NetSol Business Unit Yokogawa Corporation of America Copyright © Yokogawa Corporation of America January 26, 2006 Yokogawa Green Series Controllers
Mar 26, 2015
NetSol Business UnitYokogawa Corporation of America
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Yokogawa Green Series Controllers
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.2
What is a controller?
A device used to set or adjust the conditions in a desired environment.– Must be able to continually sense the conditions in
the environment.• Thermocouple• Flow meter• Level transmitter
– Must be able to have a desired condition set by a user.
• Setpoint
– Must have the ability to change the conditions in the environment.
• Turn on an electric heater• Open or close a gas or water valve
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.3
Simple Temperature Controller
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.4
Simple Control System
Thermocouple
Electric Heating Element
Setpoint Control
Load
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.5
Typical Control Drawing
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.6
Inputs and Outputs
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.7
Unsurpassed Selection
YS170 Dual Loop Programmable Controllers– pH, boiler & other complicated control actions.– Maximum versatility with custom programming.
US1000 Digital Loop Controllers– Single loop or dual loop control.– Custom computation and expanded discrete I/O.
GREEN series Industrial Controllers– Primarily used in the heat treating industries.– Can be used in many process applications.– Most cost effective for many control applications.– 301, 400, 500 or 700 series: – Provide only the functions required.
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.8
More Product Selections
UT100 Series Temperature Controllers– Focused on plastic and OEM markets– 1/16, 1/8 or 1/4 DIN size– High reliability and easy configuration
at a very low price
JUXTA Signal Conditioners– Large number of functions– Isolators, T/C, RTD, frequency
inputs– VJ series allows BRAIN &
PC configuration
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.9
Industrial/Process Controllers
YS170 Series
Full Featured Process Control
US1000 Series
UT100 Series
GREEN SeriesHigh Performance Industrial Control
High LevelProcessControl
Full Featured Temperature Control
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.10
Where Do You Find Control Applications?
Simple Controller ApplicationsTemperatureLevelpHFlowPressureRatioHeat/Cool
Programmable Controller Applications
Furnaces (Lab & Industrial)
Environmental
Chambers
Ovens
Refrigeration
Kilns
Just about anywhere you make sales calls!
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.11
What about PID
Proportional Band– Set as (PB) Proportional Band– Proportional makes the controller output move in proportion to the error between
set point and controlled variable.– K (Gain) = measure of the sensitivity of the final control element position change to
a given error– K is the inverse of PB (K= 100/PB)– Two items to set: Proportional Band (PB) & Manual Reset (MR)
Integral– Integral - “automatic reset” of final control element– Integral changes output over time– Integral repeats proportional action in integral time.– Integral tuning parameter is time based: the smaller the number the stronger the
action.– Integral continues to act until error is zero.
Derivitive– Derivative has no effect when error is not changing– Gives anticipatory response - not effective in fast loops, i.e., flow, pressure,
pH, etc.... etc...…– Derivative acts on “rate of change”, performs breaking action
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.12
UT 100 Series Dynamic Self Tune
Dynamic Self Tuning is initialized when applying power or changing set point.– Parameter CTL must be in
SLF mode (Default).– Does not use open loop
response like Auto Tuning, uses PV wave form analysis.
– Calculates new P, I & D parameters.
SP
0%
100%PV
PV
Time
100%
0%
Output
Time
Self Tune STARTSSP change or Power ON
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.13
Auto Tune
The standard GREEN series Auto Tune can be implemented in the Operating menu if the CTL parameter is placed in the PID mode. This bypasses the Self Tuning operation.
PV
SV
MV
100%
0%
100%
Being Auto-tuning Auto-tuning ends at 3rd peak.
PID control according to PID parameterobtained by auto-tuning.
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.14
Super Control
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.15
SUPER 2 Function
Hunting occurs during:– Set point changes– Load changes
SameFurnace
CoilSheet
SUPER2=O
NHunting
PID parameters are set at this condition.
