GAIA Aria

MSER-XEE

Packaged unit using renewable energy for domestic comfort, designed for direct connection to solar panels.

Guida_2011_v26.indd 23Guida_2011_v26.indd 23 15/03/11 17:5615/03/11 17:56

Page 2: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

2424

MSER-XEE 31÷61

GAIA ARIA

PATENTPENDING

Eurovent EnergyEfficiency Class

Termostato HID-H1

ACQUEDOTTO

Scambiatore di energia

Gaia

Pannellosolare

CENTRALINA

POMPA

NON FORNITO DA CLIVET

Gaia

Pannellosolare

RICIRCOLO SANITARIOCircolatire inclusonell’ELFOEnergy GAIA

Two-section reversible heat pumpAir cooledIndoor installationCapacity from 3,0 to 16,3 kW

GAIA Aria is the innovative annual cycle heat pump that generates comfort and uses from 75% to 100% renewable energy.Its main features are:

4SYSTEM MACHINE - it can be used with radiant panel systems, room terminals and radiators. It includes all the necessary devices to ensure summer and winter air-conditioning as well as the production of domestic hot water. Installation times and costs are drastically reduced because GAIA Aria contains the pumping groups, the domestic hot water storage tanks and connection to solar panels;

4MAXIMUM SAVINGS - electronic control allows to freely establish temperature, humidity and operating times. Once set, the control automatically manages summer or winter operation, and the production of domestic hot water. Overall energy efficiency is maximized through constant monitoring of building needs and of the temperature of fresh air;

4INVERTER DC TECHNOLOGY - GAIA Aria provides you with winter heating and summer cooling with the maximum energy efficiency thanks to the DC inverter technology applied to the compressor, the circulator, and the fan. Thanks to the inverter, the speed of the various devices can be adjusted based on the actual requested energy, allowing further reduction of consumption and a substantial increase in seasonal efficiency;

4PRIMARY CIRCUIT - it has got a low consumption DC circulator that allows to adjust the water flowrate according to the compressor speed thus maximising the heat exchange regardless the flow variations required by the system.

4SECONDARY CIRCUITS - GAIA Aria can manage up to three different zones having different temperatures in function of the type of terminal through mixing valves and low consumption DC circulators with an automatic modulation of the waterflow depending on the delta temperature. Between the primary and the secondary circuit an hydraulic separator is built in to separate the unit from the user side in order to assure the best operating conditions of GAIA Aria.

4SAFE AND ECOLOGICAL - GAIA Aria does not use gas or other fuels and thus precludes the possibility of leakage of hazardous substances into the environment. It does not produce exhaust gas and does not require a flue pipe. Therefore, it does not require obligatory maintenance such as boiler cleaning and smoke control. It does not release CO2 into the atmosphere.

OUTDOOR UNIT (MSER-XEE OUT)It allows to recover the heating and cooling energy contained in outdoor air at temperatures down to -22°C. Thanks to the use of the innovative energy exchanger the defrost cycles are reduced up to 70% compared to the traditional units.

MSER-XEE OUT adapts to many positioning solutions:external with or without ducting; under roof; in the basement.

INDOOR UNITCompact and packaged. 4 - 60% space taken in the central heating4 - 20% installation time of the complete

system.

GAIA Aria ensures the constant availability of hot domestic water, which can be produced up to a temperature of 55°C. The domestic hot water is stored in a 200-litre tank built into the unit. A special anti-stratification system makes it possible to contain the entire volume of water in the pump at a more or less constant temperature for added comfort. The unit avoids all energy and water waste thanks to the hot water circulator with inverter in the domestic hot water system. GAIA Aria also encompasses the expansion vessel, the safety valve, the anti-scald pressure switch valve and an electric safety heater.

GAIA has been designed for connection to solar heating panels.This leads to a further increase in the use of renewable energy sources for the free production of hot domestic water, through the solar energy captured by the solar panels.On days when the solar energy is insufficient, or if solar panels have not been installed, the hot domestic water is heated by the heat pump.

BUILT-IN HOT DOMESTIC WATER DIRECT CONNECTION TO THE SOLAR PANELS

Guida_2011_v26.indd 24Guida_2011_v26.indd 24 15/03/11 17:5615/03/11 17:56

Page 3: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

2525

31 61

4 kW 7,28 16,3kW 1,58 3,63- 4,60 4,49- 4,51 4,41

4 kW 6,22 12,5kW 1,59 3,32- 3,86 3,77

4 kW 7,15 13,1kW 2,20 4,50- 3,24 2,90

4 kW 8,16 17,7kW 2,11 4,93- 3,86 3,60

3,80 3,65

4 kW 6,79 15,2kW 1,93 4,52- 3,51 3,36

4 kW 5,80 11,7kW 1,94 4,14- 2,97 2,82

4 kW 6,76 12,4kW 2,64 5,41- 2,57 2,29

4 kW 5,83 13,3kW 1,91 4,61- 3,05 2,89- 5,44 5,41

4 kW 6,36 14,5kW 2,30 5,35- 2,77 2,72

4 kW 5,44 11,1kW 2,31 4,90- 2,35 2,28

4 kW 6,27 12,0kW 2,95 6,58- 2,15 1,82°C -22 -22°C 60 60I/s 0,36 0,78kPa 62 28kPa 90 90l 200 200W/°K 2703 3186dB(A) 42/38 43/36V/Ph/Hz 230/1/50 400/3/50+N

NEW

technical data

Data referred to the following conditions:

(1) A7/W35 internal exchanger water 30/35°C; external air temperature 7°C D.B./ 6°C W.B.A2/W35 internal exchanger water 30/35°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W35 internal exchanger water 30/35°C; external air temperature -5°C D.B./ -5,4°C W.B.A7/W45 internal exchanger water 40/45°C; external air temperature 7°C D.B./ 6°C W.B.A2/W45 internal exchanger water 40/45°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W45 internal exchanger water 40/45°C; external air temperature -5°C D.B./ -5,4°C W.B.A7/W55 internal exchanger water 45/55°C; external air temperature 7°C D.B./ 6°C W.B.A2/W55 internal exchanger water 45/55°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W55 internal exchanger water 45/55°C; external air temperature -5°C D.B./ -5,4°C W.B.A35/W18 internal exchanger water 23/18°C; external air temperature 35°CA35/W7 internal exchanger water 12/7°C; external air temperature 35°CThe rated heating and cooling capacities refer to 75% of the maximum compressor revolutions. Capacity modulation is comprised between 30% and 100%.Modulation between 75% and 100% only takes place at a temperature of below 0°C.

(2) The total power input is the total power absorbed by the compressors + fans - the power absorbed by the fan to supply the remaining available head to the system + the power absorbed by the auxiliary circuit

(3) EUROVENT COP: coefficient of performance in heating mode. Relationship between heating capacity output and power input according to EUROVENT. The power input is the total power absorbed by the compressor

+ fan + auxiliary circuit + defrost cycles.(4) COP (EN 14511:2008) coefficient of performance in heating mode. Relationship between heating capacity

output and power input according to standard EN 14511:2008. The power input is the total power absorbed by the compressor + fan + auxiliary circuit + defrost cycles + part of the pump to overcome internal pressure drops.

(5) EUROVENT EER calculated as the relationship between the cooling capacity and the total power input.(6) EER (EN 14511:2008) coefficient of performance in cooling mode. Relationship between the cooling

capacity output and the power input according to standard EN 14511:2008. The power input is the total power absorbed by the compressor + auxiliary circuit + part of the pump to overcome internal pressure drops

(7) ESEER coefficient of seasonal performance in cooling mode calculated according to Eurovent. Outlet water 7°C.

(8) Water flow and available head in winter operating conditions A7/W35: water at the internal heat exchanger 30/35°C; outdoor air temperature 7°C D.B. / 6°C W.B.

(9) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m (indoor unit) / 10 m (outdoor unit) from the external surface of the internal unit in open field conditions.

SizesApplication with radiant panels

A7/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)COP (EN 14511:2008) (4)

A2/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A35/W18 (1)Cooling capacityTotal input (2)EER EUROVENT (5)EER (EN 14511:2008) (6)

Application with terminal unitsA7/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A2/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A35/W7 (1)Cooling capacityTotal input (2)EER EUROVENT (5)ESEER EUROVENT (7)

Application with radiatorsA7/W55 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A2/W55 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W55 (1)Heating capacityTotal input (2)COP EUROVENT (3)

Minimum external air temperatureMaximum water temperatureWater flow rate (8)Pump working head (8)Air side available head (8)Domestic hot water storageSolar heat exchanger capacitySound pressure level (indoor/outdoor unit) (9)Power supply

Guida_2011_v26.indd 25Guida_2011_v26.indd 25 15/03/11 17:5615/03/11 17:56

Page 4: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

2626

31 61

mm 600 600mm 800 800mm 2030 2030

4 mm 500 500mm 800 800mm 800 800mm 100 100mm 200 200kg 430 460

31 61

mm 860 1250mm 720 788mm 845 1304mm 800 800mm 300 300mm 300 300mm 800 800kg 58 105

BB1

B2

C

C1

AA1

A2

AA2

A1

C

BB1

B2

MSER-XEE

MSER-XEE OUT

MSER-XEE 31

R-410AAIR

230M(1)

KIR1(2)

-(3)

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

Sizes MSER-XEELength (A)Width (B)Height (C)

(A1)(A2)(B1)(B2)(C1)

Weight in oper.

Sizes MSER-XEE OUT Length (A)Width (B)Height (C)

(A1)(A2)(B1)(B2)

Weight in oper.The above data refer to standard units.

The above data refer to standard units.

dimensions and clearances

accessories

■ Accessories supplied separately.

Key to symbols:

■ 4 Multi-function keypad holder■ 4 Connection flange for underground exhaust air duct■ 4 Secondary hydraulic kit at high temperature not mixed■ 4 Secondary hydraulic kit at low temperature mixed■ 4 Control board second and third secondary pump

Heating-Cooling Air cooled Indoor inst. Refrig. R-410A Herm. Scroll(size 61)

ELFOControl Full InverterDC

functions and features

available configurations

(1) SUPPLY VOLTAGE:4400TN 400/3/50+N (Standard for size 61, not available

for size 31)4230M 230/1/50 (Standard for size 31)

(2) SECONDARY HYDRAULIC KIT4KIR1 1 zone (Standard)4KIR2H 2 zones: both at high temperature4KIR2HL 2 zones: high temperature + low temperature (mixed)4KIR3H 3 zones: all at high temperature4KIR3HLL 3 zones: one at high temperature + two at low temperature

(mixed)4KIR3HHL3 zones: two at high temperature + one at low temperature

(mixed)

(3) AUXILIARY ELECTRIC HEATERS:4- Not required (Standard)4EH246 Modulating auxiliary electric heater from 0 to 6 kW (size 61)4EH04 Modulating auxiliary electric heater from 0 to 4 kW (size 31)

Herm. rotary(size 31)

Guida_2011_v26.indd 26Guida_2011_v26.indd 26 15/03/11 17:5615/03/11 17:56

Page 5: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

GAIA Acqua

WSHR-XEE

Renewable energy packaged heating unit for domestic comfort, designed for direct connection to solar panels. It makes use of the water-cooled heat pump principle, making it suitable for ground water and geothermal systems.

Guida_2011_v26.indd 27Guida_2011_v26.indd 27 15/03/11 17:5615/03/11 17:56

Page 6: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

28

WSHR-XEE 31÷61

GAIA ACQUA

PATENTPENDING

Eurovent EnergyEfficiency Class

Reversible heat pumpWater cooledIndoor installationCapacity from 3,0 to 15,6 kW

GAIA Acqua is the innovative annual cycle heat pump, which generates comfort and uses from 75% to 100% renewable energy, recovering it from the water or ground depending on the system adopted.Its main features are:

4SYSTEM MACHINE - it can be used with radiant panel systems, room terminals and radiators. It includes all the necessary devices to ensure summer and winter air-conditioning as well as the production of domestic hot water. Installation times and costs are drastically reduced because GAIA Acquacontains the pumping groups, the domestic hot water storage tanks and connection to solar panels;

4MAXIMUM SAVINGS - electronic control allows to freely establish temperature, humidity and operating times. Once set, the control automatically manages summer or winter operation, and the production of domestic hot water. Overall energy efficiency is maximized through constant monitoring of building needs and of the temperature of fresh air;

4INVERTER DC TECHNOLOGY - GAIA Acqua provides you with winter heating and summer cooling with the maximum energy efficiency thanks to the DC inverter technology applied to the compressor and the circulators. Thanks to the inverter, the speed of the various devices can be adjusted based on the actual requested energy, allowing further reduction of consumption and a substantial increase in seasonal efficiency;

4 INTEGRATED PRODUCTION OF DOMESTIC HOT WATER - the unit features a 200 liter tank for domestic water that can be heated by solar panels. On days when solar heating is not sufficient or if solar panels have not been installed, the domestic hot water will be heated by the energy contained in the earth or in the water. GAIA Acqua avoids energy wastage thanks to the inverter circulator for the circulation of hot water in the domestic hot water circuit;

4PRIMARY CIRCUIT - it has got a low consumption DC circulator that allows to adjust the water flowrate according to the compressor speed thus maximising the heat exchange regardless the flow variations required by the system.

4SECONDARY CIRCUITS - GAIA Acqua can manage up to three different zones having different temperatures in function of the type of terminal through mixing valves and low consumption DC circulators with an automatic modulation of the waterflow depending on the delta temperature. Between the primary and the secondary circuit an hydraulic separator is built in to separate the unit from the user side in order to assure the best operating conditions of GAIA Acqua.

4SAFE AND ECOLOGICAL - GAIA Acqua does not use gas or other fuels and thus precludes the possibility of leakage of hazardous substances into the environment. It does not produce exhaust gas and does not require a flue pipe. Therefore, it does not require obligatory maintenance such as boiler cleaning and smoke control. It does not release CO2 into the atmosphere.

