2) 3-600 KCMIL

(4) 3-600 KCMIL

(3) 3-600 KCMIL

(3) 3-400 KCMIL

(2) 3-250 KCMIL

(2) 3-500 KCMIL

(2) 3-350 KCMIL

3-600 KCMIL

(2) 3#4/0

3#1

3#2

3#2/0

3#1/0

3#4/0

3#3/0

3-250 KCMIL

3-500 KCMIL

3-350 KCMIL

3#10

3#8

3#10

3#8

3#8

3#6

3#4

3#8

3#2

3#4

3#12

(8)400 KCMIL

(6)350 KCMIL

(10)500 KCMIL

2

(2) 2

(2) 1

(2) 1

(2) 2

(5)250 KCMIL

(4) 4/0

(3) 3/0

(3) 2/0

(2) 1/0

4

2

4

4

6

6

6

6

8

10

10

10

10

10

10

10

8

8

8

12

(6) 4"

(8) 4"

(10) 4"

4"

(2) 4"

(2) 3"

(2) 3"

(3) 3"

(5) 4"

(4) 4"

(3) 4"

(2) 4"

(2) 2 1/2"

1 1/2"

1 1/4"

1 1/2"

2 1/2"

2"

3"

4"

3"

2"

3/4"

1 1/4"

1 1/4"

1 1/4"

1"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

ALL CONDUCTORS ARE COPPER, TYPE THWN/THHN UNLESS OTHERWISE NOTED.

35Y

40Y

30Y

45Y

50Y

60Y

70Y

80Y

90Y

125Y

100Y

175Y

200Y

225Y

250Y

150Y

300Y

350Y

450Y

400Y

600Y

700Y

800Y

1000Y

500Y

1200Y

1600Y

2000Y

2500Y

3000Y

25Y

20Y

4000Y

5000Y

4#6

(3) 4-600 KCMIL

(4) 4-600 KCMIL

(5) 4-600 KCMIL

(8) 4-500 KCMIL

(6) 4-600 KCMIL

(10) 4-600 KCMIL

(12) 4-600 KCMIL

(2) 4-250 KCMIL

(2) 4-350 KCMIL

(2) 4-500 KCMIL

(2) 4-600 KCMIL

(3) 4-400 KCMIL

4-250 KCMIL

(2) 4#4/0

4-350 KCMIL

4-500 KCMIL

4-600 KCMIL

4#4

4#4

4#2

4#2

4#1/0

4#2/0

4#3/0

4#4/0

4#1

4#10

4#10

4#12

4#8

4#8

4#8

4#8

(3) 3/0

(4) 4/0

(5) 250 KCMIL

(6) 350 KCMIL

(8) 400 KCMIL

(10) 500 KCMIL

(12) 700 KCMIL

4

(2) 2

(2) 1

(2) 1

(2) 2

(2) 1/0

(3) 2/0

2

4

2

6

6

4

6

6

8

8

8

8

10

10

12

10

10

10

10

10

(3) 4"

(4) 4"

(5) 4"

(6) 4"

(8) 4"

(10) 4"

(12) 4"

3"

(2) 3"

(2) 4"

(2) 4"

(3) 3"

(2) 3"

(2) 2 1/2"

4"

3"

4"

1 1/4"

1 1/4"

1 1/4"

1 1/4"

2 1/2"

1 1/2"

2"

2"

2"

3/4"

3/4"

1"

3/4"

3/4"

3/4"

3/4"

3/4"

THREE PHASE FOUR WIRE & GROUND FEEDER

NOTE:

NOTESDESIGNATION

FEEDER SCHEDULE (CONT.)

CONDUCTORS GROUND CONDUIT

ALL CONDUCTORS ARE COPPER, TYPE THWN/THHN UNLESS OTHERWISE NOTED.

EQUIPMENT BONDING JUMPER FOR SEPARATELY DERIVED SYSTEMS PERNEC 250.66 (PROVIDE CONDUCTOR GROUND BELOW INSTEAD OF FEEDER GROUND FOR

THREE PHASE,4-WIRE SYSTEMS INDICATED ABOVE)

8

6

100Y-E

THREE PHASE FOUR WIRE 200% NEUTRAL & GROUND FEEDER

150Y-E

225Y-E

350Y-E

500Y-E

400Y-E

3-250 KCMIL,2-250 KCMIL NEUT.(2) 3#3/0,(2) 2#3/0 NEUT.(2) 3#4/0,(2) 2#4/0 NEUT.(2) 3-350 KCMIL,(2) 2-350KCMIL NEUT.

3#2, 1#4/0 NEUTRAL

3#2/0, 2#2/0 NEUT.

(2) 2

(2) 2

8

(2) 2

4

6 2"

2 1/2"

2"

(2) 3"

(2) 2 1/2"

(2) 2 1/2"

20YS THRU 100YS

125YS THRU 150YS

4175YS THRU 200YS

2225YS THRU 300YS

1/0350YS THRU 500YS

2/0600YS THRU 700YS

GROUNDDESIGNATION

800YS THRU 5000YS 3/0

800Y-E(2) 3-600 KCMIL,(2) 2-600KCMIL NEUT.

(2) 1/0 (2) 4"

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

As indicated

E-601A

NEW ARTBUILDINGNMSU LAS CRUCES, NM

ELECTRICAL DIAGRAMS

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB

OU

1/8" = 1'-0"E-601A

1 ELECTRICAL ONE LINE DIAGRAM (NEW WORK--EXISTING WILLIAMS HALL AND ANNEX)

1/8" = 1'-0"E-601A

2 ELECTRICAL ONE LINE DIAGRAM (DEMOLITION--EXISTING WILLIAMS HALL AND ANNEX)

NO SCALEE-601A

3 COPPER SCHEDULE.

1. NEW ELECTRICAL EQUIPMENT AND/OR FEEDER TO BE PROVIDED AND INSTALLED BY NMSU.

2. EXISTING ELECTRICAL EQUIPMENT AND/OR FEEDERS TO BE REMOVED IN ITS ENTIRETY.

3. DISCONNECT FROM EXISTING CIRCUIT AND REMOVE CONDUITS AND CONDUCTORS FROM VAULT.

4. EXISTING ELECTRICAL EQUIPMENT TO REMAIN AS PRESENTLY INSTALLED.5. EXISTING PANEL WILL BE RE-FED FROM "DB1". COORDINATE LOCATION OF

SPLICE WITH FIELD CONDITIONS.6. NMSU WILL PROVIDE AND INSTALL TRANSFORMER. STUB-UP CONDUITS UP

THROUGH CONCRETE PAD. COORDINATE WITH NMSU PRIOR TO ENERGEZING CONDUCTORS.

7. EXISTING LOADS ARE NOT BEING USED ANYMORE. REMOVE BRANCH CIRCUIT UP TO LOAD/DEVICE.

8. EXTEND UNDERGROUND RACEWAY PATHS AND CONDUCTORS FROM "DB1" TO EACH EXISTING FEEDER AS SHOWN. SPLICE CONDUCTORS IN NEW HANDHOLE. REFER TO SITE PLAN FOR ADDITIONAL INFORMATION.

9. 3#4/0 25 KV ALUMINUM, 100% INSULATION WITH 1/3 NEUTRAL AND 1#1/0 COPPER GROUND, IN ONE 4" PVC CONDUIT. EXTEND CONDUCTORS FROM EX. XFMT "T25-423" TO NEW "T1". COORDINATE WITH NMSU TERMINATIONS AT THE TRANSORMER(S). REFER TO SHEET ES-101 FOR TRANSFORMER LOCATIONS.

10. NOT USED.11. OVERCURRENT PROTECTION DEVICE SHALL BE ADJUSTED PER

COORDINATION STUDY.12. REFER TO SHEET ES-101 AND ESD-101 FOR SITE POLE LUMINAIRES

LOCATIONS AND ADDITIONAL INFORMATION.13. EXISTING PHOTOCELL SYSTEM IS MOUNTED AT THE VAULT. DISCONNECT

FROM EXISTING CIRCUIT AND PROTECT UNTIL RE-INSTALL.14. EXISTING PHOTOCELL SYSTEM SHALL BE RELOCATED AND MOUNTED TO

"DB1" AS SHOWN IN ES-101. 15. REMOVE EXISTING "ATS" AND SPLICE CONDUCTORS TO ASSURE CIRCUIT

CONTINUITY TO EX. PANEL "E1". MINIMIZE WORK AT THIS AREA AS MUCH AS POSSIBLE. COORDINATE WITH NMSU SHUTDOWN TIME TO THE EXISTING BUILDING.

A. PANELBOARD AIC RATINGS FOR PANELBOARDS ARE INDICATED ON THE PANEL SCHEDULES.

B. INFORMATION SHOWN IS DIAGRAMMATIC AND IS NOT INTENDED TO REPRESENT PHYSICAL ARRANGEMENTS, LOCATIONS, ROUTING ORCONNECTIONS. PHYSICAL LAYOUTS ARE TO BE PER FIELD CONDITIONS AND AS INDICATED ELSEWHERE IN THE ELECTRICAL PLANS.

C. REFERENCE THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTSREGARDING EQUIPMENT AND INSTALLATION.

D. CONTRACTOR WILL MEASURE AND TORQUE ALL PANEL FEEDERS, MEASURE RESISTANCE TO GROUND AT SERVICE GROUND AND PROVIDE WRITTEN DOCUMENTATION OF TEST RESULTS.

E. CONTRACTOR WILL LABEL ALL DISTRIBUTION EQUIPMENT PRIOR TO FINAL OBSERVATION WALKTHROUGH.

GENERAL SHEET NOTES

KEYNOTES

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:11:21-07'00'

Page 5: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

"T2"PADMOUNTED

TRANSFORMER3

1600 Y

1600AMCB

GFP

7

5

23.9 KV 480/277Y

M

"MSB"

480Y/277V, 3PH, 4W 1200A MAIN SWITCHBOARD

DEVICES MINIMUM

BUS BRACING MINIMUM

42KAIC

42KA

SPD

GROUND BUS

8

60A3P6

400A3P

60 Y

SECOND LEVEL

FIRST LEVEL

PENTHOUSE

225A3P

2

100 Y

PANEL"H2A"

100A

MLO

"T2DB"225KVA480-208Y/120V

400

10

100A3P

9

800 Y

400A3P

PANEL"1LP4"

PANEL"1LP3

PANEL"1LP2"

PANEL"1LP1"

225A3P6

225A3P6

225 Y 225 Y

225A3P6

225 Y

225A3P6

225 Y

"L1DB"

208Y/120V, 3PH, 4W 800A DIST. BOARD

DEVICES MINIMUM

BUS BRACING MINIMUM

22KAIC

22KA

PANEL"2LP4"

PANEL"2LP3"

PANEL"2LP2"

PANEL"2LP1"

100A3P6

225A3P6

225 Y 100 Y

100A3P6

100 Y

100A3P6

100 Y

"L2DB"

208Y/120V, 3PH, 4W 800A DIST. BOARD

DEVICES MINIMUM

BUS BRACING MINIMUM

14KAIC

14KA

PANEL"1LP5"

450A3P6

450 Y

PANEL"1LP6"

225A3P6

225 Y

PANEL"1LP7"

225A3P6

225 Y

PANEL"1LP8"

225A3P6

225 Y

600A3P

225 Y

225A

"TP"75KVA480-208Y/120V

600Y

100A3P

600A3P

85A3P

60A3P6

60 Y

SPD

60A3P6

60 Y

SPD

5

5

100 Y

1 E-602

TYP.

1 E-602

TYP.

1 E-602

1

"T1DB"300KVA480-208Y/120V

TYP.

1 E-602

400

800AMCB

800AMCB

800 Y

PANEL "LP"

150A3P

150A3P

16

15

3P150A

150

12

13

11

14

ELEVATORCONTROLLER

40

150A

G

ELEVATOR

SPARE SPACE

PANEL"M2A"

100A

MLO

150A

PANEL "MP"

600A

150 Y

SPARE SPACE SPARE

225A

MLO

225A

MLO

225A

MLO

225A

MLO

600A

MLO

225A

MLO

225A

MLO

225A

MLO

100A

MLO

100A

MLO

225A

MLO

100A

MLO

PANEL"L1A"

100A3P6

100 Y

100A

MLO

PANEL"L2A"

225A3P6

225 Y

225A

MLO

150A3P

150A3P

SPARE SPACE

70A3P6

"T-LT"45KVA480-208Y/120V

TYP.

1 E-602

70

PANEL"LT"

225A

MLO

150AD1

M

M

M

12,470 V

R

EXISTING MANHOLE

EXISTING MANHOLE R

PAD MOUNTED SWITCH

WORK WITHIN DASHED LINES IS BY NMSU.SHOWN HERE FOR INFORMATION ONLY.

M

M

M

M

M

4

LSIG LSIG LSIG LSIG LSIG

PANEL"LT2"

100A

MLO

225 Y

PANEL"H1B"

100A

MLO

225A3P

100A3P

100 Y

PANEL"M1"

225A

MLO

LSIG LSIG

PANEL"H1A"

100A

MLO

100A3P

100 Y

LSIG

16 17

PANEL"L1B"

225A3P6

225 Y

225A

MLO SPD

SPD

150 Y

100 Y

(2 SEC.) (2 SEC.)

(2 SEC.) (2 SEC.) (2 SEC.) (2 SEC.) (2 SEC.) (3 SEC.)

(2 SEC.)

25

40

35

30

45

50

60

70

90

80

125

100

200

175

225

250

150

300

350

450

400

700

600

800

1000

500

1200

1600

2500

2000

3000

NOTE:

NOTESDESIGNATION

35Y

40Y

30Y

45Y

50Y

60Y

70Y

80Y

90Y

125Y

100Y

175Y

200Y

225Y

250Y

150Y

300Y

350Y

450Y

400Y

600Y

700Y

800Y

1000Y

500Y

1200Y

1600Y

2000Y

2500Y

3000Y

THREE PHASE THREE WIRE & GROUND FEEDER

FEEDER SCHEDULE

25Y

20Y

EQUIPMENT BONDING JUMPER FOR SEPARATELY DERIVED SYSTEMS PERNEC 250.66 (PROVIDE CONDUCTOR GROUND BELOW INSTEAD OF FEEDER GROUND FOR

THREE PHASE,4-WIRE SYSTEMS INDICATED ABOVE)

20

4000

4000Y

5000Y

CONDUCTORS

4#6

(3) 4-600 KCMIL

(4) 4-600 KCMIL

(5) 4-600 KCMIL

(8) 4-500 KCMIL

(6) 4-600 KCMIL

(10) 4-600 KCMIL

(12) 4-600 KCMIL

(2) 4-250 KCMIL

(2) 4-350 KCMIL

(2) 4-500 KCMIL

(2) 4-600 KCMIL

(3) 4-400 KCMIL

4-250 KCMIL

(2) 4#4/0

4-350 KCMIL

4-500 KCMIL

4-600 KCMIL

4#4

4#4

4#2

4#2

4#1/0

4#2/0

4#3/0

4#4/0

4#1

4#10

4#10

4#12

4#8

4#8

4#8

4#8

GROUND

(3) 3/0

(4) 4/0

(5) 250 KCMIL

(6) 350 KCMIL

(8) 400 KCMIL

(10) 500 KCMIL

(12) 700 KCMIL

4

(2) 2

(2) 1

(2) 1

(2) 2

(2) 1/0

(3) 2/0

2

4

2

6

6

4

6

6

8

8

8

8

10

10

12

10

10

10

10

10

CONDUIT

(3) 4"

(4) 4"

(5) 4"

(6) 4"

(8) 4"

(10) 4"

(12) 4"

3"

(2) 3"

(2) 4"

(2) 4"

(3) 3"

(2) 3"

(2) 2 1/2"

4"

3"

4"

1 1/4"

1 1/4"

1 1/4"

1 1/4"

2 1/2"

1 1/2"

2"

2"

2"

3/4"

3/4"

1"

3/4"

3/4"

3/4"

3/4"

3/4"

(6) 3-600 KCMIL

(8) 3-500 KCMIL

(10) 3-600 KCMIL

(5) 3-600 KCMIL

(2) 3-600 KCMIL

(4) 3-600 KCMIL

(3) 3-600 KCMIL

(3) 3-400 KCMIL

(2) 3-250 KCMIL

(2) 3-500 KCMIL

(2) 3-350 KCMIL

3-600 KCMIL

(2) 3#4/0

3#1

3#2

3#2/0

3#1/0

3#4/0

3#3/0

3-250 KCMIL

3-500 KCMIL

3-350 KCMIL

3#10

3#8

3#10

3#8

3#8

3#6

3#4

3#8

3#2

3#4

3#12

(8)400 KCMIL

(6)350 KCMIL

(10)500 KCMIL

2

(2) 2

(2) 1

(2) 1

(2) 2

(5)250 KCMIL

(4) 4/0

(3) 3/0

(3) 2/0

(2) 1/0

4

2

4

4

6

6

6

6

8

10

10

10

10

10

10

10

8

8

8

12

(6) 4"

(8) 4"

(10) 4"

4"

(2) 4"

(2) 3"

(2) 3"

(3) 3"

(5) 4"

(4) 4"

(3) 4"

(2) 4"

(2) 2 1/2"

1 1/2"

1 1/4"

1 1/2"

2 1/2"

2"

3"

4"

3"

2"

3/4"

1 1/4"

1 1/4"

1 1/4"

1"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

8

6

THREE PHASE FOUR WIRE & GROUND FEEDER

ALL CONDUCTORS ARE COPPER, TYPE THWN/THHN UNLESS OTHERWISE NOTED.

100Y-E

THREE PHASE FOUR WIRE 200% NEUTRAL & GROUND FEEDER

150Y-E

225Y-E

350Y-E

500Y-E

400Y-E

3-250 KCMIL,2-250 KCMIL NEUT.(2) 3#3/0,(2) 2#3/0 NEUT.(2) 3#4/0,(2) 2#4/0 NEUT.(2) 3-350 KCMIL,(2) 2-350KCMIL NEUT.

3#2, 1#4/0 NEUTRAL

3#2/0, 2#2/0 NEUT.

(2) 2

(2) 2

8

(2) 2

4

6 2"

2 1/2"

2"

(2) 3"

(2) 2 1/2"

(2) 2 1/2"

20YS THRU 100YS

125YS THRU 150YS

4175YS THRU 200YS

2225YS THRU 300YS

1/0350YS THRU 500YS

2/0600YS THRU 700YS

GROUNDDESIGNATION

800YS THRU 5000YS 3/0

800Y-E(2) 3-600 KCMIL,(2) 2-600KCMIL NEUT.

(2) 1/0 (2) 4"

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

As indicated

E-601B

NEW ARTBUILDINGNMSU LAS CRUCES, NM

ELECTRICAL DIAGRAMS

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB

OU

SCALE: NONEA3 PHASE 3. ELECTRICAL ONE LINE DIAGRAM1

SCALE: NO SCALEA1 COPPER SCHEDULE1

ELECTRICAL CALCULATIONSScale: NOT TO SCALE

C2

1. SOLID STATE, ELECTRONIC TRIP CIRCUIT BREAKER WITH LONG-TIME, SHORT-TIME, INSTANTANEOUS AND GROUND FAULT FUNCTIONS. 100% RATED WITH ADJUSTABLE SETTINGS.

2. MEDIUM VOLTAGE SYSTEM TO BE PROVIDED BY NMSU. REFER TO SHEET ES-101 FOR ADDITIONAL INFORMATION.

3. SERVICE TRANSFORMER TO BE PROVIDED BY NMSU.4. SUBMETERS FOR FEEDER. BASIS OF DESIGN IS SQUARE D POWER LOGIC

ION 7300 METER WITH BACNET COMPABILITY OUTPUT.5. SPD MOUNTED EXTERNALLY TO SWITCHBOARD/PANELBOARD. WHERE

EQUIPMENT IS INSTALLED EXTERIOR TO THE BUILDING, THE EQUIPMENT WILL BE IN A NEMA 3R ENCLOSURE, LOCKABLE AND HINGED DOOR. SIZE OF ENCLOSURE WILL BE LARGE ENOUGH TO ACCOMMODATE MANUFATURER;S CLEARANCE REQUIREMENTS OF SPD DEVICE.

6. MOLDED CASE, THERMAL-MAGNETIC CIRCUIT BREAKERS, 100% RATED AND LOCKABLE.

7. INTEGRAL POWER MONITOR MOUNTED INTERNALLY TO SWITCHBOARD. REFER TO SPECIFICATIONS FOR METERING INSTRUMENTATION REQUIREMENTS.

8. REFER TO DETAIL 1 ON SHEET E-602 FOR GROUNDING INFORMATION FOR THIS EQUIPMENT.

9. METER TO BE PROVIDED BY OWNER.. PROVIDE CT'S AND PR'S AS REQUIRED. SIZE CT'S FOR FULL LOAD OF TRANSFORMER. PROVIDE (1) 1" CONDUIT FROM MSB TO NEAREST I/T ROOM.

10. ETHERNET OUTLET ADJACENT TO EACH METER. INCLUDE CONNECTION TO SERVER.

11. ELEVATOR CONTROL MODULE.12. GROUND CONDUCTOR FOR THIS ELEVATOR FEEDER WILL BE RATED FOR

100% OF THE PHASE CONDUCTORS AND NOT AS CALLED FOR IN FEEDER TAG/SCHEDULE.

13. CIRCUIT BREAKER WITH SHUNT TRIP COIL PROVIDED IN CONTROLLER BY ELEVATOR MANUFACTURER.

14. CONNECT FIRE ALARM AND ELEVATOR RECALL PER ELEVATOR INSTALLER'S RECOMMENDATIONS.

15. PROVIDE GFP FOR ELEVATOR.16. PROVIDE (3)2" UNDERGROUND SPARE CONDUITS FROM ELECTRICAL - M150

TO ELEC M125B. 17. PROVIDE (2)1" CONDUITS FROM ELECTRICAL - M150 TO PENTHOUSE FOR

FUTURE PV SYSTEM.

A. PANELBOARD AIC RATINGS FOR PANELBOARDS ARE INDICATED ON THE PANEL SCHEDULES.

B. INFORMATION SHOWN IS DIAGRAMMATIC AND IS NOT INTENDED TO REPRESENT PHYSICAL ARRANGEMENTS, LOCATIONS, ROUTING ORCONNECTIONS. PHYSICAL LAYOUTS ARE TO BE PER FIELD CONDITIONS AND AS INDICATED ELSEWHERE IN THE ELECTRICAL PLANS.

C. REFERENCE THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTSREGARDING EQUIPMENT AND INSTALLATION.

D. CONTRACTOR WILL MEASURE AND TORQUE ALL PANEL FEEDERS, MEASURE RESISTANCE TO GROUND AT SERVICE GROUND AND PROVIDE WRITTEN DOCUMENTATION OF TEST RESULTS.

E. CONTRACTOR WILL LABEL ALL DISTRIBUTION EQUIPMENT PRIOR TO FINAL OBSERVATION WALKTHROUGH.

GENERAL SHEET NOTES

KEYNOTES

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:16:51-07'00'

Page 6: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

~ ~

M

25 kV SYSTEM BY NMSU

<5'-0"

#4/0

#4/0

METER &BACKFLOWPREVENTER(S)

#4/0

#4/0

METER &BACKFLOWPREVENTER(S)

NEUTRALGROUND

COLDWATER

PIPE

GROUND NEUTRAL

"MSB"SERVICEENTRANCEEQUIPMENT

"T1DB"TRANSFORMER FORSEPARATELY DERIVEDSYSTEM (SIMILAR FORALL SEPARATELYDERIVED DRY-TYPETRANSFORMERS)

GROUND NEUTRAL

GROUND NEUTRALMAIN GROUNDINGELECTRODEGROUND BAR

TELECOMM ROOM

CW HW

WATERHEATER(TYPICAL)

NEUTRALGROUND

GROUND NEUTRAL

BUILDINGSTRUCTURALSTEEL

COLDWATER

PIPE

H1A, H1B, M1A

GROUND

#4/0

"LT" & "LT2"

#4/0WITH 600VINSULATION

GRADE

GROUND NEUTRAL

"T2"OUTDOORTRANSFORMERBY NMSU

#6

PIPE/CONDUIT

CABLE TRAY

#6

NOTE: ALL CONDUCTORS ARE COPPER.

SIZE OF LARGEST UNGROUNDED SERVICE-ENTRANCE

CONDUCTOR OR EQUIVALENT AREA FOR PARALLEL

CONDUCTORS.(AWG OR kCMIL)

SIZE OF GROUNDING ELECTRODE

CONDUCTOR (AWG)

<= #2

#1 OR 1/0

2/0 OR 3/0

OVER 3/0THROUGH 350

OVER 350THROUGH 600

OVER 600THROUGH 1100

OVER 1100

8

6

4

2

1/0

2/0

SEE KEYED NOTE 16

GROUNDING ELECTRODECONDUCTOR SCHEDULE

1010

10

2

1

7

10

9

6

5

4

14

10

10 1

16

10

10

16

10

3

1

11

20'-0" MINIMUM

12 13

15

METALLIC PIPE

14

BY NMSU

BY CONTRACTOR

#4/0

NEUTRALGROUND

GROUND NEUTRAL

"T2DB"TRANSFORMER FORSEPARATELY DERIVEDSYSTEM (SIMILAR FORALL SEPARATELYDERIVED DRY-TYPETRANSFORMERS)

NEUTRALGROUND

10

10 1

1610

SECONDARY GROUNDINGELECTRODEGROUND BAR

GROUND NEUTRALGROUND NEUTRAL

H2A, M2A

10

10

GROUND NEUTRALGROUND NEUTRAL

MP

10

"L2DB"

NEUTRALGROUND NEUTRALGROUND

10

10 1

TYPICAL FOR ALL 2LPX PANELS AND L2A

BUILDINGSTRUCTURAL

STEEL

NEUTRALGROUND

COLDWATER

PIPE

GROUND NEUTRAL

"TP"TRANSFORMER FORSEPARATELY DERIVEDSYSTEM

NEUTRALGROUND

4

14

10

10 1

1610

"LP"

BUILDINGSTRUCTURAL

STEEL

COLDWATER

PIPE

4

14

"L2DB"

NEUTRALGROUND NEUTRALGROUND

10

10 1

TYPICAL FOR ALL 1LPX PANELS AND L1A/L1B

GROUND NEUTRAL

"T2DB"TRANSFORMER FORSEPARATELY DERIVEDSYSTEM (SIMILAR FORALL SEPARATELYDERIVED DRY-TYPETRANSFORMERS)

10

1

1610

BUILDINGSTRUCTURAL

STEEL

COLDWATER

PIPE

4

14

NEUTRALNEUTRAL

GROUND NEUTRAL

"T3"OUTDOORTRANSFORMERBY NMSU

1010

10

2

"EM"GROUND NEUTRAL

16

10

GROUND NEUTRALGROUND NEUTRAL

EM1

10

GROUND NEUTRALGROUND NEUTRAL

EM2

10

5 kV EMERGENCY SYSTEM BY NMSU

"DB1"OUTDOOR SWITCHGEAR

GROUND NEUTRAL

GROUND NEUTRAL

"T1"OUTDOORTRANSFORMERBY NMSU

1010

10

2

1

16

10

1

"J1"

1

EX. WILLIAMS

HALL

"J2" "J3" "J4"

EX. ANNEX (NORMAL)

EX. ANNEX (EMERG.)

EX. SITE POLE

LUMINAIRES

PHASE II & III

PHASE I

P

TTB

FACP

MDF134

120VAC

120VAC

DC

SUP.RET.

12

7

2

11

3

TYP.

6

8

4

TYP.

1

MM

13

R

FSTS

FTS

14

L1C1-95

15

HOT BOX

1"C

PIV

FAA9

L1C1-XX

1"C

GENERAL SHEET NOTES

KEYNOTES

1. XXXX.

A. XXXX.A. INSTALL GROUNDING CONNECTIONS TO BUILDING STRUCTURE AND WATER PIPES AT LOCATIONS THAT ARE VISIBLE AND ACCESSIBLE FOR INSPECTION, MAINTENANCE, AND TESTING.

B. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC SERVICE ENTRANCE CONDUIT. BOND TO SERVICE ENTRANCE EQUIPMENT GROUND BUS USING NEC TABLE 250.102 (C)(1).

C. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC FEEDER CONDUIT. BOND TO GROUND BUS USING CONDUCTOR THAT IS SIZED EQUAL TO EQUIPMENT GROUNDING CONDUCTOR.

D. BOND ELECTRICAL EQUIPMENT ENCLOSURES TO GROUND BAR USING SAME SIZE CONDUCTOR AS FEEDER EQUIPMENT GROUND CONDUCTOR OR FACTORY PROVIDED GREEN SCREW.

E. CLEAN COATED RE-BAR PRIOR TO PERFORMING ELECTRICAL CONNECTIONS.

1. REFER TO ONE-LINE DIAGRAM AND FEEDER SCHEDULE FOR GROUNDED CONDUCTOR SIZE.

2. CONNECT GROUNDING ELECTRODE CONDUCTOR TO GROUND ROD.3. FOR EQUIPMENT GROUNDING CONDUCTOR SIZE REFER TO ONE-LINE

DIAGRAM AND FEEDER SCHEDULE.4. PROVIDE GROUNDING ELECTRODE CONDUCTOR SIZE BASED ON THE

CONDUCTOR SIZE OF THE SECONDARY OF THE TRANSFORMER. SIZE PER NEC 250.66 AND PER SCHEDULE ON THIS SHEET.

5. PROVIDE A CONCRETE-ENCASED MAIN GROUNDING ELECTRODE IN THE BUILDING FOUNDATION AROUND THE ENTIRE PERIMETER OF THE BUILDING. LOCATE ELECTRODE IN THE BOTTOM ONE-THIRD OF THE FOUNDATION WITH AT LEAST 3 INCHES OF CONCRETE COVER. USE EITHER #4/0 BARE COPPER CABLE OR #6 OR LARGER STEEL REINFORCING BARS MADE ELECTRICALLY CONTINUOUS USING EXOTHERMICALLY WELDED #4/0 JUMPERS.

6. BOND EACH PERIMETER STRUCTURAL STEEL COLUMN TO THE CONCRETE-ENCASED MAIN GROUNDING ELECTRODE. USE EXOTHERMIC WELDS.

7. PROVIDE A 1/4" X 4" X 12" "MAIN GROUNDING ELECTRODE GROUND BAR" FOR SINGLE POINT GROUNDING. LOCATE AT AN ACCESSIBLE POINT NEAR THE SERVICE ENTRANCE EQUIPMENT. MAKE OTHER CONNECTIONS TO THE GROUND BAR USING TWO-HOLE COMPRESSION SPADE LUGS THAT MEET IEEE 837 REQUIREMENTS. LABEL EACH CONNECTION.

8. XX9. INSTALL A 1/4" X 4" COPPER "TELECOMMUNICATIONS GROUNDING

BUSBAR" IN EACH TELECOMMUNICATIONS ROOM. CONNECT CABLES TO THE "TELECOMMUNICATIONS GROUNDING BUSBAR" USING COMPRESSION SPADE LUGS. LABEL CONDUCTORS PER ANSI-J-STD-607-A. LABEL EACH CONNECTION. SEE PLAN FOR BAR LENGTH AND LOCATIONS.

10. BONDING JUMPER SIZED PER GROUNDING ELECTRODE CONDUCTOR SCHEDULE THIS SHEET.

11. BOND HOT WATER PIPE TO COLD WATER PIPE AT EACH WATER HEATER WITH A #8 BARE COPPER CONDUCTOR.

12. PROVIDE A GROUND RING PER NEC 250.52 A.4.13. PROVIDE A GROUND ROD PER NEC 250.52 A.514. BOND ALL METALLIC PIPING SYTEMS WITHIN STRUCTURE.15. PROVIDE A GROUNDING ELECTRODE SYSTEM PER 2014 NMEC.16. MAIN BONDING JUMPER AND/OR SYSTEM BONDING JUMPER SIZE BASED

ON UNGROUNDED CONDUCTOR SIZE AND GROUNDING ELECTRODE CONDUCTOR SCHEDULE ON THIS SHEET UNLESS UNGROUNDED CONDUCTOR SIZE OR EQUIVALENT IS GREATER THAN 1100 KCMIL. IF GREATER THAN 1100 KCMIL (OR 1750 KCMIL FOR ALUMINUM) SIZE JUMPER PER NEC TABLE 250.102 (C)(1).

17. LIGHTNING PROTECTION COUNTERPOISE - #4/0 BARE COPPER.18. BOND EACH CORNER STRUCTURAL STEEL AND PERIMETER

STRUCTURAL STEEL AT NO MORE THAN 50 FOOT SPACING TO THE LIGHTNING PROTECTION COUNTERPOISE.

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

As indicated

E-602

NEW ARTBUILDINGNMSU LAS CRUCES, NM

GROUNDING DIAGRAM

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB

OU

SCALE: NO SCALEA4 FIRE ALARM RISER DIAGRAM1

GENERAL SHEET NOTES

KEYNOTES

1. XXXX.

A. XXXX.1. MINIMUM 3/4" CONDUIT AND FIRE ALARM CABLING AS REQUIRED BY THE FIRE ALARM MANUFACTURER.

2. INDEPENDENTLY SUPERVISE EACH FLOW AND TAMPER SWITCH WITH AN ADDRESSABLE MODULE. REFER TO FIRE PROTECTION/PLUMBING PLANS FOR LOCATION OF EACH LOCATION.

3. DIGITAL COMMUNICATOR FOR CENTRAL STATION MONITORING. 4. CONDUIT AND COMMUNICATIONS CABLING FOR CENTRAL STATION

REPORTING. 5. FIRE ALARM TERMINAL CABINETS (FATC) WILL BE FACTORY

MANUFACTURED, UL LABELED PANELS. THE FATC WILL ENCLOSE ALL TERMINATIONS FOR DEVICES ON THE FLOOR OR AREA IT SERVES. INTELLIGENT CARDS AS REQUIRED OR INDEPENDENT OPERATION, POWER SUPPLIES AND STANDBY BATTERIES WILL BE PROVIDED AT EACH LOCATION.

6. DUCT SMOKE DETECTOR, FURNISHED BY DIVISION 28. INSTALLED IN DUCT BY DIVISION 23. CONNECTED, WIRED AND TESTED BY DIVISION 28. REFERENCE MECHANICAL CONTROL DIAGRAMS FOR MECHANICAL INTERCONNECTIONS. PROVIDE DUCT DETECTORS IN NEW AND EXISTING UNITS WHERE 2000CFM AND ABOVE EXIST. INSTALL PER CODE.

7. FIRE SMOKE DAMPER. ROUTE 120VAC VIA FIRE ALARM ADDRESSABLE RELAY.

8. TELEPHONE TERMINAL BOARD. 9. PROVIDE NEW ANNUNCIATOR PANEL. FIELD COORDINATE EXACT

LOCATION.10. PROVIDE RACEWAY PATH OVERHEAD OR UNDERGROUND TO FATC. 11. NEW FIRE ALARM SYSTEM. LOCATION OF FACT AS SHOWN ON PLANS.12. PROVIDE SURGE PROTECTION FOR CIRCUIT TO FIRE ALARM PANEL.13. RELAY MODULES FOR SHUNT TRIP, AUTO RECALL, ALTERNATE RECALL,

AND FIRE CAP.14. TAMPER SWITCH IN HOT BOX. TERMINATE AS REQUIRED FOR

NOTIFICATION OF TAMPERING OF EQUIPMENT.PROVIDE SEPERATE DROP FOR ANALOG CONNECTION TO FIRE ALARM CONTROL PANEL, SHOULD DPS WISH TO HAVE FACP COMMUNICATION IN THIS FASHION.

A. FIRE ALARM DIAGRAM INDICATES GENERAL DIAGRAMMATIC CONNECTIONS ONLY. ALL CONNECTIONS AND INSTALLATION WILL BE PER FIRE ALARM SYSTEM MANUFACTURER'S SHOP DRAWINGS.

B. DEVICE QUANTITIES ARE NOT INDICATED ON THIS DRAWING. REFER TO FLOOR PLANS FOR QUANTITIES AND LOCATIONS.

C. REFER TO SPECIFICATION SECTION 283111 FOR FIRE ALARM SYSTEM REQUIREMENTS.

D. FIRE ALARM WIRING AND CABLING SHALL BE IN CONFORMANCE WITH NEC AND TYPE SHALL BE AS RECOMMENDED BY FIRE ALARM SYSTEM MANUFACTURER.

E. SEAL ALL PENETRATIONS THROUGH WALLS, FLOOR, CEILINGS AND ROOF PER ARCHITECTURAL SPECIFIED REQUIREMENTS. SEAL WILL MATCH THE FIRE RATING OF EACH PENETRATION LOCATION.

F. IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASIC PRESENTATION OF THE MINIMUM FIRE ALARM SYSTEM REQUIREMENTS. DEVICES INDICATED ON THESE DOCUMENTS ARE IN NO WAY IMPLIED TO BE COMPREHENSIVE OF THE FINAL DESIGN. IT IS THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR TO PROVIDE A COMPLETE FIRE ALARM SYSTEM BASED UPON THOROUGH REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR TO ENSURE THAT THE FIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE REQUIREMENTS OF THE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSTEMS IMPACTING THE FIRE ALARM SYSTEM.

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:17:04-07'00'

Page 7: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

Local Room Dataline

REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION

SEE INSTALLATION INSTRUCTIONSFOR TERMINATION TYPE.QUANTITY AS SHOWN ON PLAN.

LIGHTING CONTROL DESCRIPTIONAll room luminaires - Manual-ON/Manual or Auto-OFF

ADDITIONAL SWITCHES WILL BE CONNECTED FROM THE NEXT SWITCH. PROVIDE CABLE AS NECESSARY FOR COMPLETE CONTROLLABILITY.

