REFRIGERANTRef. Line ConnectionsCouplingorConn.Size—in.GasCouplingorConn.Size—in.Liq.
DIMENSIONSCrated(In.)Uncrated
WEIGHTShipping(Lbs.)/Net(Lbs.)
GeneralData
4TEE3C01A1000A
200-230/1/60
SeeO.D.Specifications
Plate Fin3—14
3.213/8-Copper
TXV-NonBleed43/4NPT
SeeOutlineDrawing
Centrifugal10x8
1Direct - Serial ECM
See Fan Performance Table1—1/2Variable
200-230/1/604.3
YesThrowaway
1 - 20 X 20 - 1 in.
See Note 5See Note 3
R-410ABrazed
3/43/8
HxWxD44-1/2x24x23-1/2
43x21-1/2x21
142/127
4TEE3C02A1000A
200-230/1/60
SeeO.D.Specifications
Plate Fin3—14
3.93/8-Copper
TXV-NonBleed43/4NPT
SeeOutlineDrawing
Centrifugal10x10
1Direct - Serial ECM
See Fan Performance Table1—1/2Variable
200-230/1/604.3
YesThrowaway
1 - 20 X 20 - 1 in.
See Note 5See Note 3
R-410ABrazed
3/43/8
HxWxD46-1/2x26x23-1/2
45x23-1/2x21
142/127
4TEE3C03A1000A
200-230/1/60
SeeO.D.Specifications
Plate Fin3—18
5.043/8-Copper
TXV-NonBleed43/4NPT
SeeOutlineDrawing
Centrifugal11x10
1Direct - Serial ECM
See Fan Performance Table1—1/2Variable
200-230/1/604.3
YesThrowaway
1 - 20 X 20 - 1 in.
See Note 5See Note 3
R-410ABrazed
5/83/8
HxWxD59-1/2x26x23-1/257-7/8x23-1/2x21
165/155
4TEE3C04A1000A
200-230/1/60
SeeO.D.Specifications
Plate Fin3—18
5.043/8-Copper
TXV-NonBleed43/4NPT
SeeOutlineDrawing
Centrifugal11x10
1Direct - Serial ECM
See Fan Performance Table1—1/2Variable
200-230/1/604.3
YesThrowaway
1 - 20 X 20 - 1 in.
See Note 5See Note 3
R-410ABrazed
3/43/8
HxWxD59-1/2x26x23-1/257-7/8x23-1/2x21
165/155
4TEE3C05A1000A
200-230/1/60
SeeO.D.Specifications
Plate Fin4—14
5.043/8-Copper
TXV-NonBleed43/4NPT
SeeOutlineDrawing
Centrifugal10x10
1Direct - Serial ECM
See Fan Performance Table1—1/2Variable
200-230/1/604.3
YesThrowaway
1 - 20 X 25 - 1 in.
See Note 5See Note 3
R-410ABrazed
3/43/8
HxWxD53-1/4x28-1/2x23-1/2
51-3/4x26x21
174/155
1These Air Handlers are A.R.I. certified with various Split System Air Conditioners and Heat Pumps(ARISTANDARD210/240).RefertotheSplitSystemOutdoorUnitProductInformationsiteorahrinet.org.
5 Forcustomereaseoffiltermaintenance, it isrecommendedthataproperlysized,remote filter and grillebeinstalledforhorizontalapplications.Airflowshouldnotexceedthefacevalueofthefilterbeingused. The factory installed filter should then be removed from the unit.
REFRIGERANTRef. Line ConnectionsCouplingorConn.Size—in.GasCouplingorConn.Size—in.Liq.
DIMENSIONSCrated(In.)Uncrated
WEIGHTShipping(Lbs.)/Net(Lbs.)
GeneralData
4TEE3C06A1000A
200-230/1/60
SeeO.D.Specifications
Plate Fin3—14
6.193/8-Copper
TXV-NonBleed43/4NPT
SeeOutlineDrawing
Centrifugal11x10
1Direct - Serial ECM
See Fan Performance Table1—3/4Variable
200-230/1/606.8
YesThrowaway
1 - 20 X 20 - 1 in.
See Note 5See Note 3
R-410ABrazed
3/43/8
HxWxD59-1/2x26x23-1/257-7/8x23-1/2x21
170/155
4TEE3C07A1000A
200-230/1/60
SeeO.D.Specifications
Plate Fin4—14
6.193/8-Copper
TXV-NonBleed43/4NPT
SeeOutlineDrawing
Centrifugal10x10
1Direct - Serial ECM
See Fan Performance Table1—3/4Variable
200-230/1/606.8
YesThrowaway
1 - 20 X 25 - 1 in.