GROUNDWATER ENERGY RECOVERY GROUND SOURCE ENERGY RECOVERY

Vertical manifolds Horizontal manifolds

Guida_2011_v26.indd 28Guida_2011_v26.indd 28 15/03/11 17:5615/03/11 17:56

Page 7: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

31 61

4 kW 8,40 15,6kW 1,62 3,03- 5,18 5,17- 5,00 5,11

4 kW 6,69 12,4kW 1,57 2,90- 4,26 4,29- 4,14 4,25

4 kW 9,31 17,2kW 1,73 3,04- 5,39 5,66- 5,17 5,89

4 kW 7,81 15,5kW 1,98 3,83- 3,95 4,06

4 kW 5,94 11,5kW 1,85 3,43- 3,21 3,35

4 kW 6,76 12,4kW 1,69 3,07- 4,00 4,04- 6,32 5,34

4 kW 6,98 13,4kW 2,25 3,94- 3,11 3,39

4 kW 5,52 9,90kW 2,16 3,76- 2,56 2,63°C -8 -8°C 60 60I/s 0,40 0,75kPa 60 32I/s 0,53 0,97kPa 40 98l 200 200W/°K 2703 3186dB(A) 42 43V/Ph/Hz 230/1/50 400/3/50+N

29

NEW

technical data

(1) W10/W35 water at the user side heat exchanger 30/35°C; inlet water at the source side heat exchanger 10°CB0/W35 water at the user side heat exchanger 30/35°C; inlet water at the source side heat exchanger 0°C; glycol 30%W10/W45 water at the user side heat exchanger 40/45°C; inlet water at the source side heat exchanger 10°CB0/W45 water at the user side heat exchanger 40/45°C; inlet water at the source side heat exchanger 0°C; glycol 30%W10/W55 water at the user side heat exchanger 45/55°C; inlet water at the source side heat exchanger 10°CB0/W55 water at the user side heat exchanger 45/55°C; inlet water at the source side heat exchanger 0°C; glycol 30%W35/W18 water at the user side heat exchanger 23/18°C; inlet water at the source side heat exchanger 30/35°CW35/W7 water at the user side heat exchanger 12/7°C; inlet water at the source side heat exchanger 30/35°CThe rated heating and cooling capacities of GAIA Acqua 31 refer to 75% of the maximum compressor revolutions. The rated heating and cooling capacities of GAIA Acqua 61 refer to 60% of the maximum compressor revolutions. Capacity modulation is comprised between 30% and 100%.The modulation to 100%% only takes place at a temperature of below 0°C.

(2) Heating capacity measured at the temperature conditions and source side water flow in cooling mode established by EUROVENT

(3) Total input is obtained from the compressor input + auxiliary circuit input(4) EUROVENT COP: coefficient of performance in heating mode. Relationship between heating capacity output

and power input according to EUROVENT. The power input is the total power absorbed by the compressor + fan + auxiliary circuit

(5) COP (EN 14511:2008) coefficient of performance in heating mode. Relationship between the heating capacity output and the power input according to standard EN 14511:2008. The power input is the total power absorbed by the compressor + auxiliary circuit + part of the pump to overcome internal pressure drops

(6) The values given refer to performances in heating mode at rated conditions(7) EUROVENT EER: coefficient of performance in cooling mode. Relationship between cooling capacity output

and power input according to EUROVENT. The power input is the total power absorbed by the compressor + auxiliary circuit

(8) EER (EN 14511:2008) coefficient of performance in cooling mode. Relationship between the cooling capacity output and the power input according to standard EN 14511:2008. The power input is the total power absorbed by the compressor + auxiliary circuit + part of the pump to overcome internal pressure drops

(9) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1m from the external surface of the unit in open field conditions.

SizesApplication with radiant panels

W10/W35 (1)Heating capacity (2)Total input (3)COP EUROVENT (4)COP (EN 14511:2008) (5)B0/W35 (1)Heating capacityTotal input (3)COP EUROVENT (4)COP (EN 14511:2008) (5)W35/W18 (1)Cooling capacity Total input (3)EER EUROVENT (7)EER (EN 14511:2008) (8)

Application with terminal unitsW10/W45 (1)Heating capacity (2)Total input (3)COP EUROVENT (4)B0/W45 (1)Heating capacity Total input (3)COP EUROVENT (4)W35/W7 (1)Cooling capacity Total input (3)EER EUROVENT (7)ESEER EUROVENT

Application with radiatorsW10/W55 (1)Heating capacity (2)Total input (3)COP EUROVENT (4)B0/W55 (1)Heating capacity Total input (2)COP EUROVENT (4)

Minimum water temperatureMaximum water temperatureWater flow rate - user side (6)Pump working head - user side (6)Water flow rate - source side (6)Pump working head - source side (6)Domestic hot water storageSolar heat exchanger capacitySound pressure level (9)Power supply

Data referred to the following conditions:

Guida_2011_v26.indd 29Guida_2011_v26.indd 29 15/03/11 17:5715/03/11 17:57

Page 8: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

30

31 61mm 600 600mm 800 800mm 2030 2030

4 mm 500 500mm 800 800mm 800 800mm 100 100mm 200 200kg 450 480

BB1

C

C1

AA1

A2

B2

WSHR-XEE 61

R-410A

400TN(1)

-(2)

KIR1(3)

HYGS(4)

-(5)

-(6)

H2O

-(7)

dimensions and clearances

accessories

■ Accessories supplied separately.

Key to symbols:

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

Sizes Length (A)Width (B)Height (C)

(A1)(A2)(B1)(B2)(C1)

Weight in oper.The above data refer to standard units.

■ 4 Multi-function keypad holder■ 4 Secondary hydraulic kit at high temperature not mixed■ 4 Secondary hydraulic kit at low temperature mixed■ 4 Control board second and third secondary pump

Heating-Cooling Indoor inst. Refrig. R-410A

functions and features

available configurations

Water cooled

(1) SUPPLY VOLTAGE:4400TN 400/3/50+N (Standard for size 61, not available

for size 31)4230M 230/1/50 (Standard for size 31)

(2) LOW TEMPERATURE:4- Not required (Standard)4BS Low water temperature source side

Prearrangement for use of source side water, with temperature conditions lower than +5°C.

(3) SECONDARY HYDRAULIC KIT4KIR1 1 zone (Standard)4KIR2H 2 zones: both at high temperature4KIR2HL 2 zones: high temperature + low temperature (mixed)4KIR3H 3 zones: all at high temperature4KIR3HLL 3 zones: one at high temperature + two at low temperature

(mixed)4KIR3HHL3 zones: two at high temperature + one at low temperature

(mixed)

(4) HYDRONIC GROUP USER SIDE:4HYGS Hydronic group user side (Standard)4- Not required

(5) WATER SIDE MOTORISED SHUT-OFF VALVES:4- Not required (Standard)4IVMS Source side modulating valve

(6) NATURAL-COOLING:4- Not required (Standard)4NC Natural-Cooling

(7) AUXILIARY ELECTRIC HEATERS:4- Not required (Standard)4EH246 Modulating auxiliary electric heater from 0 to 6 kW (size 61)4EH04 Modulating auxiliary electric heater from 0 to 4 kW (size 31

Herm. Scroll(size 61)

ELFOControl Full InverterDC

Herm. rotary(size 31)

Guida_2011_v26.indd 30Guida_2011_v26.indd 30 15/03/11 17:5715/03/11 17:57

Page 9: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFOFresh²

CPAN-U

Air renewal unit, full fresh air, which, as it renews and purifies the air, also recovers the energy present in the exhaust air flow, multiplying it thanks to the heat pump technology and supplying it to the serviced rooms. It reduces the fresh air load and supplies additional capacity, helping to maintain comfortable conditions.

Guida_2011_v26.indd 31Guida_2011_v26.indd 31 15/03/11 17:5715/03/11 17:57

Page 10: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

32

CPAN-U 200÷650

ELFOFRESH2

4

PATENTPENDING

ELFOFresh2 is the innovative renewal and purification unit for consistently clean air, at the right temperature and the right level of humidity, for total wellbeing in the home.At the same time, ELFOFresh2 also recovers the energy contained in the exhaust air flow, multiplying it thanks to the heat pump technology and supplying it to the serviced rooms. In this way it reduces the fresh air load and supplies additional capacity, helping to maintain comfortable conditions.

The main characteristics are:

4 High efficiency summer and winter active thermodynamic heat recovery4 80% satisfaction of the building’s heating requirement4 Reduced consumption and simplified system4 Electronic filtration for effective protection against even the most insidious

pollutants (i.e. PM10, bacteria, pollen)4 Summer dehumidification, ideal for combination with radiant cooling4 Free-Cooling

Air renewal and purification unit, full fresh airWith return/exhaust and thermodynamic heat recovery

Reversible heat pumpIndoor installationAir flow rate from 200 to 650 m3/h

ELFOFresh2 uses an active thermodynamic heat recovery unit, in which the inlet and outlet air flows are separated completely by a steel wall. The heat transfer takes place through the cooling circuit, without the risk of contamination between the two air flows.In traditional enthalpic rotary recovery units, on the other hand, vapour is exchanged between the indoor discharge air flow and the outdoor fresh air flow, leading to substantial possibilities of contamination.

ELFOFresh2 rejects the stale air and introduces purified and climate controlled outdoor air. The harmful elements and smells present in the outdoor air or those produced inside the home are eliminated by the efficient filtration system. The electrostatic filter is easy to extract and can be fully restored through washing.

AIR RENEWAL, PURIFICATION AND ENERGY PRODUCTION ELIMINATES POLLUTANTS

Guida_2011_v26.indd 32Guida_2011_v26.indd 32 15/03/11 17:5715/03/11 17:57

Page 11: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

33

200 300 500 650

4 kW 1,82 2,31 3,60 5,02kW 0,42 0,57 0,79 1,21- 4,33 4,05 4,56 4,15

4 kW 1,87 2,36 3,75 5,12kW 0,34 0,41 0,63 0,94- 5,50 5,75 5,95 5,45

4 kW 1,56 2,10 2,96 3,96kW 0,52 0,67 0,98 1,40- 3,00 3,13 3,02 2,83

4 kW 1,57 2,02 2,86 3,86kW 0,55 0,7 1,04 1,45- 2,85 2,89 2,75 2,66l/s 54 85 136 181W 40 52 90 150Pa 120 120 120 120°C -15 -15 -15 -15°C 40 (38) 40 (38) 40 (38) 40 (38)dB(A) 39 41 44 46V/Ph/Hz 230/1/50

CPAN-U 200

FCR-410AAIR

FAS(2)

CHIDP1(3)

-(4)

-(5)

-(1)

Data referred to the following conditions:

technical data

All the data provided meets standard EN 14511:2008 and refers to an available head of 50 Pa. When in cooling mode it is possible that the unit is operating at a reduced flow to ensure a specific humidity for the air introduced into the environment in keeping with the setpoint.(1) A7 External air temperature 7°C D.B./ 6°C W.B., Exhaust air temperature 20°C D.B./ 15°C W.B.

A-5 External air temperature -5°C D.B./ -5.4°C W.B., Exhaust air temperature 20°C D.B./ 15°C W.B.A30 External air temperature 30°C D.B./ 22°C W.B., Exhaust air temperature 27°C D.B./ 19°C W.B.A35 External air temperature 35°C D.B./ 24°C W.B., Exhaust air temperature 27°C D.B./ 19°C W.B.

(2) Capacity referring to operation in heating mode in conditions A -5. Important: the COP and EER already include the fan power input. This information is provided for the purposes of energy certification programmes. If this information is taken into account, the COP used must be the COP without the fan power input.

(3) In places where the outdoor air temperature falls below -5°C for a large number of hours per year, we recommend using the EHPCX accessory - ducted heater kit

(4) With RH = 40%; in parentheses, the limit at which a specific humidity of 10.5 g/kg is guaranteed for the air introduced into the environment, with a 50% reduction in the maximum flow

(5) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions.

SizesA7 (1)Heating capacityTotal inputCOPA-5 (1)Heating capacityTotal inputCOPA30 (1)Cooling capacityTotal inputEERA35 (1)Cooling capacityTotal inputEER

Nominal air flow rateFan power input (2)Maximum available static pressureOperating limit in heating mode (3)Operating limit in cooling mode (4)Sound pressure level (5)Power supply

Heating-Cooling Air cooled Indoor inst. Uncased horizontal inst. Refrig. R-410A Herm. Rotary ELFOControl Free-Cooling Active Thermodynamic Heat Recovery

(1) OPERATION:4- Operation in cooling and heating (Standard) 4OHO Operation in heating-only

(2) FILTRATION:4FAS Pleated filter G3 (Standard)4FES Electronic filter

(3) CONTROL SYSTEMS:4CHIDP1 HID-P1 thermostat (Standard) 4PRELF ELFOSystem enabled with RS485 Modbus serial

port4HIDRS HID-P1 thermostat and RS485 Modbus serial port

(4) DIFFERENTIAL PRESSURE SWITCH FOR FILTERS:4- Not required (Standard) 4PSAE Fresh air filter differential pressure switch

(5) CONDENSATE DRAIN PUMP:4- Not required (Standard)4CDP Condensate drain pump

functions and features

available configurations

Guida_2011_v26.indd 33Guida_2011_v26.indd 33 15/03/11 17:5715/03/11 17:57

Page 12: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

B

B1

B2

A

A2

C

A1D

(*)

(*)

34

200 300 500 650803 803 1038 1038120 120 120 120704 704 792 792364 364 423 423

4 580 580 580 580300 300 300 300300 300 300 30070 75 95 100

dimensions and clearances

accessories

■ Accessories supplied separately.

Key to symbols:

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

Sizes Length (A) mmLength (B) mmWidth (B) mmHeight (C) mm

(A1) mm(B1) mm(B2) mm

Weight in oper. kg

Ambient air return

Ambient air supply

Air intake

Air exhaust

■ 4 Ducted 1.5/3 kW electric heaters ■ 4 Immerse electrode steam humidifier■ 4 Electronic filter■ 4 Discharge air filter

Guida_2011_v26.indd 34Guida_2011_v26.indd 34 15/03/11 17:5715/03/11 17:57

Page 13: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFORoom2

Room terminal units specifically designed to distribute hot and cold air in the home.They use direct current technology, guaranteeing the highest standard of comfort, quiet operation and low energy consumption.

