Figure 2 Load Flow Calculation Here are the steps in calculating the values in above Figure 2: I. Downstream Values:Note: These are the values above the arrow. 33KV Bus: 11KV Bus 10MVA Transformer: Page 2 of 12 MVA Method Load Flow Calculation – Ver Pangonilo - Filipino Engineer 8/22/2011 http://s.pangonilo.com/index.php/tutorials/mva-method/mva-method-load-flow-calculation/4
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
7/29/2019 mva-metho.pdf
http://slidepdf.com/reader/full/mva-methopdf 1/5
Figure 2 Load Flow Calculation
Here are the steps in calculating the values in above Figure 2:
I. Downstream Values: Note: These are the values above the arrow. 33KV Bus:
11KV Bus
10MVA Transformer:
Page 2 of 12MVA Method Load Flow Calculation – Ver Pangonilo - Filipino Engineer
From here, we are not able to go any further since we need values from downstream to be able tocalculate the equivalent MVA between the 5MVa transformer and the 5MVa motor.
II. Upstream Values:
At 400V Bus:
At 6.6KV Bus:
2MVA Transformer:
5MVA Transformer:
At 11KV Bus:
5MVA Transformer:
10MVA Transformer:
4MVA Transformer:
At 33KV Bus:
Page 3 of 12MVA Method Load Flow Calculation – Ver Pangonilo - Filipino Engineer
At this point, we have completed all the values in the upstream MVA contribution for load flow.
Let us now go back to the downstream calculation where we stopped. (Note: I will leave thiscalculation for you to do).
Popularity: 21%
Pages: 1 2 3 4 5
By Ver 8:48 AM
8 Responses
Stay in touch with the conversation, subscribe to the RSS feed for comments on this post.
tiong says
Quoted” 1. Motor MVAs are equal to the rated Equivalent MVAs.”
I wish to confirm that Motor MVAs is the short circuit MVA please? Thank you
August 16, 2010, 3:36 PM
1.
Ver says
Hi Tiong,
Motor MVAs in load flow calculation is the rated motor MVA, not the short circuit MVA
August 16, 2010, 4:18 PM
2.
artem says
@ 11kv bus as per mva diagram,upstream values mva are 67.33 (transfo. 2) and 44.94 (motor 5mva)downstream values mva are 8.55 (transfo. 1) and 3.94 (generator side)..Please help me to explain sir how did these values came. How to perform this calculation…Thank you.
3.
Page 4 of 12MVA Method Load Flow Calculation – Ver Pangonilo - Filipino Engineer
exactly sir ver, this helps a lot. thank you very much..mabuhay ka and god bless.
February 2, 2011, 10:56 AM
5.
artem says
I’m sorry sir Ver but i have additional query about the voltage dip or voltage drop upon startingthe motor 150kva on the system which draws a power of 0.9 MVA..I have a result by handcalculations at 400V Bus: 77.22%, at 6.6kV: 87.72%, at 11kV: 89.28% which is a littledifferent result on your MVA Diagram as shown that at 400V Bus: 76.7% (shown calculation),
6.
Page 5 of 12MVA Method Load Flow Calculation – Ver Pangonilo - Filipino Engineer