RELAY 4

RELAY 3

RELAY 2

RELAY 1 DIM 1

DIM 2

DIM 3

DIM 4

ROOM CONTROLLER#WRC-3160

DATALINE

ROOMLUMINAIRES

Hot

120/277

0-10V CONTROL

ONE BUTTON DIMMING SWITCH

TYPE "D"#WSD-3501

EM. EXPANSION

TOPOLOGY/POLARITY FREE

BACK TO DIALOG PANEL

ONE BUTTON DIMMING SWITCH

TYPE "D"#WSD-3501

(ZONES AS NOTED ON DRAWINGS)

REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION

RELAY 4

RELAY 3

RELAY 2

RELAY 1 DIM 1

DIM 2

DIM 3

DIM 4

ROOM CONTROLLER#WRC-3160

DATALINE

LightingLoad(a)

LightingLoad(a)

Hot

120/277

0-10V CONTROL

EM. EXPANSION

Local Room Dataline18AWG / 2-Wire

Non-Polarized

VACANCY SENSOR TYPE "DCDT"#WORSDG1

DAYLIGHT SENSOR#WPS-3711-P-N

TOPOLOGY/POLARITY FREE

ADDITIONAL SWITCHES WILL BE CONNECTED FROM THE NEXT SWITCH. PROVIDE CABLE AS NECESSARY FOR COMPLETE CONTROLLABILITY.

BACK TO DIALOG PANEL

DRIVER

Line

White

Green

Black

Neutral

Ground

Gray

120V/230V/277V Ground

Violet

YellowTraveler

Red

0-10V

0-10V

OCC

LIGHTING CONTROL DESCRIPTION

All room luminaires - Auto-ON/Manual or Auto-OFF

REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION

VACANCY SENSOR TYPE "DCDT"#WORSDG1

SEE INSTALLATION INSTRUCTIONSFOR TERMINATION TYPE.

LIGHTING CONTROL DESCRIPTIONMain Scene (1) (Dimming Switches will control all lights in room) Manua-ON/Auto-OFF. Note: If two or more main dimmers exist within same room, last dimmer setting will override

the other dimmer status to that same dimmed level

Scene (1) (100% lumen output of all LED luminaires) Manual-ON/Auto-OFFScene (2) (50% lumen output of all LED luminaires) Manual-ON/Auto-OFFScene (3) (turn off front of room luminaires and 50% lumen output of back of

room LED luminaires. If there is an odd number of luminaire rows, include the middle row as part of the back room luminares (50%)) Manual-ON/Auto-OFF

THREE BUTTON SWITCHTYPE "3"

#WSW-3513

ADDITIONAL SWITCHES/SENSORS WILL BE CONNECTED FROM THE NEXT SWITCH/SENSOR.

PROVIDE CABLE AS NECESSARY FOR COMPLETE CONTROLLABILITY.

100% LIGHT LEVEL

50% = 50% LIGHT LEVEL

A/V=FRONT OFF/BACK 50%

LIGHTING CONTROL DESCRIPTION PLACARD

MOUNT ADJACENT TO SWITCH(ES)

RELAY 4

RELAY 3

RELAY 2

RELAY 1 DIM 1

DIM 2

DIM 3

DIM 4

ROOM CONTROLLER#WRC-3160

DATALINE

BACK OF ROOMLUMINAIRES

FRONT OF ROOMLUMINAIRES

Hot

120/277

0-10V CONTROL

ONE BUTTON DIMMING SWITCH

TYPE "D"#WSD-3501

DAYLIGHT SENSOR#WPS-3711-P-N

EM. EXPANSIONREFER TO E-603 FOR

ADDITIONAL INFORMATION

Dimmer UpDimmer Down

All Lights On

Local Room Dataline18AWG / 2-Wire

Non-Polarized

100%

50%

A/VTOPOLOGY/POLARITY FREE

BACK TO DIALOG PANEL

Local Room Dataline

REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION

SEE INSTALLATION INSTRUCTIONSFOR TERMINATION TYPE.QUANTITY AS SHOWN ON PLAN.

LIGHTING CONTROL DESCRIPTIONAll room luminaires - Manual-ON/Manual or Auto-OFF

ADDITIONAL SWITCHES WILL BE CONNECTED FROM THE NEXT SWITCH. PROVIDE CABLE AS NECESSARY FOR COMPLETE CONTROLLABILITY.

RELAY 2

RELAY 1 DIM 1

DIM 2

ROOM CONTROLLER#WRC-3260

DATALINE

ROOMLUMINAIRES

Hot

120/277

0-10V CONTROL

ONE BUTTON DIMMING SWITCH

TYPE "D"#WSD-3501

EM. EXPANSION

DAYLIGHT SENSOR#WPS-3711-P-N

TOPOLOGY/POLARITY FREE

DATALINE BACK TO DIALOG PANEL

REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION

Neutral

LANTERNLUMINAIRES

DMX CONDUCTORDMX CONTROLLER

STICK-DE3

Hot

120/277

POWER4M

TO LIGHTING CONTROL UNIT

6-7VDC

POWER SUPPLY(DRIVER)

120/277

Hot

DATA BOX

REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION

TRACK LIGHTING SYSTEM

LUMINAIRES

36 CIRCUITRELAY BOX

120/277

Hot

DIMMER BOXDOUGLAS #DLS-RP

1LP70-10V

LCPBACK TO DIALOG PANEL

LCP SHALL PROVIDESEPARATE DIMMING CONTROL FOR EACH ZONES (TRACK ROW)

a,b,c,d,e,f,g

WRC-LCD

Hot

120/277

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

As indicated

E-603

NEW ARTBUILDINGNMSU LAS CRUCES, NM

LIGHTING CONTROL DIAGRAMS

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

Checker

Author

NO SCALEE-603

2 DOUGLAS CONTROL WIRING DIAGRAM

NO SCALEE-603

5 DOUGLAS CONTROL WIRING DIAGRAM

GENERAL SHEET NOTES

A. CONTRACTOR WILL PROVIDE ENGRAVED SWITCHES AND A PLACARD WITH CONTROL DESCRIPTION. PLACARD WILL BE PER ARCHITECTURAL REQUIREMENTS, PLACARD WILL BE NO LARGER THAN A SWITCH COVER PLATE.

B. DIAGRAMS ARE FOR INFORMATION ONLY AND DO NOT REFLECT THE CORRECT NUMBER OF DEVICES. REFER TO "EL" SHEETS FOR QUANTITIES AND TO MANUFACTURERS RECOMMENDATIONS FOR LOCATION OF LIGHTING CONTROL DEVICES.

1/8" = 1'-0"E-603

3 WALL OCC SENSOR 0-10V DIMMING SINGLE LOAD

LIGHTING SEQUENCE: TYPE "E" (CONFERENCE ROOM)

LIGHTING SEQUENCE: TYPE "H" (LABS W/O PROJECTOR)

NO SCALEE-603

6 DOUGLAS CONTROL WIRING DIAGRAMLIGHTING SEQUENCE: TYPE "G" (LABS W/ PROJECTOR)

NO SCALEE-603

4 DOUGLAS CONTROL WIRING DIAGRAM

NO SCALEE-603

1 DMX CONTROL WIRING DIAGRAM

LIGHTING SEQUENCE: TYPE "D" (OFFICES)

LIGHTING SEQUENCE: (LANTERN DMX)

LIGHTING SEQUENCE: TYPE "A" (RESTROOMS)

LIGHTING SEQUENCE OF OPERATION

A. RESTROOMS (MEN & WOMEN):a. DUAL TECHNOLOGY (ULTRASONIC/INFRARED) SENSORS WILL CONTROL

ENTIRE ROOM. • OCCUPIED MODE: OCCUPANCY SENSOR WILL TURN LIGHTS IN

RESTROOM UPON MOTION DETECTION, AUTO-ON, AUTO-OFF.• UNOCCUPIED MODE: ALL LIGHT SHALL BE DISABLED IN RESTROOM

BY OCCUPANCY SENSOR(S) AFTER 10 MINUTES OF NO MOTION DETECTION.

B. FAMILY RESTROOMS (SMALL):a. SMALL: THE WALL-MOUNTED SENSOR WILL CONTROL LUMINAIRES.

MANUAL ON/ AUTO OFF. WALKTHROUGH FEATURE IS DESIRED.C. UTILITY ROOMS (STORAGE, JANITORS AND THE LIKE): WALL-MOUNTED

OCCUPANCY SENSOR WILL CONTROL THE LUMINAIRE(S) IN THE ROOM. MANUAL ON/ AUTO OFF.

D. OFFICES, SMALL/LARGE:a. WALL-MOUNTED DIMMING SWITCHES WILL CONTROL LUMINAIRES. MANUAL

ON/ AUTO OFF. b. WHEN ROOM IS UNOCCUPIED, ALL LIGHTING SHALL BE DISABLED AND DE-

ENERGIZED BY OCCUPANCY SENSOR(S) IN ROOM CEILING E. CONFERENCE ROOMS

a. WALL-MOUNTED DIMMING SWITCHES WILL CONTROL LUMINAIRES. MANUAL ON/ AUTO OFF.

b. WHEN ROOM IS UNOCCUPIED, ALL LIGHTING SHALL BE DISABLED AND DE-ENERGIZED BY OCCUPANCY SENSOR(S) IN ROOM CEILING

c. REFER TO FLOOR PLAN FOR LIGHTING ZONES.F. UNDERCABINETS LIGHT (APPLIES TO ALL UNDER CABINET LIGHT)

a. DEDICATED-TO-CABINET TOGGLE SWITCHES WILL CONTROL UNDERCABINET TASK LUMINAIRES.

b. OCCUPANCY SENSOR ON ROOM/SPACE WILL ALSO DE-ENERGIZE UNDERCABINET TASK LIGHTING WHEN SENSOR TIMES OUT.

c. LOCATE HARDWIRE POWER SUPPLY (DRIVER) INSIDE OF CABINET AND COORDINATE WITH CABINET INSTALLER. COORDINATE NUMBER OF POWER SUPPLY BASED ON THE NUMBER OF FIXTURES IT CAN POWER (BASIS OF DESIGN IS 100W POWER SUPPLY).

d. COORDINATE LENGTH OF LUMINAIRE WITH CABINET ACTUAL LENGTH DIMENSIONS.

G. LABORATORY WITH PROJECTOR/PRESENTATION SCREEN (VARIOUS ROOMS WILL HAVE DIFFERING CONTROL LOADS. SEE DIAGRAMS AND ROOMS FOR ADDITIONAL INFORMATION. INFORMATION BELOW IS TYPICAL.)a. LIGHTING CONTROL IN ROOM WILL BE ENABLED BY MAIN DIMMING

SWITCHES IN ROOM. NO LUMINAIRE WILL AUTOMATICALLY ENERGIZZE.b. IN ADDITION, THREE-BUTTON WALL MOUNTED SWITCHES BY THE

INSTRUCTORS DESK WILL PROVIDE OVERRIDE SETTINGS AS SHOWN ON DETAIL DIAGRAM.

H. LABORATORY WITHOUT PROJECTOR/PRESENTATION SCREEN (VARIOUS ROOMS WILL HAVE DIFFERING CONTROL LOADS. SEE DIAGRAMS AND ROOMS FOR ADDITIONAL INFORMATION. INFORMATION BELOW IS TYPICAL.)a. LIGHTING CONTROL IN ROOM WILL BE ENABLED BY MAIN DIMMING

SWITCHES IN ROOM. NO LUMINAIRE WILL AUTOMATICALLY ENERGIZED.b. IN ADDITION, THREE-BUTTON WALL MOUNTED SWITCHES BY THE

INSTRUCTORS WORKING DESK WILL PROVIDE OVERRIDE SETTINGS AS SHOWN ON DETAIL DIAGRAM.

I. ART GALLERYa. WALL-MOUNTED SWITCHES WILL CONTROL TRACK LIGHTING. MANUAL ON/

AUTO OFF. REFER TO FLOOR PLAN FOR LIGHTING ZONES.b. A SEPARATE SWITCH WILL CONTROL AMBIENT LIGHT FOR CLEANING AND

MAINTENANCE PURPOSES.J. PHOTOGRAPHY LAB

a. WALL-MOUNTED DIMMING SWITCHES WILL CONTROL LUMINAIRES. MANUAL ON/ MANUAL OFF. REFER TO FLOOR PLAN FOR LIGHTING ZONES.

b. TUNNABLE WHITE LIGHT WILL BE PROVIDED FOR LAB FLEXIBILITY GIVING THE USERS THE ABILITY TO CHANGE THE COLOR TEMPERATURE OF THE LIGHTS.

K. FILM PROCESSING LAB - DARK ROOMa. WALL-MOUNTED SWITCHES WILL CONTROL LUMINAIRES. MANUAL ON/

MANUAL OFF. REFER TO FLOOR PLAN FOR LIGHTING ZONES.b. SPECIALTY TYPE LIGHT WILL BE PROVIDED TO AVOID FILM DAMAGE.

L. EXTERIOR BUILDING LIGHTING:a. ALL EXTERIOR BUILDING LIGHTING WILL BE PROGRAMMED TO COME ON A

1/2 HOUR BEFORE DUSK AND OFF A 1/2 HOUR AFTER DAWN.M. DAYLIGHT SENSORS:

a. DAYLIGHT SENSORS WILL CONTROL LUMINAIRES WITHIN 15 FT OF LOBBY VERTICAL FENESTRATION AND WINDOW WIDTH PLUS 2 FT ON EACH SIDE. DAYLIGHT SENSOR WILL MAINTAIN 20 FOOTCANDLES AT ALL TIMES.

b. DAYLIGHT SENSOR WILL OVERRIDE ANY LIGHT LEVEL SET BY THE LUMINAIRE SWITCH.

N. SITE LIGHTING:1. ALL ROADWAY LIGHTING WILL BE PROGRAMMED TO COME ON A 1/2

HOUR BEFORE DUSK AND OFF A 1/2 HOUR AFTER DAWN.2. PARKING LOT AREA LIGHTING WILL BE PROGRAMMED TO COME ON A 1/2

HOUR BEFORE DUSK AND OFF AT 11 PM.3. ALL WALKWAY LIGHTING, EXCEPT THOSE NOTED, WILL COME ON A 1/2

HOUR BEFORE DUSK AND OFF AT 11 PM.4. DESIGNATED WALKWAY LIGHTING WILL BE ON A 1/2 HOUR BEFORE

DUSK AND OFF A 1/2 HOUR AFTER DAWN.

NO SCALEE-603

7 DOUGLAS CONTROL WIRING DIAGRAM

NO. ISSUE DATE1 DESIGN DEVELOPMENT - PRELIMINARY SUBMITTAL 05/03/2017

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:17:14-07'00'

Page 8: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

FIRST FLOOR SECOND FLOOR

ZONE 1

ZONE 2

ZONE 3

ZONE 4

ZONE 5

ZONE 6

ZONE 7

ZONE 8

ZONE 6

ZONE 9

ZONE 5

H101B

HALL

H101A

HALL

100B

ENTRANCELOBBY

H101

EXHIBITIONHALL

H101D

HALL

H101F

HALL

100F

ELEVATORLOBBY

120

STUDENTCOLLABORATION

H101E

HALL

140A

RECEIVINGYARD

140

EXTERIORYARD

H201E

HALL

120

STUDENTCOLLABORATION

H201F

HALL

H201F

HALL

ST101B

SOUTHSTAIR

ST101B

SOUTHSTAIR

H201D

HALL

ZONE 10

D

J127

JANITOR

DMX

D

D

DOUGLAS LIGHTING

CONTROL UNIT

EXTERIOR LTG -NORTH/WEST)

ETHERNET OUTLET ADJACENT TO RELAY PANEL. INCLUDE CONNECTION TO SERVER

H1B-7

277 V

LCP-BROOM: ELEC-M125B

LIGHTING CONTROL

UNIT

277 V

WLC-3150

LIGHTING RELAY PANEL

WRD-3408

LCP-CROOM: ELEC-T225B

LIGHTING RELAY PANEL

WRD-3408

1ST LEVEL HALLWAY

SOUTH/EASTDM. 0-10V

LCU

K

DATA LINEOS OCCUPANCY SENSORS ARE

USED IN HALLWAYS FOR AFTER HOUR USE

DATA LINEOS OCCUPANCY SENSORS ARE

USED IN HALLWAYS FOR AFTER HOUR USE

PC

1ST LEVEL HALLWAY

SOUTH/EASTDM. 0-10V

K

K

H1B-4

EM1-1

SPAREK

SPAREK

SPAREK

SPAREK

ETHERNET OUTLET ADJACENT TO RELAY PANEL. INCLUDE CONNECTION TO SERVER

PANEL EM1

"H" PANEL

"H" PANEL

2ND LEVEL HALLWAY

DM. 0-10V

K

2ND LEVEL HALLWAY

DM. 0-10V

K

LANTERN LIGHTSDMX

H2A-9"H" PANEL

H2A-5

EM2-5

SPAREK

SPAREK

SPAREK

SPARE

"H" PANEL

EXHIBITION HALL

DM. 0-10V

K

EXHIBITION HALL

DM. 0-10V

K

H2A-7

EM2-11

"H" PANEL

E-RELAY

E-RELAY

1ST LEVEL HALLWAY

NORTH/EASTDM. 0-10V

K

1ST LEVEL HALLWAY

NORTH/EASTDM. 0-10V

K

H1B-9

EM1-3PANEL

EM1

"H" PANEL

PANEL EM2

PANEL EM2

E-RELAY

E-RELAY

DOUGLAS LIGHTING

CONTROL UNIT

ETHERNET OUTLET ADJACENT TO RELAY PANEL. INCLUDE CONNECTION TO SERVER

277 V

LCP-AROOM: ELEC-M150

LIGHTING RELAY PANEL

WRD-3408LCU

PC

SPAREK

SPAREK

SPAREK

SPAREK

EXTERIOR YARD (PHOTOCELL

CONTROLLED)DM. 0-10V

K

DM. 0-10V

K

H1A-3

EM-1PANEL

EM1

"H" PANEL

E-RELAY

EXTERIOR LIGHTING -

SOUTH AND YARD

K

EXTERIOR LIGHTING -

SOUTH

K

H1A-5

EM-3PANEL

EM1

"H" PANEL

E-RELAY

EXTERIOR YARD (PHOTOCELL

CONTROLLED)

SPAREK

SPAREK

1ST LEVEL HALLWAY

WESTDM. 0-10V

K

1ST LEVEL HALLWAY

WESTDM. 0-10V

K

H1B-10

EM1-5PANEL

EM1

"H" PANEL

E-RELAY

EXTERIOR WALL

PACKSDM. 0-10V

K

EXTERIOR WALL

PACKS SOUTH

DM. 0-10V

K

H2A-4

EM2-1

"H" PANEL

E-RELAY

PANEL EM2

EXTERIOR WALL

PACKS NORTH

DM. 0-10V

KEM2-3

E-RELAY

PANEL EM2

120V

120V

120V

120V120V

120V

120V

120V

120V

277V

277V

277V

277V

277V

277V

277V

277V

277V

277V

MOUNT PHOTOCELL ON EXTERIOR YARD

CANOPY ROOF ROOF MOUNTED

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

NO SCALE

E-604

NEW ARTBUILDINGNMSU LAS CRUCES, NM

ELECTRICAL LIGHTING DIAGRAMS

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB

OU

NO SCALEE-604

1 LIGHTING HALLWAY CONTROL

1. ZONE 1 (EXHIBITION HALL & ENTRANCE LOBBY): a. OVERALL CONTROL WILL BE PROGRAMMED ON AT 5 AM AND OFF AT 11 PM.b. FROM 11 PM TO 5 AM. OCCUPANCY SENSORS WILL OVERRIDE CLOCK AND

TURN LIGHTS ON FOR 30 MINUTE INCREMENTS. LIGHTING WILL SIGNAL A BLINK OF THE LIGHTS (5) FIVE MINUTES BEFORE SHUT DOWN.

c. OVERRIDE HALLWAY CONTROL WILL BE SET THROUGH DIMMER SWITCHES LOCATED AT THE ART GALLERY - 105.

2. ZONE 2 (HALL H101B & H101A), ZONE 3 (ROOMS 118, 1180G & 118H), ZONE 4 (HALL H101F, H101F, H101E) & ZONE 9 (HALL H201E, H201D, H201F, H201F)a. OVERALL CONTROL WILL BE PROGRAMMED ON AT 5 AM AND OFF AT 11 PM.b. FROM 11 PM TO 5 AM. OCCUPANCY SENSORS WILL OVERRIDE CLOCK AND

TURN LIGHTS ON FOR 30 MINUTE INCREMENTS. LIGHTING WILL SIGNAL A BLINK OF THE LIGHTS (5) FIVE MINUTES BEFORE SHUT DOWN.

3. ZONE 5 (SOUTH STAIR - ST101B)a. LUMINAIRES WILL OPERATE 24/7.b. FROM 11 PM TO 5 AM. OCCUPANCY SENSORS IN HALLWAYS/CORRIDOR

WILL DIM THE LIGHTS DOWN UPON NO DETECTION (DAMP DOWN/RAMP UP).

4. ZONE 6 (STUDENT COLLABORATION - 120)a. OVERALL CONTROL WILL BE PROGRAMMED ON AT 5 AM AND OFF AT 11 PM.b. FROM 5 AM TO 11 PM. OVERRIDE DIMMING SWITCHES, LOCATED AT THE

FIRST FLOOR AREA, WILL OVERRIDE ZONE 6 LUMINAIRES.c. AFTER HOURS: OVERRIDE DIMMING SWITCHES WILL CONTROL AND TURN

LIGHTS ON FOR 1 HOURS ONLY. IF LIGHTING WAS ON BEFORE CLOCK OFF SETPOINT, LIGHTS WILL STAY ON FOR 1 HOUR AFTER THAT TIME. LIGHTING WILL SIGNAL A BLINK OF THE LIGHTS (5) FIVE MINUTES BEFORE SHUT DOWN.

5. ZONE 7 (EXTERIOR YARD - 140)a. LUMINAIRES WILL BE CONTROLLED BY A PHOTOCELL MOUNTED ON TOP OF

THE CANOPY. LUMINAIRES WILL BE OFF DURING THE DAY AND ON DURING NIGHT/DARK TIME.

b. OVERRIDE SWTICHES LOCATED AT FACULTY STUDIO (SAFETY)-242 WILL OVERRIDE LUMINAIRES IN ZONE 7.

6. ZONE 8 (RECIEVING AREA - 140A)a. EXTERIOR LIGHTING WILL BE ON 1/2 HOUR BEFORE DUSK AND OFF 1/2

HOUR AFTER DAWN.b. OVERRIDE SWITCHES WILL TURN LIGHTS ON FOR 2 HOURS.

7. ZONE 10 (CUPULA) RGB EXTERIOR LUMINAIRES - DMX CONTROLa. OVERALL CONTROL WILL BE PROGRAMMED ON AT 5 AM AND OFF AT 11 PM.

COORDINATE FINAL SETTINGS WITH NMSU REPRESENTATIVE/USERS.b. CONTROLLER WILL PROVIDE AUTOMATED SELECTION OF MULTIPLE

SCENES WITH PROGRAMMING CAPABILITIESc. CONTROLLER WILL PROVIDE SCENES OF DIFFERENT COLORS THAT CAN

BE SELECTED MANUALLY AT CONTROL KEYPAD OR AUTOMATICALLY THOUGH A BACNET ENABLED FMS SYSTEM.

d. DMX CONTROLLER WILL BE LOCATED IN FIRST FLOOR JANITOR CLOSET.

LIGHTING SEQUENCE OF OPERATIONFOR PROGRAMMABLE CONTROL SETTINGS

NO SCALEE-604

2 LIGHTING RELAY PANEL DIAGRAM2

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:17:25-07'00'

Page 9: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

E-701

NEW ARTBUILDINGNMSU LAS CRUCES, NM

ELECTRICAL LUMINAIRE SCHEDULES

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB

OU

ELECTRICAL LUMINAIRE SCHEDULE

TYPE DESCRIPTION VOLTS MOUNTINGLAMPS (NEED TO BE ENERGY STAR

OR DLC LISTED) LED DRIVERINPUTWATTS EM. BAT. PK. LENS MANUFACTURER/MODEL NOTES

A2 2' x 2' X 3 1/4" RECESSED LED VOLUMETRIC LUMINAIRE, COLD ROLLED STEELHOUSING, BAKED WHITE ENAMEL FINISH WITH MODULAR FIELD UPGRADEABLE LEDSAND DRIVERS. WHITE FINISH STANDARD

277 0R 120MULTI TAP

(UNV.)

RECESSED T-BAR LED3500K4400 LUMEN85 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE WHITE ACRYLIC METALUX #22CZ

AR 2' x 4' ARCHITECTURAL/DECORATIVE LED LUMINAIRE. HIGH ENERGY EFFICIENCY. LOWPROFILE, WIDE DISTRIBUTION WITH 0-10V DIMMING CONTROL. BAKED MATTE WHITEENAMEL FINISH.

277 OR 120MULTI-TAP

(UNV.)

CEILING RECESSED (LAY-IN GRID) LED3500K3000 LUMEN85 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE WHITE ACRYLIC METALUX # 24CZ 1

AR2 2' x 2' X 3 1/4" RECESSED LED VOLUMETRIC LUMINAIRE, COLD ROLLED STEELHOUSING, BAKED WHITE ENAMEL FINISH WITH MODULAR FIELD UPGRADEABLE LEDSAND DRIVERS. WHITE FINISH STANDARD

277 0R 120MULTI TAP

(UNV.)

RECESSED T-BAR LED3500K3000 LUMEN85 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE WHITE ACRYLIC METALUX #22CZ

AR2E 2' x 2' X 3 1/4" RECESSED LED VOLUMETRIC LUMINAIRE, COLD ROLLED STEELHOUSING, BAKED WHITE ENAMEL FINISH WITH MODULAR FIELD UPGRADEABLE LEDSAND DRIVERS. EMERGENCY THROUGH LIGHTING INVERTER. WHITE FINISH STANDARD

277 0R 120MULTI TAP

(UNV.)

RECESSED T-BAR LED3500K3000 LUMEN85 CRI MIN.

0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING

CIRCUIT

WHITE ACRYLIC METALUX #22CZ 1,2

ARD 2' x 4' ARCHITECTURAL/DECORATIVE LED LUMINAIRE. HIGH ENERGY EFFICIENCY. LOWPROFILE, WIDE DISTRIBUTION WITH 0-10V DIMMING CONTROL. BAKED MATTE WHITEENAMEL FINISH.

277 OR 120MULTI-TAP

(UNV.)

CEILING RECESSED (LAY-IN GRID) 4500 LUMEN LED,3500° K,85 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE WHITE ACRYLIC METALUX # 24CZ 1

ARE 2' x 4' ARCHITECTURAL/DECORATIVE LED LUMINAIRE. HIGH ENERGY EFFICIENCY. LOWPROFILE, WIDE DISTRIBUTION WITH 0-10V DIMMING CONTROL. BAKED MATTE WHITEENAMEL FINISH.

277 OR 120MULTI-TAP

(UNV.)

CEILING RECESSED (LAY-IN GRID) LED3500K3000 LUMEN85 CRI MIN.

0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING

CIRCUIT

WHITE ACRYLIC METALUX # 24CZ 1,3,4

Bl 4' LONG LIFE LED, HIGH ENERGY EFFICIENT LINEAR STRIP LUMINAIRE. BAKED MATTEWHITE ENAMEL FINISH.

277 OR 120MULTI-TAP

(UNV.)

CEILING SURFACE OR BOTTOM OFJOIST OR WALL MOUNTED AT 8'-0"

LED3500K3700 LUMEN85 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE SEMI-FROST METALUX # 4SNLED 1,2

BlE 4' LONG LIFE LED, HIGH ENERGY EFFICIENT LINEAR STRIP LUMINAIRE. BAKED MATTEWHITE ENAMEL FINISH.

277 OR 120MULTI-TAP

(UNV.)

CEILING SURFACE OR BOTTOM OFJOIST OR WALL MOUNTED AT 8'-0"

LED3500K3700 LUMEN85 CRI MIN.

0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING

CIRCUIT

SEMI-FROST METALUX # 4SNLED 1,2

C1 6" ROUND LED DOWN LIGHT FIXTURE, OPEN OPTICS, SEMI-SPECULAR CLEARREFLECTOR, WHITE TRIM RING. LISTED FOR DAMP LOCATION.

277 OR 120MULTI-TAP

(UNV.)

CEILING RECESSED LED3500K1500 LUMEN80 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE NO LENS (OPENOPTICS)

ATLANTIC # LED6 1

C1E 6" ROUND LED DOWN LIGHT FIXTURE, OPEN OPTICS, SEMI-SPECULAR CLEARREFLECTOR, WHITE TRIM RING. LISTED FOR DAMP LOCATION.

277 OR 120MULTI-TAP

(UNV.)

CEILING RECESSED LED3500K1500 LUMEN80 CRI MIN.

0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING

CIRCUIT

NO LENS (OPENOPTICS)

ATLANTIC # LED6 1

C2 6" ROUND LED DOWN LIGHT FIXTURE, OPEN OPTICS, SEMI-SPECULAR CLEARREFLECTOR, WHITE TRIM RING. WALL WASH OPTION.

277 OR 120MULTI-TAP

(UNV.)

CEILING RECESSED LED3500K1500 LUMEN80 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE NO LENS (OPENOPTICS)

ATLANTIC # LED6 1

C6 6" ROUND LED DOWN LIGHT FIXTURE, OPEN OPTICS, SEMI-SPECULAR CLEARREFLECTOR, WHITE TRIM RING.

277 OR 120MULTI-TAP

(UNV.)

CEILING RECESSED LED3500K1500 LUMEN80 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE NO LENS (OPENOPTICS)

ATLANTIC # LED6 1

C6E 6" ROUND LED DOWN LIGHT FIXTURE, OPEN OPTICS, SEMI-SPECULAR CLEARREFLECTOR, WHITE TRIM RING.

277 OR 120MULTI-TAP

(UNV.)

CEILING RECESSED LED3500K1500 LUMEN80 CRI MIN.

0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING

CIRCUIT

NO LENS (OPENOPTICS)

ATLANTIC # LED6 1

CA 6" ROUND LED CYLINDER TYPE DOWN LIGHT FIXTURE, CLEAR OPTICS, BLACK FINISH. 277 OR 120MULTI-TAP

(UNV.)

SURFACE MOUNTED TO DECK LED3000K1500 LUMEN80 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE CLEAR OPTIC ATLANTIC # SLED 610 1

CAE 6" ROUND LED CYLINDER TYPE DOWN LIGHT FIXTURE, CLEAR OPTICS, BLACK FINISH. 277 OR 120MULTI-TAP

(UNV.)

SURFACE MOUNTED TO DECK LED3000K1500 LUMEN80 CRI MIN.

0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING

CIRCUIT

CLEAR OPTIC ATLANTIC # SLED 610 1

E LED SINGLE FACED EXIT SIGN, EMERGENCY, DIE CAST ALUMINUM HOUSING WITHGREEN CHARACTERS, BLACK HOUSING AND BRUSHED ALUMINUM FACE (DIRECTIONALARROWS AS INDICATED ON LIGHTING PLANS). MEETS UL LISTINGS FOR THIS TYPE OFLUMINAIRE. WITH SELF-CONTAINED, SELF DIAGNOSING, EMERGENCY BATTERY PACK.

277 OR 120MULTI-TAP

(UNV.)

UNIVERSAL MOUNTING TO CEILINGOR WALL SURFACE 8'-6" A.F.F. OR AS

DIRECTED BY ARCHITECT

LED LAMPS NONE NICKELCADIMUMPER MFG.

BRUSHEDALUMINUM FACE

SURE-LITES # CX 1,2

E2 LED DOUBLE FACED EXIT SIGN, EMERGENCY, DIE CAST ALUMINUM HOUSING WITHGREEN CHARACTERS, BLACK HOUSING AND BRUSHED ALUMINUM FACE (DIRECTIONALARROWS AS INDICATED ON LIGHTING PLANS). MEETS UL LISTINGS FOR THIS TYPE OFLUMINAIRE. WITH SELF-CONTAINED, SELF DIAGNOSING, EMERGENCY BATTERY PACK.

277 OR 120MULTI-TAP

(UNV.)

CEILING SURFACE OR WALLSURFACE AT 8'-6" A.F.F. OR AS

DIRECTEDBY ARCHITECT

LED LAMPS NONE NICKELCADIMUMPER MFG.

BRUSHEDALUMINUM FACE

SURE-LITES # CX72S 1,2

F1 FLOODLIGHT IP66 RATED LUMINAIRE, HEAVY-DUTY, DIE CAST ALUMINUM HOUSING,ADJUSTED 5 DEGREE INCREMENTS, DISTRIBUTION 6 X 6 WIDE. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.

277 OR 120MULTI-TAP

(UNV.)

WALL SURFACE 9'-0" AFF OR ASINDICATED ON PLANS

LED4000K10,530 LUMEN

0-10V DIMMABLE LED DRIVER NONE IMPACTRESISTANTTEMPERED

LENS

LUMARK #NFFLD-C25 1

F1E FLOODLIGHT IP66 RATED LUMINAIRE, HEAVY-DUTY, DIE CAST ALUMINUM HOUSING,ADJUSTED 5 DEGREE INCREMENTS, DISTRIBUTION 6 X 6 WIDE. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.

277 OR 120MULTI-TAP

(UNV.)

WALL SURFACE 9'-0" AFF OR ASINDICATED ON PLANS

LED4000K10,530 LUMEN

0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING

CIRCUIT

IMPACTRESISTANTTEMPERED

LENS

LUMARK #NFFLD-C25 1

Fb EXTERIOR RECESSED DIE-CAST STEP LIGHT WITH STAINLESS STEEL FACE PLATE.9.5"H x 2"W x 3"D. IP65, MARINE GRADE, CORROSION RESISTANT, HEAVY WALLED,ALUMINUM CONSTRUCTION. WHITE FINISH STANDARD

277 0R 120MULTI TAP

(UNV.)

RECESSED ON WALL, 2 FT A.F.F. ORAS NOTED ON PLANS

LED4000K360 LUMENS

0-10V DIMMABLE LED DRIVER NONE 1/4" THICKTEMPERED

LENS

FC LIGHTING #FCSL902 1,3

FL2 8"H x 7"W x4"D, SLIM, LOW PROFILE ONE PIECE DIE CAST HOUSING. SILICONE SEALEDOPTICAL CHAMBER WITH IMPACT RESISTANT TEMPERED GLASS LENS, FULL CUT-OFF.WHITE FINISH STANDARD

277 OR 120MULTI-TAP

(UNV.)

WALL SURFACE 9'-0" AFF OR ASINDICATED ON PLANS

LED4000K2103 LUMEN

0-10V DIMMABLE LED DRIVER NONE IMPACTRESISTANTTEMPERED

LENS

LUMARK #XTOR 1

FL2E 8"H x 7"W x4"D, SLIM, LOW PROFILE ONE PIECE DIE CAST HOUSING. SILICONE SEALEDOPTICAL CHAMBER WITH IMPACT RESISTANT TEMPERED GLASS LENS, FULL CUT-OFF.WHITE FINISH STANDARD

277 OR 120MULTI-TAP

(UNV.)

WALL SURFACE 9'-0" AFF OR ASINDICATED ON PLANS

LED4000K2103 LUMEN

0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING

CIRCUIT

IMPACTRESISTANTTEMPERED

LENS

LUMARK #XTOR 1

Fo1 WALL MOUNTED 4' LONG X 3.5" DEPTH X 5.0" HEIGHT, SQUARE HOUSING,INDIRECT/DIRECT, LED LUMINAIRE WITH INTEGRAL POWER SUPPLY, AND ALUMINUMEXTRUDED HOUSING. SYMMETRIC NARROW DISTRIBUTION. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.

277 0R 120MULTI TAP

(UNV.)

EXTERIOR WALL MOUNTED (REFERTO ARCHITECTURAL ELEVATIONS).

LED4000K1061 LUMEN/FT85 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE DIFFUSE LENS A-LIGHT #D2 SERIES 1,2

Fo1E WALL MOUNTED 4' LONG X 3.5" DEPTH X 5.0" HEIGHT, SQUARE HOUSING,INDIRECT/DIRECT, LED LUMINAIRE WITH INTEGRAL POWER SUPPLY, AND ALUMINUMEXTRUDED HOUSING. SYMMETRIC NARROW DISTRIBUTION. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.

277 0R 120MULTI TAP

(UNV.)

EXTERIOR WALL MOUNTED (REFERTO ARCHITECTURAL ELEVATIONS).

LED4000K1061 LUMEN/FT85 CRI MIN.

0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING

CIRCUIT

DIFFUSE LENS A-LIGHT #D2 SERIES 1,2

Fo2 WALL MOUNTED 4' LONG X 3.5" DEPTH X 5.0" HEIGHT, SQUARE HOUSING, INDIRECTCOMPONENT ONLY, LED LUMINAIRE WITH INTEGRAL POWER SUPPLY, AND ALUMINUMEXTRUDED HOUSING. SYMMETRIC NARROW DISTRIBUTION. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.

277 0R 120MULTI TAP

(UNV.)

EXTERIOR WALL MOUNTED (REFERTO ARCHITECTURAL ELEVATIONS).

LED4000K1061 LUMEN/FT85 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE DIFFUSE LENS A-LIGHT #D2 SERIES 1,2

Fo3 WALL MOUNTED 4' LONG X 3.5" DEPTH X 5.0" HEIGHT, SQUARE HOUSING,INDIRECT/DIRECT, LED LUMINAIRE WITH INTEGRAL POWER SUPPLY, AND ALUMINUMEXTRUDED HOUSING. SYMMETRIC NARROW DISTRIBUTION. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.