Temperature Change
SUPER2=ON
Hunting
Load Change
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.16
UT130 1/16 DIN Controller
3 digit LED display (shared PV & SP)High performance at a very low costT/C or RTD input onlySpecify ON/OFF relay or voltage pulse outputDynamic Self tuneAuto Tune & Super ControlHeat/cool outputs*Two alarms relays*Heater break alarms*RS485 communication*
*Option
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.17
UT150 1/16 DIN Controller
4 digit LED display of PV & SP (Red and Green)Universal input (T/C, RTD, mV or VDC)Specify relay, voltage pulse or DC current outputHeat/cool outputs*Two alarm contacts*Heater break alarms*Retransmission of PV*Two contact inputs for SP selection & timer function*RS485 communication*
*Option
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.18
UT152 & UT155 Controllers
Universal input (T/C, RTD, mV or VDC)Specify relay, voltage pulse or DC current outputHeat/cool outputs*Two alarm contacts*Heater break alarms*Retransmission*Contact inputs for SP selection & timer function*RS485 communication*
*Option
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.19
UP150 1/16 DIN Program Controller
1 Program pattern, 16 segments 4 digit LED display of PV & SP (Red and Green)Universal input (T/C, RTD, mV or VDC)Specify relay, voltage pulse or DC current outputHeat/cool outputs*Two Event contacts*Retransmission of PV*External contact input RS485 communication*
*Option
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.20
Oven Temp Control with SSR
Simple control application to control temperature in an oven or electric furnace.Probably the simplest and one of the most common control applications.Points to note– SSR needs a time proportional,
voltage pulse output to operate properly.
– Cycle time setting can affect control if too large.
Applicable control units– All
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.21
GREEN Series Standard Features
Universal inputs (T/C, RTD, mV or VDC)Universal outputs (Relay, voltage pulse or4-20mADC current)Retransmission of PV, SP, output OR15VDC loop power supplyMultiple contact inputs and outputsAuto Tune for easy start upSuper Control for SP overshoot suppressionUL, CSA & CE approvalsIP55 front panel assembly (Splash Proof)
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.22
UT321/351 Industrial Controllers
Large 4 digit 20mm “active” LEDdisplay of PV (UT351)Single loop controlAuto/Manual switching2 contact inputs (SP, A/M)3 contact outputs (Alarms)Heat/cool output optionOptional 24VDC loop power supplyRS485 communication optionGeneral purpose temperature controlInexpensive alternative for level, flow & pressure control
UT351UT321
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.23
UP351 Program Controller
2 patterns, 10 segments each2 contact inputs (Pattern select, HOLD)3 contact outputs– 1 time event alarm– 2 PV event alarms
NO local set point capabilityRS485 comm. optionSmall furnaces & environmental chambers
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.24
Temperature Programs
Ramp & SoakSelect Program bypressing PRG keyRESET key to stopprogramTime event to startauxiliary heater,fan, etc.Up to 4 PID Sets fortighter control
SP
PRG2PRG1
PRG2
PRG1
PRG2
KEYS
RESET
PV MVControl
PRG1Time Event
PID 3
PID 2
PID 1
PID 4
2nd Reference point
1st Reference point
Reference Deviation
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.25
Active Color PV Display
PV Display LED color changes between Green-color and Red-color
It can be explained as "the function to actively change a display color according to conditions."
•Active Color PV Display:
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.26
Industrial Ethernet
Industrial Ethernet Protocol allows a variety of industrial control devices to be integrated into the same application.Modbus TCP/IPGateway function
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.27
Single Loop Control
Universal input4-20mADC output for gas controlRetransmission of PV toa recorderRoasted hot dog??
AnalogOutput
UT450/420
PV Input
4-20 mAOutput
Temperature
PIDRecorder
Air flow
Gas
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.28
Furnace Temp Control with SCR
Simple control application to control temperature in an oven or electric furnace.One of the simplest and one of the most common control applications.Points to note– SCR needs an analog 4 - 20 mA output from the
controller.Applicable control units– All
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.29
UT420/450 Controllers
Large 5 digit 20mm LED display of PV (UT450)Single loop control strategyPosition proportional control option (motorized valve)Heat/cool output optionOptional 24VDC looppower supplyOptional remote set pointUp to 7 contact inputsUp to 4 contact outputsRS485 comm. option
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.30
Steam
Control
CoolingWater
CoolingOutput
HeatingOutput
RawMaterial
TC
MVCo
olin
g O
utpu
t
MV
Heat
ing
Out
put
Heat & Cool Control
Heat output & cool outputcan be relay, voltage pulse,or DC current individually.Cool output 0 to 100%above set pointHeat output 0 to 100% belowset pointDeadband around set pointis adjustable
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.31
Position Proportional Control
Uses two relay contactsto increase or decreasevalve positionSlide wire feedback forreading valve positionon the output display“Assuming” mode can beused with no slide wireDO NOT USE for standardPID control
ValvePosition
Direct/Reverserotation
M
UT450
PositionFeedback
Control
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.32
UT520/550 Industrial Controllers
Large 5 digit 20mm LED display (UT550)Remote set point option (Ratio Control)Up to eight pre-defined control strategies– Cascade control– Analog backup for PLC’s– Input auto selector
Up to 7 contact inputsUp to 7 contact outputsHeat/cool control optionPosition proportional control option (motorized valve)Optional 24VDC loop power supply
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.33
Single Station Cascade
Water
RawMaterials
JacketTemp.