Guida_2011_v26.indd 35Guida_2011_v26.indd 35 15/03/11 17:5715/03/11 17:57

Page 14: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

36

ELFOROOM2 3÷15

ELFOROOM2

ELFOROOM2 3

H2O

230M(2)

VER(1)

NEW

ELFOROOM2

OUTVT

ELFOROOM2

INVOTELFOROOM2

INVOTELFOROOM2

OUTVOT

ELFORoom2 is a clever mix of technology and design that provides a high level of comfort, better than any other diffusion system (radiators, fancoil, radiant panels).It is the ideal solution for the refurbishment: ELFORoom2 can be installed to replace radiators and, thanks to the low operating temperatures, allows a big saving on the life cycle costs and a better air quality thanks to the continuous filtration. Beside heating the room, ELFORoom2 allows to cool and dehumidify the room in summer remembering to insulate the piping and allowing an adequate drain of the condensation. It is also a good option for the new built houses: because of the low heating loads required ELFORoom2 allows lower first costs compared to a radiant system and also to quickly reach the required temperature thanks to the lower thermal inertia.ELFORoom2 allows then to have:

4ALWAYS WELL BLENDED TEMPERATURE - It eliminates temperature stratification of the air thanks to the continuous fan speed modulation

4REDUCED CONSUMPTION - the unique motor allows big savings on consumptions

4QUIET OPERATION - the continuous fan operation allows to always operate at the lowest speed reducing the noise

4CLEAN AIR WHILE AIRCONDITIONING - continuously mixing the air allows a constant filtration thus a better air quality

4SUITABLE FOR ALL THE INSTALLATIONS - available in horizontal and vertical versions both cased and uncased.

Water terminal unitVertical or horizontal indoor installation, cased or uncasedCapacity from 0,8 to 3,3 kW

Heating-Cooling Indoor inst. Cased vertical inst. Refrig. Water ELFOControl

(1) VERSION 4OUTVT Vertical cased with onboard thermostat (standard)

4OUTVOT Vertical/Horizontal cased without thermostat (to be connected with HID wall thermostat)

4INVOT Vertical/Horizontal uncased without thermostat (to be connected with HID wall thermostat)

(2) SUPPLY VOLTAGE:4230M 230/1/50 (Standard)

functions and features

available configurations

Uncased horizontal inst.Uncased vertical inst. Cased horizontal inst.

Guida_2011_v26.indd 36Guida_2011_v26.indd 36 15/03/11 17:5815/03/11 17:58

Page 15: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

37

3 5 11 154 kW 0,83 1,76 2,63 3,33

kW 0,62 1,27 1,96 2,65kW 0,017 0,038 0,041 0,042

4 kW 0,94 1,98 2,72 3,46l/s 45 89 128 160- TGZdB(A) 39 40 39 39V/Ph/Hz 230/1/50

3 5 11 15

737 937 1137 1337129 129 129 129579 579 579 579

4 20 20 20 2020 20 20 20400 400 400 40080 80 80 80140 140 140 14017 20 23 26

3 5 11 15

527 727 927 1127126 126 126 126576 576 576 576

4 63 63 63 63100 100 100 10020 20 20 20

360-648 360-648 360-648 360-6489 12 15 18

A

A1

A2

C

BB1

C1

C2

A

A2

A1B

B1

C

C1

C2

B

CC2

A

A2

A1

C1

B

A

A2

A1

C2

C1

C

ELFOROOm2

OUTVOTELFOROOm2

OUTVT- OUTVOT

ELFOROOm2

INVOT

■ Accessories supplied separately.

Key to symbols:

SizesCooling capacity (1)Sensible cooling capacity (1)Total input (1)Heating capacity (2)

Air flow rate (3)Fan type (4)Sound pressure level (5)Power supply

(1) Ambient air at 27°C/19.5 W.B.; water at inlet 7°C and outlet 12°C(2) Ambient air at 20°C D.B.; water at inlet 45°C(3) Air flow rate at maximum speed

(4) TGZ = cross-flow fan(5) The values have been measured at 1 m from the external surface of the unit, in a closed ambient of 100m3

and a reverberation time of 0.5 sec.

Data referred to the following conditions:

Sizes ELFORoom2 OUTVT - OUTVOTLength (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(C1) mm(C2) mm

Weight in oper. kg

The above data refer to standard units with 2-pipe systemPlease contact our sales department for the dimensions of the 4-pipes version

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

accessories

dimensions and clearances

technical data

■ 4 KCCDX - Motor connection Kit for units with connections on th right side ■ 4 KV3BX - 3 way valve Kit with electrothermal head and balancing■ 4 KPDX - Plinth kit■ 4 BACKVX - Back aesthetic panel■ 4 FXPPX - Floor fixing bracket kit■ 4 PMSTX - Telescopic upper supply plenum kit■ 4 KASPX - Return plenum kit■ 4 PR90MX - supply plenum kit at 90°■ 4 GMX - Kit supply grille wall mounted■ 4 GRA1X - Kit suction grille wall mounted■ 4 CSFIX - Formwork for uncased installation

■ 4 PCIX - Uncased closure panel■ 4 HID-T2X - HID-T2 Thermostat (external, only temperature)■ 4 HID-TI2X - HID-Ti2 Thermostat (recessed, only temperature)■ 4 HID-T3X - HID-T3 Thermostat (external, temperature and humidity)CONFIGURATIONS BY REQUESTELFORoom2 configurations available only on requests and not kept on stock 4 4-pipe exchange coil4 Panel colours4 KIT germicidal lamp4 Kit fan control with autotransformer4 Simplified built-in electronic control kit

Sizes ELFORoom2 INVOTLength (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(C1) mm(C2) (1) mm

Weight in oper. kg

The above data refer to standard units with 2-pipe systemPlease contact our sales department for the dimensions of the 4-pipes version(1) min and max value for the correct unit operation (with the PR90MX option the min is 150)

Guida_2011_v26.indd 37Guida_2011_v26.indd 37 21/03/11 16:5021/03/11 16:50

Page 16: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

3838

Guida_2011_v26.indd 38 15/03/11 17:58

Page 17: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFOControl HOME

Control unit for domestic heating, cooling, hot water and air quality systems. ELFOControl HOME is the “brain” behind the system, communicating with all the installed components.

Guida_2011_v26.indd 39Guida_2011_v26.indd 39 15/03/11 17:5815/03/11 17:58

Page 18: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

40

ELFOCONTROL HOME

functions and features

ELFOControl HOME is the "brain" of the ELFOSystem system.It is connected with all the installed components, checking the working conditions of each device and letting you adjust operation of the entire system from a single control center, where you can set all of the desired parameters for better comfort.Adjustment of values is simple and functional and the aid of pre-defined operating scenarios allows the user to select the one that best suits his needs from a range of comfort profiles.

Control unit for autonomous residential systemsTouch screen displayControl over the entire systemOptimization of energyCustomized managementTime programming

TURN IT ON AND RELAXELFOControl manages all the elements of the system. it automatically changes over from summer to winter operation and monitors the entire system with no user action required.The touch screen of ELFOControl makes any operation easier: controls and settings are easy to use and are immediately understandable.

CONTROL OF ALL DEVICES FROM A SINGLE POSITIONELFOControl manages any type of system, such as systems with ELFORoom room terminals, with radiators, with radiant panels, or mixed systems. It also extends its control to other system components, such as zone valves and pumps. ELFOControl coordinates all of the elements present, ensuring high quality systems with the utmost energy efficiency.

OPTIMIZATION OF ENERGYELFOControl activates the most energy-efficient devices to attain the required comfort based on measured conditions. For example, when a limited quantity of energy is required, it chooses to use ELFOFresh² for its excellent performance in these circumstances, while it activates ELFOEnergy when the conditions make this solution more convenient and efficient.

CUSTOMIZED MANAGEMENTThe user has the utmost freedom to define values of temperature, humidity, and hours of operation for each room in the house. Various rooms may be grouped together as zones, setting the same comfort values or hours of operation.Ample flexibility in the management of rooms of the home, which can be organized into 10 separate zones and configured independently. Assignment to each zone of a name defined by the user (e.g.: “Kitchen”).

MAXIMUM FLEXIBILITYELFOControl keeps temperature, humidity and other set values constant in the keeping with the time settings for each zone; however, on the basis of individual requirements, it can also override individual thermostats. Overrides are particularly useful, for example, when you want to set a different temperature level in an individual room (i.e. +2°C for the “Sitting Room” in the “Living Area”).

Guida_2011_v26.indd 40Guida_2011_v26.indd 40 15/03/11 17:5815/03/11 17:58

Page 19: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

41

2237865176

technical data

dimensions and clearances

ELFOControlLength (A) mmWidth (B) mmWidth (D) mmHeight (C) mm

Display Touch Screen - dimensions 5,7” - color Control capacity 10 climatic Zones—32 total elements manageableConnectivity 1 RS485 serial port (master)Network characteristics Cable for RS485 serial lines (example BELDEN 3105A or similar)Power 25 VADegree of protection IP40Power supply 24 VAC 50 Hz—24 VDC

Installation Functions Dimensions

TR24X: Supply transformer 230/1/50 - 24Vac Allows transformation from 230/1/50 to 24 VAC to power ELFOControl 70 x 85 x 65 mm4 Modules DIN

CIECX: Flush-mounted pre-installation box Allows recessed installation of ELFOControl 216 x 168 x 73 mm

CBSX: shielded cable for bus RS485 Allows connection of all devices that make of the system 50 meter skein

Radiant panels - Terminal units

KGPRX: Mixing group control module It is the electronic module that manages a mixing group not furnished by Clivet

210 x 155 x 80 mm

CMZRX: Radiant zones module Controls up to 6 cut-off valves that feed radiant panels, radiators, or heating system furnishing

157 x 90 x 60 mm 9 Modules DIN

CMRSX: Single zone module Controls 1 cut-off valve which feeds radiant panels, radiators or heating system furnishing

105 x 90 x 60 mm6 Modules DIN

System components

MIOX: Input/Output ModuleControl of substitution generator (boiler) Control of zone valves or transfer pumpsControl of remote consent

70 x 85 x 65 mm4 Modules DIN

Domestic hot water

CACSX: Domestic hot water kit control This is the electronic module that lets you control a storage tank not provided by Clivet

290 x 410 x 140 mm

KBQRE3X: 300 litres domestic hot water kit This is the kit complete with electronic module, storage tank of 300 litres, three-way valve D.600 x 1680 mm

KBQRE5X: 500 litres domestic hot water kit This is the kit complete with electronic module, storage tank of 500 litres, three-way valve. D.760 x 1690 mm

Thermostats

HID-T2X: HID-T2 local electronic room control Temperature-only thermostat - wall-mounted 184 X 82 X 27 mm

HID-T3X: HID-T3 local electronic room control Temperature and humidity thermostat - wall-mounted 184 X 82 X 27 mm

HID-TI2X: HID-TI2 local electronic room control Temperature-only thermostat - recessed 65 x 45 x 54 mm

system management elements

Guida_2011_v26.indd 41Guida_2011_v26.indd 41 15/03/11 17:5815/03/11 17:58

Page 20: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

42

Guida_2011_v26.indd 42 15/03/11 17:58

Page 21: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFOEnergy Horus

WSAR-MT-E

Heat pump suitable for systems with radiant panels and water terminal units, with a design that guarantees quiet operation.

Guida_2011_v26.indd 43Guida_2011_v26.indd 43 15/03/11 17:5815/03/11 17:58

Page 22: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

44

WSAR-MT-E 21÷81

WSAR-MT-E 21 400TN(1)

S(2)

-(3)

-(4)

-(5)

-(6)

ELFOENERGY HORUS

HIDH1S(7)

-(8)

-(9)

CCS(10)

4

-(11)

KCUX(12)

The ELFOEnergy HORUS WSAR-MT-E, heat pump, ideal for the residential sector and optimized for heating, grants maximum energetic efficiency in the many different conditions of use: water production for radiant panels, terminals and for domestic hot water.

4An appliance that is ideal for individual homes, o be installed in the garden, where its elegant design hides all the technical elements from view. A structure designed to protect the coil from wind and snow which allows to direct the flow of air to the ground and not towards the window of the next door neighbour.

