FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE 5006168-CTG-C-1015 TECHNICAL GUIDE MODULAR PSC AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: MP SERIES Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at: www.upgnet.com and www.colemanac.com Additional rating information can be found at: www.ahridirectory.org WARRANTY SUMMARY Standard 5-year limited parts warranty. Extended 10-year limited parts warranty when product is registered online within 90 days of purchase for replacement or closing for new home construction. ® DESCRIPTION This fan coil line offers the ultimate in application flexibility. This unit may be used for upflow, downflow, horizontal right, or horizontal left applications. All JCI Unitary Products air handlers and coils can use a TXV to provide our customers with the optimum performance and refrigerant control. Air handlers are shipped with “Flex-coils” without a factory installed metering device. For added flexibility, an R-22 or R-410A TXV or orifice must be field installed to meet the requirement of the desired refrigerant. FEATURES COMMON MP AIR HANDLER AND CM COIL FEATURES RC 2 - Rigid Case Construction interior endoskeleton for structural support, flush side, and locks in insulation. Powder-painted - G30 galvanized steel case provide a coated edge that resists corrosion and rust creep. Quality Construction - Structural components are made of Aluminum or G90 galvanized steel to prevent corrosion. Improved Insulation Design - Single piece with no external screws to reduce thermal transmission paths to prevent sweating. Foil faced insulation for ease of cleaning. Case Depth - These models have 20.5” casing which provide ease of attic access and tight applications. MP AIR HANDLERS Factory Sealed - Achieves 2% or less total airflow leakage rate at duct leakage test conditions in positive and negative pressure for system airflow verification. Enhanced Filter Rack - All models have integrated internal filter racks provided for use with 1” thick standard size filters. Electric Heat Kits - 6HK series of field installed electric heat kits are available for installation-friendly and easy service applications. Blowers - All models use direct-drive, multi-speed PSC motors. CM COILS MaxAlloy TM Coil - Long life aluminum coils built to deliver lasting performance, efficiency and reliability. Thermostatic Expansion Valve - The accessory bolt-on TXV provides easy installation to convert the indoor coil to the required refrigerant that does not require brazing to replace or install. Some models are available with factory installed TXV. Thermoset Drain Pan - Positive slope for drainage to reduce cause for potential mold or contaminants. Accessories - A full line of matching accessories available for use with the blower and coils to allow any type application.
14
Embed
MODULAR PSC AIR HANDLERS FOR USE WITH … DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE 5006168-CTG-C-1015 TECHNICAL GUIDE MODULAR PSC AIR HANDLERS FOR USE WITH SPLIT-SYSTEM
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
5006168-CTG-C-1015
TECHNICAL GUIDEMODULAR PSC AIR HANDLERSFOR USE WITH SPLIT-SYSTEMCOOLING & HEAT PUMPSMODELS: MP SERIES
Due to continuous product improvement, specifications are subject to change without notice.Visit us on the web at:
www.upgnet.com and www.colemanac.comAdditional rating information can be found at:
www.ahridirectory.org
WARRANTY SUMMARYStandard 5-year limited parts warranty.Extended 10-year limited parts warranty when product isregistered online within 90 days of purchase for replacementor closing for new home construction.
®
DESCRIPTIONThis fan coil line offers the ultimate in application flexibility. Thisunit may be used for upflow, downflow, horizontal right, orhorizontal left applications.All JCI Unitary Products air handlers and coils can use a TXV toprovide our customers with the optimum performance andrefrigerant control. Air handlers are shipped with “Flex-coils”without a factory installed metering device. For added flexibility,an R-22 or R-410A TXV or orifice must be field installed to meetthe requirement of the desired refrigerant.
FEATURESCOMMON MP AIR HANDLER AND CM COIL FEATURES
RC2 - Rigid Case Construction interior endoskeleton forstructural support, flush side, and locks in insulation. Powder-painted - G30 galvanized steel case provide a coatededge that resists corrosion and rust creep. Quality Construction - Structural components are made ofAluminum or G90 galvanized steel to prevent corrosion. Improved Insulation Design - Single piece with no externalscrews to reduce thermal transmission paths to preventsweating. Foil faced insulation for ease of cleaning.Case Depth - These models have 20.5” casing which provideease of attic access and tight applications.