277 0R 120MULTI TAP

(UNV.)

EXTERIOR WALL MOUNTED (REFERTO ARCHITECTURAL ELEVATIONS).

LED4000K530 LUMEN/FT85 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE DIFFUSE LENS A-LIGHT #D2 SERIES 1,2

Fo3E WALL MOUNTED 4' LONG X 3.5" DEPTH X 5.0" HEIGHT, SQUARE HOUSING,INDIRECT/DIRECT, LED LUMINAIRE WITH INTEGRAL POWER SUPPLY, AND ALUMINUMEXTRUDED HOUSING. SYMMETRIC NARROW DISTRIBUTION. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.

277 0R 120MULTI TAP

(UNV.)

EXTERIOR WALL MOUNTED (REFERTO ARCHITECTURAL ELEVATIONS).

LED4000K530 LUMEN/FT85 CRI MIN.

0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING

CIRCUIT

DIFFUSE LENS A-LIGHT #D2 SERIES 1,2

Fo4 WALL MOUNTED 2' LONG X 3.5" DEPTH X 5.0" HEIGHT, SQUARE HOUSING,INDIRECT/DIRECT, LED LUMINAIRE WITH INTEGRAL POWER SUPPLY, AND ALUMINUMEXTRUDED HOUSING. SYMMETRIC NARROW DISTRIBUTION. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.

277 0R 120MULTI TAP

(UNV.)

EXTERIOR WALL MOUNTED (REFERTO ARCHITECTURAL ELEVATIONS).

LED4000K1061 LUMEN/FT85 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE DIFFUSE LENS A-LIGHT #D2 SERIES 1,3

LUMINAIRE SCHEDULE NOTES:1. MANUFACTURERS CATALOG NUMBERS REPRESENT MANUFACTURER SERIES. SHOP DRAWING SUBMITTALS WILL INCLUDE ALL PART NUMBERS REPRESENTING ALL ITEMS OF THIS LUMINAIRE SCHEDULE. IT IS THE

RESPONSIBILITY OF THE CONTRACTOR TO ORDER LUMINAIRES TO INCLUDE ALL PARTS INDICATED ON SCHEDULE FOR EACH LUMINAIRE. SUBMITTAL WILL CALL OUT EACH PART CLEARLY.2. LUMINAIRE REQUIRES MOUNTING COORDINATION WITH ARCHITECT PRIOR TO COMMENCEMENT OF ANY WORK. THIS LUMINAIRE MAY REQUIRE A HIGHER OR LOWER MOUTING FROM THAT PROVIDED ON THIS

SCHEDULE OR NOTES ON PLAN DUE TO ARCHITECTURAL REQUIREMENTS OR CONSTRUCTION CONDITIONS.

1,2

1,2

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:17:35-07'00'

Page 10: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

E-702

NEW ARTBUILDINGNMSU LAS CRUCES, NM

ELECTRICAL LUMINAIRE SCHEDULES

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

Checker

Author

ELECTRICAL LUMINAIRE SCHEDULE (CONT.)

TYPE DESCRIPTION VOLTS MOUNTINGLAMPS (NEED TO BE ENERGY STAR

OR DLC LISTED) LED DRIVERINPUTWATTS

EM. BAT.PK. LENS MANUFACTURER/MODEL NOTES ADD. ALTER

L4 4' LONG HEAVY DUTY STEEL HOUSING, ONE – EXTRUDED LINEAR RIBBEDPOLYCARBONATE LENS, VANDAL RESISTANT, FINISHED IN MATTE WHITE STANDARD.

277 OR 120MULTI-TAP

(UNV)

PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”

AFF OR SURFACE MOUNTED TOCEILING.

LED3500K3503 LUMEN85 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE WHITE ACRYLIC FAILSAFE #HVSL 1,2

L8 8' LONG HEAVY DUTY STEEL HOUSING, ONE – EXTRUDED LINEAR RIBBEDPOLYCARBONATE LENS, VANDAL RESISTANT, FINISHED IN MATTE WHITE STANDARD.

277 OR 120MULTI-TAP

(UNV)

PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”

AFF OR SURFACE MOUNTED TOCEILING.

LED3500K3503 LUMEN85 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE WHITE ACRYLIC FAILSAFE #HVSL 1,2

L8E 8' LONG HEAVY DUTY STEEL HOUSING, ONE – EXTRUDED LINEAR RIBBEDPOLYCARBONATE LENS, VANDAL RESISTANT, FINISHED IN MATTE WHITE STANDARD.

277 OR 120MULTI-TAP

(UNV)

PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”

AFF OR SURFACE MOUNTED TOCEILING.

LED3500K3503 LUMEN85 CRI MIN.

0-10V DIMMABLE LED DRIVER NMSUCONTINUO

USLIGHTINGCIRCUIT

WHITE ACRYLIC FAILSAFE #HVSL 1,2

L83 8' LONG HEAVY DUTY STEEL HOUSING, ONE – EXTRUDED LINEAR RIBBEDPOLYCARBONATE LENS, VANDAL RESISTANT, FINISHED IN MATTE WHITE STANDARD.

277 OR 120MULTI-TAP

(UNV)

PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”

AFF OR SURFACE MOUNTED TOCEILING.

LED3000K3503 LUMEN85 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE WHITE ACRYLIC FAILSAFE #HVSL 1,2 LITHONIA #LBL

L83E 8' LONG HEAVY DUTY STEEL HOUSING, ONE – EXTRUDED LINEAR RIBBEDPOLYCARBONATE LENS, VANDAL RESISTANT, FINISHED IN MATTE WHITE STANDARD.

277 OR 120MULTI-TAP

(UNV)

PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”

AFF OR SURFACE MOUNTED TOCEILING.

LED3000K3503 LUMEN85 CRI MIN.

0-10V DIMMABLE LED DRIVER NMSUCONTINUO

USLIGHTINGCIRCUIT

WHITE ACRYLIC FAILSAFE #HVSL 1,2 LITHONIA #LBL

LDMX HIGH PERFORMANCE, COLOR CHANGING, LINEAR SURFACE MOUNT LED LUMINAIREWITH EXTRUDED ALUMINUM HOUSING. PROVIDE WITH ADJUSTABLE BRACKETS ANDSNAP-IN CONNECTORS FOR DAISY CHAINING. (4) ROWS OF 7 FT NOMINAL LENGHT.

277 OR 120MULTI-TAP

(UNV.)

TOP MOUNT TO STRUCTURE ON THEINTERIOR OF LANTERN

LED4000K553 LM/FT85 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE CLEARTEMPERED

GLASS COVERLENS

GVA LIGHTING #STR9-LITE RGB 1,2 METALUX #SNLED LENSED

LG 4' LONG X 6”W X 4”D SEMI-DIRECT ALUMINUM SQUARE HOUSING LED PENDANTLUMINAIRE WITH 0-10V DIMMING CAPABILITY. SUSPENDED WITH AIRCRAFT CABLETHAT IS FIELD ADJUSTABLE. COLOR TO BE MATTE WHITE.

277 OR 120MULTI-TAP

(UNV)

PROVIDE 24” ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”

AFF. REFER TO ARCHITECTURALSECTIONS FOR ADDITIONAL

INFORMATION.

LED3500K8078 LUMEN85 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE CLEAR LINEARPRISMATIC

CORELITE #RZL-WB 1,2

LP 8' EXTRUDED ALUMINUM AND WELDED HOUSING LED DIRECT OUTPUT, PENDANTLUMINAIRE. LUMINAIRE WITH (2)0-10V DIMMING CAPABILITY FOR COLORS WHITE ANDRED COLOR. PROVIDE WITH 2 ROW FOR HIGUER LUMEN CAPACITY.

277 OR 120MULTI-TAP

(UNV)

PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”

AFF OR SURFACE MOUNTED TOCEILING.

LED3500K1020 LM/FT

0-10V DIMMABLE LED DRIVER(DUAL)

NONE WHITE ACRYLIC PMC LIGHTING #ES66-LED 1,2 LITHONIA #LBL

LP4 4' EXTRUDED ALUMINUM AND WELDED HOUSING LED DIRECT OUTPUT, PENDANTLUMINAIRE. LUMINAIRE WITH (2)0-10V DIMMING CAPABILITY FOR COLORS WHITE ANDRED COLOR. PROVIDE WITH 2 ROW FOR HIGUER LUMEN CAPACITY.

277 OR 120MULTI-TAP

(UNV)

PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”

AFF OR SURFACE MOUNTED TOCEILING.

LED3500K1020 LM/FT

0-10V DIMMABLE LED DRIVER(DUAL)

NONE WHITE ACRYLIC PMC LIGHTING #ES66-LED 1,2 LITHONIA #LBL

LPE 8' EXTRUDED ALUMINUM AND WELDED HOUSING LED DIRECT OUTPUT, PENDANTLUMINAIRE. LUMINAIRE WITH (2)0-10V DIMMING CAPABILITY FOR COLORS WHITE ANDRED COLOR. PROVIDE WITH 2 ROW FOR HIGUER LUMEN CAPACITY.

277 OR 120MULTI-TAP

(UNV)

PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”

AFF OR SURFACE MOUNTED TOCEILING.

LED3500K1020 LM/FT

0-10V DIMMABLE LED DRIVER(DUAL)

NMSUCONTINUO

USLIGHTINGCIRCUIT

WHITE ACRYLIC PMC LIGHTING #ES66-LED 1,2 LITHONIA #LBL

N1 FLAT LINEAR, LED CONTINUOUS RUN LUMINAIRE. IP68 RATED, WHITE FINISHSTANDARDS WITH REMOTE DRIVER. PROVIDE COMPATIBLE ALUMINUM, SUAREMOUNTING LOW PROFILE CHANNEL WITH LENS. .1.39" WIDE X 1.39" HEIGHT. (2) ROWS27' INDIVIDUAL LENGTH (VERIFY EXACT LENGHTS WITH CONSTRUCTIONCOORDINATION DRAWINGS)

277 0R 120MULTI TAP

(UNV.)

SURFACE MOUNTED TO CASEWORK LED3000K371 LM/FT

0-10V DIMMABLE LED DRIVER NONE FROSTED LENS OPTIC ARTS #FLEX DC 44, CHW 1,2 --

N2 EXTRUDED ALUMINUM 2" RECESSED LINEAR LED SLOT LUMINAIRE. FLANGED,CUSTOM TOTAL LENGTH = 146 FT WITH ONE 90 DEGREE RECESSED CORNER (VERIFYEXACT LENGHTS WITH CONSTRUCTION COORDINATION DRAWINGS). WHITE FINISHSTANDARD

277 0R 120MULTI TAP

(UNV.)

RECESSED CEILING. SEE ARCHPLANS FOR CEILING TYPE.

LED3500K1580 LUMENS

0-10V DIMMABLE LED DRIVER NONE FLUSH-SATINLENS

ZUMTOBEL SLOTLIGHT LED II 1,2 --

N3 EXTRUDED ALUMINUM 2" RECESSED LINEAR LED SLOT LUMINAIRE. FLANGED,CUSTOM TOTAL LENGTH = 146 FT WITH ONE 90 DEGREE RECESSED CORNER (VERIFYEXACT LENGHTS WITH CONSTRUCTION COORDINATION DRAWINGS). WHITE FINISHSTANDARD

277 0R 120MULTI TAP

(UNV.)

RECESSED CEILING. SEE ARCHPLANS FOR CEILING TYPE.

LED3500K1580 LUMENS

0-10V DIMMABLE LED DRIVER NONE FLUSH-SATINLENS

ZUMTOBEL SLOTLIGHT LED II 1,2

N6 FLAT LINEAR, LED CONTINUOUS RUN LUMINAIRE. IP68 RATED, WHITE FINISHSTANDARDS WITH REMOTE DRIVER. PROVIDE COMPATIBLE ALUMINUM, SUAREMOUNTING LOW PROFILE CHANNEL WITH LENS. .92" WIDE X .39" HEIGHT. 16'INDIVIDUAL LENGTH (VERIFY EXACT LENGHTS WITH CONSTRUCTION COORDINATIONDRAWINGS)

277 0R 120MULTI TAP

(UNV.)

SURFACE MOUNTED TO CANOPY LED4000K813 LM/FT

0-10V DIMMABLE LED DRIVER NONE FROSTED LENS OPTIC ARTS #FLEX DC 88, CHW 1,2 --

N12 EXTRUDED ALUMINUM 2" RECESSED LINEAR LED SLOT LUMINAIRE. FLANGED, 12'INDIVIDUAL LENGTH (VERIFY EXACT LENGHTS WITH CONSTRUCTION COORDINATIONDRAWINGS). WHITE FINISH STANDARD

277 0R 120MULTI TAP

(UNV.)

RECESSED CEILING. SEE ARCHPLANS FOR CEILING TYPE.

LED3500K1580 LUMENS

0-10V DIMMABLE LED DRIVER NONE FLUSH-SATINLENS

ZUMTOBEL SLOTLIGHT LED II 1,2 --

P8 3" ROUND LED, CYLINDER TYPE DOWN LIGHT FIXTURE. COORDINATE FINISH COLORWITH ARCHITECT AT SUBMITTAL REVIEW.

277 OR 120MULTI-TAP

(UNV.)

PENDANT CYLINDER (DOWN TOCEILING LEVEL)

LED3500K1360 LUMEN80 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE DIFFUSE LENS BRUCK #112 1 --

P8E 6" ROUND LED DOWN LIGHT FIXTURE, OPEN OPTICS, SEMI-SPECULAR CLEARREFLECTOR, WHITE TRIM RING. WHITE FINISH STANDARD

277 OR 120MULTI-TAP

(UNV.)

CEILING RECESSED LED3500K1500 LUMENS

LED DRIVER VIAGENERAT

OR

NO LENS (OPENOPTICS)

ATLANTIC # LED6OR APPROVED EQUAL.

1,2 --

P44 4" ROUND AND 4 FT LONG PENDANT CYLINDER LED DOWNLIGHT. MATTE WHITEALRYLIC DIFFUSER. WHITE FINISH STANDARD

277 0R 120MULTI TAP

(UNV.)

PENANT CYLINDER - COORDINATEFINAL MOUNTING WITH

ARCHITECTURAL DRAWINGS.

LED3500K6000 LUMENS

0-10V DIMMABLE LED DRIVER NONE NONE DELRAY #6300-4 1 KIRLING #LSR-12381-25L-MFL-ABS-87

P44E 4" ROUND AND 4 FT LONG PENDANT CYLINDER LED DOWNLIGHT. MATTE WHITEALRYLIC DIFFUSER. WHITE FINISH STANDARD

277 0R 120MULTI TAP

(UNV.)

PENANT CYLINDER - COORDINATEFINAL MOUNTING WITH

ARCHITECTURAL DRAWINGS.

LED3500K6000 LUMENS

0-10V DIMMABLE LED DRIVER NMSUCONTINUO

USLIGHTINGCIRCUIT

NONE DELRAY #6300-4 1 KIRLING #LSR-12381-25L-MFL-ABS-87

PD1 EXTRUDED ALUMINUM 4" PENDANT MOUNTED LINEAR LED SLOT LUMINAIRE. FLANGEDAT THE LENS TO ACCEPT THE CEILING PANELS, SINGLE LONG RUN - 8' INDIVIDUALLENGTH (VERIFY EXACT LENGHTS WITH CONSTRUCTION COORDINATION DRAWINGS).WHITE FINISH STANDARD

277 OR 120MULTI-TAP

(UNV)

PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”

AFF. REFER TO ARCHITECTURALSECTIONS FOR ADDITIONAL

INFORMATION.

LED3500K4136 LUMEN85 CRI MIN.

0-10V DIMMABLE LED DRIVER NONE FLUSH-SATINLENS

NEORAY #PDRS124 1,2 --

PDE EXTRUDED ALUMINUM 4" PENDANT MOUNTED LINEAR LED SLOT LUMINAIRE. FLANGEDAT THE LENS TO ACCEPT THE CEILING PANELS, SINGLE LONG RUN - 8' INDIVIDUALLENGTH (VERIFY EXACT LENGHTS WITH CONSTRUCTION COORDINATION DRAWINGS).WHITE FINISH STANDARD

277 OR 120MULTI-TAP

(UNV)

PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”

AFF. REFER TO ARCHITECTURALSECTIONS FOR ADDITIONAL

INFORMATION.

LED3500K4136 LUMEN85 CRI MIN.

0-10V DIMMABLE LED DRIVER NMSUCONTINUO

USLIGHTINGCIRCUIT

FLUSH-SATINLENS

NEORAY #PDRS124 1,2 --

SB POLE MOUNTED WALKWAY LUMINAIRE, SINGLE HEAD, DIE CAST ALUMINUM HOUSING,GASKETED DOOR, FOUR INSET QUICK RELEASE FASTENERS FOR EASY RELAMPING,TYPE V DISTRIBUTION, HORIZONTAL FULL CUT OFF, ROUND STRAIGHT POLE. DARKSKY COMPLIANT. COORDINATE FINISH COLOR WITH ARCHITECT AT SUBMITTAL OFLUMINAIRES. PROVIDE FUSES AT BOTTOM OF POLE.

277 OR 120MULTI-TAP

(UNV)

12'-0" POLE LED4000K9000 LUMENS

LED DRIVER NONE FLAT, CLEAR,HIGH IMPACT,

TEMPEREDGLASS

IINVUE #MSA-E05LED-E1-5WQ-BK /SRX4A16-XXX-5

1,2

T1 ARCHITECTURAL STYLE LED WITH HIGH PERFORMANCE ENERGY EFFICIENT TRACKLUMINAIRE. 0-10V DIMMING CONTROL. EXTRUDED ALUMINUM, ANODIZED FINISH, TWOCIRCUIT, COMMERCIAL GRADE SYSTEM. COORDINATE FINISH COLOR WITHARCHITECT AT SUBMITTAL OF LUMINAIRES AND TRACK.

120 DOUBLE CIRCUIT TRACK MOUNTEDTO STRUCTURE

SURFACE MOUNT TO CEILING

DOUBLE CIRCUIT TRACK 0-10V DIMMABLE LED DRIVER NONE NONE ERCO 2-CIRCUIT TRACK 1 HALO #TEK4

TH CYLINDRICAL CAST ALUMINUM, POWDER COATED LED HEAD WITH FULL 360 DEGREETILT ADAPTER. .COORDINATE FINISH COLOR WITH ARCHITECT AT SUBMITTAL OFLUMINAIRES AND TRACK.

120 TRACK MOUNTEDSURFACE MOUNT TO CEILING

LED3000K1126 DELIVERED LUMENS PER HEAD90 CRI (MIN)

0-10V DIMMABLE LED DRIVER0-10V DIMMING

NONE SPHEROLITLENS FLOOD

ERCO #OPTECT SPOTLIGHT 1

U3 3' LONG X 1.5" WIDE X ".3 -.8" DEPTH,THIN PROFILE UNDERCABINET, LED LUMINAIREWITH EXTRUDED ALUMINUM HOUSING AND 0-10V DIMMING CONTROL. COORDINATEFINISH COLOR WITH ARCHITECT AT SUBMITTAL REVIEW. WHITE FINISH STANDARD.PROVIDE AND MOUNT POWER SUPPLY ADJACENT TO FIXTURE UNDER CABINET.

277 0R 120MULTI TAP

(UNV.)

UNDERCABINET SURFACE MOUNTED LED4000K300 LUMENS

0-10V DIMMABLE LED DRIVER NONE WHITE LENS SSL #UNL-36"-4K-WL 1,2 --

W2l UL LISTED CAST ALUMINUM HOUSING WITH WIRE GUARD. WHITE FINISH STANDARD 120 SURFACE 6" BELOW LOWER FLOORLEVEL IN ELEVATOR PIT

LED 0-10V DIMMABLE LED DRIVER NONE WIREGUARD LURALINE #LVB43 1,2 --

LUMINAIRE SCHEDULE NOTES:1. MANUFACTURERS CATALOG NUMBERS REPRESENT MANUFACTURER SERIES. SHOP DRAWING SUBMITTALS WILL INCLUDE ALL PART NUMBERS REPRESENTING ALL ITEMS OF THIS LUMINAIRE SCHEDULE. IT IS THE

RESPONSIBILITY OF THE CONTRACTOR TO ORDER LUMINAIRES TO INCLUDE ALL PARTS INDICATED ON SCHEDULE FOR EACH LUMINAIRE. SUBMITTAL WILL CALL OUT EACH PART CLEARLY.2. LUMINAIRE REQUIRES MOUNTING COORDINATION WITH ARCHITECT PRIOR TO COMMENCEMENT OF ANY WORK. THIS LUMINAIRE MAY REQUIRE A HIGHER OR LOWER MOUTING FROM THAT PROVIDED ON THIS

SCHEDULE OR NOTES ON PLAN DUE TO ARCHITECTURAL REQUIREMENTS OR CONSTRUCTION CONDITIONS.

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:17:47-07'00'

Page 11: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

E-703

NEW ARTBUILDINGNMSU LAS CRUCES, NM

ELECTRICAL PANEL SCHEDULES

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB

OU

Notes:

Total Est. Demand Current: 6 ATotal Conn. Current: 5 A

Total Est. Demand: 4881 VALTG-EXT 2070 VA 125.00% 2588 VA Total Conn. Load: 3905 VALTG 1846 VA 125.00% 2308 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 3 A 5 A 7 ATotal Load: 720 VA 1388 VA 1815 VA

29 Spare 20 A 1 0 VA 0 VA -- -- Space 30

27 Spare 20 A 1 0 VA 0 VA -- -- Space 28

25 Spare 20 A 1 0 VA 0 VA -- -- Space 26

23 Spare 20 A 1 0 VA 0 VA -- -- Space 24

21 Spare 20 A 1 0 VA 0 VA -- -- Space 22

19 Spare 20 A 1 0 VA 0 VA -- -- Space 20

17 Spare 20 A 1 0 VA 0 VA -- -- Space 18

15 Spare 20 A 1 0 VA 0 VA -- -- Space 16

13 Spare 20 A 1 0 VA 0 VA -- -- Space 14

11 Spare 20 A 1 0 VA 0 VA -- -- Space 12

9 Spare 20 A 1 0 VA 0 VA -- -- Space 10

7 Spare 20 A 1 0 VA 0 VA -- -- Space 8

5 LTG EXTERIOR, STUDIO WING 20 A 1 1815... 0 VA -- -- Space 6

3 LTG LOCKERS 130G 20 A 1 861 VA 542 VA 1 20 A LTG TOP CORRIDOR STUDIO WING 4

1 Space -- -- 0 VA 720 VA 1 20 A LTG EXTERIOR YARD-1 140-1 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 42Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: MSB Phases: 3 Mains Type:Location: ELECTRICAL M150 Volts: 480/277 Wye A.I.C. Rating: 35000

Branch Panel: H1A

Notes:

Total Est. Demand Current: 10 ATotal Conn. Current: 8 A

Total Est. Demand: 8209 VALTG 6567 VA 125.00% 8209 VA Total Conn. Load: 6567 VAOther 0 VA 0.00% 0 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 10 A 5 A 9 ATotal Load: 2658 VA 1511 VA 2401 VA

29 Spare 20 A 1 0 VA 0 VA -- -- Space 30

27 Spare 20 A 1 0 VA 0 VA -- -- Space 28

25 Spare 20 A 1 0 VA 0 VA -- -- Space 26

23 Spare 20 A 1 0 VA 0 VA -- -- Space 24

21 Spare 20 A 1 0 VA 0 VA -- -- Space 22

19 Spare 20 A 1 0 VA 0 VA -- -- Space 20

17 Spare 20 A 1 0 VA 0 VA -- -- Space 18

15 Spare 20 A 1 0 VA 0 VA -- -- Space 16

13 Spare 20 A 1 0 VA 0 VA -- -- Space 14

11 LTG CLAY MIXING 122C 20 A 1 918 VA 0 VA -- -- Space 12

9 LTG ELEVATOR/STAIR LOBBY-1 100F-1 20 A 1 329 VA 324 VA 1 20 A LTG ROOM H101B, H101C, H101-1 10

7 LTG EXTERIOR, GALLERY WING 20 A 1 493 VA 756 VA 1 20 A LTG ROOM 124-1, 123-1, 122E, 122,... 8

5 LTG ROOM M125C, R123C, 130C, 130-... 20 A 1 726 VA 758 VA 1 20 A LTG STU.COLB & GRAD STUDIOS 6

3 LTG ROOM ST101AAAA, 108 20 A 1 290 VA 578 VA 1 20 A LTG ROOM 130-1, 130A 4

1 LTG ROOM105 20 A 1 52 VA 1366... 1 20 A LTG ROOM R112, 105, R108, 113, 107,... 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 42Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: MSB Phases: 3 Mains Type:Location: ELEC M125B Volts: 480/277 Wye A.I.C. Rating: 14000

Branch Panel: H1B

Notes:

Total Est. Demand Current: 7 ATotal Conn. Current: 6 A

Total Est. Demand: 5949 VALTG-EXT 600 VA 125.00% 750 VA Total Conn. Load: 4759 VALTG 4162 VA 125.00% 5202 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 7 A 5 A 5 ATotal Load: 1969 VA 1454 VA 1340 VA

29 Spare 20 A 1 0 VA 0 VA -- -- Space 30

27 Spare 20 A 1 0 VA 0 VA -- -- Space 28

25 Spare 20 A 1 0 VA 0 VA -- -- Space 26

23 Spare 20 A 1 0 VA 0 VA -- -- Space 24

21 Spare 20 A 1 0 VA 0 VA -- -- Space 22

19 Spare 20 A 1 0 VA 0 VA -- -- Space 20

17 Spare 20 A 1 0 VA 0 VA -- -- Space 18

15 Spare 20 A 1 0 VA 0 VA -- -- Space 16

13 Spare 20 A 1 0 VA 0 VA -- -- Space 14

11 Spare 20 A 1 0 VA 0 VA -- -- Space 12

9 LTG 20 A 1 82 VA 0 VA -- -- Space 10

7 LTG STUDY/ RESOURCE RM-1 229-1 20 A 1 336 VA 0 VA -- -- Space 8

5 LTG TOP CORRIDOR - STUDIO WING 20 A 1 826 VA 515 VA 1 20 A LTG GRADUATE STUDIO-1 220A-1 6

3 LTG - BOTTOM RIGHT STUDIO WING 20 A 1 434 VA 945 VA 1 20 A LTG 4

1 LTG-LEFT STUDIO WING 20 A 1 1098... 539 VA 1 20 A LTG - TOP RIGHT STUDIO WING 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 42Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: MSB Phases: 3 Mains Type:Location: ELEC. RM-1 M225B-1 Volts: 480/277 Wye A.I.C. Rating: 14000

Branch Panel: H2A

KEY NOTE

H1A H1B

H2A EM

EM1 EM2

Notes:

Total Est. Demand Current: 1 ATotal Conn. Current: 1 A

LTG 26 VA 125.00% 33 VA Total Est. Demand: 213 VANC 180 VA 100.00% 180 VA Total Conn. Load: 206 VAOther 0 VA 0.00% 0 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 2 A 0 ATotal Load: 180 VA 26 VA

29 Space -- -- 0 VA 0 VA -- -- Space 30

27 Space -- -- 0 VA 0 VA -- -- Space 28

25 Space -- -- 0 VA 0 VA -- -- Space 26

23 Space -- -- 0 VA 0 VA -- -- Space 24

21 Space -- -- 0 VA 0 VA -- -- Space 22

19 Space -- -- 0 VA 0 VA -- -- Space 20

17 Space -- -- 0 VA 0 VA -- -- Space 18

15 Space -- -- 0 VA 0 VA -- -- Space 16

13 Space -- -- 0 VA 0 VA -- -- Space 14

11 Other FABRICATION LAB-1 129-1 20 A 1 0 VA 0 VA 1 20 A Spare 12

9 NC-FACP 20 A 1 180 VA 0 VA 1 20 A Spare 10

7 Other CONSERVATION LAB 115 20 A 1 26 VA 0 VA 1 20 A Spare 8

5 Other 20 A 1 0 VA 0 VA 1 20 A Spare 6

3 Other HALL H101F 20 A 1 0 VA 0 VA 1 20 A Spare 4

1 Other HALL H101F 20 A 1 0 VA 0 VA 1 20 A Spare 2

CKT Circuit Description Notes Trip Poles A B Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 84Mounting: Surface Wires: 3 Mains Rating: 100 A

Supply From: EM Phases: 1 Mains Type:Location: ELEC M125B Volts: 120/240 Single A.I.C. Rating:

Branch Panel: EM1

Notes:

Total Est. Demand Current: 2 ATotal Conn. Current: 2 A

LTG 73 VA 125.00% 91 VA Total Est. Demand: 391 VANC 180 VA 100.00% 180 VA Total Conn. Load: 373 VAOther 120 VA 100.00% 120 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 2 A 1 ATotal Load: 227 VA 146 VA

29 Space -- -- 0 VA 0 VA -- -- Space 30

27 Space -- -- 0 VA 0 VA -- -- Space 28

25 Space -- -- 0 VA 0 VA -- -- Space 26

23 Space -- -- 0 VA 0 VA -- -- Space 24

21 Space -- -- 0 VA 0 VA -- -- Space 22

19 Space -- -- 0 VA 0 VA -- -- Space 20

17 Space -- -- 0 VA 0 VA -- -- Space 18

15 Space -- -- 0 VA 0 VA 1 20 A Spare 16

13 Space -- -- 0 VA 0 VA 1 20 A Spare 14

11 120 VA 0 VA 1 20 A Spare 12

9EM2 50 A 2

47 VA 0 VA 1 20 A Spare 10

7 26 VA 0 VA 1 20 A Spare 8

5EM1 50 A 2

180 VA 0 VA 1 20 A Spare 6

3 Other 20 A 1 0 VA 0 VA 1 20 A Spare 4

1 Other EXTERIOR YARD-1 140-1 20 A 1 0 VA 0 VA 1 20 A Spare 2

CKT Circuit Description Notes Trip Poles A B Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 30Mounting: Surface Wires: 3 Mains Rating: 100 A

Supply From: Phases: 1 Mains Type:Location: ELECTRICAL M150 Volts: 120/240 Single A.I.C. Rating: 10000

Branch Panel: EM

Notes:

Total Est. Demand Current: 1 ATotal Conn. Current: 1 A

Total Est. Demand: 179 VALTG 47 VA 125.00% 59 VA Total Conn. Load: 167 VAOther 120 VA 100.00% 120 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 0 A 1 ATotal Load: 47 VA 120 VA

29 Space -- -- 0 VA 0 VA -- -- Space 30

27 Space -- -- 0 VA 0 VA -- -- Space 28

25 Space -- -- 0 VA 0 VA -- -- Space 26

23 Space -- -- 0 VA 0 VA -- -- Space 24

21 Space -- -- 0 VA 0 VA -- -- Space 22

19 Space -- -- 0 VA 0 VA -- -- Space 20

17 Space -- -- 0 VA 0 VA -- -- Space 18

15 Space -- -- 0 VA 0 VA -- -- Space 16

13 Space -- -- 0 VA 0 VA -- -- Space 14

11 Other EXHIBITION HALL-1 H101-1 20 A 1 0 VA 0 VA 1 20 A Spare 12

9 Other HALL-1 H201D-1 20 A 1 0 VA 0 VA 1 20 A Spare 10

7 Other DESIGN STUDIO-1 224-1 20 A 1 0 VA 0 VA 1 20 A Spare 8

5 Other HALL H201E 20 A 1 47 VA 0 VA 1 20 A Spare 6

3 Other 20 A 1 120 VA 0 VA 1 20 A Spare 4

1 Other 20 A 1 0 VA 0 VA 1 20 A Spare 2

CKT Circuit Description Notes Trip Poles A B Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 30Mounting: Surface Wires: 3 Mains Rating: 100 A

Supply From: EM Phases: 1 Mains Type:Location: ELEC. RM-1 M225B-1 Volts: 120/240 Single A.I.C. Rating:

Branch Panel: EM2

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:18:22-07'00'

Page 12: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

E-704

NEW ARTBUILDINGNMSU LAS CRUCES, NM

ELECTRICAL PANEL SCHEDULES

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB

OU

Notes:

Total Est. Demand Current: 4 ATotal Conn. Current: 4 A

REC 720 VA 100.00% 720 VA Total Est. Demand: 1440 VAMTR 360 VA 100.00% 360 VA Total Conn. Load: 1440 VANC 360 VA 100.00% 360 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 9 A 3 A 0 ATotal Load: 1080 VA 360 VA 0 VA

29 Space -- -- 0 VA 0 VA -- -- Space 30

27 Space -- -- 0 VA 0 VA -- -- Space 28

25 Space -- -- 0 VA 0 VA -- -- Space 26

23 Space -- -- 0 VA 0 VA -- -- Space 24

21 Space -- -- 0 VA 0 VA -- -- Space 22

19 Space -- -- 0 VA 0 VA -- -- Space 20

17 Spare 20 A 1 0 VA 0 VA -- -- Space 18

15 Spare 20 A 1 0 VA 0 VA -- -- Space 16

13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14

11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12

9 MTR ELECTRICAL M150 20 A 1 180 VA 0 VA 1 20 A Spare 10

7 REC ELECTRICAL M150 20 A 1 540 VA 0 VA 1 20 A Spare 8

5 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 6

3 MTR-HEATED ENCLOSURE 20 A 1 180 VA 0 VA 1 20 A Spare 4

1 REC LOCKERS 130G 20 A 1 540 VA 0 VA 1 20 A Spare 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: L1DB Phases: 3 Mains Type:Location: ELECTRICAL M150 Volts: 120/208 Wye A.I.C. Rating: 14000

Branch Panel: L1A

Notes:

Total Est. Demand Current: 102 ATotal Conn. Current: 152 A

REC 46680 VA 60.71% 28340 VA Total Est. Demand: 36590 VAMTR 1440 VA 100.00% 1440 VA Total Conn. Load: 54930 VANC 6810 VA 100.00% 6810 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 154 A 165 A 143 ATotal Load: 18250 VA 19580 VA 17100 VA

125 Spare 20 A 1 0 VA 0 VA -- -- Space 126

123 Spare 20 A 1 0 VA 0 VA -- -- Space 124

121 Spare 20 A 1 0 VA 0 VA -- -- Space 122

119 Spare 20 A 1 0 VA 0 VA -- -- Space 120

117 Spare 20 A 1 0 VA 0 VA -- -- Space 118

115 Spare 20 A 1 0 VA 0 VA -- -- Space 116

113 Spare 20 A 1 0 VA 0 VA -- -- Space 114

111 Spare 20 A 1 0 VA 0 VA -- -- Space 112

109 Spare 20 A 1 0 VA 0 VA -- -- Space 110

107 Spare 20 A 1 0 VA 0 VA -- -- Space 108

105 Spare 20 A 1 0 VA 0 VA -- -- Space 106

103 MTR MECHANICAL ROOM M125C 20 A 1 360 VA 0 VA -- -- Space 104

101 REC Room ST101O, 120K 20 A 1 540 VA 0 VA -- -- Space 102

99 REC Room ST101O, 120K 20 A 1 540 VA 0 VA 1 20 A Spare 100

97 REC Room ST101O, 120K, 120L 20 A 1 540 VA 0 VA 1 20 A Spare 98

95 REC Room ST101O, 120L, 120K 20 A 1 540 VA 0 VA 1 20 A Spare 96

93 REC GRADUATE STUDIO 120L 20 A 1 540 VA 0 VA 1 20 A Spare 94

91 REC GRADUATE STUDIO 120L 20 A 1 540 VA 0 VA 1 20 A Spare 92

89 REC DROP-CORD, LAB 129 20 A 1 180 VA 0 VA 1 20 A Spare 90

87 REC DROP-CORD, LAB 129 20 A 1 180 VA 0 VA 1 20 A Spare 88

85 REC DROP-CORD, LAB 129 20 A 1 180 VA 0 VA 1 20 A Spare 86

83 REC DROP-CORD, LAB 129 20 A 1 180 VA 0 VA 1 20 A Spare 84

81 REC VENDING MACHINE, HALL H101F 20 A 1 1200... 600 VA 1 20 A REC DIGITAL SIGNAGE, LOBBY-1... 82

79 REC VENDING MACHINE, HALL H101F 20 A 1 1200... 300 VA 1 20 A NC PROJECTION SCREEN, STUDY 106 80

77 REC VENDING MACHINE, HALL H101F 20 A 1 1200... 360 VA 1 20 A REC RECEIVING YARD-1 140A-1 78

75 REC RETABLOS GALLERY 110 20 A 1 540 VA 1200... 1 20 A NC HANDICAP DOOR, VEST. 100E 76

73 REC RETABLOS GALLERY 110 20 A 1 540 VA 600 VA 1 20 A NC HANDICAP DOOR, H101E 74

71 NC SUPPORT EXTRACTOR,... 20 A 1 400 VA 600 VA 1 20 A REC WATER COOLER, HALL H101D 72

69 REC ROOM 100B-1, H101-1 20 A 1 660 VA 360 VA 1 20 A REC WATER COOLER, HALL H101F 70

67 REC CORRIDOR 20 A 1 780 VA 540 VA 1 20 A REC STUDENT COLLABORATION-1... 68

65 REC CORRIDOR 20 A 1 960 VA 540 VA 1 20 A REC STUDENT COLLABORATION-1... 66

63 DRINKING FOUNTAING - REC HALL... 20 A 1 360 VA 720 VA 1 20 A REC HALL 101F 64

61 REC ROOM 106-1 20 A 1 360 VA 1080... 1 20 A REC HALL 101E, 101F J131 62

59 REC UAG COLLECTION STUDY-1 106-1 20 A 1 540 VA 1080... 1 20 A REC HALL 101E, 101F 60

57 REC ROOM 109, 111 20 A 1 720 VA 540 VA 1 20 A REC GRADUATE STUDIO 120H 58

55 REC ROOM 109, 111 20 A 1 720 VA 540 VA 1 20 A REC GRADUATE STUDIO 120H 56

53 DWH-1-REC MECHANICAL ROOM... 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120G 54

51 WS-1-REC MECHANICAL ROOM M125C 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120G 52

49 REC ELEVATOR/STAIR LOBBY-1 100F-1 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120F 50

47 NC ELEVATOR/STAIR LOBBY-1 100F-1 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120F 48

45 FSD-MTR RETABLOS GALLERY 110 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO 120E 46

43 FSD-MTR RETABLOS GALLERY 110 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO 120E 44

41 FACP 20 A 1 500 VA 540 VA 1 20 A REC GRADUATE STUDIO 120D 42

39 PROJECTOR SCREEN FABRICATION... 20 A 1 500 VA 540 VA 1 20 A REC GRADUATE STUDIO 120D 40

37 30N PAINT BOOTH LIGHTING 20 A 1 250 VA 540 VA 1 20 A REC GRADUATE STUDIO 120C 38

35 REC REFRIGERATOR 20 A 1 900 VA 540 VA 1 20 A REC GRADUATE STUDIO 120C 36

33 REC ART GALLERY 105 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120B 34

31 REC ART GALLERY 105 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120B 32

29 REC ROOM 118H, 118G 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120A 30

27 REC ROOM 118H, 118G, H101C 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120A 28

25 REC ROOM 118H, 118F 20 A 1 540 VA 600 VA 1 20 A REC REFR, GRADUATE STUDIO 120L 26

23 REC ROOM 118H, 118F 20 A 1 720 VA 540 VA 1 20 A REC SPACE ST101O 24

21 REC ROOM 118E, 118D, 118C 20 A 1 1080... 720 VA 1 20 A REC SPACE ST101O 22

19 REC ROOM 118E, 118D, 118C 20 A 1 1080... 1080... 1 20 A REC ROOM 120K, 120L 20

17 REC ROOM 118A, 118B 20 A 1 900 VA 900 VA 1 20 A REC ROOM 120K, 120L 18

15 REC ROOM 118A, 118B 20 A 1 1080... 1200... 1 20 A REC VENDING MACHINE , HALL H101E 16

13 REC RETABLOS 110 20 A 1 540 VA 180 VA 1 20 A REC HALL H101F 14

11 REC RETABLOS 110 20 A 1 360 VA 720 VA 1 20 A REC FABRICATION LAB-1 129-1 12

9 REC GALLERY STORAGE 108 20 A 1 600 VA 720 VA 1 20 A REC FABRICATION LAB-1 129-1 10

7 REC GALLERY STORAGE 108 20 A 1 540 VA 180 VA 1 20 A NC IRRIGATION 8

5 REC CEILING PROJECTOR, STUDY 106 20 A 1 600 VA 600 VA 1 20 A REC CEILING PROJECTOR, LAB129 6

3 NC HANDICAP DOOR, 100A 20 A 1 1200... 540 VA 1 20 A REC JEWELRY FACULTY 130D-1 4

1 NC HANDICAP DOOR, H101 20 A 1 1200... 720 VA 1 20 A REC JEWELRY FACULTY 130D-1 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 126 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: Phases: 3 Mains Type:Location: ELEC M125B Volts: 120/208 Wye A.I.C. Rating: 14000