4Production domestic hot water up to 60°C4Operation with air up to –15°C4Reliability and easy maintenance: feasily removable side panels4Refrig. R407C: in order to combine reduced dimensions of the unit, high

efficiency and wider operating limits4Axial fan also available in high energetic efficiency version4Low noise: soundproof headphones to bring down noise emission;4Innovative multifunction remote keyboard with machine interface functions,

ambient time thermostat and optional system supervisor4Satin-finished AISI 304 stainless steel base with adjustable feet4Axial fan also available in high energetic efficiency version4Modular integral electric heater, available in 2-4-6 kW4he ductable version is available, with high efficiency axial fan, for indoor

installation.

available configurations

Water chillerReversible heat pump

Air cooledOutdoor/indoor installationCapacity from 6,13 to 22,9 kW

(1) SUPPLY VOLTAGE:4400TN 400/3/50+N4230M 230/1/50 (only for sizes 21÷41)

(2) VERSION:4S Basic (Standard)4SUP Full Optional

Hydronic kit including: circulator, 3bar water safety valve, heating element 2/4/6 kW, high-pressure valve (bypass differential) (only for sizes 21÷51), 18 litres plumbing circuit expansion tank (only for sizes 61-81)

(3) ENERGY EFFICIENCY:4- Not required (Standard)4HEOH High energy efficiency in heating mode only (only

available with option SUP)

(4) HIGH EFFICIENCY FAN:4- Not required (Standard)4VEC High efficiency fan

(5) HIGH EFFICIENCY HYDRONIC GROUP:4- Not required (Standard)4GCEC High efficiency hydronic group available only with

SUP option

(6) ADDITIONAL HEATING ELEMENT (already included in version SUP):4- Not required (Standard)

4EH246 Modular integration electric heater 2-4 and 6 kW

(7) MULTI-FUNCTION KEYPAD:4HIDH1S Standard multifunction keypad (up to 50m) (Standard)4HIDH1M System multifunction keypad (BMS, system accessories, up to

1km)

(8) SOFT STARTER:4- Not required (Standard)4SFSTR4N Device for inrush current reduction for 400/3/50+N4SFSTR1 Device for inrush current reduction for 230/1/50

(9) PHASE MONITOR:4- Not required (Standard)4PM Phase monitor (with option 400TN only)

(10) CONDENSER COIL:4CCS Standard condenser coil

4CCCA Condenser coil in copper/aluminium with acrylic coating4CCCA1 Condenser coil in copper/aluminium with Energy Guard

DCC Aluminium treatment4CCCC Condenser coil in copper/copper

(11) WATER CIRCUIT:4- Not required (Standard)43DHW 3-way valve for sanitary hot water onboard

(12) UNIT INSTALLATION:4KCUX Metallic caps for outdoor installation kit4CAN Ductable with high efficiency fans

Multi-function remote keypad

Guida_2011_v26.indd 44Guida_2011_v26.indd 44 15/03/11 17:5815/03/11 17:58

Page 23: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

45

R-407CAIR

21 25 31 41 51 61 81

4 kW 6,13 8,16 10,0 11,2 14,0 17,7 22,9kW 1,57 2,05 2,51 2,87 3,55 4,42 5,87- 3,95 4,03 4,03 3,96 4,00 4,06 3,96- 3,91 3,98 3,98 3,90 3,94 4,01 3,90- 4,10 4,12 4,10 4,16 4,11 4,14 4,10

4 kW 4,81 6,49 7,83 8,80 11,1 13,9 18,1kW 1,49 1,92 2,35 2,72 3,33 4,11 5,48- 3,24 3,38 3,33 3,24 3,34 3,38 3,31

4 kW 4,35 5,86 7,01 7,96 9,90 12,5 16,2kW 1,46 1,86 2,27 2,63 3,21 3,96 5,25- 2,98 3,15 3,09 3,03 3,08 3,16 3,09

4 kW 6,44 8,50 10,7 11,9 14,5 18,1 22,4kW 2,26 2,99 3,81 4,46 5,61 6,26 8,07- 2,88 2,87 2,83 2,68 2,61 2,92 2,81

4 kW 6,06 7,95 9,70 11,0 13,4 17,1 22,1kW 1,86 2,43 2,98 3,54 4,29 5,23 6,65- 3,26 3,27 3,25 3,11 3,12 3,27 3,32

4 kW 5,20 6,90 8,35 6,93 11,6 14,7 19,1kW 1,79 2,33 2,85 3,41 4,12 4,98 6,33- 2,91 2,96 2,93 2,03 2,82 2,95 3,02

4 kW 4,32 5,73 6,95 8,13 9,76 12,2 15,7kW 1,72 2,21 2,71 3,26 3,91 4,71 5,96- 2,51 2,59 2,56 2,49 2,50 2,59 2,63

4 kW 4,68 6,25 8,07 9,03 10,7 13,4 16,4kW 1,99 2,64 3,31 3,99 4,92 5,40 6,98- 2,35 2,37 2,44 2,26 2,17 2,48 2,35- 2,62 2,62 2,71 2,57 2,46 2,74 2,51°C -15 -15 -15 -15 -15 -15 -15°C 60 60 60 60 60 60 60I/s 0,29 0,39 0,48 0,54 0,67 0,85 1,09kPa 56 47 59 56 28 114 101dB(A) 31 33 35 36 37 43 44V/Ph/Hz 400/3/50+N

Heating-Cooling Air cooled Outdoor inst. Refrig. R-407C Herm. Scroll ELFOControl Ice protectionsystem

Vary Flow

functions and features

Indoor inst.

technical data

Data referred to the following conditions:

(1) A7/W35 internal exchanger water 30/35°C; external air temperature 7°C D.B./ 6°C W.B.A2/W35 internal exchanger water 30/35°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W35 internal exchanger water 30/35°C; external air temperature -5°C D.B./ -5,4°C W.B.A7/W45 internal exchanger water 40/45°C; external air temperature 7°C D.B./ 6°C W.B.A2/W45 internal exchanger water 40/45°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W45 internal exchanger water 40/45°C; external air temperature -5°C D.B./ -5,4°C W.B.A35/W18 internal exchanger water 23/18°C; external air temperature 35°CA35/W7 internal exchanger water 12/7°C; external air temperature 35°C

(2) The total power input is the total power absorbed by the compressors + fans - the power absorbed by the fan to supply the remaining available static pressure to the system + the power absorbed by the auxiliary circuit

(3) EUROVENT COP: coefficient of performance in heating mode. Relationship between heating capacity output and power input according to EUROVENT. The power input is the total power absorbed by the compressor + fan + auxiliary circuit + defrost cycles.

(4) COP (EN 14511:2008) coefficient of performance in heating mode. Relationship between heating capacity

output and power input according to standard EN 14511:2008. The power input is the total power absorbed by the compressor + fan + auxiliary circuit + defrost cycles + part of the pump to overcome internal pressure drops.

(5) The values refer to the unit with option HEOH and SUP (6) EUROVENT EER calculated as the relationship between the cooling capacity and the total power input.(7) ESEER coefficient of seasonal performance in cooling mode calculated according to Eurovent. Outlet water

7°C.(8) Water flow and available static pressure in winter operating conditions A7/W35: water at the internal heat

exchanger 30/35°C; outdoor air temperature 7°C D.B. / 6°C W.B.(9) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 10

m from the external surface of the unit in open field conditions.

SizesApplication with radiant panels

A7/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)COP (EN 14511:2008) (4)COP (EN 14511:2008) (4),(5)

A2/W35 (1)Heating capacityTotal input (2)COP (EN 14511:2008) (4)

A-5/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A35/W18 (1)Cooling capacityTotal input (2)EER EUROVENT (6)

Application with terminal unitsA7/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A2/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A35/W7 (1)Cooling capacityTotal input (2)EER EUROVENT (6)ESEER (7)

Minimum external air temperatureMaximum water temperatureWater flow rate (8)Pump working head (8)Sound pressure level (9)Power supply

Guida_2011_v26.indd 45Guida_2011_v26.indd 45 15/03/11 17:5815/03/11 17:58

Page 24: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

46

21 25 31 41 51 61 811420 1420 1420 1420 1420 1835 1835600 600 600 600 600 775 775800 800 800 800 800 1250 12501485 1485 1485 1485 1485 1770 1770

4 2000 2000 2000 2000 2000 2000 20002000 2000 2000 2000 2000 2000 20001000 1000 1000 1000 1000 1000 10001000 1000 1000 1000 1000 1000 1000100 100 100 100 100 100 100500 500 500 500 500 500 500216 221 226 231 251 305 365191 196 201 206 226 275 335

B1D

D2

C

D1B

B2

A

DD4

C

D3B

B1

B2

accessories

SizesLength (A) mmLength (D) mmWidth (B) mmHeight (C) mm

(D1) mm(D2) mm(D3) mm(D4) mm(B1) mm(B2) mm

Weight in oper. (1) kgWeight in oper. (2) kg

dimensions and clearances

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(1) Standard Unit(2) Ductable Unit

■ 4 Set point compensation with according to outdoor enthalpy ■ 4 3 ways-valve

■ Accessories supplied separately.

Key to symbols:

SYSTEM ACCESSORIES■ 4 300 litres domestic hot water kit■ 4 500 litres domestic hot water kit■ 4 Domestic hot water kit control■ 4 100 litres hydraulic breaker■ 4 Mixing group control module■ 4 Boiler control kit

Ductable unit

Standard unit

Guida_2011_v26.indd 46Guida_2011_v26.indd 46 15/03/11 17:5815/03/11 17:58

Page 25: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFOEnergy Horus+

WSAR-HT-E

Heat pump, optimised for heating, suitable for traditional systems with radiators, and guaranteeing maximum efficiency.

Guida_2011_v26.indd 47Guida_2011_v26.indd 47 15/03/11 17:5815/03/11 17:58

Page 26: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

48

WSAR-HT-E 31÷81

ELFOENERGY HORUS +4

WSAR-HT-E 31 400TN(1)

S(2)

-(3)

-(4)

-(5)

-(6)

HIDH1S(7)

-(8)

-(9)

CCS(10)

-(11)

KCUX(12)

The ELFOEnergy HORUS+ WSAR-HT-E, heat pump, ideal for the residential sector and optimized for heating, grants maximum energetic efficiency in the many different conditions of use: water production for radiant panels, terminals and for domestic hot water.

4An appliance that is ideal for individual homes, to be installed in the garden, where its elegant design hides all the technical elements from view. A structure designed to protect the coil from wind and snow that allows to direct the flow of air to the ground and not towards the window of the next door neighbour;

4Production domestic hot water up to 62°C;4Operation with air up to –17°C;4Reliability and easy maintenance: easily removable side panels;4Refrig. R407C: in order to combine reduced dimensions of the unit, high

efficiency and wider functioning limits;4Axial fan also available in high energetic efficiency version;4Low noise: soundproof headphones to bring down noise emission;4Innovative multifunction remote keyboard with machine interface functions,

ambient time thermostat and optional system supervisor;4Satin-finished AISI 304 stainless steel base with adjustable feet;4Axial fan also available in high energetic efficiency version;4Modular integral electric heater, available in 2-4-6 kW;4The ductable version is available, with high efficiency axial fan, for indoor

installation.

available configurations

Water chillerReversible heat pump

Air cooledOutdoor/indoor installationCapacity from 9,11 to 24,4 kW

(1) SUPPLY VOLTAGE:4400TN 400/3/50+N4230M 230/1/50 (only for size 41)

(2) VERSION:4S Basic (Standard)4SUP Full Optional

Hydronic kit including: circulator, 3bar water safety valve, heating element 2/4/6 kW, high-pressure valve (bypass differential) (only for sizes 31÷41), 18 litres plumbing circuit expansion tank (only for sizes 61-81)

(3) ENERGY EFFICIENCY:4- Not required (Standard)4HEOH High energy efficiency in heating mode only (only

available with option SUP)

(4) HIGH EFFICIENCY FAN:4- Not required (Standard)4VEC High efficiency fan

(5) HIGH EFFICIENCY HYDRONIC GROUP:4- Not required (Standard)4GCEC High efficiency hydronic group available only with

SUP option

(6) ADDITIONAL HEATING ELEMENT (already included in version SUP):4- Not required (Standard)

4EH246 Modular integration electric heater 2-4 and 6 kW

(7) MULTI-FUNCTION KEYPAD:4HIDH1S Standard multifunction keypad (up to 50m) (Standard)4HIDH1M System multifunction keypad (BMS, system accessories, up to

1km)

(8) SOFT STARTER:4- Not required (Standard)4SFSTR4N Device for inrush current reduction for 400/3/50+N4SFSTR1 Device for inrush current reduction for 230/1/50

(9) PHASE MONITOR:4- Not required (Standard)4PM Phase monitor (with option 400TN only)

(10) CONDENSER COIL:4CCS Standard condenser coil

4CCCA Condenser coil in copper/aluminium with acrylic coating4CCCA1 Condenser coil in copper/aluminium with Energy Guard

DCC Aluminium treatment4CCCC Condenser coil in copper/copper

(11) WATER CIRCUIT:4- Not required (Standard)43DHW 3-way valve for sanitary hot water onboard

(12) UNIT INSTALLATION:4KCUX Metallic caps for outdoor installation kit4CAN Ductable with high efficiency fans

Multi-function remote keypad

Guida_2011_v26.indd 48Guida_2011_v26.indd 48 15/03/11 17:5815/03/11 17:58

Page 27: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

49

R-407CAIR

31 41 61 81

4 kW 9,11 12,3 19,2 24,4kW 2,46 3,27 4,88 6,13- 3,73 4,12 3,98 4,06- 3,70 4,06 3,94 3,98- 4,10 4,18 4,16 4,12

4 kW 7,37 10,9 15,5 19,6kW 2,30 3,15 4,62 5,84- 3,20 3,45 3,36 3,36

4 kW 6,07 8,99 12,9 16,1kW 2,21 3,13 4,56 5,70- 2,75 2,87 2,83 2,83

4 kW 9,47 13,7 19,7 25,3kW 3,81 5,03 6,87 9,24- 2,50 2,75 2,89 2,77

4 kW 9,05 13,3 19,2 24,7kW 2,86 3,83 5,70 7,34- 3,16 3,47 3,37 3,36

4 kW 7,98 11,9 17,0 21,8kW 2,72 3,74 5,52 7,08- 2,93 3,18 3,08 3,08

4 kW 6,05 9,17 13,1 16,6kW 2,56 3,62 5,32 6,74- 2,36 2,53 2,46 2,47

4 kW 7,20 10,6 15,0 19,4kW 3,20 4,44 6,11 8,02- 2,25 2,39 2,46 2,42- 2,43 2,61 2,65 2,68

4 kW 9,04 15,5 18,9 25,2kW 3,43 4,63 6,82 9,03- 2,64 3,13 2,77 2,79

4 kW 8,00 12,10 16,8 22,4kW 3,28 4,52 6,62 8,66- 2,44 2,68 2,54 2,59

4 kW 6,15 9,43 13,1 17,1kW 3,11 4,40 6,39 8,22- 1,98 2,14 2,05 2,08°C -17 -17 -17 -17°C 62 62 62 62I/s 0,44 0,64 0,92 1,17kPa 45 42 112 77dB(A) 36 37 43 45V/Ph/Hz 400/3/50+N

functions and features

Heating-Cooling Air cooled Outdoor inst. Refrig. R-407C Herm. Scroll ELFOControl Ice protectionsystem

Vary FlowIndoor inst.

technical data

Data referred to the following conditions:

(1) A7/W35 internal exchanger water 30/35°C; external air temperature 7°C D.B./ 6°C W.B.A2/W35 internal exchanger water 30/35°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W35 internal exchanger water 30/35°C; external air temperature -5°C D.B./ -5,4°C W.B.A7/W45 internal exchanger water 40/45°C; external air temperature 7°C D.B./ 6°C W.B.A2/W45 internal exchanger water 40/45°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W45 internal exchanger water 40/45°C; external air temperature -5°C D.B./ -5,4°C W.B.A7/W55 internal exchanger water 50/55°C; external air temperature 7°C D.B./ 6°C W.B.A2/W55 internal exchanger water 50/55°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W55 internal exchanger water 50/55°C; external air temperature -5°C D.B./ -5,4°C W.B.A35/W18 internal exchanger water 23/18°C; external air temperature 35°CA35/W7 internal exchanger water 12/7°C; external air temperature 35°C

(2) The total power input is the total power absorbed by the compressors + fans - the power absorbed by the fan to supply the remaining available static pressure to the system + the power absorbed by the auxiliary circuit

(3) EUROVENT COP: coefficient of performance in heating mode. Relationship between heating capacity output and power input according to EUROVENT. The power input is the total power absorbed by the compressor

+ fan + auxiliary circuit + defrost cycles.(4) COP (EN 14511:2008) coefficient of performance in heating mode. Relationship between heating capacity

output and power input according to standard EN 14511:2008. The power input is the total power absorbed by the compressor + fan + auxiliary circuit + defrost cycles + part of the pump to overcome internal pressure drops.