ReactorTemp.
UT550
Steam
Ctrl1
Ctrl2
Heat&CoolUM330
Performs cascade loop control within a single controller.Two temperature measurement signals are available.– Universal PV input– Auxiliary analog
voltage input
Can be used for heat and cool control.
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.34
Cascade Control for Jacketed Vessel
This application explains how cascade control can be used to control temperature in a vessel.Points to note– This application requires two
independent control loops– Loops can be referred to as inner &
outer, master & slave, or primary & secondary
– There must be a significant difference in the response times for the inner and outer loops for the process to function properly. The larger the better.
– The outer loop must be tuned first and then the inner loop.
Applicable control units– 500 Series and higher or– Any combination of controllers in a
Master Slave configuration. (minor differences)
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.35
Automatic Analog Back Up
MV feed-backBack-upControl Mode
Fail4 - 20mA
UT550/UT520
Ctrl
Steam
RawMaterials
ControlSystem
Back-upAuto
Under normal conditions, the tracking input for UT520/550 from the supervisory control system is the control output. When the supervisory control system has failed, UT520/550 begins automatic backup control.
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.36
UP550 Program Controller
5 digit 20 mm LED and backlit LCD displays– LCD display can show temperature pattern
30 Patterns, up to 300 SegmentsFive control strategiesSeven contact inputs & outputs– Time events & process events
Heat /cool control optionPosition proportional controloption (motorized valve)
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.37
Temperature Programs
Pattern can be seen in LCD displayPattern numberSegment numberTime remaining in currentsegmentCan be used with UT controllers as a set pointgenerator for multi-zonefurnaces
ProgramControl
SP1 SP2
SP1SP2
SP1SP2
30ptn
99 seg./ptn (Total 300 seg.)
Retransmissonoutput
Loop1
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.38
PV Auto-Selector
Selects maximum, minimumor average of 2 PV inputsTemperature sensors canbe located at differentlocations within thefurnaceOne universal inputOne analog voltageinput
Electric Furnace
CtrlSelector
Product
SCR
UM330
UP550
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.39
PV Switching
Switches between twoinputs depending ontemperature rangeA contact input orUP550 temperatureset point flag switchesthe inputsOne universal inputOne analog voltageinput
TC for Low Temp.Universal PV input
TC for High Temp.Auxiliary analog input
CtrlSwitching
SCR
UP550
UM330
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.40
UT750 Industrial Controller
Large 5 digit 20mm LED with backlit LCD display.
Up to 13 types of control functions including dual loop control, cascade control, temperature/humidity and more.
Custom Computation function for complex regulatory control and sequential logic.
7 contact inputs & 7 outputs Expandable to 23 each with
external modules using RS485 50ms scan time is available for
pressure/speed/flow control.
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.41
Dual Loop Control
RawMaterial
Ctrl1 Ctrl2
CoolingMedium
Controls two loops in a single instrument.Example: Control two stages of a multi-stage heat exchanger.T/Cs or RTDs can be directly connected to UT750-5X. Both control loops have run/stop functions and set point selection by an external contact input.
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.42
PV Auto-Select
Heater
Contact Input
CtrlSwitching
SCR
Raw Materials
Switches and controls from one of two measured inputs by using a contact input or input range.Controls either furnace or product temperature according to certain conditions.Two universal inputs allow T/C or RTD inputs
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.43
UP750 Program Controller
Up to 300 patterns, 3000 segments (99 seg/pattern)Ten resident control strategies– Dual loop control with universal inputs– Single station cascade with universal inputs– Auto-selector & PV Switching
Custom computation capability7 event alarms std (Time & PV)Up to 23 contact inputs (7 Std)– Requires RS485 option &
expansion modules
Up to 23 contact outputs (7 Std)
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.44
UT/UP750 Custom Computation Function
ControlFunction
TemperatureComp.
Flow Pressure
Square root
DI1 DI2 DI3
Man MV
A/MAM
Temp.
Pressure Comp.
OR
AND
Performs special computations that are not included in the standard pre-configured control strategies.Users can customize input/output computations by linking function modules.Math, logic & special function modulesExamples: Carbon potential, pressure/temperature compensated flow and other sophisticated applications.