Branch Panel: L1B

KEY NOTE

L1A L2A

LPL1B

Notes:

Total Est. Demand Current: 81 ATotal Conn. Current: 128 A

Total Est. Demand: 29105 VAREC 43770 VA 61.42% 26885 VA Total Conn. Load: 45990 VANC 2220 VA 100.00% 2220 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 129 A 134 A 122 ATotal Load: 15420 VA 15910 VA 14660 VA

125 Space -- -- 0 VA 0 VA -- -- Space 126

123 Space -- -- 0 VA 0 VA -- -- Space 124

121 Space -- -- 0 VA 0 VA -- -- Space 122

119 Space -- -- 0 VA 0 VA -- -- Space 120

117 Space -- -- 0 VA 0 VA -- -- Space 118

115 Space -- -- 0 VA 0 VA -- -- Space 116

113 Space -- -- 0 VA 0 VA -- -- Space 114

111 Space -- -- 0 VA 0 VA -- -- Space 112

109 Space -- -- 0 VA 0 VA -- -- Space 110

107 Space -- -- 0 VA 0 VA -- -- Space 108

105 Space -- -- 0 VA 0 VA -- -- Space 106

103 Space -- -- 0 VA 0 VA -- -- Space 104

101 Space -- -- 0 VA 0 VA -- -- Space 102

99 Space -- -- 0 VA 0 VA 1 20 A Spare 100

97 Space -- -- 0 VA 0 VA 1 20 A Spare 98

95 Space -- -- 0 VA 0 VA 1 20 A Spare 96

93 Space -- -- 0 VA 0 VA 1 20 A Spare 94

91 Space -- -- 0 VA 0 VA 1 20 A Spare 92

89 Space -- -- 0 VA 0 VA 1 20 A Spare 90

87 Space -- -- 0 VA 0 VA 1 20 A Spare 88

85 Space -- -- 0 VA 0 VA 1 20 A Spare 86

83 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 900 VA 0 VA 1 20 A Spare 84

81 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 1080... 0 VA 1 20 A Spare 82

79 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 1080... 0 VA 1 20 A Spare 80

77 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 1830... 0 VA 1 20 A Spare 78

75 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 1080... 0 VA 1 20 A Spare 76

73 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 1080... 0 VA 1 20 A Spare 74

71 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 750 VA 0 VA 1 20 A Spare 72

69 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 750 VA 0 VA 1 20 A Spare 70

67 REC PRINTER, DIGITAL PRINTING-1... 20 A 1 750 VA 0 VA 1 20 A Spare 68

65 REC PRINTER, DIGITAL PRINTING-1... 20 A 1 750 VA 0 VA 1 20 A Spare 66

63 REC PRINTER, DIGITAL PRINTING-1... 20 A 1 750 VA 0 VA 1 20 A Spare 64

61 REC PRINTER, DIGITAL PRINTING-1... 20 A 1 750 VA 0 VA 1 20 A Spare 62

59 REC SCANNER, DIGITAL PRINTING-1... 20 A 1 750 VA 500 VA 1 20 A SCREEN CONFERENCE RM-1 235-1 60

57 REC SCANNER, DIGITAL PRINTING-1... 20 A 1 750 VA 360 VA 1 20 A REC COMPUTER LAB-1 231-1 58

55 REC SCANNER, DIGITAL PRINTING-1... 20 A 1 750 VA 360 VA 1 20 A REC COMPUTER LAB-1 231-1 56

53 REC TECHNOLOGY LAB-1 233-1 20 A 1 540 VA 360 VA 1 20 A REC COMPUTER LAB-1 231-1 54

51 REC CEILING PROJECTOR,... 20 A 1 1100... 360 VA 1 20 A REC COMPUTER LAB-1 231-1 52

49 REC MAC LAB-1 231-1 20 A 1 540 VA 720 VA 1 20 A REC DESIGN STUDIO-1 224-1 50

47 REC MAC LAB-1 231-1 20 A 1 720 VA 180 VA 48

45 REC CEILING PROJECTOR, LAB-1... 20 A 1 1100... 180 VA2 20 A REC TECHNOLOGY LAB-1 233-1

46

43 REC HALL-1 H201F-1 20 A 1 720 VA 360 VA 1 20 A REC COMPUTER LAB-1 231-1 44

41 REC TECHNOLOGY LAB-1 233-1 20 A 1 360 VA 360 VA 1 20 A REC COMPUTER LAB-1 231-1 42

39 REC TECHNOLOGY LAB-1 233-1 20 A 1 900 VA 540 VA 1 20 A REC HALL H201E 40

37 REC TECHNOLOGY LAB-1 233-1 20 A 1 720 VA 900 VA 1 20 A REC Room T225A-1, H201F-1, H201E,... 38

35 REC LASER CUTTER, LAB-1 233-1 20 A 1 180 VA 1080... 1 20 A REC Room R223A-1, T225A-1, H201D,... 36

33 REC TECHNOLOGY LAB-1 233-1 20 A 1 600 VA 1080... 1 20 A REC Room R223B-1, H201G-1, H201F-... 34

31 REC SCANNER, TECHNOLOGY LAB-1... 20 A 1 750 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220A-1 32

29 REC 3D PRINTER, TECHNOLOGY LAB... 20 A 1 360 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220A-1 30

27 REC TECHNOLOGY LAB-1 233-1 20 A 1 360 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220B-1 28

25 REC JEWELRY FACULTY STUDIO-1... 20 A 1 360 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220B-1 26

23 REC JEWELRY FACULTY STUDIO-1... 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220C-1 24

21 REC PROJECTOR , RM 236 20 A 1 600 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220C-1 22

19 REC CONFERENCE RM-1 235-1 20 A 1 720 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220D-1 20

17 REC CONFERENCE RM-1 235-1 20 A 1 720 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220D-1 18

15 REC PAINTING FACULTY STUDIO-1... 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220E-1 16

13 REC PAINTING FACULTY STUDIO-1... 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220E-1 14

11 REC PHOTO FACULTY STUDIO-1... 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220F-1 12

9 REC PHOTO FACULTY STUDIO-1... 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220F-1 10

7 REC PRTN FACULTY STUDIO-1 238C-1 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220G-1 8

5 REC PRTN FACULTY STUDIO-1 238C-1 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220G-1 6

3 REC PRNT FACULTY STUDIO-1 238D-1 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220H-1 4

1 REC PRNT FACULTY STUDIO-1 238D-1 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220H-1 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 126Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: L2DB Phases: 3 Mains Type:Location: ELEC. RM-1 M225B-1 Volts: 120/208 Wye A.I.C. Rating: 14000

Branch Panel: L2A

Notes:

Total Est. Demand Current: 64 ALTG 696 VA 125.00% 870 VA Total Conn. Current: 63 AREC 3600 VA 100.00% 3600 VA Total Est. Demand: 22909 VAMTR 4687 VA 100.00% 4687 VA Total Conn. Load: 22735 VANC 13752 VA 100.00% 13752 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 82 A 42 A 74 ATotal Load: 9321 VA 5005 VA 8409 VA

41 Space -- -- 0 VA 0 VA -- -- Space 42

39 Space -- -- 0 VA 0 VA -- -- Space 40

37 IP-1 20 A 1 997 VA 0 VA -- -- Space 38

35 IP-3 20 A 1 1696 VA 0 VA -- -- Space 36

33 Spare 20 A 1 0 VA 0 VA -- -- Space 34

31 AHU LTS/POW 20 A 1 500 VA 0 VA -- -- Space 32

29 AHU-1 LTS/POW 20 A 1 500 VA 0 VA 1 20 A Spare 30

27 AHU-2 LTS/POW 20 A 1 500 VA 0 VA 1 20 A Spare 28

25 REC PENTHOUSE 20 A 1 1260 VA 0 VA 1 20 A Spare 26

23 REC 20 A 1 900 VA 0 VA 1 20 A Spare 24

21 REC 2ND FLOOR ROOF S 20 A 1 720 VA 0 VA 1 20 A Spare 22

19 2028 VA 0 VA 1 20 A Spare 20

17CU-5 20 A 2

2028 VA 0 VA 1 20 A Spare 18

15 1560 VA 0 VA 1 20 A Spare 16

13CU-4 20 A 2

1560 VA 0 VA 1 20 A Spare 14

11 728 VA 0 VA 1 20 A Spare 12

9CU-3 15 A 2

728 VA 0 VA 10

7 1560 VA 0 VA2 20 A Spare

8

5CU-2 20 A 2

1560 VA 997 VA 1 20 A MTR-IP-3 6

3 NC 20 A 1 500 VA 997 VA 1 20 A MTR-IP-2 4

1 REC LOWER ROOF 20 A 1 720 VA 696 VA 1 20 A EF-2 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: TP Phases: 3 Mains Type:Location: MECH. PENTHOUSE M300 Volts: 120/208 Wye A.I.C. Rating: 10000

Branch Panel: LP225A

30

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:18:37-07'00'

Page 13: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

E-705

NEW ARTBUILDINGNMSU LAS CRUCES, NM

ELECTRICAL PANEL SCHEDULES

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

Checker

Author

SKIRT: TOP & BOTTOMNotes:

Total Est. Demand Current: 56 ATotal Conn. Current: 63 A

REC 14802 VA 83.78% 12401 VA Total Est. Demand: 20161 VANC 7760 VA 100.00% 7760 VA Total Conn. Load: 22562 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 76 A 77 A 43 ATotal Load: 8593 VA 8773 VA 5197 VA

83 Spare 20 A 1 0 VA 0 VA -- -- Space 84

81 Spare 20 A 1 0 VA 0 VA -- -- Space 82

79 Spare 20 A 1 0 VA 0 VA -- -- Space 80

77 Spare 20 A 1 0 VA 0 VA -- -- Space 78

75 Spare 20 A 1 0 VA 0 VA -- -- Space 76

73 Spare 20 A 1 0 VA 0 VA -- -- Space 74

71 Spare 20 A 1 0 VA 0 VA -- -- Space 72

69 Spare 20 A 1 0 VA 0 VA -- -- Space 70

67 Spare 20 A 1 0 VA 0 VA -- -- Space 68

65 Spare 20 A 1 0 VA 0 VA -- -- Space 66

63 Spare 20 A 1 0 VA 0 VA -- -- Space 64

61 Spare 20 A 1 0 VA 0 VA -- -- Space 62

59 Spare 20 A 1 0 VA 0 VA -- -- Space 60

57 Spare 20 A 1 0 VA 0 VA -- -- Space 58

55 Spare 20 A 1 0 VA 0 VA -- -- Space 56

53 Spare 20 A 1 0 VA 0 VA -- -- Space 54

51 Spare 20 A 1 0 VA 0 VA -- -- Space 52

49 Spare 20 A 1 0 VA 0 VA -- -- Space 50

47 Spare 20 A 1 0 VA 0 VA -- -- Space 48

45 Spare 20 A 1 0 VA 0 VA -- -- Space 46

43 Spare 20 A 1 0 VA 0 VA -- -- Space 44

41 Spare 20 A 1 0 VA 0 VA -- -- Space 42

39 Spare 20 A 1 0 VA 0 VA -- -- Space 40

37 Spare 20 A 1 0 VA 0 VA -- -- Space 38

35 Spare 20 A 1 0 VA 0 VA -- -- Space 36

33 Spare 20 A 1 0 VA 0 VA -- -- Space 34

31 Spare 20 A 1 0 VA 0 VA -- -- Space 32

29 REC DROP-CORD, WOOD SHOP-1 126-1 20 A 1 180 VA 0 VA -- -- Space 30

27 2184 VA 0 VA -- -- Space 28

25 20E SAW TABLE LAB UNIT, WOODEQUIPMENT SHOP-1 126-1 30 A 2

2184 VA 0 VA -- -- Space 26

23 REC WOOD EQUIPMENT SHOP-1 126-1 20 A 1 360 VA 0 VA -- -- Space 24

21 REC WOOD EQUIPMENT SHOP-1 126-1 20 A 1 720 VA 0 VA -- -- Space 22

19 REC WOOD EQUIPMENT SHOP-1 126-1 20 A 1 540 VA 0 VA -- -- Space 20

17 REC MITER SAW, SHOP-1 126-1 20 A 1 1800 VA 0 VA -- -- Space 18

15 22E REC DRILL PRESS SHOP-1 126-1 20 A 1 1800 VA 0 VA -- -- Space 16

13 27E REC BANDSAW, SHOP-1 126-1 30 A 1 1800 VA 0 VA -- -- Space 14

11 24E REC DISC SANDER SHOP-1 126-1 20 A 1 1680 VA 0 VA -- -- Space 12

9 1177 VA 0 VA -- -- Space 10

7 1177 VA 0 VA -- -- Space 8

525E MTR WOOD EQUIPMENT SHOP-1126-1 20 A 3

1177 VA 0 VA -- -- Space 6

3 1196 VA 1696 VA 1 20 A 50N AIR FILTER WOOD SHOP-1 126-1 4

1 26E REC WOOD EQUIPMENT SHOP-1126-1 20 A 2

1196 VA 1696 VA 1 20 A 50N AIR FILTER WOOD SHOP-1 126-1 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 84 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: L1DB Phases: 3 Mains Type:Location: WOOD SHOP-1 126-1 Volts: 120/208 Wye A.I.C. Rating: 10000

Branch Panel: 1LP2

SKIRT: TOP & BOTTOMNotes:

Total Est. Demand Current: 93 ATotal Conn. Current: 145 A

REC 48157 VA 60.38% 29079 VA Total Est. Demand: 33331 VANC 4252 VA 100.00% 4252 VA Total Conn. Load: 52409 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 138 A 154 A 147 ATotal Load: 16558 VA 18384 VA 17468 VA

83 REC ROOM 122B-1, 122C 20 A 1 720 VA 0 VA -- -- Space 84

81 REC CERAMICS FACULTY STUDIO 122A 20 A 1 540 VA 0 VA -- -- Space 82

79 REC CERAMICS FACULTY STUDIO 122A 20 A 1 540 VA 0 VA -- -- Space 80

77 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 78

75 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 76

73 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 74

71 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 72

69 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 70

67 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 68

65 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 66

63 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 64

61 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 62

59 REC CERAMICS 122 20 A 1 540 VA 0 VA -- -- Space 60

57 REC CERAMICS 122 20 A 1 720 VA 0 VA -- -- Space 58

55 REC CERAMICS 122 20 A 1 900 VA 0 VA -- -- Space 56

53 REC CEILING PROJECTOR, CERAMICS... 20 A 1 600 VA 0 VA 1 20 A Spare 54

51 1560 VA 0 VA 1 20 A Spare 52

4939E REC CLAY MIXING 122C 20 A 2

1560 VA 0 VA 1 20 A Spare 50

47 40E REC PUGMILL, CLAY MIXING 122C 30 A 1 3000 VA 0 VA 1 20 A Spare 48

45 720 VA 0 VA 1 20 A Spare 46

43 720 VA 0 VA 1 20 A Spare 44

41

42E REC CLAY MIXING 122C 20 A 3

720 VA 0 VA 1 20 A Spare 42

39 1141 VA 0 VA 1 20 A Spare 40

37 1141 VA 0 VA 1 20 A Spare 38

35

37E REC CLAY MIXING 122C 20 A 3

1141 VA 0 VA 1 20 A Spare 36

33 540 VA 0 VA 1 20 A Spare 34

31 540 VA 0 VA 1 20 A Spare 32

29

43E REC CLAY MIXING 122C 20 A 3

540 VA 0 VA 1 20 A Spare 30

27 REC AIR CLEANER, GLAZE LAB-1 122B-1 25 A 1 1656 VA 1696 VA 1 20 A 41E AIR FILTER 28

25 NC EXHAUST, GLAZE LAB-1 122B-1 20 A 1 180 VA 500 VA 1 20 A PROJECTOR SCREEN CERAMICS 122 26

23 32E REC LAMAN SLIP MIXER, CERAMICS... 20 A 1 1176 VA 600 VA 1 20 A PROJECTOR CERAMICS 122 24

21 REC AIR COMPRESSOR, CERAMICS 122 30 A 1 1920 VA 180 VA 1 20 A REC DROP-CORD, MOLD RM-1 123-1 22

19 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 180 VA 1 20 A REC DROP-CORD, MOLD RM-1 123-1 20

17 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 720 VA 1 20 A REC MOLD RM-1 123-1 18

15 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 720 VA 1 20 A REC MOLD RM-1 123-1 16

13 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 540 VA 1 20 A REC WET ROOM 122E 14

11 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 900 VA 1 20 A REC WASOUT SINK, ROOM 122C, 122B-1 12

9 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 180 VA 1 20 A NC EYE WASH, CERAMICS 122 10

7 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 2520 VA 8

5 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 2520 VA 6

3 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 2520 VA

3 20 A REC CLAY MIXING 122C

4

1 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 1696 VA 1 20 A 36E HEPA AIR FILTER 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 84 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: L1DB Phases: 3 Mains Type:Location: CERAMICS 122 Volts: 120/208 Wye A.I.C. Rating: 10000

Branch Panel: 1LP4

Notes:

Total Est. Demand Current: 74 ATotal Conn. Current: 111 A

REC 37188 VA 63.45% 23594 VA Total Est. Demand: 26534 VANC 2940 VA 100.00% 2940 VA Total Conn. Load: 40128 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 105 A 108 A 123 ATotal Load: 12570 VA 12882 VA 14676 VA

83 84

81 82

79 80

77 78

75 76

73 74

71 72

69 70

67 68

65 66

63 64

61 62

59 60

57 REC METALS/JEWELRY-1 130-1 20 A 1 1440 VA 58

55 REC METALS/JEWELRY-1 130-1 20 A 1 1440 VA 56

53 REC METALS/JEWELRY-1 130-1 20 A 1 540 VA 54

51 REC METALS/JEWELRY-1 130-1 20 A 1 360 VA 52

49 REC METALS/JEWELRY-1 130-1 20 A 1 540 VA 50

47 REC METALS/JEWELRY-1 130-1 20 A 1 540 VA 48

45 1040 VA 46

43REC ENAMEL 130A 20 A 2

1040 VA 44

41 REC METALS/JEWELRY-1 130-1 20 A 1 540 VA 42

39 REC METALS/JEWELRY-1 130-1 20 A 1 540 VA 540 VA 1 20 A REC METALS/JEWELRY-1 130-1 40

37 REC METALS/JEWELRY-1 130-1 20 A 1 720 VA 180 VA 1 20 A REC METALS/JEWELRY-1 130-1 38

35 REC METALS/JEWELRY-1 130-1 20 A 1 360 VA 540 VA 1 20 A REC METALS/JEWELRY-1 130-1 36

33 REC METALS/JEWELRY-1 130-1 20 A 1 540 VA 540 VA 1 20 A NC METALS/JEWELRY-1 130-1 34

31 REC METALS/JEWELRY-1 130-1 20 A 1 540 VA 1260 VA 1 20 A NC ENAMEL 130A 32

29 99E REC METALS/JEWELRY-1 130-1 20 A 1 720 VA 360 VA 1 20 A REC ENAMEL 130A 30

27 200 VA 540 VA 1 20 A REC RAISING ROOM 130B 28

25 REC PUK 4 MICRO WELDER,METALS/JEWELRY STUDIO-1 130-1 30 A 2

200 VA 540 VA 1 20 A REC RAISING ROOM 130B 26

23 REC METALS/JEWELRY-1 130-1 20 A 1 1656 VA 1980 VA 1 20 A REC METALS/JEWELRY STUDIO-1 130-1 24

21 98E REC KILN, ENAMEL 130A 20 A 1 1440 VA 1620 VA 1 20 A REC METALS/JEWELRY STUDIO-1 130-1 22

19 REC BAND SAW, STUDIO-1 130-1 30 A 1 1920 VA 1440 VA 1 20 A REC METALS/JEWELRY STUDIO-1 130-1 20

17 REC BELT SANDER, STUDIO-1 130-1 20 A 1 864 VA 1440 VA 1 20 A REC METALS/JEWELRY STUDIO-1 130-1 18

15 REC SANDER, STUDIO-1 130-1 20 A 1 1176 VA 720 VA 1 20 A REC METALS/JEWELRY STUDIO-1 130-1 16

13 REC SCROLL SAW, STUDIO-1 130-1 20 A 1 80 VA 900 VA 1 20 A REC Room 130A, 130-1 14

11 REC METAL MATHE, STUDIO-1 130-1 25 A 1 1656 VA 900 VA 1 20 A REC Room 130A, 130-1 12

9 REC METAL MATHE, STUDIO-1 130-1 25 A 1 1656 VA 180 VA 1 20 A NC FUME HOOD, STUDIO-1 130-1 10

7 REC DRILL PRESS, STUDIO-1 130-1 20 A 1 240 VA 180 VA 1 20 A NC FUME HOOD, STUDIO-1 130-1 8

5 REC DRILL PRESS, STUDIO-1 130-1 35 A 1 2400 VA 180 VA 1 20 A 27N NC FUME HOOD, STUDIO-1 130-1 6

3 REC SLOW COOKER, STUDIO-1 130-1 20 A 1 250 VA 100 VA 1 20 A NC SUPPORT EXTRACTOR, JEWELRY-1... 4

1 REC SLOW COOKER, STUDIO-1 130-1 20 A 1 250 VA 1100 VA 1 20 A REC CEILING PROJECTOR , STUDIO-1... 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 84 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: L1DB Phases: 3 Mains Type:Location: METALS/JEWELRY-1 130-1 Volts: 120/208 Wye A.I.C. Rating: 10000

Branch Panel: 1LP1

KEY NOTE

1LP1 1LP2

1LP41LP3

SKIRT: TOP & BOTTOMNotes:

Total Est. Demand Current: 72 ATotal Conn. Current: 114 A

REC 40632 VA 62.31% 25316 VA Total Est. Demand: 25846 VANC 530 VA 100.00% 530 VA Total Conn. Load: 41162 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 113 A 98 A 137 ATotal Load: 13264 VA 11720 VA 16178 VA

83 Spare 20 A 1 0 VA 0 VA -- -- Space 84

81 Spare 20 A 1 0 VA 0 VA -- -- Space 82

79 Spare 20 A 1 0 VA 0 VA -- -- Space 80

77 Spare 20 A 1 0 VA 0 VA -- -- Space 78

75 Spare 20 A 1 0 VA 0 VA -- -- Space 76

73 Spare 20 A 1 0 VA 0 VA -- -- Space 74

71 REC HYDRAULIC PRESS, SCULPTURE-1... 20 A 1 600 VA 0 VA -- -- Space 72

69 REC BENCH GRINDER, SCULPTURE-1... 20 A 1 600 VA 0 VA -- -- Space 70

67 NC SUPPORT EXTRACTOR, SCULPTURE... 20 A 1 50 VA 0 VA -- -- Space 68

65 0 VA -- -- Space 66

63 0 VA -- -- Space 64

61 REC DROP-CORD SCULPTURE-1 124-1 20 A 1 180 VA 0 VA -- -- Space 62

59 REC DROP-CORD SCULPTURE-1 124-1 20 A 1 180 VA 0 VA -- -- Space 60

57 REC DROP-CORD SCULPTURE-1 124-1 20 A 1 180 VA 0 VA -- -- Space 58

55 REC DROP-CORD SCULPTURE-1 124-1 20 A 1 180 VA 0 VA -- -- Space 56

53 REC DROP-CORD SCULPTURE-1 124-1 20 A 1 180 VA 0 VA -- -- Space 54

51 0 VA -- -- Space 52

49 REC SCULPTURE FACULTY STUDIO 124A 20 A 1 540 VA 0 VA -- -- Space 50

47 REC SCULPTURE FACULTY STUDIO 124A 20 A 1 720 VA 0 VA -- -- Space 48

45 0 VA -- -- Space 46

43 0 VA -- -- Space 44

41 REC SCULPTURE STUDIO-1 124-1 20 A 1 1080 VA 0 VA -- -- Space 42

39 REC SCULPTURE STUDIO-1 124-1 20 A 1 900 VA 0 VA -- -- Space 40

37 NC PROJECTION SCREEN , STUDIO-1... 20 A 1 300 VA 0 VA -- -- Space 38

35 REC CEILING PROJECTOR , STUDIO-1... 20 A 1 600 VA 0 VA -- -- Space 36

33 NC EYE WASH, STUDIO-1 124-1 20 A 1 180 VA 0 VA -- -- Space 34

31 0 VA -- -- Space 32

29 0 VA -- -- Space 30

27 0 VA 0 VA 1 20 A Spare 28

2512E WELDER 30 A 2

0 VA 0 VA 1 20 A Spare 26

23 5200 VA 0 VA 1 20 A Spare 24

21GEN WELDER REC 2 30 A 2

5200 VA 0 VA 1 20 A Spare 22

19 2418 VA 0 VA 1 20 A Spare 20

1713E WELDER REC 50 A 2

2418 VA 0 VA 1 20 A Spare 18

15 2740 VA 0 VA 1 20 A Spare 16

13REC SCULPTURE STUDIO-1 124-1 50 A 2

2740 VA 0 VA 1 20 A Spare 14

11 0 VA 0 VA 1 20 A Spare 12

9GEN WELDER REC 50 A 2

0 VA 0 VA 1 20 A Spare 10

7 5200 VA 0 VA 1 20 A Spare 8

53E REC SCULPTURE STUDIO-1 124-1 70 A 2

5200 VA 0 VA 1 20 A Spare 6

3 REC DRILL PRESS STUDIO-1 124-1 30 A 1 1920 VA 0 VA 1 20 A Spare 4

1 REC SPAY BOOTH, STUDIO-1 124-1 25 A 1 1656 VA 0 VA 1 20 A Spare 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 84 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: L1DB Phases: 3 Mains Type:Location: SCULPTURE-1 124-1 Volts: 120/208 Wye A.I.C. Rating: 10000

Branch Panel: 1LP3

Spare 20 A 1

Spare 20 A 1

Spare 20 A 1

Spare 20 A 1

Spare 20 A 1

Spare 20 A 1

Spare 20 A 1

Spare 20 A 1

Spare 20 A 1

Spare 20 A 1

Spare 20 A 1

Spare 20 A 1

Spare 20 A 1

Spare1 20 A

Spare1 20 A

Spare1 20 A

Spare1 20 A

Spare1 20 A

Spare1 20 A

Spare1 20 A

Space

Space

Space

Space

Space

Space

Space

Space

Space

Space

Space

Space

Space

Space

Space

84

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:19:02-07'00'

Page 14: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

E-706

NEW ARTBUILDINGNMSU LAS CRUCES, NM

ELECTRICAL PANEL SCHEDULES

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

Checker

Author

KEY NOTE

1LP-5 1LP-6

1LP-81LP-7

SKIRT: TOP & BOTTOMNotes:

Total Est. Demand Current: 364 ATotal Conn. Current: 498 A

REC 106972 VA 54.67% 58486 VA Total Est. Demand: 130978 VAMTR 0 VA 0.00% 0 VA Total Conn. Load: 179464 VANC 72492 VA 100.00% 72492 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 440 A 527 A 551 ATotal Load: 52854 VA 61825 VA 64785 VA

83 Space -- -- 0 VA 0 VA -- -- Space 84

81 REC ROOM 142, 122F 20 A 1 720 VA 0 VA -- -- Space 82

79 REC ROOM 140-1, 130F 20 A 1 540 VA 0 VA -- -- Space 80

77 REC ROOM 140-1, 130F, M150 20 A 1 540 VA 0 VA -- -- Space 78

75 1463 VA 0 VA -- -- Space 76

73 1463 VA 0 VA -- -- Space 74

71

NC COMPRESSOR RM 142 30 A 3

1463 VA 0 VA -- -- Space 72

69 7176 VA 0 VA -- -- Space 70

67REC SKUTT KILN, KILN ROOM 122F 30 A 2

7176 VA 0 VA -- -- Space 68

65 REC DOLL KILN, KILN ROOM 122F 20 A 1 6000 VA 0 VA -- -- Space 66

63 REC DOLL KILN, KILN ROOM 122F 20 A 1 6000 VA 0 VA -- -- Space 64

61 REC DOLL KILN, KILN ROOM 122F 20 A 1 6000 VA 0 VA -- -- Space 62

59 REC DOLL KILN, KILN ROOM 122F 20 A 1 6000 VA 0 VA -- -- Space 60

57 409 VA 0 VA -- -- Space 58

55 409 VA 0 VA -- -- Space 56

53

NC KILN ROOM 122F 30 A 3

409 VA 0 VA -- -- Space 54

51 REC EXHAUST, KILN ROOM 122F 20 A 1 360 VA 0 VA 1 20 A Spare 52

49 7904 VA 0 VA 1 20 A Spare 50

47REC SKUTT KILN, KILN ROOM 122F 100 A 2

7904 VA 0 VA 1 20 A Spare 48

45 2777 VA 0 VA 1 20 A Spare 46

43REC SKUTT KILN, KILN ROOM 122F 100 A 2

2777 VA 0 VA 1 20 A Spare 44

41 4992 VA 0 VA 1 20 A Spare 42

39REC SKUTT KILN, KILN ROOM 122F 100 A 2

4992 VA 0 VA 1 20 A Spare 40

37 2777 VA 0 VA 1 20 A Spare 38

35RECSKUTT KILN, KILN ROOM 122F 100 A 2

2777 VA 0 VA 1 20 A Spare 36

33 4992 VA 0 VA 1 20 A Spare 34

31REC SKUTT KILN, KILN ROOM 122F 100 A 2

4992 VA 180 VA 1 20 A AD-1 COMPRESSOR RM 142 32

29 3120 VA 4800 VA 1 20 A REC CASTING 130F 30

27 REC MIG WELDER, EXTERIOR YARD-1140-1 30 A 2

3120 VA 2080 VA 28

25 3120 VA 2080 VA 26

23 REC MIG WELDER, EXTERIOR YARD-1140-1 30 A 2

3120 VA 2080 VA

3 20 A REC

24

21 7176 VA 720 VA 1 20 A REC KILN ROOM 122F 22

19 REC MIG WELDER, EXTERIOR YARD-1140-1 30 A 2

7176 VA 200 VA 20

17 16640 VA 200 VA 18

15REC WELDER, EXTERIOR YARD-1 140-1 30 A 2

16640 VA 200 VA

3 20 A NC EXTERIOR YARD-1 140-1

16

13 REC CASTING, CASTING AREA 130F 20 A 1 2400 VA 1680 VA 14

11 REC KILN, CASTING AREA 130F 20 A 1 2400 VA 1680 VA 12

9 REC WAX INJECTOR, CASTING AREA 130F 20 A 1 660 VA 1680 VA

3 20 A NC EXTERIOR YARD-1 140-1

10

7 REC CRUCIBLE. CASTING AREA 130F 20 A 1 1680 VA 0 VA 1 20 A Spare 8

5 REC PRESS, CASTING AREA 130F 20 A 1 660 VA 0 VA 1 20 A Spare 6

3 REC WAX INJECTOR CASTING AREA 130F 20 A 1 660 VA 0 VA 1 20 A Spare 4

1 REC CLEANER, CASTING AREA 130F 20 A 1 300 VA 0 VA 1 30 A MTR-EF-1 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 84 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: L1DB Phases: 3 Mains Type:Location: EXTERIOR YARD-1 140-1 Volts: 120/208 Wye A.I.C. Rating: 10000

Branch Panel: 1LP5

SKIRT: TOP & BOTTOMNotes:

Total Est. Demand Current: 68 ATotal Conn. Current: 104 A

REC 36020 VA 63.88% 23010 VA Total Est. Demand: 24563 VAMTR 1373 VA 100.00% 1373 VA Total Conn. Load: 37573 VANC 180 VA 100.00% 180 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 115 A 102 A 98 ATotal Load: 13675 VA 12167 VA 11731 VA

83 Space -- -- 0 VA 0 VA -- -- Space 84

81 Space -- -- 0 VA 0 VA -- -- Space 82

79 Space -- -- 0 VA 0 VA -- -- Space 80

77 Space -- -- 0 VA 0 VA -- -- Space 78

75 Space -- -- 0 VA 0 VA -- -- Space 76

73 Space -- -- 0 VA 0 VA -- -- Space 74

71 Space -- -- 0 VA 0 VA -- -- Space 72

69 Space -- -- 0 VA 0 VA -- -- Space 70

67 Space -- -- 0 VA 0 VA -- -- Space 68

65 Space -- -- 0 VA 0 VA -- -- Space 66

63 Space -- -- 0 VA 0 VA -- -- Space 64

61 Space -- -- 0 VA 0 VA -- -- Space 62

59 Space -- -- 0 VA 0 VA -- -- Space 60

57 Space -- -- 0 VA 0 VA -- -- Space 58

55 Space -- -- 0 VA 0 VA -- -- Space 56

53 Space -- -- 0 VA 0 VA -- -- Space 54

51 PLASMA TABLE 20 A 1 600 VA 0 VA -- -- Space 52

49 REC EXTERIOR YARD-1 140-1 20 A 1 540 VA 0 VA -- -- Space 50

47 REC EXTERIOR YARD-1 140-1 20 A 1 360 VA 0 VA -- -- Space 48

45 REC POWDER COATING 130H 20 A 1 540 VA 0 VA -- -- Space 46

43 REC MACHINERY 130J 20 A 1 1728 VA 0 VA -- -- Space 44

41 REC MACHINERY 130J 20 A 1 1728 VA 0 VA -- -- Space 42

39 REC BENCH GRINDER, EXTERIOR YARD... 20 A 1 600 VA 0 VA -- -- Space 40

37 1040 VA 0 VA 1 20 A Spare 38

35REC EXTERIOR YARD-1 140-1 40 A 2

1040 VA 0 VA 1 20 A Spare 36

33 REC BLAST CABINET, EXTERIOR YARD 35 A 1 2400 VA 0 VA 1 20 A Spare 34

31 REC PANEL SAW, EXTERIOR YARD-1... 20 A 1 1800 VA 0 VA 1 20 A Spare 32

29 668 VA 0 VA 1 20 A Spare 30

27 668 VA 0 VA 1 20 A Spare 28

25

REC EXTERIOR YARD-1 140-1 20 A 3

668 VA 0 VA 1 20 A Spare 26

23 458 VA 0 VA 1 20 A Spare 24

21 458 VA 0 VA 1 20 A Spare 22

19

MTR EXTERIOR YARD-1 140-1 30 A 3

458 VA 180 VA 1 20 A REC EXTERIOR YARD-1 140-1 20

17 REC POWDER COATING 130H 35 A 1 2400 VA 360 VA 1 20 A REC EXTERIOR YARD-1 140-1 18

15 REC BENCH GRINDER, MACHINERY 130J 20 A 1 864 VA 180 VA 1 20 A REC EXTERIOR YARD-1 140-1 16

13 REC MACHINERY 130J 20 A 1 720 VA 2773 VA 14

11 REC POLISHER & DUST COLLECTION... 20 A 1 864 VA 2773 VA 12

9 REC MACHINERY 130J 20 A 1 360 VA 2773 VA

3 50 A11E PLASMA TABLE REC EXTERIORYARD-1 140-1

10

7 REC MACHINERY 106E 20 A 1 864 VA 360 VA 1 20 A REC EXTERIOR YARD-1 140-1 8

5 REC EXTERIOR YARD-1 140-1 20 A 1 180 VA 900 VA 1 20 A REC EXTERIOR YARD-1 140-1 6

3 2184 VA 540 VA 1 20 A REC ROOM 140-1, M150 4

1REC EXTERIOR YARD-1 140-1 30 A 2

2184 VA 360 VA 1 20 A REC ROOM 140-1, 130H 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 84 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: L1DB Phases: 3 Mains Type:Location: EXTERIOR YARD-1 140-1 Volts: 120/208 Wye A.I.C. Rating: 10000