(5) The values refer to the unit with option HEOH and SUP (6) EUROVENT EER calculated as the relationship between the cooling capacity and the total power input.(7) ESEER coefficient of seasonal performance in cooling mode calculated according to Eurovent. Outlet water

7°C.(8) Water flow and available static pressure in winter operating conditions A7/W35: water at the internal heat

exchanger 30/35°C; outdoor air temperature 7°C D.B. / 6°C W.B.(9) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 10

m from the external surface of the unit in open field conditions.

SizesApplication with radiant panels

A7/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)COP (EN 14511:2008) (4)COP (EN 14511:2008) (4),(5)

A2/W35 (1)Heating capacityTotal input (2)COP (EN 14511:2008) (4)

A-5/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A35/W18 (1)Cooling capacityTotal input (2)EER EUROVENT (6)

Application with terminal unitsA7/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A2/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A35/W7 (1)Cooling capacityTotal input (2)EER EUROVENT (6)ESEER (7)

Application with radiatorsA7/W55 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A2/W55 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W55 (1)Heating capacityTotal input (2)

COP EUROVENT (3)Minimum external air temperatureMaximum water temperatureWater flow rate (8)Pump working head (8)Sound pressure level (9)Power supply

Guida_2011_v26.indd 49Guida_2011_v26.indd 49 15/03/11 17:5915/03/11 17:59

Page 28: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

50

31 41 61 811420 1420 1835 1835600 600 775 775800 800 1250 12501485 1485 1770 1770

4 2000 2000 2000 20002000 2000 2000 20001000 1000 1000 10001000 1000 1000 1000100 100 100 100500 500 500 500226 241 315 375201 216 285 345

B1D

D2

C

D1B

B2

A

DD4

C

D3B

B1

B2

dimensions and clearances

accessories

■ 4 Set point compensation with according to outdoor enthalpy ■ 4 3 ways-valve

■ Accessories supplied separately.

Key to symbols:

SYSTEM ACCESSORIES■ 4 300 litres domestic hot water kit■ 4 500 litres domestic hot water kit■ 4 Domestic hot water kit control■ 4 100 litres hydraulic breaker■ 4 Mixing group control module■ 4 Boiler control kit

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

Ductable unit

Standard unitSizesLength (A) mmLength (D) mmWidth (B) mmHeight (C) mm

(D1) mm(D2) mm(D3) mm(D4) mm(B1) mm(B2) mm

Weight in oper. (1) kgWeight in oper. (2) kg

(1) Standard Unit(2) Ductable Unit

Guida_2011_v26.indd 50Guida_2011_v26.indd 50 15/03/11 17:5915/03/11 17:59

Page 29: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFOEnergy Vulcan

WBAN

High temperature heat pump, for heating only, suitable for traditional systems with radiators.

Guida_2011_v26.indd 51Guida_2011_v26.indd 51 15/03/11 18:1915/03/11 18:19

Page 30: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

52

WBAN 41÷81

WBAN 41 400TN(1)

CCS(3)

-(4)

HYGU(5)

-(6)

-(7)

ELFOENERGY VULCAN

-(2)

Pompe à chaleur

Certificat NF 414-269du 30/04/2010www.certita.org

30/35 40/45 47/55

available configurations

Heat pumpAir cooledOutdoor installationCapacity from 14,7 to 25,6 kW

WBAN heat pumps represent a huge leap forward in dedicated heating pump technology and respect for the environment. The WBAN range incorporates the best in the latest technology and stands out for its:

4PERFORMANCE - A clever design enables WBAN heat pumps to achieve excellent energy efficiency even in extreme operating conditions (minimum operating temperature of -18°C and 60°C hot water production with outside temperatures of -10°C);

4SELF ADAPTATION - Advanced electronics automatically adapt the cooling unit’s operating parameters to match the load of the system in which the pump is installed, thus optimising the system’s consumption, efficiency and working life;

4EASY INSTALLATION - Each unit comes complete with a hydronic group, and is factory tested to ensure quick and easy installation.

(1) SUPPLY VOLTAGE:4400TN 400/3/50+N (Standard for sizes 41-51)4230M 230/1/50 (Standard and only for sizes 21-31)

(2) ENERGY EFFICIENCY:4- Not required (Standard)4H High energy efficiency

(3) CONDENSER COIL:4CCS Standard condenser coil

4CCCA Condenser coil in copper/aluminium with acrylic coating

4CCCA1 Condenser coil in copper/aluminium with Energy Guard DCC Aluminium treatment

4CCCC Condenser coil in copper/copper

(4) AUXILIARY ELECTRIC HEATING ELEMENTS:4- Not required (Standard)

4EH246 Modular integration electric heater 2-4 and 6 kW

(5) HYDRONIC GROUP:4HYGU Hydronic group user side (Standard)

4- Not required

(6) 3-WAY VALVE: 4- Not required (Standard) 43WV 3-way valve for sanitary hot water

(7) SOFT STARTER: 4- Device for inrush current reduction (Standard for size 41 with

230/1/50)Not required (Standard for sizes 61-81)

4SFSTR4N Device for inrush current reduction for 400/3/50+N units

Guida_2011_v26.indd 52Guida_2011_v26.indd 52 15/03/11 18:1915/03/11 18:19

Page 31: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

53

R-407CAIR

41 61 81

4 kW 14.7 19.4 25.6kW 3,56 4,55 6,11- 4,13 4,26 4,19- 3,90 4,08 3,90- 4,10 4,14 4,10

4 kW 13,1 17,3 23,0kW 3,44 4,35 5,89- 3,80 3,95 3,90

4 kW 9,52 12,4 16,3kW 3,55 4,47 6,06- 2,68 2,77 2,69

4 kW 14,9 19,3 26,3kW 4,31 5,69 7,91- 3,45 3,39 3,32

4 kW 13,3 17,2 23,5kW 4,16 5,37 7,55- 3,19 3,20 3,11

4 kW 9,79 12,8 17,0kW 4,22 5,41 7,55- 2,32 2,37 2,25

4 kW 15,2 19,2 27,1kW 5,06 6,83 9,71- 2,99 2,81 2,79

4 kW 13,5 17,1 24,0kW 4,88 6,40 9,21- 2,76 2,67 2,61

4 kW 10,1 13,3 17,7kW 4,89 6,36 9,04- 2,06 2,09 1,96°C -18 -17 -17°C 60 60 60I/s 0,63 0,79 1,06kPa 43 60 100dB(A) 42 44 48V/Ph/Hz 230/1/50 400/3/50+N

functions and features

Heating only Air cooled Outdoor inst. Refrig. R-407C Herm. Scroll ELFOControl

technical data

Data referred to the following conditions:

(1) A7/W35 internal exchanger water 30/35°C; external air temperature 7°C D.B./ 6°C W.B.A2/W35 internal exchanger water 30/35°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W35 internal exchanger water 30/35°C; external air temperature -5°C D.B./ -5,4°C W.B.A7/W45 internal exchanger water 40/45°C; external air temperature 7°C D.B./ 6°C W.B.A2/W45 internal exchanger water 40/45°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W45 internal exchanger water 40/45°C; external air temperature -5°C D.B./ -5,4°C W.B.A7/W55 internal exchanger water 50/55°C; external air temperature 7°C D.B./ 6°C W.B.A2/W55 internal exchanger water 50/55°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W55 internal exchanger water 50/55°C; external air temperature -5°C D.B./ -5,4°C W.B.

(2) The total power input is the total power absorbed by the compressors + fans - the power absorbed by the fan to supply the remaining available static pressure to the system + the power absorbed by the auxiliary circuit

(3) EUROVENT COP: coefficient of performance in heating mode. Relationship between heating capacity output and power input according to EUROVENT. The power input is the total power absorbed by the compressor + fan + auxiliary circuit + defrost cycles.

(4) COP (EN 14511:2008) coefficient of performance in heating mode. Relationship between heating capacity output and power input according to standard EN 14511:2008. The power input is the total power absorbed by the compressor + fan + auxiliary circuit + defrost cycles + part of the pump to overcome internal

pressure drops.(5) The values refer to the unit with the High Efficiency option(6) Water flow and available static pressure in winter operating conditions A7/W35: water at the internal heat

exchanger 30/35°C; outdoor air temperature 7°C D.B. / 6°C W.B.(7) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 10

m from the external surface of the unit in open field conditions.

The NF mark identifies the units that have been certified according to the following conditions:A7/W35 internal exchanger water 30/35°C; external air temperature 7°C D.B./ 6°C W.B.A7/W45 internal exchanger water 40/45°C; external air temperature 7°C D.B./ 6°C W.B. A-7/W35 internal exchanger water */35°C; external air temperature -7°C D.B./ -8°C W.B.A-7/W45 internal exchanger water */45°C; external air temperature -7°C D.B./ -8°C W.B.A7/W55 internal exchanger water 47/55°C; external air temperature 7°C D.B./ 6°C W.B.A-7/W55 internal exchanger water */55°C; external air temperature -7°C D.B./ -8°C W.B.The certified values are the heating capacity, the total input power and the COP and are calculated according to the EN14511:2008.

SizesApplication with radiant panels

A7/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)COP (EN 14511:2008) (4)COP (EN 14511:2008) (4),(5)

A2/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)

Application with terminal unitsA7/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A2/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

Application with radiatorsA7/W55 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A2/W55 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W55 (1)Heating capacityTotal input (2)COP EUROVENT (3)

Minimum external air temperatureMaximum water temperatureWater flow rate (6)Pump working head (6)Sound pressure level (7)Power supply

Vary Flow(sizes 41÷61)

Guida_2011_v26.indd 53Guida_2011_v26.indd 53 15/03/11 18:2015/03/11 18:20

Page 32: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

54

BB2

A

A1

C

B

C

B2 AA1

41 61 811120 1120 1526524 524 5571176 1176 1224150 150 150500 500 500150 157 266

41÷61

81

dimensions and clearances

accessories

■ Accessories supplied separately.

■ Rubber antivibration mounts ■ Serial communication module to supervisor (MODBUS)■ Phase monitor ■ Service keypad (cable from 1,5 metres)

Key to symbols:

SYSTEM ACCESSORIES■ 100 litres hydraulic breaker■ Hose kit for connection to chiller/heat pump. With connections

of 1"■ Hose kit for connection to chiller/heat pump. With connections of

1 1/4"■ Radiant panels management kit with 1" connections■ Radiant panels management kit with 1 1/4" connections■ 500 litres domestic hot water kit■ Boiler control kit■ Electronic wall-mounting room thermostat■ Domestic hot water kit control

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm (B2) mmWeight in oper. kgThe above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

leave free

leave free

Page 33: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFOEnergy Extended

WSAN-XPR

Heat pump optimised for heating for systems with radiant panels and systems with terminal units.

Guida_2011_v26.indd 55Guida_2011_v26.indd 55 15/03/11 18:1615/03/11 18:16

Page 34: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

56

WSAN-XPR 21÷51

ELFOENERGY EXTENDED

WSAN-XPR 21 HYGU(4)

CCS(5)

4

400TN(2)

-(6)

-(7)

S(1)

-(3)

Eurovent EnergyEfficiency Class

available configurations

Water chillerReversible heat pump

Air cooledOutdoor installationCapacity from 6,72 to 13,6 kW

ELFOEnergy EXTENDED WSAN-XPR water cooling units use R-410A refrigerant. Because they are so compact, they are ideal for residential applications. And they keep on working under all conditions thanks to a variable speed fan and water pump.Optimised for heating, the range guarantees:

4versatile operation with both radiator and radiant panel systems;

4storage-free operation and temperature modulation for a perfect balance between output power and energy consumption.

(1) LOW TEMPERATURE:4- Not required (Standard)4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +5°C and -8°C inclusive.