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.45
PC Configuration Using the Light Loader
With Model LL100 PC-Based Parameters Setting Tool, all parameters of GREEN series controllers can be set on a PC.– Parameter setting function– Write/read parameters to/from
controllers– Saves to a disk– Printout (Hard copy
documentation)– Tuning function
Custom computation in the UT/UP750 requires LL200
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.46
LL100 Parameters Setting Tool
Use with 300E, 400E, 500E & 700E seriesCan be used with older UT520, UT/UP550, UT/UP750
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.47
LL200 Custom Computation Tool
Use for creating special programs for UT/UP750Eand UT750-7X
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.48
RS485 Communication Option
PC-Link Communication
RS485 2Wire or 4Wire
1 2 UT/UP Controllers 31
Up to 9600bpsYokogawa PC-Link or Modbus communication protocol are used.Number of units: 31 units/serial portCommunication distance: Up to 4000 Ft.Communication interface: RS485
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.49
UM331/351 Digital Indicators
Large 4 digit 20mm displayFront panel configurationRetransmission of PVThree alarms standardOptional 4th alarmOptional 24VDC loop powersupplyIP55 front panelUL, CSA & CE approvalsRS485 comm. option
UM351
UM331
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.50
UD310/320/350 Manual Setters
Large 4 digit 20mm display (UD350)Front panel configurationSetpoint loading via the arrow keysRetransmission of PV standardTwo alarms standardIP65 (UD310), IP55 (UD320/350),
front panel UL, CSA & CE approvals
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.51
GREEN Series Selections
Simple applications
UT750
UT351/321
Smaller sizeUT150/130
UT520/550
Complex control applications
Most complex applicationsDual Loop
Custom ComputationMultiple contact I/O
Select UT420/450 First
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.52
JUXTA Signal Conditioners
Lightening Arresters
Power Distributors
J Series Socket Mount
Programmable Mathusing BRAIN terminal
F Series (24VDC)
W Series (110VAC or 24VDC)
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.53
Furnace Control Using Zone PID
Zone control is used when multiple setpoint are used in the furnace and the control characteristics of the process changes as temperature changes.Points to note– Reference points must be set to activate switching
action– RDV (Reference Deviation) is available if special PID
control is necessary if PV deviates from SP by a set amount.
Applicable control units– All units except; 100 series, US1000 & YS series
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.54
Tank Level Control
Controller can be used to control the level in a tankPoints to note– Can be controlled in a variety of different methods
depending on the control elements.• Alarms can be used for control in very simple on/off
application• Controller can supply 15 or 24 VDC power for the
transmitter
Applicable control units– All
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.55
Air Conditioner Temperature Control
Controller can be used to control both the heat and cool control elements of a packaged AC systemPoints to note– Can be controlled in a variety of different methods
depending on the control elements.
• Alarms can be used for control in very simple on/off solenoid application
• Heat/cool units a recommended for control elements that are not on/off
Applicable control units– All - very simple applications– All heat/cool control units
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.56
Heat Exchanger Temperature Control
Heat exchanger is a device that transfers heat from one medium to another without the two mediums physically touching.– Liquid to liquid– Steam to liquid– Steam to air
Points to note– If there is a pump on the secondary side of the H.E.,
you may want a DI for the pump to turn off the controller.
Applicable control units– All
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.57
Heat Exchanger Control & BTU Calculation
Allows for control of a heat exchanger as well as track the BTU transferred though the heat exchanger. The BTU (British Thermal Unit) is universally accepted as a unit of heat transfer measurement. The BTU is defined as the quantity of heat required to raise the temperature of one pound of water 1F.Can be used for billing purposes or maintenance of the heat exchangerPoints to note– Feed forward input is necessary for application to work– Custom programming is required
Applicable control units– US1000– YS170
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.58
Carbon Potential Control
Controlling Carbon PotentialPoints to note– CP is not a direct measurement but an estimated
value based upon some assumptions. The only true way of determining if the CP is effective is a shim stock test.
– The Carbon Master does not supply the carbon content to the furnace, It trims the CP by adding small amounts of gas & air to maintain the desired CP.
Applicable units– CX, UT750 & UP750
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.59
Neutralization Control for Wastewater
Used to balance the PH of wastewaterPoints to note– This method does not use feed forward
control, so simpler controllers can be used.– Is tricky to control properly due to changing
gain as PH approaches 7. Zone PID must be used.