See Note 5See Note 3
R-410ABrazed
3/43/8
HxWxD59-1/2x28-1/2x23-1/2
57-7/8x26x21
188/173
4TEE3C08A1000A
200-230/1/60
SeeO.D.Specifications
Plate Fin3—14
6.193/8-Copper
TXV-NonBleed43/4NPT
SeeOutlineDrawing
Centrifugal11x10
1Direct - Serial ECM
See Fan Performance Table1—1
Variable200-230/1/60
7.0
YesThrowaway
1 - 20 X 20 - 1 in.
See Note 5See Note 3
R-410ABrazed
3/43/8
HxWxD59-1/2x26x23-1/257-7/8x23-1/2x21
170/155
4TEE3C09A1000A
200-230/1/60
SeeO.D.Specifications
Plate Fin4—14
7.333/8-Copper
TXV-NonBleed43/4NPT
SeeOutlineDrawing
Centrifugal10x10
1Direct - Serial ECM
See Fan Performance Table1—1
Variable200-230/1/60
7.5
YesThrowaway
1 - 20 X 25 - 1 in.
See Note 5See Note 3
R-410ABrazed
3/43/8
HxWxD63-1/4x28-1/2x23-1/2
62-3/4x26x21
218/196
4TEE3C10A1000A
200-230/1/60
SeeO.D.Specifications
Plate Fin4—14
7.333/8-Copper
TXV-NonBleed43/4NPT
SeeOutlineDrawing
Centrifugal10x10
1Direct - Serial ECM
See Fan Performance Table1—1
Variable200-230/1/60
7.5
YesThrowaway
1 - 20 X 25 - 1 in.
See Note 5See Note 3
R-410ABrazed
3/43/8
HxWxD63-1/4x28-1/2x23-1/2
62-3/4x26x21
218/196
1These Air Handlers are A.R.I. certified with various Split System Air Conditioners and Heat Pumps(ARISTANDARD210/240).RefertotheSplitSystemOutdoorUnitProductInformationsiteorahrinet.org.
5 Forcustomereaseoffiltermaintenance, it isrecommendedthataproperlysized,remote filter and grillebeinstalledforhorizontalapplications.Airflowshouldnotexceedthefacevalueofthefilterbeingused. The factory installed filter should then be removed from the unit.
Pub. No. 22-1819-04 7
PerformanceData
4TEE3C01A AIRFLOW PERFORMANCE TABLE
Airflow Performance 4TEE3C01A1: with Wet coil, No Heaters, Filter
NOTES:Airflow Demand is OD size (tons) * Speed (cfm/ton) - see Demand Airflow Chart
COMM SYS mode will auto-detect OD size, with default speed 400cfm/ton & 1.5 minute off-delayAt continuous fan setting: Airflow values are approximately 30% of listed values.
8 Pub. No. 22-1819-04
PerformanceData
4TEE3C02A AIRFLOW PERFORMANCE TABLE
Airflow Performance 4TEE3C02A1: with Wet coil, No Heaters, Filter
NOTES:Airflow Demand is OD size (tons) * Speed (cfm/ton) - see Demand Airflow Chart
COMM SYS mode will auto-detect OD size, with default speed 400cfm/ton & 1.5 minute off-delayAt continuous fan setting: Airflow values are approximately 30% of listed values.
Pub. No. 22-1819-04 9
PerformanceData
4TEE3C03A, 04A AIRFLOW PERFORMANCE TABLE
Airflow Performance 4TEE3C03A1 & 4TEE3C04A1: with Wet coil, No Heaters, Filter
NOTES:Airflow Demand is OD size (tons) * Speed (cfm/ton) - see Demand Airflow Chart
COMM SYS mode will auto-detect OD size, with default speed 400cfm/ton & 1.5 minute off-delayAt continuous fan setting: Airflow values are approximately 30% of listed values.
10 Pub. No. 22-1819-04
PerformanceData
4TEE3C05A AIRFLOW PERFORMANCE TABLE
Airflow Performance 4TEE3C05A1: with Wet coil, No Heaters, Filter
NOTES:Airflow Demand is OD size (tons) * Speed (cfm/ton) - see Demand Airflow Chart
COMM SYS mode will auto-detect OD size, with default speed 400cfm/ton & 1.5 minute off-delayAt continuous fan setting: Airflow values are approximately 30% of listed values.