Branch Panel: 1LP6

Notes:

Total Est. Demand Current: 31 ATotal Conn. Current: 30 A

LTG 1110 VA 125.00% 1388 VA Total Est. Demand: 11047 VAREC 9600 VA 100.00% 9600 VA Total Conn. Load: 10780 VANC 120 VA 100.00% 120 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 37 A 39 A 19 ATotal Load: 4107 VA 4392 VA 2281 VA

41 LTG ART GALLERY 105 20 A 1 15 VA 0 VA 1 20 A Spare 42

39 LTG ART GALLERY 105 20 A 1 15 VA 0 VA 1 20 A Spare 40

37 LTG ART GALLERY 105 20 A 1 15 VA 0 VA 1 20 A Spare 38

35 LTG ART GALLERY 105 20 A 1 15 VA 0 VA 1 20 A Spare 36

33 LTG ART GALLERY 105 20 A 1 15 VA 0 VA 1 20 A Spare 34

31 LTG ART GALLERY 105 20 A 1 15 VA 0 VA 1 20 A Spare 32

29 LTG ART GALLERY 105 20 A 1 15 VA 0 VA 1 20 A Spare 30

27 LTG ART GALLERY 105 20 A 1 105 VA 0 VA 1 20 A Spare 28

25 LTG ART GALLERY 105 20 A 1 105 VA 0 VA 1 20 A Spare 26

23 LTG ART GALLERY 105 20 A 1 90 VA 0 VA 1 20 A Spare 24

21 LTG ART GALLERY 105 20 A 1 120 VA 0 VA 1 20 A Spare 22

19 LTG ART GALLERY 105 20 A 1 105 VA 0 VA 1 20 A Spare 20

17 LTG ART GALLERY 105 20 A 1 105 VA 0 VA 1 20 A Spare 18

15 REC ART GALLERY-1 105-1 20 A 1 1440 VA 75 VA 1 20 A LTG RETABLOS GALLERY 110 16

13 REC ART GALLERY-1 105-1 20 A 1 1800 VA 30 VA 1 20 A LTG RETABLOS GALLERY 110 14

11 REC ART GALLERY-1 105-1 20 A 1 900 VA 60 VA 1 20 A LTG MODERN & CONTEMPORARY ART... 12

9 REC ART GALLERY-1 105-1 20 A 1 1080 VA 60 VA 1 20 A LTG MODERN & CONTEMPORARY ART... 10

7 REC ART GALLERY-1 105-1 20 A 1 960 VA 60 VA 1 20 A LTG MODERN & CONTEMPORARY ART... 8

5 REC ART GALLERY-1 105-1 20 A 1 1080 VA 15 VA 1 20 A LTG ART GALLERY 105 6

3 REC MODERN ART GALLERY 105A 20 A 1 900 VA 600 VA 1 20 A REC CEILING PROJECTOR, GALLERY... 4

1 REC MODERN ART GALLERY 105A 20 A 1 960 VA 75 VA 1 20 A LTG 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Recessed Wires: 4 Mains Rating: 225 A

Supply From: L1DB Phases: 3 Mains Type:Location: ART GALLERY 105 Volts: 120/208 Wye A.I.C. Rating: 10000

Branch Panel: 1LP7

Notes:

Total Est. Demand Current: 25 ATotal Conn. Current: 25 A

LTG 0 VA 0.00% 0 VA Total Est. Demand: 9180 VAREC 8700 VA 100.00% 8700 VA Total Conn. Load: 9180 VANC 480 VA 100.00% 480 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 24 A 28 A 25 ATotal Load: 2880 VA 3360 VA 2940 VA

41 Space -- -- 0 VA 0 VA -- -- Space 42

39 Space -- -- 0 VA 0 VA -- -- Space 40

37 Space -- -- 0 VA 0 VA -- -- Space 38

35 Spare 20 A 1 0 VA 0 VA -- -- Space 36

33 Spare 20 A 1 0 VA 0 VA -- -- Space 34

31 Spare 20 A 1 0 VA 0 VA -- -- Space 32

29 Spare 20 A 1 0 VA 0 VA -- -- Space 30

27 Spare 20 A 1 0 VA 0 VA -- -- Space 28

25 Spare 20 A 1 0 VA 0 VA -- -- Space 26

23 Spare 20 A 1 0 VA 0 VA -- -- Space 24

21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22

19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20

17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18

15 PROJECTINO SCREEN RM 115 20 A 1 300 VA 0 VA 1 20 A CEF-2 16

13 REC ROOM 115 20 A 1 540 VA 0 VA 1 20 A CEF-1 14

11 REC PREP + FRAMING ROOM 113 20 A 1 360 VA 600 VA 1 20 A REC CEILING PROJECTOR, LAB 115 12

9 REC PREP + FRAMING ROOM 113 20 A 1 900 VA 180 VA 1 20 A NC FUME HOOD, CONSERVATION LAB 115 10

7 REC GALLERY PREP ROOM (DIRTY) 107 20 A 1 360 VA 900 VA 1 20 A REC ROOM 115 8

5 REC PREP + FRAMING ROOM 113 20 A 1 1080 VA 900 VA 1 20 A REC CONSERVATION LAB 115 6

3 REC GALLERY PREP ROOM (DIRTY) 107 20 A 1 900 VA 1080 VA 1 20 A REC CONSERVATION LAB 115 4

1 REC GALLERY PREP ROOM (DIRTY) 107 20 A 1 720 VA 360 VA 1 20 A REC PREP + FRAMING ROOM 113 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Recessed Wires: 4 Mains Rating: 225 A

Supply From: L1DB Phases: 3 Mains Type:Location: FRAME PREP ROOM 113 Volts: 120/208 Wye A.I.C. Rating: 10000

Branch Panel: 1LP8

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:19:37-07'00'

Page 15: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

E-707

NEW ARTBUILDINGNMSU LAS CRUCES, NM

ELECTRICAL PANEL SCHEDULES

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

Checker

Author

KEY NOTE

2LP1 2LP2

2LP42LP3

SKIRT: TOP & BOTTOMNotes:

Total Est. Demand Current: 25 ATotal Conn. Current: 25 A

Total Est. Demand: 8840 VAREC 8340 VA 100.00% 8340 VA Total Conn. Load: 8840 VANC 500 VA 100.00% 500 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 28 A 23 A 23 ATotal Load: 3360 VA 2760 VA 2720 VA

41 Space -- -- 0 VA 0 VA -- -- Space 42

39 Space -- -- 0 VA 0 VA -- -- Space 40

37 Space -- -- 0 VA 0 VA -- -- Space 38

35 Space -- -- 0 VA 0 VA -- -- Space 36

33 Space -- -- 0 VA 0 VA -- -- Space 34

31 Spare 20 A 1 0 VA 0 VA -- -- Space 32

29 Spare 20 A 1 0 VA 0 VA -- -- Space 30

27 Spare 20 A 1 0 VA 0 VA -- -- Space 28

25 Spare 20 A 1 0 VA 0 VA -- -- Space 26

23 REC Room 224B-1, 224A-1, 224C-1 20 A 1 540 VA 0 VA 1 20 A Spare 24

21 REC Room 224B-1, 224A-1, 224C-1 20 A 1 540 VA 0 VA 1 20 A Spare 22

19 REC WASH OUT-1 224A-1 20 A 1 1350 VA 0 VA 1 20 A Spare 20

17 REC CEILING PROJECTOR, DESIGN... 20 A 1 1100 VA 0 VA 1 20 A Spare 18

15 REC DESIGN STUDIO-1 224-1 20 A 1 1080 VA 0 VA 1 20 A Spare 16

13 REC DESIGN STUDIO-1 224-1 20 A 1 1080 VA 0 VA 1 20 A Spare 14

11 REC DESIGN STUDIO-1 224-1 20 A 1 900 VA 0 VA 1 20 A Spare 12

9 REC DESIGN STUDIO-1 224-1 20 A 1 900 VA 0 VA 1 20 A Spare 10

7 REC LARGE PRINTER, WORKSHOP-1... 20 A 1 750 VA 0 VA 1 20 A Spare 8

5 REC VALAD HOT PLATE, WORKSHOP-1... 20 A 1 180 VA 0 VA 1 20 A Spare 6

3 REC EXPOSURE TABLE, WORKSHOP-1... 20 A 1 240 VA 0 VA 1 20 A Spare 4

1 REC LIGHT TABLE, WORKSHOP-1 224-1 20 A 1 180 VA 0 VA 1 20 A Spare 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: L2DB Phases: 3 Mains Type:Location: DESIGN STUDIO-1 224-1 Volts: 120/208 Wye A.I.C. Rating: 10000

Branch Panel: 2LP2

SKIRT: TOP & BOTTOMNotes:

Total Est. Demand Current: 18 ATotal Conn. Current: 18 A

Total Est. Demand: 6307 VAREC 5307 VA 100.00% 5307 VA Total Conn. Load: 6307 VANC 1000 VA 100.00% 1000 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 16 A 27 A 11 ATotal Load: 1874 VA 3154 VA 1280 VA

41 Space -- -- 0 VA 0 VA -- -- Space 42

39 Space -- -- 0 VA 0 VA -- -- Space 40

37 Space -- -- 0 VA 0 VA -- -- Space 38

35 Space -- -- 0 VA 0 VA -- -- Space 36

33 REC DROP-CORD, DRAWING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 34

31 REC DROP-CORD, DRAWING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 32

29 REC DROP-CORD, DRAWING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 30

27 REC DROP-CORD, DRAWING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 28

25 Spare 20 A 1 0 VA 0 VA -- -- Space 26

23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24

21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22

19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20

17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18

15 REC CEILING PROJECTOR, PAINTING-1... 20 A 1 1100 VA 0 VA 1 20 A Spare 16

13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14

11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12

9 REC DRAWING/PAINTING-1 232-1 20 A 1 1080 VA 0 VA 1 20 A Spare 10

7 REC DRAWING/PAINTING-1 232-1 20 A 1 1080 VA 0 VA 1 20 A Spare 8

5 REC CEILING PROJECTOR, PAINTING-1... 20 A 1 1100 VA 0 VA 1 20 A Spare 6

3 614 VA 0 VA 1 20 A Spare 4

1 REC GAS KILN, DRAWING/PAINTING-1232-1 30 A 2

614 VA 0 VA 1 20 A Spare 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: L2DB Phases: 3 Mains Type:Location: DRAWING STUDIO-1 232-1 Volts: 120/208 Wye A.I.C. Rating: 10000

Branch Panel: 2LP4

SKIRT: TOP & BOTTOMNotes:

Total Est. Demand Current: 46 ATotal Conn. Current: 62 A

Total Est. Demand: 16513 VAREC 21666 VA 73.08% 15833 VA Total Conn. Load: 22346 VANC 680 VA 100.00% 680 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 77 A 55 A 54 ATotal Load: 9180 VA 6636 VA 6530 VA

83 Space -- -- 0 VA 0 VA -- -- Space 84

81 Space -- -- 0 VA 0 VA -- -- Space 82

79 Space -- -- 0 VA 0 VA -- -- Space 80

77 Space -- -- 0 VA 0 VA -- -- Space 78

75 Space -- -- 0 VA 0 VA -- -- Space 76

73 Space -- -- 0 VA 0 VA -- -- Space 74

71 Spare 20 A 1 0 VA 0 VA -- -- Space 72

69 Spare 20 A 1 0 VA 0 VA -- -- Space 70

67 Spare 20 A 1 0 VA 0 VA -- -- Space 68

65 Spare 20 A 1 0 VA 0 VA -- -- Space 66

63 Spare 20 A 1 0 VA 0 VA -- -- Space 64

61 Spare 20 A 1 0 VA 0 VA -- -- Space 62

59 Spare 20 A 1 0 VA 0 VA -- -- Space 60

57 Spare 20 A 1 0 VA 0 VA -- -- Space 58

55 Spare 20 A 1 0 VA 0 VA -- -- Space 56

53 Spare 20 A 1 0 VA 0 VA -- -- Space 54

51 Spare 20 A 1 0 VA 0 VA -- -- Space 52

49 Spare 20 A 1 0 VA 0 VA -- -- Space 50

47 Spare 20 A 1 0 VA 0 VA -- -- Space 48

45 Spare 20 A 1 0 VA 0 VA -- -- Space 46

43 Spare 20 A 1 0 VA 0 VA -- -- Space 44

41 REC Room 222C-1, 222D-1 20 A 1 360 VA 0 VA -- -- Space 42

39 REC Room 222C-1, 222D-1 20 A 1 360 VA 0 VA -- -- Space 40

37 REC GANG DARK RM. 222B 20 A 1 540 VA 0 VA -- -- Space 38

35 REC Room 210-1, 222A 20 A 1 540 VA 0 VA -- -- Space 36

33 REC REFRIGERATOR, STORAGE 222A 20 A 1 600 VA 0 VA 1 20 A Spare 34

31 REC VENDING MACHINE , HALL H101E 20 A 1 1200 VA 0 VA 1 20 A Spare 32

29 REC DROP-CORD FILM PROCESSING... 20 A 1 180 VA 0 VA 1 20 A Spare 30

27 REC DROP-CORD FILM PROCESSING... 20 A 1 180 VA 0 VA 1 20 A Spare 28

25 NC EYE WASH, FILM PROCESSING RM-1... 20 A 1 180 VA 360 VA 1 20 A REC FACULTY STUDIO (SAFETY)-1 242-1 26

23 REC FILM PROCESSING RM-1 222E-1 20 A 1 360 VA 600 VA 1 20 A REC GANG DARK RM 222B 24

21 REC FILM PROCESSING RM-1 222E-1 20 A 1 360 VA 600 VA 1 20 A REC GANG DARK RM 222B 22

19 REC PHOTO STUDIO-1 222-1 20 A 1 900 VA 600 VA 1 20 A REC BESELER ENLARGER, GANG DARK... 20

17 REC PHOTO STUDIO-1 222-1 20 A 1 1080 VA 600 VA 1 20 A REC BESELER ENLARGER, GANG DARK... 18

15 REC EXPOSURE TABLE, PHOTO STUDIO... 20 A 1 1800 VA 600 VA 1 20 A REC BESELER ENLARGER, GANG DARK... 16

13 REC LIGHT TABLE, PHOTO STUDIO-1... 20 A 1 1680 VA 600 VA 1 20 A REC BESELER ENLARGER, GANG DARK... 14

11 REC CEILING PROJECTOR, PHOTO... 20 A 1 1100 VA 600 VA 1 20 A REC BESELER ENLARGER, GANG DARK... 12

9 REC PRESS, PROCESSING RM-1 222E-1 20 A 1 996 VA 600 VA 1 20 A REC BESELER ENLARGER, GANG DARK... 10

7 REC REFRIGERATOR, PROCESSING RM-... 20 A 1 600 VA 360 VA 1 20 A REC FACULTY STUDIO (SAFETY)-1 242-1 8

5 REC DRUM DRYER, PROCESSING RM-1... 20 A 1 750 VA 360 VA 1 20 A REC FACULTY STUDIO (SAFETY)-1 242-1 6

3 REC FILM PROCESSING RM-1 222E-1 20 A 1 180 VA 360 VA 1 20 A REC GRAD STUDIO HUDDLE-1 240-1 4

1 REC COPY STAND, PROCESSING RM-1... 20 A 1 1800 VA 360 VA 1 20 A REC GRAD STUDIO HUDDLE-1 240-1 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 84Mounting: RECESSED Wires: 4 Mains Rating: 225 A

Supply From: L2DB Phases: 3 Mains Type:Location: PHOTO STUDIO-1 222-1 Volts: 120/208 Wye A.I.C. Rating: 10000

Branch Panel: 2LP3

SKIRT: TOP & BOTTOMNotes:

Total Est. Demand Current: 12 ATotal Conn. Current: 12 A

Total Est. Demand: 4340 VATotal Conn. Load: 4340 VA

REC 4340 VA 100.00% 4340 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 16 A 14 A 8 ATotal Load: 1760 VA 1620 VA 960 VA

41 Spare 20 A 1 0 VA 0 VA -- -- Space 42

39 Spare 20 A 1 0 VA 0 VA -- -- Space 40

37 Spare 20 A 1 0 VA 0 VA -- -- Space 38

35 Spare 20 A 1 0 VA 0 VA -- -- Space 36

33 Spare 20 A 1 0 VA 0 VA -- -- Space 34

31 Spare 20 A 1 0 VA 0 VA -- -- Space 32

29 Spare 20 A 1 0 VA 0 VA -- -- Space 30

27 Spare 20 A 1 0 VA 0 VA -- -- Space 28

25 Spare 20 A 1 0 VA 0 VA -- -- Space 26

23 Spare 20 A 1 0 VA 0 VA -- -- Space 24

21 Spare 20 A 1 0 VA 0 VA -- -- Space 22

19 REC FLAT SCREEN, METALS/JEWELRY-1... 20 A 1 500 VA 0 VA -- -- Space 20

17 REC DROP-CORD, PAINTING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 18

15 REC DROP-CORD, PAINTING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 16

13 REC DROP-CORD, PAINTING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 14

11 REC DROP-CORD, PAINTING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 12

9 REC ROOM 230B-1, 230-1 20 A 1 540 VA 0 VA 1 20 A Spare 10

7 REC WASHER, PAINTING-1 230-1 20 A 1 180 VA 0 VA 1 20 A Spare 8

5 REC REFRIGERATOR, PAINTING-1 230-1 20 A 1 600 VA 0 VA 1 20 A Spare 6

3 REC PAINTING-1 230-1 20 A 1 900 VA 0 VA 1 20 A Spare 4

1 REC PAINTING-1 230-1 20 A 1 900 VA 0 VA 1 20 A Spare 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: L2DB Phases: 3 Mains Type:Location: PAINTING STUDIO-1 230-1 Volts: 120/208 Wye A.I.C. Rating: 10000

Branch Panel: 2LP1

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:20:03-07'00'

Page 16: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

E-708

NEW ARTBUILDINGNMSU LAS CRUCES, NM

ELECTRICAL PANEL SCHEDULES

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

Checker

Author

Notes:

LTG 1093 VA 125.00% 1366 VA Total Est. Demand Current: 547 AREC 3600 VA 100.00% 3600 VA Total Conn. Current: 547 AMTR 322759 VA 100.00% 322759 VA Total Est. Demand: 455031 VANC 116130 VA 100.00% 116130 VA Total Conn. Load: 454760 VAOther 11185 VA 100.00% 11185 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 553 A 542 A 548 ATotal Load: 152924 VA 150213 VA 151623 VA

125 Space -- -- 0 VA 0 VA -- -- Space 126

123 Space -- -- 0 VA 0 VA -- -- Space 124

121 Space -- -- 0 VA 0 VA -- -- Space 122

119 Space -- -- 0 VA 0 VA -- -- Space 120

117 Space -- -- 0 VA 0 VA -- -- Space 118

115 Space -- -- 0 VA 0 VA -- -- Space 116

113 Space -- -- 0 VA 0 VA -- -- Space 114

111 Spare 20 A 1 0 VA 0 VA -- -- Space 112

109 Spare 20 A 1 0 VA 0 VA -- -- Space 110

107 Spare 20 A 1 0 VA 0 VA 108

105 Spare 20 A 1 0 VA 0 VA 106

103 Spare 20 A 1 0 VA 0 VA

3 80 A Spare

104

101 Spare 20 A 1 0 VA 0 VA 102

99 Spare 20 A 1 0 VA 0 VA 100

97 Spare 20 A 1 0 VA 0 VA

3 50 A Spare

98

95 Spare 20 A 1 0 VA 0 VA 96

93 7479... 0 VA 94

91 7479... 0 VA

3 30 A Spare

92

89

VFD-16 - AHU-2 SF(2) 50 A 3

7479... 0 VA 90

87 7479... 0 VA 88

85 7479... 0 VA

3 20 A Spare

86

83

VFD-15 - AHU-2 SF(2) 50 A 3

7479... 5817... 84

81 2105... 5817... 82

79 2105... 5817...

3 20 A VFD-14 - DOAS-1

80

77

VFD-17 - AHU-2 RF 40 A 3

2105... 1108... 78

75 7479... 1108... 76

73 7479... 1108...

3 80 A VFD-8 - LED-1(1)

74

71

VFD-16 - AHU-2 SF 50 A 3

7479... 1108... 72

69 7479... 1108... 70

67 7479... 1108...

3 80 A VFD-7 - LED-1(2)

68

65

VFD-15 - AHU-2 SF 50 A 3

7479... 3878... 66

63 FCU-2/3 20 A 1 1994... 3878... 64

61 LTG PENTHOUSE 20 A 1 410 VA 3878...

3 30 A VFD-8 - MAU-1(4)

62

59 9418... 3728... 60

57 9418... 3728... 58

55

LEF1 FAN 2 75 A 3

9418... 3728...

3 30 A Other

56

53 9418... 3878... 54

51 9418... 3878... 52

49

LEF1 FAN 1 75 A 3

9418... 3878...

3 30 A VFD-8 - MAU-1(3)

50

47 831 VA 3878... 48

45 831 VA 3878... 46

43

EF-3 15 A 3

831 VA 3878...

3 30 A VFD-9 - MAU-1(2)

44

41 582 VA 3878... 42

39 582 VA 3878... 40

37

EF-4 15 A 3

582 VA 3878...

3 30 A VFD-9 - MAU-1(1)

38

35 1329... 2105... 36

33 1329... 2105... 34

31

EF-5 15 A 3

1329... 2105...

3 20 A VFD-13 - AHU-1 RF

32

29 2105... 5817... 30

27 2105... 5817... 28

25

EF-6 20 A 3

2105... 5817...

3 40 A VFD-10 - MAU-1 SF

26

23 2105... 5817... 24

21 2105... 5817... 22

19

EF-7 20 A 3

2105... 5817...

3 40 A VFD-11 - MAU-1 SF

20

17 3878... 2105... 18

15 3878... 2105... 16

13

RTU-2 20 A 3

3878... 2105...

3 20 A VFD-12 - AHU-1 RF

14

11 3878... 2105... 12

9 3878... 2105... 10

7

RTU-1 30 A 3

3878... 2105...

3 20 A VFD-18 - AHU-2 RF

8

5 1248... 8409... 6

3 1248... 5005... 4

1

C-1 60 A 3

1248... 9321...

3 20 A TP

2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 126 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 600 A

Supply From: MSB Phases: 3 Mains Type:Location: MECH. PENTHOUSE M300 Volts: 480/277 Wye A.I.C. Rating: 25000

Branch Panel: MP

KEY NOTE

MP

Notes:

Total Est. Demand Current: 23 ATotal Conn. Current: 23 A

Total Est. Demand: 19200 VATotal Conn. Load: 19200 VA

MTR 19200 VA 100.00% 19200 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 26 A 45 A 4 ATotal Load: 6480 VA 11520 VA 1200 VA

29 Space -- -- 0 VA 0 VA -- -- Space 30

27 Spare 20 A 1 0 VA 0 VA -- -- Space 28

25 Spare 20 A 1 0 VA 0 VA -- -- Space 26

23 Spare 20 A 1 0 VA 0 VA -- -- Space 24

21 Spare 20 A 1 0 VA 0 VA -- -- Space 22

19 Spare 20 A 1 0 VA 0 VA -- -- Space 20

17 Spare 20 A 1 0 VA 0 VA -- -- Space 18

15 Spare 20 A 1 0 VA 0 VA -- -- Space 16

13 Spare 20 A 1 0 VA 0 VA -- -- Space 14

11 Spare 20 A 1 0 VA 0 VA -- -- Space 12

9 Spare 20 A 1 0 VA 0 VA -- -- Space 10

7 Spare 20 A 1 0 VA 0 VA -- -- Space 8

5 MTR TU2-201-TU2-208 20 A 1 1200... 0 VA -- -- Space 6

3 MTR ECV 20 A 1 1152... 0 VA -- -- Space 4

1 MTR ECV 20 A 1 6480... 0 VA -- -- Space 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 42Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: MSB Phases: 3 Mains Type:Location: ELEC. RM-1 M225B-1 Volts: 480/277 Wye A.I.C. Rating: 22000

Branch Panel: M2A

KEY NOTE

M2A

Notes:

Total Est. Demand Current: 19 ATotal Conn. Current: 19 A

Total Est. Demand: 7020 VATotal Conn. Load: 7020 VA

REC 7020 VA 100.00% 7020 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 29 A 12 A 19 ATotal Load: 3330 VA 1485 VA 2205 VA

29 Space -- -- 0 VA 0 VA -- -- Space 30

27 Space -- -- 0 VA 0 VA -- -- Space 28

25 Space -- -- 0 VA 0 VA -- -- Space 26

23 Space -- -- 0 VA 0 VA -- -- Space 24

21 Space -- -- 0 VA 0 VA -- -- Space 22

19 Space -- -- 0 VA 0 VA -- -- Space 20

17 Space -- -- 0 VA 0 VA -- -- Space 18

15 Space -- -- 0 VA 0 VA 1 20 A Spare 16

13 Space -- -- 0 VA 0 VA 1 20 A Spare 14

11 REC ROOM T125A, M125B, M127 20 A 1 1080... 0 VA 1 20 A Spare 12

9 REC MDF T125A 20 A 1 360 VA 0 VA 1 20 A Spare 10

7 1125... 0 VA 1 20 A Spare 8

5REC MDF T125A 30 A 2

1125... 0 VA 1 20 A Spare 6

3 1125... 0 VA 1 20 A Spare 4

1REC MDF T125A 30 A 2

1125... 1080... 1 20 A REC ROOM T125A, M125B, R123C 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 30 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: T-LT Phases: 3 Mains Type:Location: MDF T125A Volts: 120/208 Wye A.I.C. Rating: 10000

Branch Panel: LT

Notes:

Total Est. Demand Current: 17 ATotal Conn. Current: 17 A

Total Est. Demand: 6300 VATotal Conn. Load: 6300 VA

REC 6300 VA 100.00% 6300 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 16 A 25 A 12 ATotal Load: 1845 VA 2970 VA 1485 VA

29 Space -- -- 0 VA 0 VA -- -- Space 30

27 Space -- -- 0 VA 0 VA -- -- Space 28

25 Space -- -- 0 VA 0 VA -- -- Space 26

23 Space -- -- 0 VA 0 VA -- -- Space 24

21 Space -- -- 0 VA 0 VA -- -- Space 22

19 Space -- -- 0 VA 0 VA -- -- Space 20

17 Space -- -- 0 VA 0 VA -- -- Space 18

15 Space -- -- 0 VA 0 VA 1 20 A Spare 16

13 Space -- -- 0 VA 0 VA 1 20 A Spare 14

11 REC TR-1 T225A-1 20 A 1 360 VA 0 VA 1 20 A Spare 12

9 REC TR-1 T225A-1 30 A 1 2250... 0 VA 1 20 A Spare 10

7 1125... 0 VA 1 20 A Spare 8

5REC TR-1 T225A-1 30 A 2

1125... 0 VA 1 20 A Spare 6

3 REC TR-1 T225A-1 20 A 1 720 VA 0 VA 1 20 A Spare 4

1 REC TR-1 T225A-1 20 A 1 720 VA 0 VA 1 20 A Spare 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 42Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: Phases: 3 Mains Type:Location: TR-1 T225A-1 Volts: 120/208 Wye A.I.C. Rating: 10000

Branch Panel: LT2

M1 LT

Notes:

Total Est. Demand Current: 125 ATotal Conn. Current: 125 A

Total Est. Demand: 103916 VAMTR 49780 VA 100.00% 49780 VA Total Conn. Load: 103916 VANC 54136 VA 100.00% 54136 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 157 A 121 A 102 ATotal Load: 42787 VA 32923 VA 28207 VA

41 Space -- -- 0 VA 0 VA -- -- Space 42

39 Space -- -- 0 VA 0 VA -- -- Space 40

37 Space -- -- 0 VA 0 VA -- -- Space 38

35 Space -- -- 0 VA 0 VA -- -- Space 36

33 Spare 20 A 1 0 VA 0 VA -- -- Space 34

31 Spare 20 A 1 0 VA 0 VA -- -- Space 32

29 Spare 20 A 1 0 VA 0 VA -- -- Space 30

27 5533 VA 696 VA 1 20 A MTR MECHANICAL ROOM M125C 28

25 5533 VA 2533 VA 26

23

AC-1-COMPRESSOR RM 142 40 A 3

5533 VA 2533 VA 24

21 3878 VA 2533 VA

3 20 A NC EXTERIOR YARD-1 140-1

22

19 3878 VA 3878 VA 20

17

NC MECHANICAL ROOM M125C 20 A 3

3878 VA 3878 VA 18

15 3878 VA 3878 VA

3 30 A MTR EXTERIOR YARD-1 140-1

16

13 3878 VA 6480 VA 1 20 A MTR CERAMICS FACULTY STUDIO 122A 14

11

NC MECHANICAL ROOM M125C 20 A 3

3878 VA 3878 VA 12

9 MTR ECV 20 A 1 4320 VA 3878 VA 10

7 MTR ECV 20 A 1 7200 VA 3878 VA

3 20 A NC MECHANICAL ROOM M125C

8

5 MTR TU2-103 - 105, STUDIO WING 20 A 1 750 VA 3878 VA 6

3 MTR TU1-10 - TU1-12, BID LOT 1 20 A 1 450 VA 3878 VA 4

1 MTR TU1-1 - TU1-9, GALLERY WING 20 A 1 1650 VA 3878 VA

3 20 A NC MECHANICAL ROOM M125C

2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: MSB Phases: 3 Mains Type:Location: ELEC M125B Volts: 480/277 Wye A.I.C. Rating: 22000

Branch Panel: M1

LT2

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:20:15-07'00'

Page 17: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

ENJAM N E. BOSSE

19418

GIN

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

E-801

NEW ARTBUILDINGNMSU LAS CRUCES, NM

LABORATORY EQUIPMENT ELECTRICALSCHEDULE

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB

OU

LABORATORY EQUIPMENT - ELECTRICAL SCHEDULEEQUIPMENT

NO. EQUIPMENT DESCRIPTION VOLTAGE PHASEEQUIPMENT LOAD BRANCH CIRCUIT

CONDUCTORCONDUIT

SIZEEQUIPMENT

TERMINATIONKEYEDNOTESCHARATERISTICS

1E 208 1 3#6 & 1#10 GND 1" RECEPTACLE2E 208 1 3#6 & 1#10 GND 1" RECEPTACLE3E MILLERMATIC 250 MIG PORTABLE WELDER 208 1 50A 3#4 & 1#8 GND 1" RECEPTACLE3N MILLERMATIC WELDER 208 1 31A 3#6 & 1#10 GND 1" RECEPTACLE4E MILLER ECONOTIG TIG WELDER 208 1 52A 3#4 & 1#8 GND 1-1/4" RECEPTACLE5E MILLER PLASMA CUTTER 208 1 60A 3#4 & 1#8 GND 1-1/4" RECEPTACLE5N MILLERMATIC WELDER 208 1 31A 3#6 & 1#10 GND 1" RECEPTACLE6E POWERMATIC DRILL PRESS 120 1 15.7A 2#12 & 1#12 GND 3/4" RECEPTACLE7E BALDOR GRINDER 120 1 3.8 2#12 & 1#12 GND 3/4" RECEPTACLE8E PIPE BENDER 208 3 6.2A 3#10 & 1#10 GND 3/4" NFSS

10E METAL PLANISHER NA NO ELEC11E PLASMA-CAM CUTTING TABLE 208 1 40A 3#6 & 1#10 GND 1" RECEPTACLE12E MILLER MIG WELDER 208 1 30A 3#6 & 1#10 GND 1" RECEPTACLE13E MILLER MIG WELDER 208 1 30A 3#6 & 1#10 GND 1" RECEPTACLE14E MILLER MIG WELDER 208 1 69A 3#6 & 1#10 GND 1" RECEPTACLE15E 1/2 TON CRANE 208 3 2A 4#12 & 1#12 GND 3/4" NFSS17E MCENGEL HI SPEED MELT FURNACE 208 3 XX 4#12 & 1#12 GND 3/4" RECEPTACLE18E BEAD BLAST CABINET 120 1HP 2#12 & 1#12 GND 3/4" RECEPTACLE19E COFFING HOIST DOWN PILLER JIB CRANE NA20E SAW STOP 10" TABLE 208 1 19.7A 3#10 & 1#10 GND 3/4" RECEPTACLE21E DEWALT 12" COMPOUND 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE22E DELTA DRILL PRESS 120 1 12A 2#12 & 1#12 GND 3/4" RECEPTACLE23E MILWAUKEE PANEL SAW 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE23N REAR DRAFT MEASURING TABLE NA NO ELEC24E POWERMATIC DISC SANDER 120 1 14A 2#12 & 1#12 GND 3/4" RECEPTACLE25E POWERMATIC DISC SANDER 208 3 9.8A 4#12 & 1#12 GND 3/4" RECEPTACLE26E ROCKWELL BANDSAW 208 1 11.5 3#12 & 1#12 GND 3/4" RECEPTACLE26N FUME HOOD 120 1 2.5A 2#12 & 1#12 GND 3/4" HARD WIRE27E DELTA BANDSAW 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE27N FUME HOOD 120 2.5 2#12 & 1#12 GND 3/4" HARD WIRE30E BRENT CXC POTTERS WHEELS 120 1 10A 2#12 & 1#12 GND 3/4" RECEPTACLE30N WALK-IN SPRAY BOOTH NA 3/4" RECEPTACLE31E THOMAS STUART POTTERS WHEELS 120 1 10.4A 2#12 & 1#12 GND 3/4" RECEPTACLE31N STAINLESS STEEL QUAD RECEP OVER

CENTRAL BENCHES120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE

32E LAMAN SLIP MIXER 120 1 7.3A 2#12 & 1#12 GND 3/4" RECEPTACLE33E AIR COMPRESSOR 120 1 1HP 2#12 & 1#12 GND 3/4" RECEPTACLE33N SNORKLE OVER RESIN PREP NA NO ELEC34E REAR DRAFT MEASURING TABLE 120 1 XX 2#12 & 1#12 GND 3/4" RECEPTACLE35E LAGUNA WET GLAZE SPRAY BOOTH NA NO ELEC35N PROJECTION SCREEN 120 1 3A 2#12 & 1#12 GND 3/4" RECEPTACLE36E BAILEY HEPA AIR FILTER 120 1 3/4 HP 3/4" RECEPTACLE37E SOLDNER CLAY MIXER 208 3 9.1A 3#12 & 1#12 GND 3/4" RECEPTACLE38E UPDRAFT EXHAUST 120 1 12A 2#12 & 1#12 GND 3/4" RECEPTACLE39E PETTER PUGGER PUGMILL 208 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE40E PETER PUGGER PUGMILL 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE41E BAILEY HEPA AIR FILTER 120 1 3/4 HP 2#12 & 1#12 GND 3/4" SWITCH42E SMALL SOLDNER CLAY MIXER 208 3 6A 3#10 & 1#10 GND 3/4" RECEPTACLE43E BLUEBIRD CLAY MIXER 208 3 4.5A 3#12 & 1#12 GND 3/4" RECEPTACLE45E SKUTT ELECTRIC KILN 208 3 76A 3#1 & 1#6 GND 1-1/2" NFSS46E SKUTT 1227PK ELECTRIC KILN 208 1 69A 2#4 & 1#8 GND 1" NFSS47E SKUTT ELECTRIC KILN 208 3 48A 3#6 & 1#10 GND 1" RECEPTACLE48E SKUTT ELECTRIC KILN 208 3 26.7A 3#10 & 1#10 GND 3/4" RECEPTACLE49E SKUTT ELECTRIC KILN 208 3 26.7A 3#10 & 1#10 GND 3/4" RECEPTACLE50E SKUTT ELECTRIC KILN 208 3 48A 3#6 & 1#10 GND 1" RECEPTACLE50N BAILEY HEPA FILTER 120 1 3/4 HP 2#12 & 1#12 GND 3/4" SWITCH51E SKUTT DOLL KILN 120 1 50A 2#4 & 1#8 GND 1" RECEPTACLE52E SKUTT DOLL KILN 120 1 50A 2#4 & 1#8 GND 1" RECEPTACLE52N 20 GALLON PARTS WASHER 120 1 F 2#12 & 1#12 GND 3/4" RECEPTACLE53E SKUTT DOLL KILN 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE54E LAGUNA DOLL KILN 120 1 50A 2#6 & 1#8 GND 1" RECEPTACLE54N PIANO BOX STORAGE NA NO ELEC55E ENVIRO-VENT EXHAUST 120 1 F 2#12 & 1#12 GND 3/4" RECEPTACLE56E PROGRAMMABLE GAS KILN 208 1 5.9A 3#10 & 1#10 GND 3/4" RECEPTACLE56N SPRAY BOOTH NA NO ELEC64E OLSEN UPDRAFT GAS KILN NA65E OLSEN UPDRAFT GAS KILN NA66E OLSEN UPDRAFT GAS KILN NA66N OLSEN UPDRAFT GAS KILN NA67E LAGUNA RAKU KILN NA68E SPENCER CENTRAL VACUUM SYSTEM 208 3 21.1A 3#10 & 1#10 GND 3/4" RECEPTACLE70N SCREEN WASHOUT SINK W/ VERTICAL