(2) SUPPLY VOLTAGE:4400TN 400/3/50+N (Standard)4230M 230/1/50

(3) ENERGY EFFICIENCY:4- Not required (Standard)4H High energy efficiency

(4) HYDRONIC GROUP:4HYGU Hydronic group user side (Standard)4- Not required

(5) CONDENSER COIL:4CCS Standard condenser coil4CCCA Condenser coil in copper/aluminium with acrylic coating4CCCA1 Condenser coil in copper/aluminium with Energy Guard

DCC Aluminium treatment4CCCC Condenser coil in copper/copper

(6) SOFT STARTER:4- Not required (Standard)4SFSTR1 Device for inrush current reduction only for sizes 21÷41 with

supply voltage 230/1/50

(7) ADDITIONAL CARDS:4- Not required (Standard)4KDT3V Double temperature control kit, set point compensation 4-20

mA, 3-way valve control

Guida_2011_v26.indd 56Guida_2011_v26.indd 56 15/03/11 18:1615/03/11 18:16

Page 35: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

57

R-410AAIR

21 31 41 51

4 kW 6,72 7,89 10,4 13,6kW 1,60 1,88 2,48 3,22- 4,20 4,20 4,20 4,22- 4,04 4,02 4,03 4,13- 4,15 4,18 4,15 4,13

4 kW 5,90 6,99 9,15 11,9kW 1,55 1,81 2,44 3,16- 3,81 3,86 3,75 3,77

4 kW 4,41 5,27 6,83 9,08kW 1,57 1,82 2,40 3,16- 2,81 2,89 2,84 2,87

4 kW 7,37 8,60 11,9 15,6kW 1,95 2,36 3,27 4,46- 3,77 3,65 3,64 3,49- 3,48 3,42 3,46 3,40

4 kW 6,58 7,67 10,1 13,3kW 2,04 2,37 3,09 4,12- 3,23 3,24 3,26 3,23

4 kW 5,84 6,86 8,90 11,8kW 1,97 2,31 2,99 4,09- 2,96 2,97 2,98 2,89

4 kW 4,47 6,11 6,73 9,17kW 2,03 2,34 2,94 4,14- 2,20 2,61 2,29 2,21

4 kW 5,36 6,65 8,61 11,7kW 1,93 2,34 3,09 4,24- 2,78 2,84 2,79 2,75- 3,29 3,43 3,34 3,26°C -15 -15 -15 -15°C 61 59 60 60I/s 0,26 0,32 0,41 0,56kPa 64 85 70 85dB(A) 38 38 39 43V/Ph/Hz 400/3/50+N

functions and features

Heating-Cooling Air cooled Outdoor inst. Refrig. R-410A Herm. Scroll ELFOControl Ice protectionsystem

Vary Flow

Data referred to the following conditions:

technical data

(1) A7/W35 internal exchanger water 30/35°C; external air temperature 7°C D.B./ 6°C W.B.A2/W35 internal exchanger water 30/35°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W35 internal exchanger water 30/35°C; external air temperature -5°C D.B./ -5,4°C W.B.A7/W45 internal exchanger water 40/45°C; external air temperature 7°C D.B./ 6°C W.B.A2/W45 internal exchanger water 40/45°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W45 internal exchanger water 40/45°C; external air temperature -5°C D.B./ -5,4°C W.B.A35/W18 internal exchanger water 23/18°C; external air temperature 35°CA35/W7 internal exchanger water 12/7°C; external air temperature 35°C

(2) The total power input is the total power absorbed by the compressors + fans - the power absorbed by the fan to supply the remaining available static pressure to the system + the power absorbed by the auxiliary circuit

(3) EUROVENT COP: coefficient of performance in heating mode. Relationship between heating capacity output and power input according to EUROVENT. The power input is the total power absorbed by the compressor + fan + auxiliary circuit + defrost cycles.

(4) COP (EN 14511:2008) coefficient of performance in heating mode. Relationship between heating capacity output and power input according to standard EN 14511:2008. The power input is the total power

absorbed by the compressor + fan + auxiliary circuit + defrost cycles + part of the pump to overcome internal pressure drops.

(5) The values refer to the unit with the High Efficiency option(6) EUROVENT EER calculated as the relationship between the cooling capacity and the total power input.(7) EER (EN 14511:2008) coefficient of performance in cooling mode. Relationship between the cooling

capacity output and the power input according to standard EN 14511:2008. The power input is the total power absorbed by the compressor + auxiliary circuit + part of the pump to overcome internal pressure drops

(8) ESEER coefficient of seasonal performance in cooling mode calculated according to Eurovent. Outlet water 7°C.

(9) Water flow and available static pressure in winter operating conditions A7/W35: water at the internal heat exchanger 30/35°C; outdoor air temperature 7°C D.B. / 6°C W.B.

(10) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 10 m from the external surface of the unit in open field conditions.

SizesApplication with radiant panels

A7/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)COP (EN 14511:2008) (4)COP (EN 14511:2008) (4)(5)

A2/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A35/W18 (1)Cooling capacityTotal input (2)EER EUROVENT (6)EER (EN 14511:2008) (7)

Application with terminal unitsA7/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A2/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A35/W7 (1)Cooling capacityTotal input (2)EER EUROVENT (6)ESEER (8)

Minimum external air temperatureMaximum water temperatureWater flow rate (9)Pump working head (9)Sound pressure level (10)Power supply

Guida_2011_v26.indd 57Guida_2011_v26.indd 57 15/03/11 18:1615/03/11 18:16

Page 36: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

58

21 31 41 51mm 800 800 800 800mm 300 300 300 300mm 930 1244 1244 1370

4 mm 100 100 100 100mm 500 500 500 500mm 150 150 150 150kg 89 106 111 135

BB2

C

A

A1

A2

dimensions and clearances

accessories

■ Accessories supplied separately.

Key to symbols:

■ 4 Hydraulic module with storage tank of 10 liters and supplementary electric heaters

■ 4 Rubber antivibration mounts ■ 4 Serial communication module to supervisor (MODBUS)■ 4 Phase monitor■ 4 Double temperature control kit, set point compensation 4-20 mA,

3-way valve■ 4 Set point compensation with according to outdoor enthalpy■ 4 Inertial storage tank of 22 litres

SYSTEM ACCESSORIES■ 4 100 litres hydraulic breaker■ 4 Hose kit for connection to chiller/heat pump. With connections

of 1"■ 4 300 litres domestic hot water kit■ 4 500 litres domestic hot water kit■ 4 Boiler control kit■ 4 Radiant panels management kit with 1" connections■ 4 Room thermostat

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

Sizes Length (A)Width (B)Height (C)

(A1)(A2)(B2)

Weight in oper.

The above data refer to standard units.

leave free

Guida_2011_v26.indd 58Guida_2011_v26.indd 58 15/03/11 18:1615/03/11 18:16

Page 37: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFOEnergy Compact

WSAN-EE WSAT-EE

Heat pump, optimised for cooling, suitable for systems with radiant panels and water terminal units.

Guida_2011_v26.indd 59Guida_2011_v26.indd 59 15/03/11 18:1615/03/11 18:16

Page 38: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

60

WSAN-EE WSAT-EE 17÷151

ELFOENERGY COMPACT

WSAN-EE 17 230M(2)

CCS(3)

4

4

HYGU(4)

-(5)

-(6)

S(1)

Water chillerWSAN-EE: reversible heat pumpWSAT-EE: cooling only

Air cooledOutdoor installationCapacity from 5,07 to 37,4 kW

ELFOEnergy COMPACT water cooling units use R-410A refrigerant. Because they are so compact, they are ideal for residential applications. And they keep on working under all conditions thanks to a variable speed fan and water pump.The series guarantees:

4silent operation thanks to a fan unit that operates at only 70% of its maximum speed under normal conditions;

4storage-free operation and temperature modulation for a perfect balance between output power and energy consumption.

(1) LOW TEMPERATURE:4- Not required (Standard)4B Low water temperature (sizes 61÷151)

This version allows unit operation within the water and glycol mixing temperature range between +5°C and -8°C inclusive.

(2) SUPPLY VOLTAGE:4230M 230/1/50 (Standard for sizes 17÷31)4400TN 400/3/50+N (Standard and only for sizes

41÷151)

(3) CONDENSER COIL:4CCS Standard condenser coil4CCCA Condenser coil in copper/aluminium with acrylic

coating4CCCA1 Condenser coil in copper/aluminium with Energy

Guard DCC Aluminium treatment4CCCC Condenser coil in copper/copper

(4) HYDRONIC GROUP:4HYGU Hydronic group user side (Standard)4- Not required

(5) SOFT STARTER:4- Not required (Standard)4SFSTR1 Device for inrush current reduction for 230/1/50 units (sizes

17÷51)4SFSTR4NDevice for inrush current reduction for 400/3/50+N units

(sizes 61÷151)

(6) ADDITIONAL CARDS:4- Not required (Standard)4KDT3V Double temperature control kit, set point compensation 4-20

mA, 3-way valve control

available configurations

Guida_2011_v26.indd 60Guida_2011_v26.indd 60 15/03/11 18:1615/03/11 18:16

Page 39: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

61

R-410AAIR

17 21 25 31 41 51 61 71 81 91 101 121 131 151

4 kW 5.07 6.28 6.51 8.81 10.4 12.4 14.7 17.2 19.6 21.8 25.6 28.8 33.8 37.4kW 1,51 1,74 2,01 2,59 2,61 3,27 3,97 4,67 5,19 5,79 6,64 7,82 8,57 9,88- 3,36 3,61 3,24 3,40 3,98 3,79 3,70 3,68 3,78 3,77 3,86 3,68 3,94 3,79- 3,13 3,36 3,05 3,12 3,65 3,53 3,46 3,48 3,58 3,59 3,82 3,68 3,96 3,78

4 kW 4,57 5,63 5,90 7,76 9,20 11,1 13,0 15,3 17,4 19,4 22,8 25,8 30,0 33,5kW 1,49 1,70 1,97 2,53 2,59 3,25 3,93 4,60 5,16 5,74 6,60 7,78 8,42 9,80- 3,07 3,31 2,99 3,07 3,55 3,42 3,31 3,33 3,37 3,38 3,45 3,32 3,56 3,42

4 kW 3,58 4,41 4,69 5,93 6,89 8,54 9,88 11,7 13,2 14,7 17,2 19,8 22,7 26,0kW 1,43 1,62 1,88 2,44 2,55 3,26 3,90 4,54 5,16 5,71 6,59 7,78 8,25 9,78- 2,50 2,72 2,49 2,43 2,70 2,62 2,53 2,57 2,55 2,57 2,61 2,54 2,75 2,66

4 kW 5,59 6,90 7,60 10,1 11,8 14,0 17,2 20,5 22,8 24,9 29,9 33,1 38,0 43,7kW 1,90 2,50 2,84 3,66 3,51 4,70 5,78 7,27 7,69 8,87 11,0 11,8 12,8 15,8- 2,94 2,76 2,68 2,76 3,36 2,98 2,98 2,82 2,96 2,81 2,73 3,22 2,59 2,77

4 kW 4,91 6,08 6,39 8,59 10,1 12,4 14,5 17,1 19,3 21,6 25,2 28,5 33,4 38,0kW 1,76 2,11 2,36 3,08 3,32 4,31 4,94 5,88 6,54 7,23 8,44 9,77 10,5 12,3- 2,79 2,89 2,71 2,83 3,04 2,88 2,94 2,90 2,95 2,99 2,99 2,91 3,18 3,09

4 kW 4,41 5,49 5,81 7,63 9,00 11,2 12,9 15,3 17,2 19,3 22,6 25,6 29,8 34,0kW 1,71 2,04 2,28 2,97 3,27 4,34 4,89 5,82 6,51 7,23 8,37 9,70 10,4 12,1- 2,58 2,69 2,55 2,57 2,75 2,58 2,64 2,63 2,64 2,67 2,70 2,64 2,87 2,81

4 kW 3,41 4,32 4,65 5,87 6,90 8,78 9,79 11,8 13,2 14,9 17,4 19,7 22,6 25,9kW 1,62 1,91 2,14 2,80 3,24 4,40 4,84 5,82 6,51 7,23 8,37 9,69 10,2 11,9- 2,10 2,26 2,18 2,09 2,13 2,00 2,02 2,03 2,02 2,06 2,07 2,03 2,21 2,18

4 kW 4,00 4,99 5,58 7,33 8,49 10,4 13,1 15,7 17,3 18,6 22,9 25,7 29,1 33,5kW 1,76 2,25 2,56 3,34 3,30 4,43 5,45 6,57 7,21 8,04 10,0 11,2 11,9 14,7- 2,28 2,22 2,17 2,19 2,57 2,35 2,40 2,38 2,40 2,31 2,28 2,29 2,44 2,28- 2,56 2,49 2,42 2,47 3,04 2,81 2,80 2,77 2,83 2,66 2,66 2,67 2,80 2,63

4 kW 4,32 5,27 5,79 7,62 8,86 11,2 14,0 16,7 18,6 21,3 24,4 27,4 32,3 37,5kW 1,89 2,28 2,53 3,23 3,12 4,34 5,27 6,84 7,03 8,11 9,56 11,0 11,5 14,1- 2,29 2,32 2,29 2,36 2,84 2,58 2,66 2,44 2,65 2,62 2,55 2,49 2,81 2,65- 2,56 2,62 2,54 2,65 3,34 3,03 3,07 2,82 3,08 2,97 2,96 2,85 3,19 3,00°C -15 -15 -15 -15 -15 -15 -14 -14 -15 -15 -13 -15 -15 -15°C 48 49 51 51 51 51 50 51 51 51 50 51 52 52I/s 0,19 0,24 0,27 0,35 0,41 0,50 0,62 0,75 0,83 0,89 1,09 1,23 1,39 1,60kPa 44 39 38 55 52 41 155 146 146 141 134 162 149 136dB(A) 32 32 34 35 35 37 46 46 47 47 47 48 49 50V/Ph/Hz 230/1/50+N 400/3/50+N

Cooling only(WSAT-EE)

Heating-Cooling(WSAN-EE)

Air cooled Outdoor inst. Refrig. R-410A Herm. rotary(17÷31)

Herm. Scroll(41÷151)

ELFOControl Ice protectionsystem (WSAN-EE only)

functions and features

Data referred to the following conditions:

technical data

(1) A7/W35 internal exchanger water 30/35°C; external air temperature 7°C D.B./ 6°C W.B.A2/W35 internal exchanger water 30/35°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W35 internal exchanger water 30/35°C; external air temperature -5°C D.B./ -5,4°C W.B.A7/W45 internal exchanger water 40/45°C; external air temperature 7°C D.B./ 6°C W.B.A2/W45 internal exchanger water 40/45°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W45 internal exchanger water 40/45°C; external air temperature -5°C D.B./ -5,4°C W.B.A35/W18 internal exchanger water 23/18°C; external air temperature 35°CA35/W7 internal exchanger water 12/7°C; external air temperature 35°C

(2) The total power input is the total power absorbed by the compressors + fans - the power absorbed by the fan to supply the remaining available static pressure to the system + the power absorbed by the auxiliary circuit

(3) EUROVENT COP: coefficient of performance in heating mode. Relationship between heating capacity output and power input according to EUROVENT. The power input is the total power absorbed by the compressor + fan + auxiliary circuit + defrost cycles.

(4) COP (EN 14511:2008) coefficient of performance in heating mode. Relationship between heating capacity

output and power input according to standard EN 14511:2008. The power input is the total power absorbed by the compressor + fan + auxiliary circuit + defrost cycles + part of the pump to overcome internal pressure drops.