MP AIR HANDLERSFactory Sealed - Achieves 2% or less total airflow leakage rateat duct leakage test conditions in positive and negativepressure for system airflow verification.Enhanced Filter Rack - All models have integrated internalfilter racks provided for use with 1” thick standard size filters. Electric Heat Kits - 6HK series of field installed electric heatkits are available for installation-friendly and easy serviceapplications. Blowers - All models use direct-drive, multi-speed PSC motors.
CM COILSMaxAlloyTM Coil - Long life aluminum coils built to deliverlasting performance, efficiency and reliability. Thermostatic Expansion Valve - The accessory bolt-on TXVprovides easy installation to convert the indoor coil to therequired refrigerant that does not require brazing to replace orinstall. Some models are available with factory installed TXV. Thermoset Drain Pan - Positive slope for drainage to reducecause for potential mold or contaminants.Accessories - A full line of matching accessories available foruse with the blower and coils to allow any type application.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
1. All dimensions are in inches as actual size (Dimensions in parenthesis are Conduit size).2. Refrigerant line sizes may require larger lines for extended line lengths. See York bulletin #690.01-AD1V for details.
Type DISPOSABLE OR PERMANENTSize 16 x 20 x 1 16 x 20 x 1 22 x 20 x 1 20 x 20 x 1 22 x 20 x 1Bottom Rack Kit 1BR01117 1BR01117 1BR01124 1BR01121 1BR01124Permanent Type Kit 1PF0601 1PF0601 1PF0603 1PF0602 1PF0603
1. FLA = Full Load Amps.2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. Refer to the latest edition of the National Electric Code or
in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
Johnson Controls Unitary Products 5
5006168-CTG-C-1015
ELECTRICAL HEAT - MINIMUM FAN SPEED
Heater Kit Models1,2 Nom. kW@240V
Air Handler ModelsMP08B MP12B MP14D MP16C MP20D
6HK(0,1)6500206 2.4 Low Low Low Low Low
6HK(0,1)6500506 4.8 Low Low Low Low Low
6HK(0,1)6500806 7.7 Low Low Low Low Low
6HK(0,1)6501006 9.6 Low Low Low Low Low
6HK(1,2)6501306 12.5 Med Low Low Low Low
6HK(1,2)6501506 14.4 – Med Low Low Low
6HK(1,2)6501806 17.3 – Med Low Low Low
6HK(1,2)6502006 19.2 – Med Med High Low
1. (0,1) - 0 = no circuit breaker OR 1 = with circuit breaker.2. (1,2) - 1 = with circuit breaker, no breaker jumper bar OR 2 = with circuit breaker & breaker jumper bar.
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect.2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar.3. For different power distributions, see conversion table on Page 4.
6 Johnson Controls Unitary Products
5006168-CTG-C-1015
ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY: 208/230-1-60
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect.2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar.3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps. Refer to the
latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
Johnson Controls Unitary Products 7
5006168-CTG-C-1015
ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-1-60
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect.2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar. 3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps. Refer to the lat-
est edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
kW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENTFor a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH data from the table by the conversionfactor in the following table.
DISTRIBUTION POWER NOMINAL VOLTAGE CONVERSION FACTOR208V 240V 0.75220V 240V 0.84230V 240V 0.92
APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM% Of Rated Airflow (CFM) 80% 90% 100% 110% 120%
Capacity Factor 0.96 0.98 1.00 1.02 1.03
POWER WIRING - LINE CONNECTIONS
GND.
FIELD POWER WIRING
(208/230V)
NO ELECTRIC HEAT
COMPONENT CODES
CKT - CIRCUIT
CN - WIRE CONNECTOR/NUT
GND - GROUND LUG
SD - SERVICE DISCONNECTPOWER
SUPPLYCN
CN
GND
JUMPER BAR
SINGLE SOURCE POWER MULTI-SOURCE POWERSINGLE-SOURCE POWER
WITH JUMPER BAR
TERMINAL BLOCK OR
SERVICE DISCONNECT
POWER
SUPPLY
POWER
SUPPLY
2 CIRCUITS ON 13KW-20KW
SD
SDPOWER
SUPPLY
GNDGND
L1
L2
L1
L2
L1
L2L1
L2 SD
SD
CKT 2
CKT 1
SINGLE PHASE ELECTRIC HEAT OPTIONS:
2 CIRCUITS ON 13KW-20KW
A0429-001
8 Johnson Controls Unitary Products
5006168-CTG-C-1015
ACCESSORIESRefer to Price Manual for specific model numbers where notshown.TXV Kits - Air handlers are shipped with “Flex-coils” without afactory installed metering device. For added flexibility, an R-22or R-410A TXV or orifice can be field installed to meet yourrefrigerant choice. All kits are bolt-on and require no brazing toinstall.Electric Heaters - 6HK models shown under electrical datainclude sequential operation and temperature dual limitswitches for safe, efficient operation. Service disconnects areprovided where shown.Bottom Rack Filter Kit - The filter frame accessory allowsinstallation of an external air handler filter in an upflowapplication, a downflow application, or a horizontal application(refer to the following illustration/table for Filter RackDimensions).