LIGHT BOX120 1 2A 2#12 & 1#12 GND 3/4" RECEPTACLE

75E WILTON DRILL PRESS 120 1 8A 2#12 & 1#12 GND 3/4" RECEPTACLE76E FOREDOM-RIO GRANDE FLEX DRILL PRESS 120 1 1.7A 2#12 & 1#12 GND 3/4" RECEPTACLE77E HAMILTON SLOW COOKER 120 1 2A 2#12 & 1#12 GND 3/4" RECEPTACLE78E FORDOM-RIO GRANDE FLEX SHAFT 120 1 1.2A 2#12 & 1#12 GND 3/4" RECEPTACLE79E CRAFTSMAN BENCH GRINDER 120 1 2.1A 2#12 & 1#12 GND 3/4" RECEPTACLE80E PROGRAMMABLE GAS KILN 120 1 2A 2#12 & 1#12 GND 3/4" RECEPTACLE81E REF 120 1 9A 2#12 & 1#12 GND 3/4" RECEPTACLE85E VULCANIZING PRESS 120 1 10A 2#12 & 1#12 GND 3/4" RECEPTACLE86E HAMILTON BEACH SLOW COOKER (PICKLE

POTS)120 1 XX 2#12 & 1#12 GND 3/4" RECEPTACLE

87E WAX INJECTOR 120 1 9A 2#12 & 1#12 GND 3/4" RECEPTACLE89E GESSWEIN ULTRASONIC CLEANER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE90E ELECTRIC MELT CRUCIBLE 120 1 11.3A 2#12 & 1#12 GND 3/4" RECEPTACLE91E ARBE POLISHER 120 1 9A 2#12 & 1#12 GND 3/4" RECEPTACLE92E HEGNER SCROLL SAW 120 1 10A 2#12 & 1#12 GND 3/4" RECEPTACLE93E BELT SANDER 120 1 5.4A 2#12 & 1#12 GND 3/4" RECEPTACLE94E DISC SANDER 120 1 14A 2#12 & 1#12 GND 3/4" RECEPTACLE95E LAMPERT-PUK 4 MICRO WELDER 120 1 6A 2#12 & 1#12 GND 3/4" RECEPTACLE96E GRIZZLY MINI LATHE 120 1 9A 2#12 & 1#12 GND 3/4" RECEPTACLE97E AMACO ENAMEL KLINN 208 1 10A 2#12 & 1#12 GND 3/4" RECEPTACLE98E PARAGON ENAMEL KILNS ON SS CART 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE99E LITTLE GIANT PUMP AND SPRAY ETCHING

TANK120 1 2.1A 2#12 & 1#12 GND 3/4" RECEPTACLE

101E WILTON BAND SAW 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE102E DAYTON BENCH GRINDER 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE103E PARAGON INVESTMENT AND DEWAX KILN 208 1 22A 2#10 & 1#10 GND 3/4" RECEPTACLE104E VIC 12 CASTING MACHINE 120 1 10A 2#12 & 1#12 GND 3/4" RECEPTACLE106E BEAD BLAST CABINET 120 1 XX 2#12 & 1#12 GND 3/4" RECEPTACLE107E DONALDSON DUST COLLECTOR 208 1 10A 2#12 & 1#12 GND 3/4" RECEPTACLE109E POWDER COATING OVEN 120 1 XX 2#12 & 1#12 GND 3/4" RECEPTACLE200E RABBIT LASER CUTTER 208 1 12A 3#10 & 1#10 GND 3/4" RECEPTACLE202E DELL OPTIPLEX COMPUTER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE203E EPSON FLATBED SCANNER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE204E CUBE 3D PRINTER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE205E SEWING MACHINE 120 1 5A 2#12 & 1#12 GND 3/4" RECEPTACLE210E GE REFRIGERATOR 120 1 9A 2#12 & 1#12 GND 3/4" RECEPTACLE225E KAISER COPY STAND 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE226E PREMIER ROTO DRUM DRYER 120 1 2.7A 2#12 & 1#12 GND 3/4" RECEPTACLE227E LIGHT TABLE 120 1 1A 2#12 & 1#12 GND 3/4" RECEPTACLE228E BRETFORD LIGHT TABLE 120 1 1A 2#12 & 1#12 GND 3/4" RECEPTACLE229E DRY MOUNTING PRESS 120 1 11.7A 2#12 & 1#12 GND 3/4" RECEPTACLE230E ABSOCOLD CUBE REFRIGERATOR 120 1 1.1A 2#12 & 1#12 GND 3/4" RECEPTACLE231E AMERGRAPH EXPOSURE TABLE 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE232E CHEM SINK NA NO ELEC233E GE REFRIGERATOR 120 1 5A 2#12 & 1#12 GND 3/4" RECEPTACLE235E BESELER ENLARGER 120 1 5A 2#12 & 1#12 GND 3/4" RECEPTACLE236E PVC CHEMICAL PROCESS SINK NA NO ELEC243E LIGHT TABLE 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE245E EXPOSURE TABLE W/ VACUUM PRESS 120 1 XX 2#12 & 1#12 GND 3/4" RECEPTACLE246E VALAD HOT PLATE 120 1 13.8A 2#12 & 1#12 GND 3/4" RECEPTACLE247E LARGE FORMAT PRINTER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE250E PVC PROCESS SINK NA NO ELEC253E IMAC COMPUTERS 120 1 2A 2#12 & 1#12 GND 3/4" RECEPTACLE254E LARGE FORMAT EPSON PRINTER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE255E LARGE FORMAT EPSON PRINTER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE256E LARGE FORMAT EPSON PRINTER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE257E FLATBED SCANNER 120 1 0.5A 2#12 & 1#12 GND 3/4" RECEPTACLE263E IMAC COMPUTERS 120 1 2A 2#12 & 1#12 GND 3/4" RECEPTACLE

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.05 09:20:28-07'00'

Page 18: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

TECHNOLOGY SYMBOL LEGEND

T4T3

A

DRAWING NUMBER WHERE TAKEN

DRAWING NUMBER WHERE DETAILED

SECTION/ELEVATION LETTER OR DETAIL NUMBER

A

T4

6

T4 DRAWING NUMBER WHERE DETAILED

SECTION/ELEVATION LETTER OR DETAIL NUMBER

NORTH ARROW OR MATCH ARCHITECT'S

SCALE BAR OR MATCH ARCHITECT'S

GENERAL DRAWING SYMBOLS

DEFINITIONABBREV.

ABBREVIATIONS

NORTH

T3 T4

6

0 10' 20' 40' 80'

1" = 40'-0"

IC

S

W

B

SC

WAP

FLUSH

+84"UON

CEILING

WALL

FLOOR

FLOOR BOX WITH POWER AND VOICE\DATA. "#" DENOTES NUMBER OF DATA PORTS.

VOICE\DATA OUTLET ABOVE COUNTER TOP

FLOOR BOX WITH A/V. REFER TO J-BOX SCHEDULE ON 600 SERIES SHEETS.

CEILING SPEAKER: LOCAL SOUND SYSTEM

INTERCOM WALL SPEAKER

INTERCOM CALL SWITCH

CABLE TRAY FOR COMMUNICATIONS

VARIESSEE

PLANS

SPECIAL SYSTEMS

+44"UONWALL

TELEPHONE OUTLET WALL MOUNTED

COMMUNICATION HORN

COMMUNICATION BELL

COMBINATION CLOCK/SPEAKER. MOUNTEDABOVE AND CENTER TO WRITING/TACK BOARD

SEEPLANSWALL

WIRELESS ACCESS POINT

J-HOOK ROUTING PATH

S

J

Jxx

S

WALL +96"UON

ABOVE CEILING

xS IC CEILING SPEAKER: INTERCOM SYSTEM

J Jx A/V JUNCTION BOX. REFER TO J-BOX SCHEDULE ON 600 SERIES SHEETS.

SEEPLANSWALL

JJx

J JJx Jx A/V J- BOXES STACKED VERTICALLY. REFER TO

J-BOX SCHEDULE ON 600 SERIES SHEETS.

SEEPLANS

+18"UONWALL

VOICE\DATA OUTLET (WITH QTY. (3) PORTS UON)

AC

DURESS ALARM PUSHBUTTON

LOCK DOWN PUSHBUTTON

DA

LDSEE

PLANSWALL

DSVD DIGITAL SIGNAGE VIDEO DISPLAY

CEILING VOICE/DATA"#" DENOTES NUMBER OF DATA PORTS.

VP VIDEO PROJECTOR

REFER TO PLANS

SEEPLANSWALL

ICM INTERCOM MASTER STATION

+44"UON

WALL

J JxCEILING MOUNTED A/V JUNCTION BOX. REFER TO J-BOX SCHEDULE ON 600 SERIES SHEETS.

CR

KP

G

DS

CARD READER

SECURITY CAMERA (BOX, FIXED)

WALL +44"UONKEY PAD

GLASS BREAK DETECTORSEE

PLANS

DOOR SWITCH

DOORSEE

PLANS

WINDOW

SECURITY CAMERA (DOME, FIXED OR PTZ)

SECURITY

SEE PLANS

VARIESSECURITY CAMERA 180°

SECURITY CAMERA 360°

M CEILING MOTION DETECTOR SEEPLANSCEILING

ES ELECTRIC STRIKE

ML MAGNETIC LOCK

MOUNTINGHT.LOC.SYMBOL DESCRIPTION

SYMBOL DESCRIPTION MOUNTINGHT.LOC.

R

EX

DEMOLITION

DASHED SYMBOL INDICATES EXISTING DEVICE OR EQUIPMENT TO BE REMOVED

SOLID SYMBOL, LIGHTER IN COLOR INDICATES EXISTING DEVICE OR EQUIPMENT TO REMAIN

EXISTING CONDUIT TO BE REUSED

REMOVE EXISTING RACEWAY IN ALL ACCESSIBLE AREAS. CAPPED AND ABANDONED IF IN UNACCESSIBLE AREA

REFER TO DEMOLITION PLANS FOR ADDITIONAL

INFORMATION

SYMBOL DESCRIPTION NOTES

GROUND BAR

SYMBOL

EQUIPMENTDESCRIPTION

ELECTRICAL PANELBOARD. DASHED LINES INDICATE CLEARANCES. (SEE ELECTRICAL DRAWINGS.)L1A

T1A

UNINTERRUPTABLE POWER SUPPLY. DASHED LINES INDICATE CLEARANCES.

DRY TYPE TRANSFORMER (15kVA OR ABOVE), WITH EQUIPMENT TAG (SEE ELECTRICAL DRAWINGS.)

UPS-A

G

DRY TYPE TRANSFORMER (LESS THAN 15kVA), WITH NO EQUIPMENT TAG.(SEE ELECTRICAL DRAWINGS.)T

CONCEALED RACEWAY BETWEEN DEVICES AND OR EQUIPMENT IN WALLS OR IN CEILING SPACE

UNDERGROUND RACEWAY BETWEEN DEVICES AND OR EQUIPMENT

EXPOSED RACEWAY BETWEEN DEVICES AND OR EQUIPMENT ON WALLS OR CEILINGS

CONDUIT TURNSDOWN UP

B BUSWAYGROUNDING CONDUCTORG

CABLE TRAY - POWER AND TELECOMMUNICATIONS

T TELECOMMUNICATIONS RACEWAYD DATA RACEWAY

FA FIRE ALARM RACEWAY

CONDUIT STUBBED AND CAPPED

VOICE/DATA COMBINATION RACEWAYV/D

RACEWAY & CONDUCTORSDESCRIPTIONSYMBOL

(NOT ALL SYMBOLS APPLY TO THIS PROJECT)

+44"

VAV-9

SYMBOL DEFINITION

REFERENCE TAGS

KEYED NOTE REFERENCE

MECHANICAL EQUIPMENT REFERENCE

DENOTES MOUNTING HEIGHT AFF

KITCHEN EQUIPMENT REFERENCE

MEDICAL EQUIPMENT REFERENCE

VR POLYCARBONITE VANDAL RESISTANT COVER

LD LOCK DOWN

DISTRIBUTION POLE FOR OVERHEAD ELECTRICAL OR COMMUNICATIONS AS INDICATED ON PLAN.

OVERHEAD UTILITY AND OR SYSTEM DISTRIBUTION.XX

3PH = THREE PHASE (SEE ELECTRICAL DRAWINGS.)

XX

UT UTILITY OR FACILITY TRANSFORMER (SEE ELECTRICAL DRAWINGS.)

MHMANHOLE - POWER OR COMMUNICATIONAS INDICATED ON PLANS

HH HAND HOLE - POWER OR COMMUNICATIONAS INDICATED ON PLANS

1PH = SINGLE PHASE (SEE ELECTRICAL DRAWINGS.)

S = ELECTRICAL SECONDARY (SEE ELECTRICAL DRAWINGS.)P = ELECTRICAL PRIMARY (SEE ELECTRICAL DRAWINGS.)

T = TELECOMMUNICATIONTV = TELEVISIONE = EMERGENCY POWERATSC=AUTOMATIC TRANSFER SWITCH CONTROL(SEE ELEC. DRAWINGS.)

TP TELECOMMUNICATION PEDESTAL

TVP TELEVISION PEDESTAL

UTILITIESDESCRIPTIONSYMBOL

UNDERGROUND UTILITY AND OR SYSTEM DISTRIBUTION.

X

X

N = NEWEX = EXISTING MULTI-OULET ASSEMBLY (SURFACE MOUNTED

RACEWAY)

COMBINATION POWER/COMMUNICATION POLE.CONFIGURATION AS NOTED ON PLANS

O/H = OVER HEADU/G = UNDERGROUND

MAIN SWITCHBOARD. DASHED LINES INDICATE CLEARANCES.(SEE ELECTRICAL DRAWINGS.)MSB

DISTRIBUTION BOARD. DASHED LINES INDICATE CLEARANCES.(SEE ELECTRICAL DRAWINGS.)

DB

MCC

MOTOR CONTROL CENTER. DASHED LINES INDICATE CLEARANCES.(SEE ELECTRICAL DRAWINGS.)

WALL MOUNTED CODE SIZE J-BOXJ

J CODE SIZE JUNCTION BOX

M WALL MOUNTED MOTION DETECTOR WALL+84"UON

S INTERCOM SPEAKER HORNIC

IC

FLAT PANEL OR PROJECTION SCREEN

TV TELEVISION OUTLET

DC DOOR CONTACT

KS KEY SWITCH

F FIBER RACEWAY

AMPS, AMPEREAMPLIFIERABOVE COUNTERALTERNATING CURRENTAMERICANS WITH DISABILITIES ACTABOVE FINISHED FLOORABOVE FINISHED GRADEAVAILABLE INTERRUPTING CURRENTALUMINUMAMERICAN NATIONAL STANDARDS INSTITUTEAUTOMATIC TRANSFER SWITCH CONTROLAUTOMATIC TRANSFER SWITCHAUDIO-VISUAL OR AUDIO-VIDEOAMERICAN WIRE GAUGEBELOW FINISHED GRADECONDUITCIRCUIT BREAKERCLOSED CIRCUIT TELEVISIONCONTRACTOR FURNISHED CONTRACTOR

INSTALLEDCIRCUITCLOCKCURRENT LIMITING FUSECONDUIT ONLYCOPPERDIMMINGDIRECT CURRENTDAY-LIGHTINGDIAMETERDIGITAL SIGNAGE VIDEO DISPLAYEMERGENCYEMERGENCY, CRITICALENGINE GENERATOREQUIPMENT & GROUNDING CONDUCTOREMERGENCY, LIFE SAFETYELECTRICAL METALLIC TUBINGELECTRIC WATER COOLEREXISTINGFUTUREFIRE ALARMFIRE ALARM ANNUNCIATORFIRE ALARM CONTROL PANELFIRE ALARM POWER SUPPLYFIRE ALARM MASS NOTIFICATION CONTROL

PANELFIRE ALARM MASS NOTIFICATION TERMINAL

PANELFEEDERFIBER DISTRIBUTION UNITGENERATORGROUND FAULT INTERRUPTERGROUND FAULT CIRCUIT INTERRUPTERGROUND FAULT PROTECTIONGROUNDHANDHOLEHAND-OFF-AUTOMATICHORSEPOWERINSTITUTE OF ELECTRICAL AND ELECTRONICS

ENGINEERSINTERCOMINTERCOM MASTERISOLATED GROUNDTHOUSAND CIRCULAR MILSKNOCK-OUTKILOVOLTKILOVOLT AMPSKILOVOLT AMPS REACTIVEKILOWATTKILOWATT HOURLIGHT INTERFACE UNITLONG TIME, SHORT TIME, INSTANTANEOUS,

AND GROUNDMAXIMUMMOTOR CONTROL CENTERMANHOLEMICROPHONEMINIMUMMIXED MEDIAMANUAL TRANSFER SWITCHMEGAVOLT AMPSNEWNOT APPLICABLENORMALLY CLOSEDNATIONAL ELECTRICAL CODENATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATIONNEUTRALNATIONAL FIRE PROTECTION ASSOCIATIONNOT IN CONTRACTNORMALNEW MEXICONORMALLY OPENOWNER FURNISHED CONTRACTOR INSTALLEDOWNER FURNISHED OWNER INSTALLEDOVERHEADPOLEPUBLIC ADDRESSPHOTOCELLPHASEPOWER MONITORING AND CONTROL SYSTEMPOWER OVER ETHERNETRIGID STEEL CONDUITSECURITYSURGE PROTECTIVE DEVICESWITCHTEMPORARYTELECOMMUNICATIONS MAIN GROUNDING

BUS BARTELEPHONE TERMINAL BOARDTELEVISIONTRANSIENT VOLTAGE SURGE SUPPRESSERTYPICALUNDER COUNTERUNDERGROUNDUNDERGROUND ELECTRICUNDERWRITERS' LABORATORIESUNLESS OTHERWISE NOTEDUNINTERRUPTIBLE POWER SUPPLYVOLTS, VOLTAGEVARIABLE FREQUENCY DRIVEVANDAL RESISTANTWIREWEATHERPROOF AND GFCIWEATHERPROOFTRANSFERTRANSFORMER

AAMPACA/CADAAFFAFGAICALANSIATSCATSAV, A/VAWGBFGCCBCCTVCFCI

CKTCLCLFCOCUDDCDLDIADSVDEECEGEGCELEMTEWCEXFUTFAFAAFACPFAPSFAMNCP

FAMNTC

FDRFDUGENGFIG,GFCIGFPGNDHHHOAHPIEEE

ICICMIGKCMILKOKVKVAKVARKWKWHLIULSIG

MAXMCCMHMICMINMMMTSMVANNANCNECNEMA

NEUTNFPANICNLNMNOOFCIOFOIOH (O/H)PPAPCPHPMCSPOERSCSECSPDSWTEMPTMGB

TTBTVTVSSTYPUCU/GUGEULUONUPSVVFDVRWWGWPXFERXFMR (TRANSF)

#

#

#

ADA AUTOMATIC DOOR ACTUATOR PUSH PLATE FOR HANDICAP ACCESSIBILITY

EN

JAM N E. BOSSE

19418

GI N

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

NO SCALE

T-001

NEW ARTBUILDINGNMSU LAS CRUCES, NM

TECHNOLOGY LEGEND

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB/SPO

CSK/JEB/SDR

ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND

INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS

AND TESTING OF ALL NETWORK CABLING.

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.04 17:23:23-07'00'

Page 19: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

DN

EV

ET

EV

DN

E

E

8'

CMU

8'

CMU

KENT HALLNEW ART BUILDING FOOTPRINT

BUSINESS COMPLEX BUILDING

HSS BUILDING

EN & SP BUILDINGS

NEW ART BUILDING FOOTPRINT

EXISTING TUNNEL(UNDERGROUND CHILLED WATER & STEAM, COMMUNICATIONS, FIRE PROTECTION)

NEW FIBER OPTIC & COPPER SERVICE ENTRANCE FROM GUTHRIE HALL BASEMENT. COORDINATE WITH NMSU ICT.

MDF T125A

EXISTING WILLIAMS HALL & ANNEX BUILDINGS

BID LOT 1

FIBER/COPPER ROUTE TEMPORARY COMMUNICATIONS PATHWAY FROM BUISNESS COMPLEX - UTILIZING EXISTING PATHWAY INTO BUILDING FROM TUNNEL. COORDINATE WITH NMSU ICT.

EXISTING POWER & FIBER TIE-IN

1

2

3

EN

JAM N E. BOSSE

19418

GI N

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

1" = 20'-0"

TS-102

NEW ARTBUILDINGNMSU LAS CRUCES, NM

TECHNOLOGY SITE PLAN

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB/SPO

CSK/JEB/SDR

GENERAL SHEET NOTES

1" = 20'-0"TS-102

1 TECHNOLOGY SITE PLAN

NORTH

0' 10' 20' 40' 80'

ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND

INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS

AND TESTING OF ALL NETWORK CABLING.

A. THE CONDUIT RUNS, AS SHOWN ON PLANS, INDICATE APPROXIMATE ROUTING. EXACT LOCATION OF CONDUIT RUNS SHALL BE AS FIELD CONDITIONS DICTATE.

B. ALL LOW VOLTAGE CONDUCTORS SHALL BE RUN IN SEPARATE RACEWAYS FROM POWER CONDUCTORS (120VAC OR HIGHER PHASE TO NEUTRAL). NO EXCEPTIONS.

C. ALL UNDERGROUND CONDUITS LOCATED UNDER ROADWAYS AND PARKING LOTS SHALL BE CONCRETE ENCASED PATHWAYS TRAFFIC RATED TIER 22.

D. ALL HANDHOLES AND MANHOLES LOCATED IN ROADWAYS AND PARKING LOTS SHALL BE TRAFFIC RATED H20.

E. ALL UNDERGROUND CABLING TO BE OSP RATED.F. ALL CONDUIT TURNS SHALL BE "SWEEP" TYPE, NO 90 DEGREE BEND FITTINGS ARE

PERMITTED.G. DURING VOICE/DATA CABLE INSTALLATION, PROPER COORDINATION AND CARE SHALL

BE TAKEN TO ENSURE CABLING DOES NOT GET PAINTED, TEXTURED OR OTHERWISE CONTAMINATED. PER MANUFACTURERS INSTALLATION GUIDELINES.

KEYNOTES

1. FIBER/COPPER ROUTE COMMUNICATIONS PATHWAY FROM TUNNEL. COORDINATE EXACT PATH WITH NMSU ICT AND ALL OTHER TRADES. PROVIDE (3) 4" UNDERGROUND CONDUITS TO MDF. PROVIDE HANDHOLES AT LOCATIONS IN CONDUIT PATHWAYS WITH NO MORE THAN (2) 90 DEGREE BENDS TOTAL. FIBER AND COPPER TO FEED FROM GUTHRIE HALL BASEMENT. REFER TO SHEET T-401 FOR ONE-LINE DIAGRAM. REFER TO DETAILS D3 AND E5 ON SHEET T-502 FOR DUCTBANK AND HANDHOLE REQUIREMENTS.

2. KEEP EXISTING WILLIAMS HALL AND ANNEX OPERATIONAL. FIBER/COPPER ROUTE COMMUNICATIONS PATHWAY FROM TUNNEL. COORDINATE EXACT PATH WITH NMSU ICT AND ALL OTHER TRADES. PROVIDE 4" UNDERGROUND CONDUITS TO EXISTING TIE-IN. PROVIDE HANDHOLES AT LOCATIONS IN CONDUIT PATHWAYS WITH NO MORE THAN (2) 90 DEGREE BENDS TOTAL. FIBER AND COPPER TO FEED FROM BUSINESS COMPLEX. COORDINATE FIBER AND COPPER CONNECTIONS TO WILLIAMS HALL AND ANNEX WITH NMSU ICT.

3. INTERCEPT EXISTING FIBER PATHWAY TO WILLIAMS HALL AND ANNEX.

REFER TO PHASING SEQUENCE PROGRAM IN SPEC SECTION 01 1000 FOR DETAIL INFORMATION FOR SITE PROGRAM

PHASING SEQUENCE:• PHASE I. UTILITIES TO KEEP EXISTING WILLIAMS HALL

AND ANNEX OPERATIONAL.

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.04 17:23:35-07'00'

Page 20: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

2

2

2

2

2

2

2

2

JJ

JJ

DSVD

CR

DS

DS

WAP

WAP

WAP WAP

VP

2

2 2

2

2

2

2

S

2

S

AD

A

ADA

AD

A

KP

CR

DS DS

KP

2

2

CR

CR

CR

CR

M

M

M

M

M

M

M

M

M

M

M

M

M

RFB4E-OG RFB4E-OG RFB4E-OG

RFB4E-OGRFB4E-OGRFB4E-OG

RFB4E-OG RFB4E-OG RFB4E-OG

CR

VP

2

J

J

WAP

2

2

S

2

S

2

2

2

2

2

2

M

M

CR

AD

A

2

2

2

2

2

22

2

2

2

2

2

KP

222

WAP

2

2

DS DSCR

2

2

M

M

CR

CR

AD

A

/1

T-1

01B

/1

T-1

01B

ART GALLERY105

UAGCOLLECTION

STUDY106

STAFF TOILETFEMALE

R108

GALLERYWORK RM

107

A.G. OFFICE109

MODERN &CONTEMPORARY

ART GALLERY105A

HALLH101B

FRAME PREPROOM

113

A.G. OFFICE111

STAFF TLTMALER112

CONSERVATIONLAB115

GALLERYSTORAGE

108

HALLH101A

TYP.

1

2

TYP.

3

TYP.

4

TYP.

9

TYP.

8

TYP.

16

TYP.

15

TYP.

5

10

TYP.

16

CONSERVATIONLAB OFFICE

115A

RETABLOSGALLERY

110

ENTRYVESTIBULE

100D

ENTRYVESTIBULE

100A

C

2

B

1

D

3

5

4

A

J1J3

J1J3

B.6 D.8

1.5

2.3

2.6

2.7

5.1

B.8

6

D.3

1.2

1.4

1.6

STORAGE115B

2.4

2.2

2.9

3.5

4.4

5.3

A.8 D.45D.4

2.65

4.5

J1

J3

TYP.

19

2

2

12

TYP.

11

TYP.

11

18

21

21

21

22

23

22

22

TYP.

22

23

23

23

23

23

23

23

23

AC ACENTRY

VESTIBULE100D

RECEPTION &ADMIN.

ASSISTANT118A

WAITING118

DEPT. HEADOFFICE

118X

A.H. OFFICE118C

A.H. OFFICE118D

A.H. OFFICE118E

A.H. OFFICE118F

WORKRM/STORAGE

118H

ENTRYVESTIBULE

100D

GALLERYSTORAGE

108

CONSERVATIONLAB OFFICE

115A

CB D

5

A

6.1

6.6

B.6

5.1

B.8

6

4.4

5.3

6.4

A.8

4.5

TYP.

12

23

22

23

22

TYP.

22

23

EN

JAM N E. BOSSE

19418

GI N

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

1/8" = 1'-0"

T-101A

NEW ARTBUILDINGNMSU LAS CRUCES, NM

BASE BID & BID LOT 1 1ST LEVEL TECHSYSTEMS FLOOR PLAN - GALLERY WING

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB/SPO

CSK/JEB/SDR

1/8" = 1'-0"T-101A

1 BASE BID 1ST LEVEL TECHNOLOGY SYSTEMS FLOOR PLAN - GALLERY WING

GENERAL SHEET NOTES

KEYNOTES

A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES.

C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING.

D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.E. ALL COMMUNICATIONS CABLING TO MEET OR EXCEED CAT6 STANDARDS.F. TELECOMMUNICATIONS OUTLETS TO BE MOUNTED AT +18" A.F.F. (BOTTOM OF

BOX) UNLESS OTHERWISE NOTED. FOR EXAMPLE, DEVICES SPECIFIED AT +18" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR POWER RECEPTACLES AND TELECOMMUNICATIONS OUTLETS. DEVICES SPECIFIED AT + 48" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR LIGHT SWITCHES ETC.

G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL, THINWALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR PATHWAYS INDICATED ON THIS SHEET. ALL CONDUITS ARE TO BE, AT A MINIMUM, 1” TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL.

H. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED. LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE SYSTEMS.

I. NUMBER ADJACENT TO TELECOMMUNICATIONS OUTLET SYMBOL REPRESENTS NUMBER OF CAT 6 CABLES TO BE INSTALLED AND TERMINATED AT THAT LOCATION. A "B" ADJACENT TO AN OUTLET LOCATION REPRESENTS A ROUGH-IN ONLY LOCATION, PROVIDE BOX, CONDUIT, AND BLANK FACEPLATE.

J. ALL CONDUIT TURNS FOR A/V AND IT CONDUITS SHALL BE "SWEEP" TYPE, NO BEND FITTINGS ARE PERMITTED.

K. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX.

L. CONTRACTOR TO VERIFY ALL CABLE COUNTS AND NUMBER OF PATCH PANELS REQUIRED.

M. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES SHEETS FOR POWER OUTLET LOCATIONS.

N. CONTRACTOR IS PROVIDE AND TERMINATE CABLING FOR THE BLACKBOARD SYSTEM AND T0 “FUTURE” CARD READERS.

O. DURING VOICE/DATA CABLE INSTALLATION, PROPER COORDINATION AND CARE SHALL BE TAKEN TO ENSURE CABLING DOES NOT GET PAINTED, TEXTURED OR OTHERWISE CONTAMINATED. PER MANUFACTURERS INSTALLATION GUIDELINES.

P. ANY ON-GRADE FLOOR BOX APPLICATIONS, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET-RATED" CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.

ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND

INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS

AND TESTING OF ALL NETWORK CABLING.

1/8" = 1'-0"T-101A

2

BID LOT 1 ADMINISTRATION1ST LEVEL TECHNOLOGY SYSTEMS FLOOR PLAN

NORTH

0' 8' 16' 32' 64'

NORTH

KEY PLAN

GALLERY

WING

STUDIO

WING EXTERIOR

YARD

MA

TC

H L

INE

RECEIVING

BID LOT 1

0' 8' 16' 32' 64'

1. STANDARD TELECOMMUNICATIONS OUTLET. CONSISTS OF CATEGORY 6 CABLES. QUANTITY AS SHOWN. REFER TO DETAILS D1 AND D2 ON SHEET T-502.

2. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. CO-LOCATE WITH CEILING POWER OUTLET. QUANTITY AS SHOWN.

3. WIRELESS ACCESS POINT LOCATION. PROVIDE A CLEAR LABEL FOR LOCATION OF WIRELESS ACCESS POINT ON ACCESSIBLE CEILING TILE OR WALL NEAR ACCESSIBLE CEILING TILE. WIRELESS ACCESS POINT HARDWARE FURNISHED AND INSTALLED BY OWNER.

4. 12" X 4" WIRE BASKET STYLE CABLE TRAY FOR HORIZONTAL TELECOMMUNICATIONS CABLING. MOUNT CABLE TRAY 10'-6" ABOVE FINISHED FLOOR, BOTTOM OF TRAY. COORDINATE WITH ALL OTHER TRADES AND ARCHITECT PRIOR TO COMMENCEMENT OF WORK. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

5. CEILING SPEAKERS FOR LOCAL SOUND SYSTEM. COORDINATE WITH OWNER FOR EXACT LOCATIONS AND QUANTITIES. REFER TO DETAILS A6 AND B6 ON SHEET T503

6. COMBINATION POWER AND DATA FLOOR BOX. DO NOT DAISY CHAIN FLOOR BOXES, PROVIDE A SEPARATE CONDUIT HOME RUN FOR EACH BOX. REFER TO DETAILS A2, B1, AND B2 ON SHEET T-502 FOR ADDITIONAL FLOOR BOX INFORMATION. ANY ON-GRADE APPLICATION, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET" RATED CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES. COORDINATE FINAL MOUNTING LOCATIONS WITH EP SERIES SHEETS AND FURNITURE PRIOR TO COMMENCEMENT OF ANY WORK.

7. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. QUANTITY AS SHOWN.

8. CEILING MOUNTED PROJECTOR LOCATION. REFER TO DETAILS A2 AND B2 ON SHEET T503 FOR ROUGH-IN REQUIREMENTS. PROVIDE 120V POWER RECEPTACLE MOUNTED PER DETAILS A2 AND B2 ON SHEET T503. DISTANCE FROM DISPLAY SURFACE IS CRITICAL, COORDINATE EXACT LOCATION / THROW DISTANCE WITH ARCHITECT AND OWNER.

9. MOTORIZED PROJECTION SCREEN LOCATION FOR LOCAL A/V SYSTEM. FOR 120V SCREEN SWITCH REQUIREMENTS REFER TO ELECTRICAL SHEETS. COORDINATE WITH OWNER FOR SCREEN ROUGH-IN REQUIREMENTS.

10. WALL MOUNTED DIGITAL SIGNAGE VIDEO DISPLAY LOCATION. PROVIDE STRUCTURAL BACKING, BACK BOXES, AND POWER/ VOICE/DATA OUTLETS AS SHOWN ON DETAIL C4 AND C5 ON SHEET T-503.

11. PULL BOXES FOR A/V CABLING. REFER TO DIAGRAMS AND A/V J-BOX SCHEDULE ON SHEET T-601 FOR REQUIREMENTS.

12. BOX AND CONDUIT ROUGH-IN FOR ACCESS CONTROL. REFER TO DOOR HARDWARE DETAILS ON SHEET T-501 AND ARCHITECTURAL DOOR HARDWARE SCHEDULE FOR ADDITIONAL REQUIREMENTS.

13. 12" X 4" WIRE BASKET STYLE CABLE TRAY BLACK POWDER COATED FOR HORIZONTAL TELECOMMUNICATIONS CABLING. PROVIDE CABLE TRAY LINER TO PROTECT CABLES IN OPEN CEILING. MOUNT CABLE TRAY 10'-6" ABOVE FINISHED FLOOR, BOTTOM OF TRAY. COORDINATE WITH ALL OTHER TRADES AND ARCHITECT PRIOR TO COMMENCEMENT OF WORK. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

14. TELECOMMUNICATIONS OUTLETS IN OPEN CEILING AREAS TO HOMERUN CONDUITS TO NEAREST CABLE TRAY.

15. BOX AND CONDUIT ROUGH-IN FOR INTRUSION ALARM SYSTEM KEYPAD. 16. AUTOMATIC DOOR ACTUATOR LOCATION FOR PUSH PLATE HANDICAP ACCESS.

REFER TO ELECTRICAL FLOOR PLANS FOR ADDITIONAL REQUIREMENTS, PATHWAYS, AND POWER.

17. 2-WAY COMMUNICATION SYSTEM CALLING STATION. PROVIDE 1" EMT CONDUIT, HOME RUN TO BASE STATION. PROVIDE PULL BOXES AS NEEDED. CABLING TO LAND TO BASE STATION. LOCATE BASE STATION . REFER TO SPECIFICATION SECTION 28 3200 FOR ADDITIONAL REQUIREMENTS.

18. 2-WAY COMMUNICATION SYSTEM BASE STATION. PROVIDE 1" EMT CONDUIT, HOME RUN TO MDF ROOM #125A.PROVIDE PULL BOXES AS NEEDED. CABLING TO LAND ON 110 FIELD FOR PHONE TERMINATION. REFER TO SPECIFICATION SECTION 28 3200 FOR ADDITIONAL REQUIREMENTS.

19. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. QUANTITY AS SHOWN.

20. COMBINATION POWER AND DATA FLOOR BOX. DO NOT DAISY CHAIN FLOOR BOXES, PROVIDE A SEPARATE CONDUIT HOME RUN FOR EACH BOX. REFER TO DETAIL A1 ON SHEET T-502 FOR ADDITIONAL FLOOR BOX INFORMATION. ANY ON-GRADE APPLICATION, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET" RATED CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.COORDINATE FINAL MOUNTING LOCATIONS WITH EP SERIES SHEETS AND FURNITURE PRIOR TO COMMENCEMENT OF ANY WORK.

21. BOX AND CONDUIT ROUGH-IN FOR FUTURE CARD READER EQUIPMENT INSTALLATION. PROVIDE BLANK COVER PLATE. STUB CONDUIT TO NEAREST ACCESSIBLE CEILING SPACE. REFER TO DOOR HARDWARE DETAILS ON SHEET T-501 AND ARCHITECTURAL DOOR HARDWARE SCHEDULE ON SHEET A-600, AND SPECIFICATION 08 7100 DOOR HARDWARE FOR ADDITIONAL REQUIREMENTS.

22. 2" CONDUIT SLEEVE THROUGH WALL AND/OR SOFFIT FOR VOICE, DATA, AND INTERCOM CABLING. PROVIDE PLASTIC BUSHINGS ON BOTH ENDS TO PROTECT CABLES. QUANTITY AS SHOWN.