– Use plenty of dead band to keep alkaline and acid from fighting one another
Applicable Controllers– US1000, YS170, UT750, UT550
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.60
Neutralization control for acid wastewater
US1000
4 to 20mA
zone PID control:Acid zone (zone 1) PID gain largeNeutralization zone (zone 2) PID gain small
pH
Neutralization control range1.0
14.0
TICPID
neutralizingpool
Acid wastewater
alkalineneutralizer
zone PIDcontrol
zone 1
zone 2
zone 3
pH sensor
9.0
5.0
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.61
Feed Forward Control
Used to allow the controller to anticipate upcoming upsets in the process and to react before they affect the processPoints to note– Used mostly in flow applications– The FF is added to the output signal directly, after
the PID computation is done. This signal may not be appropriate for the process. A FF ratio and bias signal must be set to ensure that the right amount of FF is added to the output. This is not easy.
Applicable Controllers– US1000, YS170
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.62
Feed Forward Control
US1000 Add the Product flow to control theMV for fast control action, beforeProduct temperature change.Temp. input Tin : 0 to 200 deg CFlow input Fin : 0 to 100L/min.
Feed Forward Calculation FF =FGN * (Fin + FBI) + FBO FF:Signal which is added to MV FGN : Gain FBI : Input bias FBO : Output bias
Product Flow(Feed Forward input signal)
T CPID
F
+
Pt100
Steam
HeatExchanger SQRTBias &
Gain
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.63
Boiler Combustion Control
Used to provide steam to a variety of applicationsPoints to note– This application requires many controllers working in
tandem to operate a boiler.• Boiler Master• Fuel Flow Controller• Air Flow Controller• Drum Level Controller
– Requires specialized knowledge to operate, so customer is usually quite familiar with application and configuration.
Applicable Controllers– US1000, YS170
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.64
Boiler Combustion Control Overview
Boiler Master Signal
Air Flow
AirFlow
Controller
FuelFlow
Controller
M
Boiler Master ControllerBoiler output Pressure control
Fuel Flow
Boiler outputPressure
Pressure
Flow
Cross LimitControl
Control ConditionSteam Pressure 50 to 150 kg/cm2Steam Flow 0 to 100 t/hFuel Flow 0 to 8.0 kl/hAir Flow 0 to 100.0 %
Air to Fuel ratio should bedecided from optimumcombustion dondition in eachboiler master zone.
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.65
Boiler Master Pressure Controller
Used to control steam header pressure by adjusting the setpoint of the air and fuel controllersPoints to note– Feed forward input from header steam flow is used
to adjust boiler air & fuel flow setpoint. Predictive action for unexpected steam demand.
– Feed forward signal must be linearized for each particular boiler
Applicable Controllers– US1000, YS170
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.66
Boiler Master Pressure Control
MV
PC001
FX +
Output tracking signal
Linearizer
Boiler Steam Flow
Pressure
Flow
Fuel Flow setpoint
Fuel control statusAUTO mode
FX Linearizor
Boiler Steam
Fuel FlowRate
This charactaristic of lineariszershould be tuned from actualSteam to fuel flow data.
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.67
Fuel Flow Control
Used to control the fuel flow to the boilerPoints to note– Controller looks at both the boiler master signal and
the air flow rate, select the lower of the two and this becomes the fuel flow setpoint. This configuration limits the fuel to keep it lagging behind the air.
Applicable Controllers– US1000, YS170
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.68
Fuel Flow Control with Cross Limit Method
LOW selector + K1
Fuel Flow RateControl
Fuel Flow
Air FlowRate
Boiler Master Signal
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.69
Air Flow Controller
Used to control air flow to the boilerPoints to note– Controller looks at both the boiler master signal and
the fuel flow rates, select the higher of the two and this becomes the air flow setpoint. This configuration limits the fuel to keep it leading the fuel.
– A ratio is placed in this controller to achieve the proper mix of air to fuel. The RT parameter can be used or this signal can be linearized
Applicable Controllers– US1000, YS170
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.70
Air Flow Control with Cross Limit Method
--
M
HI selector Air to FuelRatio
Air Flow RateControl
Air Flow
- K2
Boiler Master SignalFuel Flow Rate
signal
Fx
Air Flow rate
Fuel FlowRate
Fx
Copyright © Yokogawa Corporation of AmericaJanuary 26, 2006
Tier 3: Yokogawa Field Instrumentation Solutions
Page.71
Drum Level Control
The Drum is the object of combustion. The drum provides steam to the header and associated equipment. The drum level controller ensures there is enough water in the drum to meet the steam demand. Points to note– There are three types of drum level configurations
• Single Element Control• Two Element Control• Three Element Control
– Applicable Controllers
– US1000, YS170