(5) EUROVENT EER calculated as the relationship between the cooling capacity and the total power input.(6) ESEER coefficient of seasonal performance in cooling mode calculated according to Eurovent. Outlet water

7°C.(7) Water flow and available static pressure in winter operating conditions A7/W35: water at the internal heat

exchanger 30/35°C; outdoor air temperature 7°C D.B. / 6°C W.B.(8) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 10

m from the external surface of the unit in open field conditions.

SizesWSAN-EEApplication with radiant panels

A7/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)COP (EN 14511:2008) (4)

A2/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A35/W18 (1)Cooling capacityTotal input (2)EER EUROVENT (5)

Application with terminal unitsA7/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A2/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A35/W7 (1)Cooling capacityTotal input (2)EER EUROVENT (5)ESEER (6)

WSAT-EEA35/W7 (1)Cooling capacityTotal input (2)EER EUROVENT (5)ESEER (6)

Minimum external air temperatureMaximum water temperatureWater flow rate (7)Pump working head (7)Sound pressure level (8)Power supply

Vary Flow(17÷91)

Guida_2011_v26.indd 61Guida_2011_v26.indd 61 15/03/11 18:1215/03/11 18:12

Page 40: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

62

BB2

C

A

A1

A2

17 21 25 31 41 51 61 71 81 91 101 121 131 151

mm 800 800 800 800 800 800 1087 1087 1373 1373 1373 1373 1715 1715mm 300 300 300 300 300 300 411 411 555 555 555 555 820 820mm 930 930 930 930 1244 1244 1175 1175 1225 1225 1225 1225 1480 1480

4 mm 100 100 100 100 100 100 100 100 100 100 100 100 100 100mm 500 500 500 500 500 500 500 500 500 500 500 500 500 500mm 150 150 150 150 150 150 150 150 150 150 150 150 150 150kg 68 76 77 91 111 120 126 135 180 184 203 206 268 273

mm 800 800 800 800 800 800 1087 1087 1373 1373 1373 1373 1715 1715mm 300 300 300 300 300 300 411 411 555 555 555 555 820 820mm 643 643 643 930 1244 1244 1175 1175 1225 1225 1225 1225 1480 1480

4 mm 100 100 100 100 100 100 100 100 100 100 100 100 100 100mm 500 500 500 500 500 500 500 500 500 500 500 500 500 500mm 150 150 150 150 150 150 150 150 150 150 150 150 150 150kg 58 66 66 80 102 110 126 135 180 184 203 206 268 273

dimensions and clearances

accessories

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

Sizes WSAN-EELength (A)Width (B)Height (C)

(A1)(A2)(B2)

Weight in oper.WSAT-EELength (A)Width (B)Height (C)

(A1)(A2)(B2)

Weight in oper.

The above data refer to standard units.

leave free

■ Accessories supplied separately.

Key to symbols:

■ 4 Rubber antivibration mounts ■ 4 Serial communication module to supervisor (MODBUS)■ 4 Phase monitor■ 4 Double temperature control kit, set point compensation 4-20 mA,

3-way valve■ 4 Set point compensation with according to outdoor enthalpy■ 4 Service keypad (cable from 1,5 metres)

Guida_2011_v26.indd 62Guida_2011_v26.indd 62 15/03/11 18:1215/03/11 18:12

Page 41: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFOEnergy Vulcan Medium

WBAN

High temperature heat pump: able to produce hot water at 60°C even when the outdoor temperature falls to -10°C.The ideal one-stop heating, cooling and hot water solution for centralised systems in residential complexes, hotels and collective buildings.

Guida_2011_v26.indd 63Guida_2011_v26.indd 63 15/03/11 18:1215/03/11 18:12

Page 42: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em WBAN 82÷302

WBAN 82 400TN(2)

1PUS(3)

-(4)

-(5)

-(6)

-(7)

ELFOENERGY VULCAN MEDIUM

S(1)

-(8)

-(9)

-(10)

-(11)

-(12)

Eurovent EnergyEfficiency Class

64

available configurations

Reversible heat pumpAir cooledOutdoor installationCapacity from 29,1 to 99,8 kW

ELFOEnergy Vulcan Medium comprises a series of high temperature heat pumps, ideal as a one-stop heating, cooling and hot water solution for centralised systems in residential complexes, hotels and collective buildings in general.

4Energy Efficiency CLASS A rating, in both heating and cooling mode;

4Ideal for all system types, including radiator systems with hot water production up to 60°C, at outdoor air temperatures down to -10°C;

4System simplification thanks to the use of a single generator for heating and cooling, doing away with the risks and maintenance costs associated with traditional combustion systems.

The units in the ELFOEnergy VULCAN Medium range offer autonomous hot water production and are enabled for use with solar panel heaters, making it possible to use direct solar energy.

(1) LOW TEMPERATURE:4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +4°C and -8°C inclusive.Two versions are available- Unit for low temperatures only- Unit with double operating set-point.Consult our Marketing Office regarding particular conditions.

4S Standard version(2) SUPPLY VOLTAGE:4400TN 400/3/50+N

(3) HYDRONIC GROUP USER SIDE:41PUS Standard pump41PUM Single pump high head41PUHE Single inverter driven pump with high head for the

primary circuit 4- Not required(4) ENERGY RECOVERY: 4- Not required4D Partial recovery

Carried out using braze-welded plate-type exchangers suited for recovering the desuperheating heat up to a maximum of 25% of the total unit heat.

(5) CONDENSER COIL:4CCS Standard condenser coil

4CCCA Condenser coil in copper/aluminium with acrylic coating

4CCCA1 Condenser coil in copper/aluminium with Energy Guard DCC Aluminium treatment

4CCCC Condenser coil in copper/copper(6) SOFT STARTER:4- Not required (Standard)

4SFSTR4N Device for inrush current reduction for 400/3/50+N units(7) CONTACTS:4- Not required (Standard)4CLSE Free Contacts External Signal

(8) SHUNT CAPACITORS (COSFI > 0,9):4PFCP Shunt capacitors (cosfi > 0,9)4- Not required

(9) 3-WAY VALVE: 4- Not required (Standard) 43DHW 3-way valve for sanitary hot water mounted on-board(11) COMPRESSOR ISOLATION:4- Not required (Standard)4IS4 Additional on-board compressor isolation

(11) PROTECTION GRILLES:4- Not required (Standard)4PGFC On-board protective grilles for finned coil exchangers

(12) PHASE MONITOR:4- Not required (Standard)4PM On-board phase monitor

Guida_2011_v26.indd 64Guida_2011_v26.indd 64 15/03/11 18:1215/03/11 18:12

Page 43: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em82 122 162 202 262 302

4 kW 29,1 41,4 52,5 71,2 83,9 99,8kW 7,13 10,2 12,8 17,4 20,6 24,4- 4,08 4,07 4,11 4,10 4,07 4,09- 4,11 4,13 4,13 4,12 4,10 4,13

4 kW 26,0 36,6 46,0 61,9 74,2 87,9kW 6,94 9,64 12,2 16,6 20,0 23,6- 3,75 3,80 3,76 3,72 3,72 3,73

4 kW 19,8 27,9 34,7 46,5 56,2 66,0kW 6,76 9,25 11,7 15,7 19,1 22,4- 2,92 3,02 2,96 2,96 2,95 2,95

4 kW 32,8 46,0 60,7 85,5 96,3 121kW 8,60 12,5 16,0 23,1 26,1 32,5- 3,81 3,68 3,80 3,69 3,69 3,72

4 kW 29,1 40,9 53,7 70,2 85,7 99,6kW 8,55 12,0 15,5 20,3 25,6 28,7- 3,40 3,40 3,47 3,45 3,35 3,47

4 kW 26,0 36,6 46,0 61,9 74,2 87,9kW 6,94 9,64 12,2 16,6 20,0 23,6- 3,75 3,80 3,76 3,72 3,72 3,73

4 kW 19,9 28,0 37,0 47,6 57,5 66,0kW 7,73 10,8 13,8 18,4 23,2 25,5- 2,58 2,59 2,68 2,58 2,48 2,59

4 kW 25,1 35,3 46,4 64,9 77,5 93,2kW 7,97 11,4 14,7 20,6 24,6 29,3- 3,15 3,10 3,16 3,16 3,15 3,18

4 kW 29,1 40,5 54,4 69,9 87,4 99,9kW 9,84 13,7 18,8 24,9 30,2 33,8- 2,96 2,95 2,89 2,80 2,90 2,96

4 kW 26,2 36,2 48,9 52,9 77,8 88,3kW 9,57 13,2 18,0 22,5 29,0 32,3- 2,74 2,74 2,71 2,35 2,69 2,74

4 kW 22,5 31,3 42,0 49,7 65,4 74,4kW 9,25 12,7 16,9 21,9 27,5 30,3- 2,43 2,46 2,48 2,27 2,38 2,46°C -18 -18 -18 -18 -18 -18°C 60 61 62 63 64 65I/s 1,62 2,27 3 4,23 4,76 5,98kPa 158 164 149 169 159 183- 2- 2 SCROLLdB(A) 47 47 49 49 51 51V/Ph/Hz 400/3/50+N

R-407CAIR

65

technical data

Data referred to the following conditions:

(1) A7/W35 internal exchanger water 30/35°C; external air temperature 7°C D.B./ 6°C W.B.A2/W35 internal exchanger water 30/35°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W35 internal exchanger water 30/35°C; external air temperature -5°C D.B./ -5,4°C W.B.A7/W45 internal exchanger water 40/45°C; external air temperature 7°C D.B./ 6°C W.B.A2/W45 internal exchanger water 40/45°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W45 internal exchanger water 40/45°C; external air temperature -5°C D.B./ -5,4°C W.B.A7/W55 internal exchanger water 50/55°C; external air temperature 7°C D.B./ 6°C W.B.A2/W55 internal exchanger water 50/55°C; external air temperature 2°C D.B./ 1,1°C W.B.A-5/W55 internal exchanger water 50/55°C; external air temperature -5°C D.B./ -5,4°C W.B.A35/W18 internal exchanger water 23/18°C; external air temperature 35°CA35/W7 internal exchanger water 12/7°C; external air temperature 35°C

(2) The total power input is the total power absorbed by the compressors + fans - the power absorbed by the fan to supply the remaining available static pressure to the system + the power absorbed by the auxiliary circuit

(3) EUROVENT COP: coefficient of performance in heating mode. Relationship between heating capacity output

and power input according to EUROVENT. The power input is the total power absorbed by the compressor + fan + auxiliary circuit + defrost cycles.

(4) COP (EN 14511:2008) coefficient of performance in heating mode. Relationship between heating capacity output and power input according to standard EN 14511:2008. The power input is the total power absorbed by the compressor + fan + auxiliary circuit + defrost cycles + part of the pump to overcome internal pressure drops.

(5) EUROVENT EER calculated as the relationship between the cooling capacity and the total power input.(6) Water flow and available static pressure in winter operating conditions A7/W35: water at the internal heat

exchanger 30/35°C; outdoor air temperature 7°C D.B. / 6°C W.B.(7) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 10

m from the external surface of the unit in open field conditions.

SizesApplication with radiant panels

A7/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)COP (EN 14511:2008) (4)

A2/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W35 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A35/W18 (1)Cooling capacityTotal input (2)EER EUROVENT (5)

Application with terminal unitsA7/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A2/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W45 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A35/W7 (1)Cooling capacityTotal input (2)EER EUROVENT (5)

Application with radiatorsA7/W55 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A2/W55 (1)Heating capacityTotal input (2)COP EUROVENT (3)

A-5/W55 (1)Heating capacityTotal input (2)COP EUROVENT (3)

Minimum external air temperatureMaximum water temperatureWater flow rate (6)Pump working head (6)Number of cooling circuitsNumber and type of compressorsSound pressure level (7)Power supply

functions and features

Heating only Air cooled Outdoor inst. Refrig. R-407C Herm. Scroll ELFOControl

Guida_2011_v26.indd 65Guida_2011_v26.indd 65 15/03/11 18:1215/03/11 18:12

Page 44: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

66

BB2

B1A

A2

C

A1

82 122 162 202 262 3021928 1928 2328 2328 2932 29321100 1100 1100 1100 1100 11001474 1474 1474 1474 1474 1474

4 700 700 700 700 700 700700 700 700 700 700 700700 700 700 700 700 700700 700 700 700 700 700420 466 635 670 803 826

dimensions and clearances

accessories

■ 4 Rubber antivibration mounts ■ 4 Finned coil protection grilles■ 4 Phase monitor to check the presence and correct sequence of the

power supply phases

Key to symbols:

4 3 ways-valve■ 4 Domestic hot water kit control■ 4 Multi-function keypad holder

■ Accessories supplied separately.

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(B2) mm

Weight in oper. kg

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

leave free

Guida_2011_v26.indd 66Guida_2011_v26.indd 66 15/03/11 18:1215/03/11 18:12

Page 45: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFOEnergy Ground

WSHN-EE WSH-EE

The geothermal heat pump that can be used to heat and cool any kind of building, from new homes to renovation projects, using the free energy found in the ground or water and offering huge benefits in terms of energy saving.

Guida_2011_v26.indd 67Guida_2011_v26.indd 67 15/03/11 18:1215/03/11 18:12

Page 46: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

68

WSHN-EE WSH-EE 17÷121

4

4

WSHN-EE 17 400TN(2)

HYGU(3)

-(4)

-(5)

ELFOENERGY GROUND

S(1)

-(6)

available configurations

Water chillerWSHN-EE: reversible heat pumpWSH-EE: cooling only

Water cooledIndoor installationCapacity from 7,05 to 41,6 kW

Geothermal energy from the ground or ground water can provide heating and cooling at considerably less expense. WSHN-EE and WSH-EE units are specially designed for use in closed or open circuit geothermal systems, while preserving all the benefits of air-cooled units, such as efficiency, automatic adaptation, and silent operation. This series also comes ready for use. All the components needed for connection are supplied without the need for additional parts. The hydronic group on the sink side (found in all air-cooled units), is backed up by a second hydronic unit on the source side.

(1) LOW TEMPERATURE:4S Standard4B Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +5°C and -8°C inclusive.

4BS Low water temperature source sidePrearrangement for use of source side water, with temperature conditions lower than +5°C.