23. 4" CONDUIT SLEEVE THROUGH WALL AND/OR SOFFIT FOR VOICE, DATA, AND INTERCOM CABLING. PROVIDE PLASTIC BUSHINGS ON BOTH ENDS TO PROTECT CABLES. QUANTITY AS SHOWN.

NOT ALL NOTES USED

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.04 17:23:53-07'00'

Page 21: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

Table

CR

2

2

2

2

2

222

DS

DS DS

CR

CR

CR

EFB8S-OG

4

2

2

2 2

222

2

2

2

WAP

WAP

WAP WAP

WAP

WAP

WAP

VP

VP

DS

DS

CR

2

2

2

2

2

2

2

2

2

VP

VP

2

2

J

J

J J

J

2

J

J2

2

2

S2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

CR

DS

DS DS

2

2

EFB8S-OG

4

M

M

M

M

M

M

M

M

M

M

M

M

M

2

2

WAP

2

WAP

2 2 2

2 2 22

2

2

2

2 4

2

2

2

WAP

CR

CR

J

J

J

J

J

2

2

2 2

2

2 2

CR

J

AD

A

2

2

2

J

2

J

2

2

2

J

/1

T-1

01A

/1

T-1

01A

WOMENSR123A

MENSR123B

HALLH101D

MDFT125A

ELECM125B

UNIVERSALTLT

R123C

MECHANICALROOMM125C

FABRICATIONLAB129

JANITORJ131

JEWELRYSTORAGE

130C

JEWELRYFACULTYSTUDIO

130D

VEST.100E

METALS/JEWELRY130

ENAMEL130A

RAISING ROOM130B

WOOD SHOP126

SCULPTURE124

WET ROOM122E

SCULPTUREFACULTYSTUDIO

124A

MOLD RM123

CERAMICS122

CERAMICSFACULTYSTUDIO

122A GLAZE LAB122B

HALLH101E

GRADUATESTUDIO

120A

GRADUATESTUDIO

120B

GRADUATESTUDIO

120C

GRADUATESTUDIO

120D

GRADUATESTUDIO

120E

GRADUATESTUDIO

120F

GRADUATESTUDIO

120G

GRADUATESTUDIO

120H

CLAY MIXING122C

EXTERIORYARD

140

KILN ROOM122F

TYP.

1

TYP.

7

TYP.

4

TYP.

3

TYP.

9

TYP.

8

TYP.

5

T-4011

EXTERIORYARD

140

CASTING130F

LOCKERS130G

ENTRYVESTIBULE

100D

F G

8

2

ED

3

5

7

10

9

11

4

6.1

9.5

6.6

ELEVEL101

J3

J1

TYP.

12

J1

J1

J3

J1 J3

6

D.8 E.5 E.8 F.4 G.4

2.3

2.6

2.7

5.1

6

D.3

AC

AC AC

AC

AC

ADMINISTRATION118A

DEPT. HEADOFFICE

118B

WORK ROOM118C

2.4 2.4

E.6 F.7 H

2.2

10.9

2.9

3.5

4.4

5.3

6.4

6.9

7.8

8.8

E.4D.45 D.9D.4

2.65

4.5

2

2

2

2

12

TYP.

11

TYP.

11

12

J3

13

14

13

14

14

13

TYP.

4

4

18

12

21

21

21

21

21

23

23

23

23 22

22

23

23

WP

WP

WP

WP

WP

WP WP

WP

WP

GRADUATESTUDIO

120L

GRADUATESTUDIO

120K

GRADUATESTUDIO

120J

ED

3

D.8

2.7

D.3

2.9

3.5

D.45 D.9

23

23

21

23

EN

JAM N E. BOSSE

19418

GI N

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

1/8" = 1'-0"

T-101B

NEW ARTBUILDINGNMSU LAS CRUCES, NM

BASE BID & BID LOT 1 1ST LEVEL TECHSYSTEMS FLOOR PLAN - STUDIO WING

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB/SPO

CSK/JEB/SDR

1/8" = 1'-0"T-101B

1 BASE BID 1ST LEVEL TECHNOLOGY SYSTEMS FLOOR PLAN - STUDIO WING

A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES.

C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING.

D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.E. ALL COMMUNICATIONS CABLING TO MEET OR EXCEED CAT6 STANDARDS.F. TELECOMMUNICATIONS OUTLETS TO BE MOUNTED AT +18" A.F.F. (BOTTOM OF

BOX) UNLESS OTHERWISE NOTED. FOR EXAMPLE, DEVICES SPECIFIED AT +18" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR POWER RECEPTACLES AND TELECOMMUNICATIONS OUTLETS. DEVICES SPECIFIED AT + 48" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR LIGHT SWITCHES ETC.

G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL, THINWALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR PATHWAYS INDICATED ON THIS SHEET. ALL CONDUITS ARE TO BE, AT A MINIMUM, 1” TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL.

H. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED. LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE SYSTEMS.

I. NUMBER ADJACENT TO TELECOMMUNICATIONS OUTLET SYMBOL REPRESENTS NUMBER OF CAT 6 CABLES TO BE INSTALLED AND TERMINATED AT THAT LOCATION. A "B" ADJACENT TO AN OUTLET LOCATION REPRESENTS A ROUGH-IN ONLY LOCATION, PROVIDE BOX, CONDUIT, AND BLANK FACEPLATE.

J. ALL CONDUIT TURNS FOR A/V AND IT CONDUITS SHALL BE "SWEEP" TYPE, NO BEND FITTINGS ARE PERMITTED.

K. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX.

L. CONTRACTOR TO VERIFY ALL CABLE COUNTS AND NUMBER OF PATCH PANELS REQUIRED.

M. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES SHEETS FOR POWER OUTLET LOCATIONS.

N. CONTRACTOR IS PROVIDE AND TERMINATE CABLING FOR THE BLACKBOARD SYSTEM AND T0 “FUTURE” CARD READERS.

O. DURING VOICE/DATA CABLE INSTALLATION, PROPER COORDINATION AND CARE SHALL BE TAKEN TO ENSURE CABLING DOES NOT GET PAINTED, TEXTURED OR OTHERWISE CONTAMINATED. PER MANUFACTURERS INSTALLATION GUIDELINES.

P. ANY ON-GRADE FLOOR BOX APPLICATIONS, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET-RATED" CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.

1/8" = 1'-0"T-101B

2

BID LOT 1 GRAD STUDIOS 1ST LEVELTECHNOLOGY SYSTEMS FLOOR PLAN

ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND

INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS

AND TESTING OF ALL NETWORK CABLING.

NORTH

KEY PLAN

GALLERY

WING

STUDIO

WING EXTERIOR

YARD

MA

TC

H L

INE

RECEIVING

BID LOT 1

0' 8' 16' 32' 64'

NORTH

GENERAL SHEET NOTESKEYNOTES

1. STANDARD TELECOMMUNICATIONS OUTLET. CONSISTS OF CATEGORY 6 CABLES. QUANTITY AS SHOWN. REFER TO DETAILS D1 AND D2 ON SHEET T-502.

2. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. CO-LOCATE WITH CEILING POWER OUTLET. QUANTITY AS SHOWN.

3. WIRELESS ACCESS POINT LOCATION. PROVIDE A CLEAR LABEL FOR LOCATION OF WIRELESS ACCESS POINT ON ACCESSIBLE CEILING TILE OR WALL NEAR ACCESSIBLE CEILING TILE. WIRELESS ACCESS POINT HARDWARE FURNISHED AND INSTALLED BY OWNER.

4. 12" X 4" WIRE BASKET STYLE CABLE TRAY FOR HORIZONTAL TELECOMMUNICATIONS CABLING. MOUNT CABLE TRAY 10'-6" ABOVE FINISHED FLOOR, BOTTOM OF TRAY. COORDINATE WITH ALL OTHER TRADES AND ARCHITECT PRIOR TO COMMENCEMENT OF WORK. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

5. CEILING SPEAKERS FOR LOCAL SOUND SYSTEM. COORDINATE WITH OWNER FOR EXACT LOCATIONS AND QUANTITIES. REFER TO DETAILS A6 AND B6 ON SHEET T503

6. COMBINATION POWER AND DATA FLOOR BOX. DO NOT DAISY CHAIN FLOOR BOXES, PROVIDE A SEPARATE CONDUIT HOME RUN FOR EACH BOX. REFER TO DETAILS A2, B1, AND B2 ON SHEET T-502 FOR ADDITIONAL FLOOR BOX INFORMATION. ANY ON-GRADE APPLICATION, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET" RATED CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES. COORDINATE FINAL MOUNTING LOCATIONS WITH EP SERIES SHEETS AND FURNITURE PRIOR TO COMMENCEMENT OF ANY WORK.

7. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. QUANTITY AS SHOWN.

8. CEILING MOUNTED PROJECTOR LOCATION. REFER TO DETAILS A2 AND B2 ON SHEET T503 FOR ROUGH-IN REQUIREMENTS. PROVIDE 120V POWER RECEPTACLE MOUNTED PER DETAILS A2 AND B2 ON SHEET T503. DISTANCE FROM DISPLAY SURFACE IS CRITICAL, COORDINATE EXACT LOCATION / THROW DISTANCE WITH ARCHITECT AND OWNER.

9. MOTORIZED PROJECTION SCREEN LOCATION FOR LOCAL A/V SYSTEM. FOR 120V SCREEN SWITCH REQUIREMENTS REFER TO ELECTRICAL SHEETS. COORDINATE WITH OWNER FOR SCREEN ROUGH-IN REQUIREMENTS.

10. WALL MOUNTED DIGITAL SIGNAGE VIDEO DISPLAY LOCATION. PROVIDE STRUCTURAL BACKING, BACK BOXES, AND POWER/ VOICE/DATA OUTLETS AS SHOWN ON DETAIL C4 AND C5 ON SHEET T-503.

11. PULL BOXES FOR A/V CABLING. REFER TO DIAGRAMS AND A/V J-BOX SCHEDULE ON SHEET T-601 FOR REQUIREMENTS.

12. BOX AND CONDUIT ROUGH-IN FOR ACCESS CONTROL. REFER TO DOOR HARDWARE DETAILS ON SHEET T-501 AND ARCHITECTURAL DOOR HARDWARE SCHEDULE FOR ADDITIONAL REQUIREMENTS.

13. 12" X 4" WIRE BASKET STYLE CABLE TRAY BLACK POWDER COATED FOR HORIZONTAL TELECOMMUNICATIONS CABLING. PROVIDE CABLE TRAY LINER TO PROTECT CABLES IN OPEN CEILING. MOUNT CABLE TRAY 10'-6" ABOVE FINISHED FLOOR, BOTTOM OF TRAY. COORDINATE WITH ALL OTHER TRADES AND ARCHITECT PRIOR TO COMMENCEMENT OF WORK. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

14. TELECOMMUNICATIONS OUTLETS IN OPEN CEILING AREAS TO HOMERUN CONDUITS TO NEAREST CABLE TRAY.

15. BOX AND CONDUIT ROUGH-IN FOR INTRUSION ALARM SYSTEM KEYPAD. 16. AUTOMATIC DOOR ACTUATOR LOCATION FOR PUSH PLATE HANDICAP ACCESS.

REFER TO ELECTRICAL FLOOR PLANS FOR ADDITIONAL REQUIREMENTS, PATHWAYS, AND POWER.

17. 2-WAY COMMUNICATION SYSTEM CALLING STATION. PROVIDE 1" EMT CONDUIT, HOME RUN TO BASE STATION. PROVIDE PULL BOXES AS NEEDED. CABLING TO LAND TO BASE STATION. LOCATE BASE STATION . REFER TO SPECIFICATION SECTION 28 3200 FOR ADDITIONAL REQUIREMENTS.

18. 2-WAY COMMUNICATION SYSTEM BASE STATION. PROVIDE 1" EMT CONDUIT, HOME RUN TO MDF ROOM #125A.PROVIDE PULL BOXES AS NEEDED. CABLING TO LAND ON 110 FIELD FOR PHONE TERMINATION. REFER TO SPECIFICATION SECTION 28 3200 FOR ADDITIONAL REQUIREMENTS.

19. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. QUANTITY AS SHOWN.

20. COMBINATION POWER AND DATA FLOOR BOX. DO NOT DAISY CHAIN FLOOR BOXES, PROVIDE A SEPARATE CONDUIT HOME RUN FOR EACH BOX. REFER TO DETAIL A1 ON SHEET T-502 FOR ADDITIONAL FLOOR BOX INFORMATION. ANY ON-GRADE APPLICATION, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET" RATED CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.COORDINATE FINAL MOUNTING LOCATIONS WITH EP SERIES SHEETS AND FURNITURE PRIOR TO COMMENCEMENT OF ANY WORK.

21. BOX AND CONDUIT ROUGH-IN FOR FUTURE CARD READER EQUIPMENT INSTALLATION. PROVIDE BLANK COVER PLATE. STUB CONDUIT TO NEAREST ACCESSIBLE CEILING SPACE. REFER TO DOOR HARDWARE DETAILS ON SHEET T-501 AND ARCHITECTURAL DOOR HARDWARE SCHEDULE ON SHEET A-600, AND SPECIFICATION 08 7100 DOOR HARDWARE FOR ADDITIONAL REQUIREMENTS.

22. 2" CONDUIT SLEEVE THROUGH WALL AND/OR SOFFIT FOR VOICE, DATA, AND INTERCOM CABLING. PROVIDE PLASTIC BUSHINGS ON BOTH ENDS TO PROTECT CABLES. QUANTITY AS SHOWN.

23. 4" CONDUIT SLEEVE THROUGH WALL AND/OR SOFFIT FOR VOICE, DATA, AND INTERCOM CABLING. PROVIDE PLASTIC BUSHINGS ON BOTH ENDS TO PROTECT CABLES. QUANTITY AS SHOWN.

NOT ALL NOTES USED

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.04 17:24:20-07'00'

Page 22: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

UP

22

2

2

2

2

2

2

2

2

2

222

2

2

2

JJ

J J

2

2J

J

2J

J

J

8ATC

2

2

2

8ATC

8ATC

JJ

44

4 4

4

2

2 2

2

2 2

2 2

2

2 2

2 2

2

2

VP

VP

VP

VP

WAP

WAP

WAP

WAP

WAP

WAP

WAP WAP

DSCR

DS

CR

2

2

2

2

2

2

2

2

2

2

2 2

2

2

2

2

8ATC

8ATC

J

J

J

J

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

2

S

CR

DS

VP

2

J

VP

VP

CR

CR

M

M

M

M

M

CR

M

M

M

2 2 2 2

2 2 2 2

WAP

2

CR

J

J

J

2

2

2 2

2 2

2

2

J J

8ATC 8ATC

8ATC8ATC

2

8ATC

8ATC

ELEVATOR/STAIRLOBBY

200F

DIGITALOUTPUT

221

GRADUATESTUDIO

220A

GRADUATESTUDIO

220B

GRADUATESTUDIO

220C

GRADUATESTUDIO

220D

GRADUATESTUDIO

220E

GRADUATESTUDIO

220F

GRADUATESTUDIO

220G

GRADUATESTUDIO

220H

HALLH201E

FACULTYSTUDIO

(SAFETY)242

GRAD STUDIOHUDDLE

240GANG DARK

RM222B

PHOTO DOC. &STORAGE

210

PHOTOSTUDIO

222

FILMPROCESSING

RM222E

DESIGNSTUDIO

224WOMENS

R223AMENSR223B

STUDY/RESOURCE RM

229TR

T225AELEC. RM

M225B

COMPUTERLAB231

TECHNOLOGYLAB233

JEWELRYFACULTYSTUDIO

234

JANITORJ227

WASH OUT224A DARKROOM

224B

ETCHING RM224C

PAINTINGSTUDIO

230

STILL LIFESTORAGE

230A

DRAWINGSTUDIO

232

STUDENTCOLLABORATION

236

HALLH201G

DWG/PAINTINGFACULTYSTUDIO

238A

PHOTO.FACULTYSTUDIO

238B

DESIGNFACULTYSTUDIO

238C

CONFERENCERM235

DESIGNFACULTYSTUDIO

238D

TYP.

1

TYP.

3

TYP.

7

TYP.

4

TYP.

8

TYP.

9

TYP.

12

TYP.

5

TYP.

9

T-4012

20

DRESSING232A

DRESSING230B

SOUTH STAIRST101B

STORAGE222A FILM LOADING

222D

FILM LOADING222C

C F G

8

2

ED

3

5

7

10

9

11

4

6.1

9.5

6.6

J1 J3

J4

J1

J3

J1

J2

J3

J3J1

J1J3

J3

J1

J1

J3

D.8 E.5 E.8 F.4

2.3

2.6

2.7

5.1

11.2

6

D.3

2.4

E.6 F.7 H

2.2

10.9

9.6

8.9

2.9

3.5

4.4

5.3

6.4

6.9

7.8

8.8

E.4D.45 D.9D.4

2.65

4.5

2

2

7

2

2

2

2

2

TYP.

11

J3 J1

13

14

13

14

13

14

13

14

13

4

17

20

20

20

TYP.

6

21

21

21

23

23

23

23

23

23

23

22

23

23

EN

JAM N E. BOSSE

19418

GI N

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

1/8" = 1'-0"

T-102B

NEW ARTBUILDINGNMSU LAS CRUCES, NM

BASE BID 2ND LEVEL TECH SYSTEMSFLOOR PLAN - STUDIO WING

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB/SPO

CSK/JEB/SDR

1/8" = 1'-0"T-102B

1 BASE BID 2ND LEVEL TECHNOLOGY SYSTEMS FLOOR PLAN - STUDIO WING

A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES.

C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING.

D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.E. ALL COMMUNICATIONS CABLING TO MEET OR EXCEED CAT6 STANDARDS.F. TELECOMMUNICATIONS OUTLETS TO BE MOUNTED AT +18" A.F.F. (BOTTOM OF

BOX) UNLESS OTHERWISE NOTED. FOR EXAMPLE, DEVICES SPECIFIED AT +18" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR POWER RECEPTACLES AND TELECOMMUNICATIONS OUTLETS. DEVICES SPECIFIED AT + 48" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR LIGHT SWITCHES ETC.

G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL, THINWALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR PATHWAYS INDICATED ON THIS SHEET. ALL CONDUITS ARE TO BE, AT A MINIMUM, 1” TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL.

H. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED. LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE SYSTEMS.

I. NUMBER ADJACENT TO TELECOMMUNICATIONS OUTLET SYMBOL REPRESENTS NUMBER OF CAT 6 CABLES TO BE INSTALLED AND TERMINATED AT THAT LOCATION. A "B" ADJACENT TO AN OUTLET LOCATION REPRESENTS A ROUGH-IN ONLY LOCATION, PROVIDE BOX, CONDUIT, AND BLANK FACEPLATE.

J. ALL CONDUIT TURNS FOR A/V AND IT CONDUITS SHALL BE "SWEEP" TYPE, NO BEND FITTINGS ARE PERMITTED.

K. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX.

L. CONTRACTOR TO VERIFY ALL CABLE COUNTS AND NUMBER OF PATCH PANELS REQUIRED.

M. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES SHEETS FOR POWER OUTLET LOCATIONS.

N. CONTRACTOR IS PROVIDE AND TERMINATE CABLING FOR THE BLACKBOARD SYSTEM AND T0 “FUTURE” CARD READERS.

O. DURING VOICE/DATA CABLE INSTALLATION, PROPER COORDINATION AND CARE SHALL BE TAKEN TO ENSURE CABLING DOES NOT GET PAINTED, TEXTURED OR OTHERWISE CONTAMINATED. PER MANUFACTURERS INSTALLATION GUIDELINES.

P. ANY ON-GRADE FLOOR BOX APPLICATIONS, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET-RATED" CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.

ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND

INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS

AND TESTING OF ALL NETWORK CABLING.

NORTH

KEY PLAN

GALLERY

WING

STUDIO

WING EXTERIOR

YARD

MA

TC

H L

INE

RECEIVING

BID LOT 1

0' 8' 16' 32' 64'

GENERAL SHEET NOTESKEYNOTES

1. STANDARD TELECOMMUNICATIONS OUTLET. CONSISTS OF CATEGORY 6 CABLES. QUANTITY AS SHOWN. REFER TO DETAILS D1 AND D2 ON SHEET T-502.

2. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. CO-LOCATE WITH CEILING POWER OUTLET. QUANTITY AS SHOWN.

3. WIRELESS ACCESS POINT LOCATION. PROVIDE A CLEAR LABEL FOR LOCATION OF WIRELESS ACCESS POINT ON ACCESSIBLE CEILING TILE OR WALL NEAR ACCESSIBLE CEILING TILE. WIRELESS ACCESS POINT HARDWARE FURNISHED AND INSTALLED BY OWNER.

4. 12" X 4" WIRE BASKET STYLE CABLE TRAY FOR HORIZONTAL TELECOMMUNICATIONS CABLING. MOUNT CABLE TRAY 10'-6" ABOVE FINISHED FLOOR, BOTTOM OF TRAY. COORDINATE WITH ALL OTHER TRADES AND ARCHITECT PRIOR TO COMMENCEMENT OF WORK. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

5. CEILING SPEAKERS FOR LOCAL SOUND SYSTEM. COORDINATE WITH OWNER FOR EXACT LOCATIONS AND QUANTITIES. REFER TO DETAILS A6 AND B6 ON SHEET T503

6. COMBINATION POWER AND DATA FLOOR BOX. DO NOT DAISY CHAIN FLOOR BOXES, PROVIDE A SEPARATE CONDUIT HOME RUN FOR EACH BOX. REFER TO DETAILS A2, B1, AND B2 ON SHEET T-502 FOR ADDITIONAL FLOOR BOX INFORMATION. ANY ON-GRADE APPLICATION, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET" RATED CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES. COORDINATE FINAL MOUNTING LOCATIONS WITH EP SERIES SHEETS AND FURNITURE PRIOR TO COMMENCEMENT OF ANY WORK.

7. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. QUANTITY AS SHOWN.

8. CEILING MOUNTED PROJECTOR LOCATION. REFER TO DETAILS A2 AND B2 ON SHEET T503 FOR ROUGH-IN REQUIREMENTS. PROVIDE 120V POWER RECEPTACLE MOUNTED PER DETAILS A2 AND B2 ON SHEET T503. DISTANCE FROM DISPLAY SURFACE IS CRITICAL, COORDINATE EXACT LOCATION / THROW DISTANCE WITH ARCHITECT AND OWNER.

9. MOTORIZED PROJECTION SCREEN LOCATION FOR LOCAL A/V SYSTEM. FOR 120V SCREEN SWITCH REQUIREMENTS REFER TO ELECTRICAL SHEETS. COORDINATE WITH OWNER FOR SCREEN ROUGH-IN REQUIREMENTS.

10. WALL MOUNTED DIGITAL SIGNAGE VIDEO DISPLAY LOCATION. PROVIDE STRUCTURAL BACKING, BACK BOXES, AND POWER/ VOICE/DATA OUTLETS AS SHOWN ON DETAIL C4 AND C5 ON SHEET T-503.

11. PULL BOXES FOR A/V CABLING. REFER TO DIAGRAMS AND A/V J-BOX SCHEDULE ON SHEET T-601 FOR REQUIREMENTS.

12. BOX AND CONDUIT ROUGH-IN FOR ACCESS CONTROL. REFER TO DOOR HARDWARE DETAILS ON SHEET T-501 AND ARCHITECTURAL DOOR HARDWARE SCHEDULE FOR ADDITIONAL REQUIREMENTS.

13. 12" X 4" WIRE BASKET STYLE CABLE TRAY BLACK POWDER COATED FOR HORIZONTAL TELECOMMUNICATIONS CABLING. PROVIDE CABLE TRAY LINER TO PROTECT CABLES IN OPEN CEILING. MOUNT CABLE TRAY 10'-6" ABOVE FINISHED FLOOR, BOTTOM OF TRAY. COORDINATE WITH ALL OTHER TRADES AND ARCHITECT PRIOR TO COMMENCEMENT OF WORK. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

14. TELECOMMUNICATIONS OUTLETS IN OPEN CEILING AREAS TO HOMERUN CONDUITS TO NEAREST CABLE TRAY.

15. BOX AND CONDUIT ROUGH-IN FOR INTRUSION ALARM SYSTEM KEYPAD. 16. AUTOMATIC DOOR ACTUATOR LOCATION FOR PUSH PLATE HANDICAP ACCESS.

REFER TO ELECTRICAL FLOOR PLANS FOR ADDITIONAL REQUIREMENTS, PATHWAYS, AND POWER.

17. 2-WAY COMMUNICATION SYSTEM CALLING STATION. PROVIDE 1" EMT CONDUIT, HOME RUN TO BASE STATION. PROVIDE PULL BOXES AS NEEDED. CABLING TO LAND TO BASE STATION. LOCATE BASE STATION . REFER TO SPECIFICATION SECTION 28 3200 FOR ADDITIONAL REQUIREMENTS.

18. 2-WAY COMMUNICATION SYSTEM BASE STATION. PROVIDE 1" EMT CONDUIT, HOME RUN TO MDF ROOM #125A.PROVIDE PULL BOXES AS NEEDED. CABLING TO LAND ON 110 FIELD FOR PHONE TERMINATION. REFER TO SPECIFICATION SECTION 28 3200 FOR ADDITIONAL REQUIREMENTS.

19. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. QUANTITY AS SHOWN.

20. COMBINATION POWER AND DATA FLOOR BOX. DO NOT DAISY CHAIN FLOOR BOXES, PROVIDE A SEPARATE CONDUIT HOME RUN FOR EACH BOX. REFER TO DETAIL A1 ON SHEET T-502 FOR ADDITIONAL FLOOR BOX INFORMATION. ANY ON-GRADE APPLICATION, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET" RATED CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.COORDINATE FINAL MOUNTING LOCATIONS WITH EP SERIES SHEETS AND FURNITURE PRIOR TO COMMENCEMENT OF ANY WORK.

21. BOX AND CONDUIT ROUGH-IN FOR FUTURE CARD READER EQUIPMENT INSTALLATION. PROVIDE BLANK COVER PLATE. STUB CONDUIT TO NEAREST ACCESSIBLE CEILING SPACE. REFER TO DOOR HARDWARE DETAILS ON SHEET T-501 AND ARCHITECTURAL DOOR HARDWARE SCHEDULE ON SHEET A-600, AND SPECIFICATION 08 7100 DOOR HARDWARE FOR ADDITIONAL REQUIREMENTS.

22. 2" CONDUIT SLEEVE THROUGH WALL AND/OR SOFFIT FOR VOICE, DATA, AND INTERCOM CABLING. PROVIDE PLASTIC BUSHINGS ON BOTH ENDS TO PROTECT CABLES. QUANTITY AS SHOWN.

23. 4" CONDUIT SLEEVE THROUGH WALL AND/OR SOFFIT FOR VOICE, DATA, AND INTERCOM CABLING. PROVIDE PLASTIC BUSHINGS ON BOTH ENDS TO PROTECT CABLES. QUANTITY AS SHOWN.

NOT ALL NOTES USED

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.04 17:24:32-07'00'

Page 23: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

CR

DS

DS

CR

2

MDFT125A

13

12

15

16

17

18

11 11

11

11

D

6.1

6

5.3

3' - 1 7/8" 3' - 0"

16

4

T-401

3

T-401

TYP.

19

20

21

TRT225A

14

15

16

17

11

11

11

11

D

6.1

6

5.3

7' - 10 1/8"

12' -

6 3

/4"

16

16

3

T-4015

T-401

2' - 5 1/8" 2' - 6"

TYP.

19

20

21

1ST LEVEL0' - 0"

2ND LEVEL15' - 6"

PENTHOUSELEVEL

30' - 8 1/2"

AFF48"

24"

MDFT125A

TRT225A

AFF48"

24"

7' -

6"

7' -

6"

GROUNDING BUS BAR

110 PUNCH BLOCK

GROUNDING BUS BAR

110 PUNCH BLOCK

4"ø

4"ø

4"ø

4"ø

4"ø

CONDUIT RISER

STRUCTURAL DECK

LADDER RACK

VERTICAL LADDER RACK

0' -

4"

3/4" AC PLYWOOD

0' -

4"

VERTICAL LADDER RACK

3/4" AC PLYWOOD

STRUCTURAL DECK

LADDER RACK

8' -

4"

8' -

4"

13

12

11

10

9

8

7

6

5

4

3

2

1

45

44

43

42

41

40

39

38

37

36

35

34

33

32

31

30

29

28

27

26

25

24

23

22

21

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

45

44

43

42

41

40

39

38

37

36

35

34

33

32

31

30

29

28

27

26

25

24

23

22

21

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

45

44

43

42

41

40

39

38

37

36

35

34

33

32

31

30

29

28

27

26

25

24

23

22

21

20

19

18

17

16

15

14

344

7

TYP.

8

TYP.

6

212

TYP.

5

9

13

12

11

10

9

8

7

6

5

4

3

2

1

45

44

43

42

41

40

39

38

37

36

35

34

33

32

31

30

29

28

27

26

25

24

23

22

21

20

19

18

17

16

15

14

43 1

9

UPS (OFOI)

RACK 3RACK 2RACK 1 RACK 4

RACK 3RACK 2RACK 1 RACK 4

FDU (BUILDING) 10

FDU (CAMPUS) 10

NETWORK SWITCH(OFOI)

NETWORK SWITCH(OFOI)

NETWORK SWITCH(OFOI)

NETWORK SWITCH(OFOI)

TYP.

9

13

12

11

10

9

8

7

6

5

4

3

2

1

45

44

43

42

41

40

39

38

37

36

35

34

33

32

31

30

29

28

27

26

25

24

23

22

21

20

19

18

17

16

15

14

42

9

13

12

11

10

9

8

7

6

5

4

3

2

1

45

44

43

42

41

40

39

38

37

36

35

34

33

32

31

30

29

28

27

26

25

24

23

22

21

20

19

18

17

16

15

14

43 1

RACK 2RACK 1

RACK 2RACK 1

FDU (BUILDING)10

TYP.

9

UPS (OFOI) TYP.

6

NETWORK SWITCH(OFOI)

NETWORK SWITCH(OFOI)

NETWORK SWITCH(OFOI)

NETWORK SWITCH(OFOI)

7

TYP.

8

TYP.

5

GUTHRIE HALL

MDF T125A

IDF T225A

48 STRAND OS2 SM OSP50 PAIR VOICE GRADE COPPER OSP

24 STRAND OS2 SM 25 PAIR VOICE GRADE COPPER

EN

JAM N E. BOSSE

19418

GI N

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

As indicated

T-401

NEW ARTBUILDINGNMSU LAS CRUCES, NM

ENLARGED TECHNOLOGY PLANS

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB/SPO

CSK/JEB/SDR

1/2" = 1'-0"T-401

1

TECHNOLOGY SYSTEMS ENLARGED1ST FLOOR PLAN - MDF T125A

1/2" = 1'-0"T-401

2

TECHNOLOGY SYSTEMS ENLARGED2ND FLOOR PLAN - TR T225A

GENERAL SHEET NOTES

KEYNOTES

1. 4 POST 84" TALL QUADRARACK TELECOMMUNICATIONS EQUIPMENT RACK. CPI# 50120-703.

2. 2 POST 84" TALL UNIVERSAL TELECOMMUNICATIONS EQUIPMENT RACK. CPI# 46353-703.

3. 6" WIDE VERTICAL WIRE MANAGERS. CPI #35571-703.4. 8" WIDE VERTICAL WIRE MANAGERS. CPI #35572-703.5. HORIZONTAL WIRE MANAGEMENT. CPI #35441-702.6. GROUND BUS BAR MOUNTED TO RACK.7. 48 PORT VOICE GRADE PATCH PANEL WITH 50 PAIR COPPER TO 110 BLOCK ON

WALL.8. 48 PORT CAT6 DATA PATCH PANEL.9. OWNER FURNISHED, OWNER INSTALLED ACTIVE NETWORK EQUIPMENT.10. FIBER DISTRIBUTION UNIT.11. 3/4" AC GRADE FIRE RESISTANT PLYWOOD WITH 2 COATS OF FIRE RESISTANT

PAINT ON ALL WALLS. LEAVE WINDOW WITH GRADE STAMP UNPAINTED.12. COPPER OSP PROTECTOR BLOCK ON WALL.13. 100 PAIR 110 STYLE PUNCHDOWN BLOCK ON WALL.14. 50 PAIR 110 STYLE PUNCHDOWN BLOCK ON WALL.15. TELECOMMUNICATIONS GROUND BUS BAR MOUNTED 24" BELOW CABLE TRAY.16. 4" FIRE-RATED CONDUIT PATHWAY. QTY AS SHOWN. REFER TO T SERIES

FLOOR PLANS FOR PATHWAY.17. (2) 4" FIRE RATED CONDUIT RISER PATHWAY. STUB UP FOR MDF 115 TO

SECOND FLOOR 6" AFF IN IT 252.18. (3) 4" UNDERGROUND CONDUIT PATHWAY. REFER TO SITE PLAN TS-102 FOR

ADDITIONAL INFORMATION.19. 18" WIDE CABLE TRAY LADDER RACK RUNWAY. PROVIDE MOUNTS,

GROUNDING, AND ACCESSORIES FOR FULL INSTALATION. CPI #10250-71820. 18" WIDE ADJUSTABLE CABLE TRAY LADDER RACK RUNWAY. PROVIDE MOUNTS,

GROUNDING, AND ACCESSORIES FOR FULL INSTALATION. CPI #14300-71821. 18" WIDE VERTICAL CABLE TRAY LADDER RACK RUNWAY. PROVIDE MOUNTS,

GROUNDING, AND ACCESSORIES FOR FULL INSTALATION.

A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES.

C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING.

D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.E. ALL COMMUNICATIONS CABLING TO MEET OR EXCEED CAT6 STANDARDS.F. TELECOMMUNICATIONS OUTLETS TO BE MOUNTED AT +18" A.F.F. (BOTTOM OF

BOX) UNLESS OTHERWISE NOTED. FOR EXAMPLE, DEVICES SPECIFIED AT +18" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR POWER RECEPTACLES AND TELECOMMUNICATIONS OUTLETS. DEVICES SPECIFIED AT + 48" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR LIGHT SWITCHES ETC.

G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL, THINWALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR PATHWAYS INDICATED ON THIS SHEET. ALL CONDUITS ARE TO BE, AT A MINIMUM, 1” TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL.

H. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED. LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE SYSTEMS.

I. NUMBER ADJACENT TO TELECOMMUNICATIONS OUTLET SYMBOL REPRESENTS NUMBER OF CAT 6 CABLES TO BE INSTALLED AND TERMINATED AT THAT LOCATION. A "B" ADJACENT TO AN OUTLET LOCATION REPRESENTS A ROUGH-IN ONLY LOCATION, PROVIDE BOX, CONDUIT, AND BLANK FACEPLATE.

J. ALL CONDUIT TURNS FOR A/V AND IT CONDUITS SHALL BE "SWEEP" TYPE, NO BEND FITTINGS ARE PERMITTED.

K. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX.

L. CONTRACTOR TO VERIFY ALL CABLE COUNTS AND NUMBER OF PATCH PANELS REQUIRED.

M. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES SHEETS FOR POWER OUTLET LOCATIONS.

N. CONTRACTOR IS PROVIDE AND TERMINATE CABLING FOR THE BLACKBOARD SYSTEM AND T0 “FUTURE” CARD READERS.

O. DURING VOICE/DATA CABLE INSTALLATION, PROPER COORDINATION AND CARE SHALL BE TAKEN TO ENSURE CABLING DOES NOT GET PAINTED, TEXTURED OR OTHERWISE CONTAMINATED. PER MANUFACTURERS INSTALLATION GUIDELINES.

P. ANY ON-GRADE FLOOR BOX APPLICATIONS, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET-RATED" CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.

NO SCALET-401

3 TECHNOLOGY SYSTEMS WALL ELEVATION: MDF T125A, IT T225A

ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND

INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS

AND TESTING OF ALL NETWORK CABLING.

GENERAL SHEET NOTES

NO SCALET-401

4

TECHNOLOGY SYSTEMS RACKELEVATION: MDF T125A

NO SCALET-401

5

TECHNOLOGY SYSTEMS RACKELEVATION: IT T225A

NO SCALET-401

6 TELECOMMUNICATIONS BACKBONE ONE-LINE DIAGRAM

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.04 17:24:44-07'00'

Page 24: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

SOLID WOOD DOOR

HOLLOW METAL DOOR

WOOD BLOCK

MAGNET

MAGNET

SWITCH

MAGNET

DW

2/3 DW 1/3 DW

FLOOR

CEILING

1/2" EMT3 PAIR 22AWG

CR

DOORPOSITIONSWITCH

J

1" EMT STUBBED INTO NEAREST ACCESSIBLE CEILING SPACE.

4" SQ BOX WITH BLANK FACEPLATE (OPPOSITE SIDE OF DOOR FROM CARD READER)

DOORPOSITIONSWITCH

1/2" EMT4 CONDUCTOR 22AWG

4" SQ BOX FOR CARD READER.

DRILL HOLE THROUGH DOOR FRAME FOR CABLE PATHWAY. FOR ELECTRIFIED HINGE, OR POWER TRANSFER DEVICE.

P

POWER

OPTIONAL HORNPROVIDE 4"sq. BOX FOR FUTURE USE.

1/2" EMT

1/2" EMT4 CONDUCTOR 22AWG

1/2" EMT4 CONDUCTOR 22AWG

4 CONDUCTOR 18AWG; SHIELDED/3 PAIR 22AWG;SHIELDED/2 CONDUCTOR 22AWG;SHIELDED/4 CONDUCTOR 22AWG;FROM BLACKBOARD CONTROLLER AT NEAREST TELCOM ROOM.