Pub. No. 22-1819-04 11
4TEE3C06A AIRFLOW PERFORMANCE TABLE
Airflow Performance 4TEE3C06A1: with Wet coil, No Heaters, Filter
NOTES:Airflow Demand is OD size (tons) * Speed (cfm/ton) - see Demand Airflow Chart
COMM SYS mode will auto-detect OD size, with default speed 400cfm/ton & 1.5 minute off-delayAt continuous fan setting: Airflow values are approximately 30% of listed values.
PerformanceData
12 Pub. No. 22-1819-04
4TEE3C07A AIRFLOW PERFORMANCE TABLE
Airflow Performance 4TEE3C07A1: with Wet coil, No Heaters, Filter
NOTES:Airflow Demand is OD size (tons) * Speed (cfm/ton) - see Demand Airflow Chart
COMM SYS mode will auto-detect OD size, with default speed 400cfm/ton & 1.5 minute off-delayAt continuous fan setting: Airflow values are approximately 30% of listed values.
PerformanceData
Pub. No. 22-1819-04 13
4TEE3C08A AIRFLOW PERFORMANCE TABLE
Airflow Performance 4TEE3C08A1: with Wet coil, No Heaters, Filter
NOTES:Airflow Demand is OD size (tons) * Speed (cfm/ton) - see Demand Airflow Chart
COMM SYS mode will auto-detect OD size, with default speed 400cfm/ton & 1.5 minute off-delayAt continuous fan setting: Airflow values are approximately 30% of listed values.
PerformanceData
14 Pub. No. 22-1819-04
4TEE3C09A, 10A AIRFLOW PERFORMANCE TABLE
Airflow Performance 4TEE3C09A1 & 4TEE3C10A1: with Wet coil, No Heaters, Filter
NOTES:Airflow Demand is OD size (tons) * Speed (cfm/ton) - see Demand Airflow Chart
COMM SYS mode will auto-detect OD size, with default speed 400cfm/ton & 1.5 minute off-delayAt continuous fan setting: Airflow values are approximately 30% of listed values.
NOTES:(+) For Upflow position without heat pump, minimum setting is 1130.(***) = additional suffix digits 000, BRK or PDC - 000 = pigtails, BRK = contains circuit breakers & PDC = contains pull disconnect.
IMPORTANT: Any power supply and / or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical codes.
(***) = additional suffix digits 000, BRK or PDC - 000 = pigtails, BRK = contains circuit breakers & PDC = contains pull disconnect.IMPORTANT: Any power supply and / or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical codes.
(3) Minimum speed in downflow installations is 1400 CFM.(4) Minimum speed in downflow installations is 1100 CFM.
MIN BLOWER SPEED CAPACITY
BAYHTR1405*** 900 (1) 900
BAYHTR1408*** 900 (2) 900
BAYHTR1410*** 900 1100
circuit 1BAYHTR1415BRK
circuit 2900 (3) 1100
BAYHTR1415BRKwith single circuit power source kit
BAYSPEK140B900 (3) 1100
BAYHTR3410*** 900 1100
BAYHTR3415*** 900 (3) 1100
circuit 1BAYHTR1419BRK
circuit 2900 (4) 1100 (3)
BAYHTR1419BRKwith single circuit power source kit
BAYSPEK140B900 (4) 1100 (3)
NOTES:(1) Minimum speed in downflow and horizontal right installations is 600 CFM.(2) Minimum speed in upflow and horizontal right installations is 600 CFM.
(***) = additional suffix digits 000, BRK or PDC - 000 = pigtails, BRK = contains circuit breakers & PDC = contains pull disconnect.IMPORTANT: Any power supply and / or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical codes.
NOTES:(+) For horizontal right and downflow position, minimum speed for heat pump applications is 1100 CFM(***) = additional suffix digits 000, BRK or PDC - 000 = pigtails, BRK = contains circuit breakers & PDC = contains pull disconnect.IMPORTANT: Any power supply and / or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical codes.
IMPORTANT: Any power supply and / or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical codes.
(4) Minimum speed in downflow and upflow installations is 1400 CFM.(5) Minimum speed in horizontal left and downflow installations is 1100 CFM.(6) Minimum speed in horizontal left installations is 1100 CFM.(***) = additional suffix digits 000, BRK or PDC - 000 = pigtails, BRK = contains circuit breakers & PDC = contains pull disconnect.
NOTES:(1) Minimum speed for horizontal left installations is 1400 CFM; in horizontal right installations is 800 CFM.(2) Minimum speed for horizonotal right installations is 800 CFM.(3) Minimum speed in downflow installations is 1400 CFM.
NOTES:(***) = additional suffix digits 000, BRK or PDC - 000 = pigtails, BRK = contains circuit breakers & PDC = contains pull disconnect.IMPORTANT: Any power supply and / or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical codes.