(2) SUPPLY VOLTAGE: 4400TN 400/3/50+N (Standard for sizes 41÷121) 4230M 230/1/50 (Standard for size 17÷31; optional for

sizes 41-51)

(3) HYDRONIC GROUP USER SIDE:4HYGU Hydronic group user side (Standard)4- Not required

(4) HYDRONIC GROUP SOURCE SIDE: 4- Not required (Standard)4HYGS Hydronic group source side

(5) SOFT STARTER:4- Not required (Standard)4SFSTR Device for inrush current reduction

(6) VALVE:4- Not required (Standard)43WV 3-way valve for sanitary hot water

Guida_2011_v26.indd 68Guida_2011_v26.indd 68 15/03/11 18:1215/03/11 18:12

Page 47: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

69

17 21 31 41 51 61 71 81 91 101 121

4 kW 7,05 7,60 9,42 12,1 16,1 19,7 24,9 26,5 31,0 36,7 41,6kW 1,27 1,39 1,76 2,26 2,89 3,54 4,43 4,90 5,63 6,42 7,20- 5,55 5,47 5,35 5,35 5,57 5,56 5,62 5,41 5,51 5,72 5,78- 5,10 5,10 5,10 5,10 5,20 5,30 5,30 5,20 5,30 5,60 5,50

4 kW 5,57 6,00 7,45 9,56 12,7 15,6 19,7 21,0 24,5 28,9 32,9kW 1,19 1,29 1,64 2,11 2,71 3,32 4,15 4,59 5,28 6,01 6,71- 4,68 4,65 4,54 4,53 4,69 4,70 4,75 4,58 4,64 4,81 4,90

4 kW 8,26 8,94 10,7 13,9 17,7 21,9 26,9 29,6 33,6 37,5 42,4kW 1,39 1,57 1,90 2,32 3,05 3,89 4,81 5,18 5,95 6,88 7,57- 5,94 5,69 5,63 5,99 5,80 5,63 5,59 5,71 5,65 5,45 5,60- 5,40 5,40 5,20 5,40 5,30 5,20 5,10 5,20 5,20 5,10 5,10

4 kW 6,78 7,37 8,95 11,6 15,7 19,1 23,8 25,3 29,5 34,7 39,1kW 1,52 1,66 2,36 2,93 3,80 4,55 5,63 6,26 7,06 8,18 8,97- 4,46 4,44 3,79 3,96 4,13 4,20 4,23 4,04 4,18 4,24 4,36

4 kW 5,41 5,87 7,19 9,32 12,5 15,2 19,0 20,3 23,6 27,7 31,5kW 1,42 1,53 2,18 2,71 3,53 4,23 5,24 5,83 6,58 7,63 8,34- 3,81 3,84 3,30 3,44 3,54 3,59 3,63 3,48 3,59 3,63 3,78

4 kW 6,13 6,47 7,94 10,7 13,1 16,1 20,5 22,1 25,6 29,0 32,6kW 1,40 1,53 1,90 2,32 3,17 3,86 4,66 4,80 5,80 6,78 7,50- 4,38 4,23 4,18 4,61 4,13 4,17 4,40 4,60 4,41 4,28 4,35- 4,82 4,71 4,49 5,15 4,50 4,48 4,86 5,14 4,87 4,76 4,80

4 kW 6,43 7,14 8,65 11 14,9 17,6 22,5 23,8 28,1 32,3 37,1kW 1,94 2,03 3,12 3,70 4,87 5,81 7,15 8,06 8,74 10,3 11,1- 3,31 3,52 2,77 2,97 3,06 3,03 3,15 2,95 3,22 3,14 3,34

4 kW 5,32 5,82 7,12 9,18 12,3 14,8 18,7 19,9 23,2 27,1 30,8kW 1,59 1,69 2,51 3,06 4,00 4,79 5,91 6,61 7,33 8,57 9,29- 3,35 3,44 2,84 3,00 3,08 3,09 3,16 3,01 3,17 3,16 3,32°C -8 -8 -8 -8 -8 -8 -8 -8 -8 -8 -8°C 55 55 55 55 55 55 55 55 55 55 55I/s 0,35 0,38 0,46 0,61 0,78 0,95 1,18 1,28 1,50 1,71 1,91kPa 50 48 51 40 25 49 38 40 32 110 77I/s 0,29 0,31 0,38 0,51 0,63 0,77 0,96 1,06 1,22 1,39 1,56kPa 52 49 47 36 20 41 30 24 18 84 41dB(A) 26 26 27 27 28 29 32 33 34 35 36V/Ph/Hz 230/1/50 400/3/50+N

R-410AH2O

Data referred to the following conditions:

technical data

SizesWSHN-EE - Unit with cooling circuit reversalApplication with radiant panels

W10/W35 (1)Heating capacity (2)Total input (3)COP EUROVENT (4)COP (EN 14511:2008) (5)B0/W35 (1)Heating capacityTotal input (3)COP EUROVENT (4)W35/W18 (1)Cooling capacity Total input (3)EER EUROVENT (7)EER (EN 14511:2008) (8)

Application with terminal unitsW10/W45 (1)Heating capacity (2)Total input (3)COP EUROVENT (4)B0/W45 (1)Heating capacity Total input (3)COP EUROVENT (4)W35/W7 (1)Cooling capacity Total input (3)EER EUROVENT (7)ESEER (9)

Application with radiatorsW10/W55 (1)Heating capacity (2)Total input (3)COP EUROVENT (4)B0/W50 (1)Heating capacity Total input (2)COP EUROVENT (4)

Minimum water temperatureMaximum water temperatureWater flow rate - user side (6)Pump working head - user side (6)Water flow rate - source side (6)Pump working head - source side (6)Sound pressure level (10)Power supply

(1) W10/W35 water at the user side heat exchanger 30/35°C; inlet water at the source side heat exchanger 10°CB0/W35 water at the user side heat exchanger 30/35°C; inlet water at the source side heat exchanger 0°C; ethylenic glycol 30% 30%W10/W45 water at the user side heat exchanger 40/45°C; inlet water at the source side heat exchanger 10°CB0/W45 water at the user side heat exchanger 40/45°C; inlet water at the source side heat exchanger 0°C; ethylenic glycol 30%W10/W55 water at the user side heat exchanger 45/55°C; inlet water at the source side heat exchanger 10°CB0/W50 water at the user side heat exchanger 45/50°C; inlet water at the source side heat exchanger 0°C; ethylenic glycol 30%W35/W18 water at the user side heat exchanger 23/18°C; inlet water at the source side heat exchanger 30/35°CW35/W7 water at the user side heat exchanger 12/7°C; inlet water at the source side heat exchanger 30/35°C

(2) Heating capacity measured at the temperature conditions and source side water flow in cooling mode established by EUROVENT

(3) Total input is obtained from the compressor input + auxiliary circuit input

(4) EUROVENT COP: coefficient of performance in heating mode. Relationship between heating capacity output and power input according to EUROVENT. The power input is the total power absorbed by the compressor + fan + auxiliary circuit

(5) COP (EN 14511:2008) coefficient of performance in heating mode. Relationship between the heating capacity output and the power input according to standard EN 14511:2008. The power input is the total power absorbed by the compressor + auxiliary circuit + part of the pump to overcome internal pressure drops

(6) The values given refer to performances in heating mode at rated conditions(7) EUROVENT EER: coefficient of performance in cooling mode. Relationship between cooling capacity output

and power input according to EUROVENT. The power input is the total power absorbed by the compressor + auxiliary circuit

(8) EER (EN 14511:2008) coefficient of performance in cooling mode. Relationship between the cooling capacity output and the power input according to standard EN 14511:2008. The power input is the total power absorbed by the compressor + auxiliary circuit + part of the pump to overcome internal pressure drops

(9) ESEER coefficient of seasonal performance in cooling mode calculated according to Eurovent. Outlet water 7°C.

(10) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 10 m from the external surface of the unit in open field conditions.

functions and features

Water cooled Indoor inst. Refrig. R-410A Herm. Scroll ELFOControl Water circuit reversal(WSH-EE)

Cooling only(WSH-EE)

Heating-Cooling(WSHN-EE)

Vary Flow(17÷91)

Guida_2011_v26.indd 69Guida_2011_v26.indd 69 15/03/11 18:1215/03/11 18:12

Page 48: MSER-XEE - Amazon Simple Storage Service · the DC inverter technology applied to the compressor, ... external air temperature 7°C D.B./ 6°C W.B. A2/W55 internal ... MSER-XEE MSER-XEE

ELFO

Syst

em

70

17 21 31 41 51 61 71 81 91 101 121402 402 402 402 402 573 573 573 573 573 573602 602 602 602 602 604 604 604 604 604 604785 785 785 785 785 858 858 858 858 858 858

4 150 150 150 150 150 150 150 150 150 150 150150 150 150 150 150 150 150 150 150 150 150600 600 600 600 600 600 600 600 600 600 600300 300 300 300 300 300 300 300 300 300 300

81 83 86 90 98 114 129 147 162 164 169

78 80 83 87 95 111 126 144 159 161 166B

C

C1

B1A

A1

A2

17 21 31 41 51 61 71 81 91 101 121

4 kW 7,27 7,85 9,59 12,6 16,2 19,9 24,6 26,4 30,9 36,1 41,4kW 1,53 1,66 1,97 2,41 3,16 3,78 4,69 5,02 5,87 6,55 7,55- 4,78 4,76 4,89 5,25 5,14 5,28 5,08 5,27 5,27 5,52 5,49

4 kW 5,78 6,24 7,61 9,96 12,8 15,8 19,4 20,9 24,4 28,5 32,7kW 1,43 1,52 1,81 2,24 2,93 3,52 4,38 4,67 5,47 6,11 7,03- 4,04 4,11 4,20 4,45 4,37 4,49 4,43 4,48 4,46 4,66 4,65

4 kW 8,34 8,95 10,1 14,0 18,3 22,5 26,1 30,0 33,4 41,8 47,5kW 1,47 1,49 1,86 2,33 2,98 3,95 4,98 5,10 6,00 6,65 7,96- 5,67 6,01 5,43 6,01 6,14 5,70 5,24 5,88 5,57 6,29 5,97

4 kW 7,00 7,63 9,28 12,0 15,6 19,1 23,4 25,1 29,5 34,3 39,3kW 1,89 2,06 2,53 3,02 4,12 4,62 5,90 6,39 7,21 8,17 9,22- 3,68 3,69 3,65 3,96 3,78 4,13 3,96 3,92 4,09 4,19 4,26

4 kW 5,64 6,15 7,48 9,65 12,5 15,3 18,9 20,2 23,7 27,5 31,4kW 1,78 1,93 2,36 2,82 3,83 4,32 5,42 5,96 6,73 7,63 8,61- 3,17 3,19 3,17 3,42 3,26 3,54 3,49 3,39 3,52 3,60 3,65

4 kW 5,95 6,42 7,90 10,5 13,4 16,7 20,2 22,1 25,8 30,5 35,0kW 1,51 1,64 1,95 2,40 3,15 3,78 4,82 5,02 5,88 6,56 7,55- 3,91 3,89 4,03 4,36 4,24 4,41 4,18 4,39 4,38 4,64 4,63- 4,29 4,25 4,54 4,84 4,48 4,70 4,59 4,92 4,86 5,13 5,04

4 kW 6,65 7,37 9,03 11,5 14,8 18,0 22,4 23,8 28,2 32,1 36,6kW 2,42 2,70 3,33 3,82 5,57 5,83 7,35 8,09 8,90 10,5 11,6- 2,75 2,73 2,71 3,01 2,66 3,09 3,05 2,94 3,17 3,06 3,16

4 kW 5,56 6,10 7,44 9,50 12,3 15,0 18,6 19,8 23,3 26,8 30,6kW 2,00 2,19 2,69 3,17 4,44 4,83 6,08 6,71 7,47 8,54 9,57- 2,78 2,79 2,77 3,00 2,77 3,11 3,06 2,95 3,12 3,14 3,20°C -8 -8 -8 -8 -8 -8 -8 -8 -8 -8 -8°C 55 55 55 55 55 55 55 55 55 55 55I/s 0,35 0,38 0,46 0,61 0,78 0,95 1,18 1,28 1,50 1,71 1,91kPa 50 48 51 40 25 49 38 40 32 110 77I/s 0,29 0,31 0,38 0,51 0,63 0,77 0,96 1,06 1,22 1,39 1,56kPa 52 49 47 36 20 41 30 24 18 84 41dB(A) 26 26 27 27 28 29 32 33 34 35 36V/Ph/Hz 230/1/50 400/3/50+N

■ Accessories supplied separately.

Key to symbols:

accessories

■ 4 Serial communication module to supervisor (MODBUS)■ 4 Double temperature control kit, set point compensation 4-20 mA,

3-way valve■ 4 Phase monitor

■ 4 Set point compensation with according to outdoor enthalpy■ 4 Source side modulating valve ■ 4 Shut-off valve on source side ■ 4 Rubber antivibration mounts

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm(B1) mm(C1) mm

WSHN-EEWeight in oper. kgWSH-EEWeight in oper. kg

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

dimensions and clearancesdimensions and clearances

The above data refer to standard units.

Data referred to the following conditions:

SizesWSH-EE - Unit with water circuit reversalApplication with radiant panels

W10/W35 (1)Heating capacity (2)Total input (3)COP EUROVENT (4)B0/W35 (1)Heating capacityTotal input (3)COP EUROVENT (4)W35/W18 (1)Cooling capacity Total input (3)EER EUROVENT (7)

Application with terminal unitsW10/W45 (1)Heating capacity (2)Total input (3)COP EUROVENT (4)B0/W45 (1)Heating capacity Total input (3)COP EUROVENT (4)W35/W7 (1)Cooling capacity Total input (3)EER EUROVENT (7)ESEER (9)

Application with radiatorsW10/W55 (1)Heating capacity (2)Total input (3)COP EUROVENT (4)B0/W50 (1)Heating capacity Total input (2)COP EUROVENT (4)

Minimum water temperatureMaximum water temperatureWater flow rate - user side (6)Pump working head - user side (6)Water flow rate - source side (6)Pump working head - source side (6)Sound pressure level (10)Power supply

See notes on the previous page

Guida_2011_v26.indd 70Guida_2011_v26.indd 70 15/03/11 18:1215/03/11 18:12