DRILL HOLE THROUGH DOOR FRAME FOR CABLE

PATHWAY. FOR ELECTRIFIED HINGE, OR

POWER TRANSFER DEVICE.

2 CONDUCTOR 12AWG

2 CONDUCTOR 12AWG

FLOOR

CEILING

ADA

DOOR OPERATOR

HANDICAP PUSH BUTTON BOTH SIDES VERIFY EXACT LOCATION WITH ARCHITECT PRIOR TO INSTALL

CR

DOORPOSITIONSWITCH

J

1-1/4" EMT STUBBED INTO NEAREST ACCESSIBLE CEILING SPACE.

4" SQ BOX WITH BLANK FACEPLATE (OPPOSITE SIDE OF DOOR FROM CARD READER)

DOORPOSITIONSWITCH

DRILL HOLE THROUGH DOOR FRAME FOR CABLE PATHWAY. FOR ELECTRIFIED HINGE, OR POWER TRANSFER DEVICE.

P

POWER

OPTIONAL HORNPROVIDE 4"sq. BOX FOR FUTURE USE.

1/2" EMT

4 CONDUCTOR 18AWG; SHIELDED/3 PAIR 22AWG;SHIELDED/2 CONDUCTOR 22AWG;SHIELDED/4 CONDUCTOR 22AWG;4 CONDUCTOR 22AWG;FROM BLACKBOARD CONTROLLER AT NEAREST TELCOM ROOM.

3/4" EMT3 PAIR 22AWG;4 CONDUCTOR 22AWG

1/2" EMT4 CONDUCTOR 22AWG

1/2" EMT4 CONDUCTOR 22AWG

DRILL HOLE THROUGH DOOR FRAME FOR CABLE PATHWAY. FOR FUTURE ELECTRIFIED HINGE, OR

POWER TRANSFER DEVICE.

2 CONDUCTOR 12AWG

2 CONDUCTOR 12AWG

1/2" EMT4 CONDUCTOR 22AWG

1/2" EMT4 CONDUCTOR 18AWG;4 CONDUCTOR 22AWG

FLOOR

CEILING

CR

DOORPOSITIONSWITCH

J

1" EMT STUBBED INTO NEAREST ACCESSIBLE CEILING SPACE.

4" SQ BOX FOR CARD READER.

4" SQ BOX WITH BLANK FACEPLATE (OPPOSITE SIDE OF DOOR FROM CARD READER)

DRILL HOLE THROUGH DOOR FRAME FOR CABLE PATHWAY. FOR ELECTRIC STRIKE.

1/2" EMT3 PAIR 22AWG

1/2" EMT4 CONDUCTOR 22AWG

4 CONDUCTOR 18AWG; SHIELDED/3 PAIR 22AWG;SHIELDED/2 CONDUCTOR 22AWG;SHIELDED/4 CONDUCTOR 22AWG;FROM BLACKBOARD CONTROLLER AT NEAREST TELCOM ROOM.

P

2 CONDUCTOR 12AWG

POWER

1/2" EMT4 CONDUCTOR

22AWG

1/2" EMT

OPTIONAL HORNPROVIDE 4"sq. BOX FOR FUTURE USE.

FLOOR

CEILING

CR

DOORPOSITIONSWITCH

J

1-1/4" EMT STUBBED INTO NEAREST ACCESSIBLE CEILING SPACE.

4" SQ BOX FOR CARD READER.

4" SQ BOX WITH BLANK FACEPLATE (OPPOSITE SIDE OF DOOR FROM CARD READER)

DRILL HOLE THROUGH DOOR FRAME FOR CABLE PATHWAY. FOR ELECTRIC STRIKE.

1/2" EMT4 CONDUCTOR 22AWG

4 CONDUCTOR 18AWG; SHIELDED/3 PAIR 22AWG;SHIELDED/2 CONDUCTOR 22AWG;SHIELDED/4 CONDUCTOR 22AWG;FROM BLACKBOARD CONTROLLER AT NEAREST TELCOM ROOM.

P

2 CONDUCTOR 12AWG

POWER

1/2" EMT4 CONDUCTOR

22AWG

1/2" EMT

OPTIONAL HORNPROVIDE 4"sq. BOX FOR FUTURE USE.

DOOR OPERATOR

1/2" EMT4 CONDUCTOR 18AWG; 4 CONDUCTOR 22AWG

ADA

HANDICAP PUSH BUTTON BOTH SIDES VERIFY EXACT LOCATION WITH ARCHITECT PRIOR TO INSTALL

3/4" EMT3 PAIR 22AWG;4 CONDUCTOR 22AWG

EXIT EXIT

PB IC

CEILING

FLOOR

EQ.

EQ.

DOOR

EQ.

12"

48"UON

(BACKSPLASH)

COUNTER

2" ABOVE BACKSPLASH(COORDINATE WITH ARCH)

18"

80"MIN

FIRE ALARM NOTIFIER(STROBE/HORN/SPEAKER)

NOTES:

1. HEIGHTS SHOWN ARE TYPICAL TO CENTER OF BACKBOX / DEVICE UNLESS NOTED OTHERWISE.2. DEVICES ABOVE DOORS SHALL BE CENTERED BETWEEN TOP OF DOOR TRIM AND CEILING LINE.3. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL GOVERN OVER THOSE SHOWN ABOVE.4. NOT ALL DEVICES SHOWN ARE USED IN THIS PROJECT.

96"MAX

6"MIN

LIGHT SWITCH (OR OCCUPANCY SENSOR/SWITCH)

PUSHBUTTON (DOOR ACTUATOR)

WALL PHONE JACK

INTERCOM SWITCH

18"

4" MAX

VOICE/DATA OUTLET

POWER OUTLET

Jx

4" MAX

AUDIO-VISUAL INPUT JACK

Jx

AUDIO-VISUAL CONTROL KEYPAD

CR

SECURITY CARD READER

80"MIN

CLOCK/SPEAKER

96"MAX

6"MIN

C S

8'-6"MAX

39"UON

FLOOR

CEILING

DOOR OPERATOR

DS DS

JUNCTION BOX

POWER SUPPLY

ADAADACR

KEYED NOTES1. 4 CONDUCTOR 18AWG2. 3 PAIR 22AWG3. 2 CONDUCTOR 22AWG4. 4 CONDUCTOR 22AWG5. 2 CONDUCTOR 12AWG6. BLACKBOARD DOOR CONTROLLER WITH

ENCLOSURE7. APPROVED POWER SUPPLY8. APPROVED JUNCTION BOX9. APPROVED ADA COMPLIANT SWING

OPERATOR10. APPROVED DOOR POSITION SWITCH11. APPROVED HC OPERATOR BUTTON12. BLACKBOARD CARD READER 13. APPROVED POWER TRANSFER14. APPROVED EXIT DEVICE WITH REQUIRED

TRIM15. APPROVED DOOR CLOSER16. OPTIONAL HORN. PROVIDE 4"sq. BOX

FOR FUTURE USE.17. 1, 120 VAC. CONNECT TO EMERGENCY

POWERED CIRCUIT WHERE AVAILABLE.

42

5 5

44

17 1 4

4

17

9

10 15

14

1313

12 11 11

7

8INSIDEOUTSIDE

CONTROLLER

617

INSTALL CONTROLLER IN LOCAL TELCOM ROOM

INTERNET CONNECTION

HORN

16

PLENUM RATED CONTROL CABLES4 CONDUCTOR 18AWG; SHIELDED/3 PAIR 22AWG;SHIELDED/2 CONDUCTOR 22AWG;SHIELDED/4 CONDUCTOR 22AWG;4 CONDUCTOR 22AWG;

PROVIDE BY DIVISION 27 AND INSTALLED BY DIVISION 27

PROVIDED BY NMSU ANDINSTALLED BY DIVISION 25

PROVIDED BY NMSU ANDINSTALLED BY DIVISION 26

PROVIDED BY DIVISION 25 ANDINSTALLED BY DIVISION 25

PROVIDED BY NMSU ANDINSTALLED BY DIVISION 25 PROVIDED BY NMSU AND

INSTALLED BY DIVISION 25

IRRIGATION

SERIAL CABLE

CAT 6

PROVIDED BY CONTRACTOR

ONICON SYSTEM-10CHW BTU METER

BACNET IP

MAIN ELECTRIC METERMODBUS TCP

MECHANICAL SYSTEMSELECTRIC SUB-METER

MODBUS TCP

LIGHTING SYSTEMSELECTRIC SUB-METER

MODBUS TCP

METRON FARNIERSPECTRUM (AMR)

DOMESTIC WATER METER

CADILLAC CMAGCONDENSATE METER

MODBUS RTU

*RED-DESIGNATES NMSUSUPPLIED METERS AND

COMMUNICATION GATEWAYS

AMRGATEWAY

PROTONODEGATEWAY

CAT-5/6ETHERNET CABLE

CAT-5/6ETHERNET CABLE

CAT-5/6ETHERNET CABLE

CAT-5/6ETHERNET CABLE

CAT-5/6ETHERNET CABLE

NETWORKSWITCH

CAT-5/6ETHERNET CABLE

QTY (2) RS-485SERIAL CABLES(BELDEN 88723)

MODBUS RTU TO BAC NET IPCOMMUNICATION GATEWAY

*RED

*RED *RED

*RED

*RED

EN

JAM N E. BOSSE

19418

GI N

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

As indicated

T-501

NEW ARTBUILDINGNMSU LAS CRUCES, NM

TECHNOLOGY DETAILS

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB/SPO

CSK/JEB/SDR

SCALE: NO SCALED5

SECURITY ALARM SYSTEM:DOOR SWITCHES

SCALE: NO SCALEA4

DOOR ROUGH-IN: CONTROLLEDACCESS ENTRY PAIRED DOORS - DETAIL D

SCALE: NO SCALEB4

DOOR ROUGH-IN: ADA CONTROLLEDACCESS ENTRY PAIRED DOORS - DETAIL B

SCALE: NO SCALEA5

DOOR ROUGH-IN: CONTROLLEDACCESS ENTRY - DETAIL C

SCALE: NO SCALEB5

DOOR ROUGH-IN: ADA CONTROLLEDACCESS ENTRY - DETAIL A

SCALE: NO SCALEA1 ELECTRICAL COMPONENT MOUNTING HEIGHTS (TYPICAL)

SCALE: NO SCALEB2 DOOR ROUGH-IN: WIRE PATHWAY DIAGRAM

ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND

INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS

AND TESTING OF ALL NETWORK CABLING.

SCALE: NO SCALED1 DATA METERING DETAIL

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.04 17:24:54-07'00'

Page 25: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

J-BOX #7 TEL CONDUIT #1 TR1-ER

TEL CONDUIT #2 TR1-ER

TEL CONDUIT #3 TR1-TR2

TEL CONDUIT #1 TR1-ER

TEL CONDUIT #2 TR1-ER

TEL CONDUIT #3 TR1-TR2

NOTE: COORDINATE WITH NMSU-ICT FOR LABELING SCHEME

U-089-1-202A

CABLE #ORIGIN (TR NAME)DESTINATION (OUTLET NAME)

CABLE TYPE: C = COPPER F = FIBER CX = COAX CABLE U = UTP

LABEL WITHIN 6"OF CABLE BREAKOUT

NOTE: COORDINATE WITH NMSU-ICT FOR LABELING SCHEME

END VIEWSECTION A

PLAN VIEW

8" SUMP

34"

6"

SPRING ASSISTED GALVANIZED DIAMONDPLATE COVER W/ LOCKING LATCH

4-3/4" DIA. RNDKNOCKOUTS 4 PER SIDE

1" DIA. GROUND ROD KNOCKOUTS 2 PLACES ON FLOOR (OPTIONAL)

GALVANIZED PULLING IRON 2 EACH END, 2 ENDS

4-3/4" DIA. RND KNOCKOUTS4 PER SIDE

(4)- 5/8" DIA. LIFTING INSERTS

2'-0"ALL AROUND

PROVIDECOPPER #6 TO ALL METALLIC PARTS

24" DRAIN

COMPACTED TO 95% RELATIVE DENSITY. FREE FROM LARGE ROCKS AND DEBRIS.(COMPACTED IN 6" LAYERS).

SPLICE ENCLOSURE BOND AS REQUIRED

8" GRAVEL BED

CONDUIT DUCTBANK

A ACOMMUNICATIONS

HH-T12

HANDHOLE IDENTIFICATION.

BOTTOM FEED.SIDE-MOUNT HOUSING ASSEMBLY FOR POWER.ACCEPTS (1)3/4" CONDUIT.WIREMOLD CAT #575CHA (TYPICAL OF 2)

TOP VIEW(COVER) ISOMETRIC VIEW

SIDE VIEW (SIDE MOUNT

HOUSING ONLY)

SIDE VIEW(ALL BOTTOM HOUSINGS)

FLANGED COVER FOR CARPET FLOOR

9 1/4"

16 3/4"BOTTOM FEED.CENTER-MOUNT HOUSING ASSEMBLY FOR TELECOM & A/V.ACCEPTS (1)1-1/4" CONDUIT.WIREMOLD CAT #1125CHA(TYPICAL OF 3)

2700V INSULATORS

STAND-OFFS

COPPER BUS BAR.

BOLT CONNECTION WITHCOMPRESSION SPADE LUGFITTING (TYPICAL)PROVIDE BONDING TO

CONNECTIONS TOCABLE TRAY SYSTEMSAND EQUIPMENT RACKS(TYPICAL)

STRUCTURE

THREADED ROD

UNISTRUT SUPPORTS

CABLE TRAY -VOICE DATA CABLING ONLY

J-HOOKS FOR NON VOICE / DATA CABLING MOUNTED TO THREADED ROD.

#6 AWG BOND. BOND ALL ENDS OF CONDUIT TO CABLE TRAYS AS PER MANUFACTURER RECOMMENDATIONS.

EMT CONDUIT SLEEVES PATHWAYS (REFER TO PLANS)

CABLE TRAY

THREADED DROP ROD

CABLE TRAY

CABLE RUNWAY RADIUS DROP

NOTE: PROVIDE CABLE TRAY LINER WHEREVER CABLE TRAY IS IN EXPOSED CEILING. VERIFY COLOR WITH OWNERAND ARCHITECT BEFORE ANY COMMENCEMENT OF WORK

SLACK LOOP

COMMUNICATIONCABLING

WALL

CONDUIT THROUGH WALL TO OUTLET

4-11/16" SQUARE,2-1/8" DEEP JUNCTIONBOX WITH 1-DEVICERAISED MUD RING

COVER PLATE

SLACK LOOP

COMMUNICATIONCABLING

WALL

CONDUIT THROUGH WALL TO OUTLET

4-11/16" SQUARE,2-1/8" DEEP JUNCTIONBOX WITH 1-DEVICERAISED MUD RING

COVER PLATE

J-HOOK

FINISHED GRADE

12"

36" MIN.

4"

3"

3" 3" 3"3"

4" PVC SCHEDULE 40 CONDUIT, QTY AS NOTED ON PLANS. PROVIDE PULLSTRINGS IN EACH.

NOTE:REFER TO SHEETS TS102 AND T-401 FOR ADDITIONAL INFORMATION REGARDING TELECOMMUNICATIONS CABLING.

FINISHED GRADE OR SURFACE REPAIR SURFACES TO MATCH EXISTING

COMPACTED TO 95% RELATIVE DENSITY. FREE FROM LARGE ROCKS AND DEBRIS.(COMPACTED IN 6" LAYERS).

UNDISTURBED EARTH

WARNING TAPE

CONCRETE DUCTBANK.

1 # 4/0 BARE COPPER

8" SAND BED.

BOTTOM FEED.SIDE-MOUNT HOUSING ASSEMBLY FOR POWER.ACCEPTS (1)3/4" CONDUIT.WIREMOLD CAT #575CHA (TYPICAL OF 2)

TOP VIEW(COVER) ISOMETRIC VIEW

SIDE VIEW (SIDE MOUNT

HOUSING ONLY)

SIDE VIEW(ALL BOTTOM HOUSINGS)

FLANGED COVER FOR CARPET FLOOR

7 1/4"

16 3/4"BOTTOM FEED.CENTER-MOUNT HOUSING ASSEMBLY FOR TELECOM & A/V.ACCEPTS (1)1-1/4" CONDUIT.WIREMOLD CAT #1125CHA(TYPICAL OF 1)

2 PORT DATA W/ 3 SLOT A/V LOCATION FOR EXTRON MAAP PLATES. WIREMOLD CAT #6MAAP2A

POWER DUPLEX 20AMP WIREMOLD CAT #68REC

(BOTH SIDES)

PROVIDE BLANK CENTER PLATE WIREMOLD CAT #6B WHEN DEVICES NOT IN USE.

1" CONDUIT & CONNECTOR.

4-11/16" SQUARE, 2-1/8" DEEPJUNCTION BOX WITH KNOCKOUTS.

4-11/16" SQUARE1-DEVICE RAISEDMUD RING.

CABLE LENGTH 12"COIL IN BACK BOX

MODULAR JACK ORBLANK AS NEEDED

FACEPLATE

CATEGORY CABLES(QTY AS INDICATEDON PLANS)

181

123-A

01-20:01

BLANK

TELECOM ROOM #

SERVICING CLOSET

PORT LABEL

OUTLET ID

OUTLET IDOUTLET ROOM #

01-20:02

01-20:03

PORT LOCATIONRACK UNIT #

EQPT. RACK ID #

12 3/4"

13 13/16"

17 5/16" 15 3/8"

6 1/8"

4 11/16"

4 13/16"

11 7/8"

A/V

POWER

DATA

RELOCATABLEDIVIDER

TUNNELEFB810-TUN

MODULE

A: 2" K.O.B: 1-1/4" K.O.C: 1" K.O.

B A,CBB

C

C

C

C

C

C

C

C

A,C

BOTTOM FEED.SIDE-MOUNT HOUSING ASSEMBLY FOR POWER.ACCEPTS (1)3/4" CONDUIT.WIREMOLD CAT #575CHA

TOP VIEW(COVER) ISOMETRIC VIEW

SIDE VIEW (SIDE MOUNT

HOUSING ONLY)

SIDE VIEW(ALL BOTTOM HOUSINGS)

FLANGED COVER FOR CARPET FLOOR

9 1/4"

16 3/4"

BOTTOM FEED.CENTER-MOUNT HOUSING ASSEMBLY FOR TELECOM.ACCEPTS (1)1-1/4" CONDUIT.WIREMOLD CAT #1125CHA

MOUNTING PLATE FOR STANDARD DUPLEX RECEPTACLE.

CONTROLLED POWER DUPLEX 20AMP

WIREMOLD CAT #68REC-CTRL(BOTH SIDES)

MOUNTING PLATE FOR DATA.PROVIDE VOLTAGE BARRIER BETWEEN DEVICES.

CO

NT

RO

LLE

D

CO

NT

RO

LLE

D

WIREMOLD 8" POKE-THRU #8STC (INCLUDES, QTY. (1) 1/2-GANG 3/4" CONDUIT HOUSING ASSEMBLY #575CHA, QTY. (1) 8" DIVIDER #8DIV, AND QTY. (1) BOTTOM HOUSING ASSEMBLY #5BLH).

PROVIDE THE FOLLOWING FOR EACH BOX:QTY. (1) BLANK HOUSING COVER #1BLHQTY. (1) BOTTOM HOUSING (DATA) #1125CHAQTY. (1) BOTTOM HOUSING (POWER) #175CHAQTY. (2) CONTROLLED RECEPTACLES #68REC-CTRLQTY. (1) DEVICE MOUNTING PLATE FOR DATA #8ATC6AQTY. (2) STANDARD DUPLEX DEVICE MOUNTING PLATE #8DPQTY. (1) FINISHING COVER ASSEMBLY AS FOLLOWS:• PROVIDE (1) FINISHING COVER ASSEMBLY AS FOLLOWS:• FOR CARPETED OR VINYL TILE FLOORING, PROVIDE SURFACE STYLE

COVER ASSEMBLY, CATALOG # 8CTC2xx.• FOR BARE/POLISHED CONCRETE OR TERRAZZO FLOORING, PROVIDE

FLUSH STYLE COVER ASSEMBLY, CATALOG # 8CT2xx. PROVIDE BARE CONCRETE/TERRAZZO TRIM RING, PROVIDE TILE SHIMS AS REQUIRED, CATALOG #8TS.

• VERIFY STYLE AND COLOR "xx" (NICKEL, BLACK, GRAY, BRASS OR BRONZE) WITH ARCHITECT PRIOR TO PURCHASE ORDER.

BOTTOM FEED.CENTER-MOUNT HOUSING ASSEMBLY FOR POWER.ACCEPTS (1)3/4" CONDUIT.WIREMOLD CAT #175CHA

EN

JAM N E. BOSSE

19418

GI N

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

As indicated

T-502

NEW ARTBUILDINGNMSU LAS CRUCES, NM

TECHNOLOGY DETAILS

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB/SPO

CSK/JEB/SDR

SCALE: NO SCALEC6

TELECOMMUNICATIONS CONDUITIDENTIFICATION SCHEME

SCALE: NO SCALED6 TYPICAL CABLE IDENTIFICATION SCHEME

SCALE: NO SCALEE5 TYPICAL HANDHOLE DETAILS

SCALE: NO SCALEB2

WIREMOLD EVOLUTION POKE THROUGHFLOOR BOX DETAILS (8ATCNK)

SCALE: NO SCALEB6

TELECOMMUNICATIONSGROUNDING BUS BAR (TYPICAL)

SCALE: NO SCALEE4 CABLE TRAY DETAILSCALE: NO SCALEE2

CABLE TRAY / CONDUIT SLEEVEBONDING AND GROUNDING

SCALE: NO SCALEE1

TELECOMMUNICATIONSCABLE TRAY RUNWAY RADIUS DROP

SCALE: NO SCALEA6 TELECOMMUNICATIONS OUTLET CONDUIT ROUTING

SCALE: NO SCALED3 TELECOM CONDUIT DUCTBANK SECTION

ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND

INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS

AND TESTING OF ALL NETWORK CABLING.

SCALE: NO SCALEB1

WIREMOLD EVOLUTION POKE THROUGHFLOOR BOX DETAILS (6ATC)

SCALE: NO SCALED1

TELECOMMUNICATIONSOUTLET BOX DETAILS (TYPICAL)

SCALE: NO SCALED2

STANDARD TELECOM OUTLETIDENTIFICATION SCHEME (TYPICAL)

SCALE: NO SCALEA2 WIREMOLD EFB8-OG

REFER TO NMSU ICT STANDARDS FOR TELECOMMUNICATIONS LABLING

STANDARD PER TIA-606

SCALE: NO SCALEA1

WIREMOLD EVOLUTION POKE THROUGHFLOOR BOX DETAILS (8STC)

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.04 17:25:04-07'00'

Page 26: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

1/16" STRANDED AIRCRAFT CABLE.LOUDSPEAKER ASSEMBLY W/TILEBRIDGE APPROX. 10LBS

LOCKING WINGS

SUSPENDED CEILINGCEILING RECESSED LOUDSPEAKER

REFER TO AUDIO-VISUALPATHWAY DIAGRAMS

SPEAKER WIRE PULL BOX(REFER TO PLANS)

LAY-IN CEILING T-GRID SYSTEMWHERE APPLICABLE

DECK

A/V & DATA EMT CONDUITS PERROOM CONDUIT PATHWAY DIAGRAMS

DOUBLE-GANG DATA WORKBOX(DOWNWARD FACING)

SINGLE-GANGELECTRICAL WORKBOX WITH

DUPLEX POWER RECEPTACLE(DOWNWARD FACING).

SCREENWALL

VIDEO PROJECTOR (O.F.O.I.)

1.5" NPT SUSPENSION COLUMN(O.F.O.I.)

DECK

!!! CRITICAL DISTANCE !!!

COORDINATE WITH OWNER AND ARCHITECT

P TO

UNISTRUT GRID MOUNTED TO DECK. CONTRACTOR TO FURNISH AND INSTALL

1.5" NPT THREADED POLE. CONTRACTOR PROVIDED.

VIDEO PROJECTORMOUNTING BRACKET (O.F.O.I.)

1.5" NPT THREADED PIPE COUPLER WITH SET SCREWS.CHIEF CMA270 OR EQUAL. CONTRACTOR PROVIDED.

1.5" NPT CEILING MOUNTED PLATE.CHIEF CMA110 OR EQUAL. CONTRACTOR PROVIDED.

OUTLINE OF SUPPORT PIPE ABOVE PROJECTOR

PROJECTION SCREEN (O.F.C.I.)

DOUBLE-GANG JUNCTION BOX WITH TELECOM OUTLET

DUPLEX POWERRECEPTACLE

VIDEO PROJECTOR(O.F.O.I.)

!!! CRITICAL DISTANCE !!!

COORDINATE WITH OWNER AND ARCHITECT

32"

DATA

60" O.C.AFF

O.U.N.

48"

NOTES:1. SPAN BACKING SEGMENTS BETWEEN STUDS.2. VERIFY LOCATIONS OF BACKING MATERIAL WITH

ARCHITECT/OWNER PRIOR TO ROUGH-IN3. FASTEN MATERIAL FLUSH TO FACE OF STUDS READY TO

ACCEPT FINISH WALLBOARD.4. TELECOM OUTLET (T.O.) FURNISHED WITH QTY(2) CAT6 DATA

DROPS. NETWORK CABLING IS O.F.C.I.

3/4" PLYWOOD BLOCKINGSPAN BETWEEN (3) STUDS

PWR

T-503C4

6 11

/16"

6 3/

32"

4 7/

32"

6"

3 15

/16"

3 13

/16"

5 3/16"

VOLTAGE BARRIER INSIDE BOX.

MODEL # TVBS505 AS MFD. BY ARLINGTON INDUSTRIES.

PROVIDE SUPPORT CABLE TAIL LENGTH SUFFICIENT TO REACH TO 8FT AFF.

AV CONTRACTOR WILL CUT SUPPORT CABLE TO CORRECT HANGING LENGTH AND

PROVIDE CONNECTION TO LOUDSPEAKER ASSEMBLY. PRIMARY & SECONDARY SUPPORT CABLES

USE 1/16" DIA. STRANDED AIRCRAFT CABLEWITH MIN. 180LB LOAD LIMIT AND BREAKINGLOAD LIMIT OF 900LB (GRIPPLE OR EQUAL)

EYE-BOLT OR SIMILAR ANCHOR TOUNDERSIDE OF DECK SUFFICIENTTO SUPPORT WEIGHT OF 10LBLOUDSPEAKER PLUS HARDWARE WITHMIN. SAFETY FACTOR OF 5X.

SPEAKER WIRE

SPEAKER WIRE PULL BOX(REFER TO PLANS)

PRIMARY SUPPORT CABLE SECURE TOLOUDSPEAKER HANGING BRACKET WITHCARIBINER PROVIDED WITH LOUDSPEAKER.

SECONDARY SUPPORT CABLE SECURED TOLOUDSPEAKER HANGING BRACKET W/#10BOLT BY AV CONTRACTOR.

TERMINALWEATHER BOOT

SIDE VIEW

WIRE CONNECTOR

HANGING BRACKET

PENDANT LOUDSPEAKER(TYPICAL)

SIDE

BOTTOM TOP

STRUCTURAL DECK

DECK

A/V & DATA EMT CONDUITS PERROOM CONDUIT PATHWAY DIAGRAMS

DOUBLE-GANG DATA WORKBOX

(DOWNWARD FACING)

SINGLE-GANGELECTRICAL WORKBOX WITH

DUPLEX POWER RECEPTACLE(DOWNWARD FACING).

SCREENWALL

VIDEO PROJECTOR (O.F.O.I.)

1.5" NPT SUSPENSION COLUMN(O.F.O.I.)

DECK

!!! CRITICAL DISTANCE !!!

COORDINATE WITH OWNER AND ARCHITECT

PTO

UNISTRUT GRID MOUNTED TO DECK. CONTRACTOR TO FURNISH AND INSTALL

1.5" NPT THREADED POLE. CONTRACTOR PROVIDED

VIDEO PROJECTORMOUNTING BRACKET (O.F.O.I.)

1.5" NPT CEILING MOUNTED PLATE.CHIEF CMA110 OR EQUAL. CONTRACTOR PROVIDED.

1.5" NPT THREADED PIPE COUPLERWITH SET SCREWS. CHIEF CMA270OR EQUAL. CONTRACTOR PROVIDED.

EN

JAM N E. BOSSE

19418

GI N

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

As indicated

T-503

NEW ARTBUILDINGNMSU LAS CRUCES, NM

AUDIO-VISUAL DETAILS

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB/SPO

CSK/JEB/SDR

SCALE: NO SCALEB6 RECESSED CEILING LOUDSPEAKER

SCALE: NO SCALEA2

CEILING MOUNTED PROJECTOR DETAIL FOR SUSPENDED LAY-IN CEILING

SCALE: NO SCALEB2 PROJECTION SYSTEM PLAN

SCALE: NO SCALEC5

ROUGH-IN AND STRUCTUAL BACKING FOR WALLMOUNTED DIGITAL SIGNAGE DISPLAY

ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND

INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS

AND TESTING OF ALL NETWORK CABLING.

SCALE: NO SCALEC4

MULTISERVICE OUTLET BOX FORWALL MOUNTED DIGITAL SIGNAGE

SCALE: NO SCALEA6 PENDANT MOUNTED LOUDSPEAKERSCALE: NO SCALEA1

CEILING MOUNTED PROJECTOR DETAILFOR OPEN CEILING

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.04 17:25:14-07'00'

Page 27: NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design phase project manager g-000 new art building aim #3035 ... fa-101a base bid & bid

TELECOM OUTLET (VOICE/DATA)

AUDIOVISUAL JUNCTION/PULL BOX

POWER OUTLETS W/ RECEPTACLE

CONDUIT STUB

J

TO

S LOUDSPEAKER RECESSED FLUSH IN CEILING

P

A/V PATHWAY DIAGRAMSYMBOLS LEGEND

LAY-INCEILINGWHERE

INDICATED

STRUCTURALDECK

FLOOR

MOTORIZED PROJECTION SCREEN(O.F.C.I.)

P

P

CONDUIT ANDWIRING TO 120V

CONTROL SWITCH IN LECTERN.

S2

CEILING MOUNTED SPEAKERS (OFCI)

S2S2TO REMAINING

SPEAKERS

J

PULL BOX

TO BLDG LAN

COIL SECOND SPEAKER CABLE

(4) DATA CABLE-OFCI(BLUE & WHITE)

(2) SPEAKER CABLES (2X18AWG PLENUM) OFCI

2' SLACK LOOP

(2) DATA CABLE-(BLUE & WHITE)

JJ1LECTERNA/V CONNECTION PANEL

(2) DATA CABLES FOR LAN (IN 1" EMT)(4) DATA CABLES FOR A/V (IN 1" EMT)(2) SPEAKER CABLES IN (3/4") EMT)

J3

VIDEO PROJECTOR(OFOI)

P TO

POWER DUPLEX MOUNTED FLUSH IN CEILING.

T.O. PLATE MOUNTED IN FLUSH IN CEILING.

(2) DATA CABLE(BLUE & WHITE)

TO BLDGLAN

UNISTRUTGRID

LAY-INCEILINGWHERE

INDICATED

STRUCTURALDECK

FLOOR

VIDEO PROJECTOR(OFOI)

MOTORIZED PROJECTION SCREEN(O.F.C.I.)

P

P

P TO

POWER DUPLEX MOUNTED FLUSH IN CEILING.

(1)1/2" FLEX

T.O. PLATE MOUNTED IN FLUSH IN CEILING.

CONDUIT TO 120V CONTROL SWITCH

IN LECTERN

(2) 1" EMTAND

(1) 3/4" EMT

(1) 1" EMT

S2

CEILING MOUNTED SPEAKERS (OFCI)

S2S2TO REMAINING

SPEAKERS

(1) 1" EMT

(1) 3/4" EMT

J

PULL BOX

(1) 1" EMT

DATA

TO CABLE TRAY

J3

JJ1LECTERNA/V CONNECTION PANEL

UNISTRUTGRID

STRUCTURALDECK

FLOOR

VIDEO PROJECTOR(OFOI)

MOTORIZED PROJECTION SCREEN(O.F.C.I.)

P

P

P TO

CONDUIT AND WIRING TO 120V CONTROL

SWITCH IN LECTERN

(4) DATA CABLE-(BLUE & WHITE)

(2) DATA CABLE-(BLUE & WHITE)

2' SLACK LOOP

JJ1LECTERNA/V CONNECTION PANEL

(2) DATA CABLES FOR LAN (IN 1" EMT)(4) DATA CABLES FOR A/V (IN 1" EMT)(2) SPEAKER CABLES IN (3/4") EMT)

S2

PENDANT MOUNTED SPEAKERS (OFCI)

S2S2

(1) 1" EMTJ

PULL BOX

(1) 1" EMT

DATA

J3

J J J

UNISTRUTGRID

STRUCTURALDECK

FLOOR

MOTORIZED PROJECTION SCREEN(O.F.C.I.)

P

P(1)1/2" FLEX

CONDUIT TO 120V CONTROL

SWITCH INLECTERN

(2) 1" EMTAND

(1) 3/4" EMT

S2

PENDANT MOUNTED SPEAKERS (OFCI)

S2S2

(1) 1" EMT

(1) 3/4" EMT

J

PULL BOX

(1) 1" EMT

DATA

J3

JJ1LECTERNA/V CONNECTION PANEL

J J J

(4) DATA CABLE-OFCI(BLUE & WHITE)

2' SLACK LOOP

VIDEO PROJECTOR(OFOI)

P TO

(2) DATA CABLE-(BLUE & WHITE)

UNISTRUTGRID

EN

JAM N E. BOSSE

19418

GI N

EE

R

ON L

E

A

N

SROFES

D

PI

CLI

ENSE

NE

WME X I COB

I

400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com

Copyright © RMKM Architecture, P.C. 2017

SHEET TITLE

SHEET NUMBER

PROJECT

MODELED BY

RMKM PROJECT NO.

SCALE

DESIGN PHASE

PROJECT MANAGER

1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018

NO SCALE

T-601

NEW ARTBUILDINGNMSU LAS CRUCES, NM

TECHNOLOGY DIAGRAMS

A01508

Replacement of Dan W. Williams Hall

CONSTRUCTION DOCUMENTS

BEB/SPO

CSK/JEB/SDR

ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND

INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS

AND TESTING OF ALL NETWORK CABLING.

SCALE: NO SCALEB2 A/V CABLE RISER DIAGRAM: TYPICAL CLASSROOM

SCALE: NO SCALEA2 A/V PATHWAY DIAGRAM: TYPICAL CLASSROOM

GENERAL SHEET NOTES

SHEET KEYNOTES

1. MOUNT BOX AT 12"-18" ABOVE SUSPENDED CEILING IN PARTITION WALL WITH ACCESS COVER/DEVICE SIDE FACING AWAY FROM WALL. IN LOCATIONS WITHOUT SUSPENDED CEILINGS MOUNT BOX IN PARTIITION WALL AT 12" - 18" BELOW STRUCTURAL DECK. COORDINATE FINAL LOCATION WITH ALL OTHER DISCIPLINES PRIOR TO INSTALLATION.

A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES.

C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING.

D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.E. ALL COMMUNICATIONS CABLING TO MEET OR EXCEED CAT6 STANDARDS.F. TELECOMMUNICATIONS OUTLETS TO BE MOUNTED AT +18" A.F.F. (BOTTOM OF

BOX) UNLESS OTHERWISE NOTED. FOR EXAMPLE, DEVICES SPECIFIED AT +18" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR POWER RECEPTACLES AND TELECOMMUNICATIONS OUTLETS. DEVICES SPECIFIED AT + 48" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR LIGHT SWITCHES ETC.

G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL, THINWALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR PATHWAYS INDICATED ON THIS SHEET. ALL CONDUITS ARE TO BE, AT A MINIMUM, 1” TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL.

H. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED. LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE SYSTEMS.

I. NUMBER ADJACENT TO TELECOMMUNICATIONS OUTLET SYMBOL REPRESENTS NUMBER OF CAT 6 CABLES TO BE INSTALLED AND TERMINATED AT THAT LOCATION. A "B" ADJACENT TO AN OUTLET LOCATION REPRESENTS A ROUGH-IN ONLY LOCATION, PROVIDE BOX, CONDUIT, AND BLANK FACEPLATE.

J. ALL CONDUIT TURNS FOR A/V AND IT CONDUITS SHALL BE "SWEEP" TYPE, NO BEND FITTINGS ARE PERMITTED.

K. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX.

L. CONTRACTOR TO VERIFY ALL CABLE COUNTS AND NUMBER OF PATCH PANELS REQUIRED.

M. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES SHEETS FOR POWER OUTLET LOCATIONS.

N. CONTRACTOR IS PROVIDE AND TERMINATE CABLING FOR THE BLACKBOARD SYSTEM AND T0 “FUTURE” CARD READERS.

O. DURING VOICE/DATA CABLE INSTALLATION, PROPER COORDINATION AND CARE SHALL BE TAKEN TO ENSURE CABLING DOES NOT GET PAINTED, TEXTURED OR OTHERWISE CONTAMINATED. PER MANUFACTURERS INSTALLATION GUIDELINES.

P. ANY ON-GRADE FLOOR BOX APPLICATIONS, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET-RATED" CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.

SCALE: NO SCALEB1 A/V CABLE RISER DIAGRAM: TYPICAL CLASSROOM WITHOUT CEILING

SCALE: NO SCALEA1 A/V PATHWAY DIAGRAM: TYPICAL CLASSROOM WITHOUT CEILING

NO. ISSUE DATE

Digitally signed by Benjamin E BosseDate: 2018.01.04 17:25:23-07'00'