NOTES:(1) Minimum speed in downflow installations is 1200 CFM.(2) Minimum speed in upflow installations is 900 CFM.(3) Minimum speed in upflow installations is 1500 CFM.(4) Minimum speed in horizontal left installations is 1500 CFM; in horizontal right installations is 900 CFM; in downflow installations is 1200 CFM. Minimum speed for upflow installations on 240 volts is 1800 CFM. Heater not approved for upflow installations on 208 volts.(5) Minimum speed in horizontal left installations is 1800 CFM.(***) = additional suffix digits 000, BRK or PDC - 000 = pigtails, BRK = contains circuit breakers & PDC = contains pull disconnect.IMPORTANT: Any power supply and / or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical codes.
BAYHTR1415BRK with single circuit power source kit
BAYSPEK140B1200 + 1500 +
1200 + 1500 +
BAYHTR3410*** 1200 1500
BAYHTR3415*** 1200 + 1500 +
BAYHTR1419BRK with single circuit power source kit
BAYSPEK140B1200 1500
BAYHTR1408*** 900 1200
BAYHTR1410*** 1200 1500
circuit 1BAYHTR1415BRK
circuit 2
circuit 1BAYHTR1419BRK
circuit 21200 1500
circuit 1
BAYHTR1425BRK circuit 2
circuit 3
1500 1800
NOTES:(+) For upflow applications only, minimum speed is 1500 with out heat pump and 1800 with heat pump.(***) = additional suffix digits 000, BRK or PDC - 000 = pigtails, BRK = contains circuit breakers & PDC = contains pull disconnect.IMPORTANT: Any power supply and / or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical codes.
MIN BLOWER SPEED
ElectricalData
Pub. No. 22-1819-04 23
DISTANCE FROM BELLY BAND TO SHAFT FACE OF MOTOR FOR MINIMUM VIBRATION
WHEEL
BLOWER HOUSING
BELLY BAND
MOTOR
A
A is determined per chart
Wheel is centered inBlower Housing
PerformanceData
Model Number "A" (inches)4TEE3C01 1.3754TEE3C02 1.3754TEE3C03 1.3754TEE3C04 1.3754TEE3C05 1.8754TEE3C06 2.1254TEE3C07 2.1254TEE3C08 2.1254TEE3C09 2.2504TEE3C10 2.250
FOR FACTORY OEM MOTORS
24 Pub. No. 22-1819-04
AIR HANDLER SUBBASE
FLOOR OPENING - SIZE
MODEL NO. A B
TAYBASE100 23-3/4 14-13/16
TAYBASE101 21-3/4 14-13/16
TAYBASE102 26-3/4 14-13/16
Mounting
Pub. No. 22-1819-04 25
WIRING DIAGRAM FOR COMMUNICATING VARIABLE SPEED AIR HANDLERS
WiringDiagram
26 Pub. No. 22-1819-04
FieldWiring
COMMUNICATING INDOOR UNITWITH COMMUNICATING COMFORT CONTROL
& COMMUNICATING OUTDOOR UNIT
COMMUNICATING INDOOR UNITWITH COMMUNICATING COMFORT CONTROL
SinceTrane has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice.
MechanicalSpecification Options
Features and General Information
Theseblowercoilunitsarecompletelyfactoryassembled including coil, condensate drain pan, fan, motor, and controls in an insulated casingthatcanbeappliedinhorizontalorverticalconfiguration.
These models have a rugged galvanizedsheetmetalandsteelframeconstruction.Thecasingispaintedwithanenamelfin-ish.Thecasing is insulatedandprovidesknockouts for electrical power and control wiring.
Refrigerant Circuits
The4TEE3Cunitshaveasinglerefrigerantcircuit.Therefrigerantcircuit iscontrolledby a factory installed non-bleed thermalexpansionvalve(NB-TXV).
Coil
Aluminum fin surface is mechanicallybondedto3/8-inchODcoppertubing.Coilsare factory pressure and leak tested.
Fan
Theblowerhousingisforwardcurved,dy-namicallybalancedwithavariablespeeddirectdrivefanmotor.ThevariablespeedECM fan motor is permanently lubricated.
Controls
Low voltage terminal board, fan contactor, and plug-in module for accessory electric heatcontrol is included.4TEE3Cmodelsalso have an internal check valve withintheTXV.
Electric Heaters
Heaters for the4TEE3Cairhandlersareavailable in a wide range of capacities and voltageswithvariousstagingoptions,andplug-incontrolwiring.Heatersfitinsidetheinternal compartment.