For upflow platform return applications, cut the hole in thereturn air platform the same size as the filter frame opening(dimensions for E x D in Table 1). DO NOT cut an oversizedhole.
Combustible Floor Base Accessory - If an electric heataccessory which is rated for greater than zero clearance tocombustible surfaces is installed in these air handlers in thedownflow operating positions on a combustible floor, one of thefollowing combustible floor base accessory models is required:S1-1FB1917, S1-1FB1921, S1-1FB1924.Breaker Moisture Seal Accessory - A clear circuit breakermoisture barrier seals the breakers from humidity and dust.The flexibility of the clear cover allows circuit breakers to beturned ON or OFF without removing the cover. The cover firmlyattaches to the access panel around the circuit breakers withthe use of double backed adhesive tape. To ensure thatmoisture or dust does not contaminate circuit breakers, an S1-02435672000, Circuit Breaker, Cover Seal may be ordered.
BLOWER SPEED CONNECTIONS
FACTORY WIRED TO
TRANSFORMER
FACTORY WIRED TO
FAN MOTOR RELAY
TERMINAL ON
CONTROL BOARD
PU
RP
UR
HIGH
MED
LOW
GND.
230 VOLT
BLOWER MOTOR
CAP
BR
N
BLK
A0342-001
PSC STANDARD MOTOR
FACTORY WIRED TO
TRANSFORMER
FACTORY WIRED TO
FAN MOTOR RELAY
TERMINAL ON
CONTROL BOARD
PSC STANDARD MOTOR
ALTERNATE CONNECTION
AP60, RFCX60, MP20
ALL OTHER AIR HANDLER
GND.
CAP
BRN
BLK
H M L
RC
PRP PRP
230 VOLT
BLOWER
MOTOR
FILTER RACK DIMENSIONS
Galvanized Models A B C D E Filer Size
1BR01117 17.50 21.56 4.00 18.63 14.25 16 x 20 x 1 or 21BR01121 21.00 21.56 4.00 18.63 17.75 20 x 20 x 1 or 21BR01124 24.50 21.56 4.00 18.63 21.25 20 x 24 x 1 or 2Note: Filters - Not supplied with kit.
NOTICEFilter frames are orientation specific. The block-off box pro-vided with the kit is to be inserted after the air filter has beeninstalled.
When attaching return air duct system to filter frame, mount-ing hardware should not have sharp extruding pointsexposed.
A
C
B
D
E
A0146-003
SIDE
TRACKS
11/16
NOTICE
Johnson Controls Unitary Products 9
5006168-CTG-C-1015
COMBUSTIBLE FLOOR BASE ACCESSORY
LIMITATIONSThese units must be wired and installed in accordance with allnational and local safety codes.Voltage limits are as follows:
Airflow must be within the minimum and maximum limitsapproved for electric heat, evaporator coils and outdoor units.
1. Air handler units have been tested to UL 1995 / CSA 22.2 standards up to 0.50" wc. external static pressure.Dry coil conditions only, tested without filters.For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Applications above 0.5" are not recommended.
1. Air handler units have been tested to UL 1995 / CSA 22.2 standards up to 0.50" wc. external static pressure.Dry coil conditions only, tested without filters.For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Applications above 0.5" are not recommended.
Johnson Controls Unitary Products 13
WIRING DIAGRAM
BLOWERMOTORRC
XFORMER
BLK
RED/WHT
RED/WHT
PRP
PRPBLU/WHT
BLU/WHT
GR
N F
AN
BRN
WHT
ORG
RE
D 2
4V (H
OT)
BLU
24V
(CO
M)
ELE
CTR
IC H
EA
T1s
t STA
GE
AU
XIL
IAR
Y H
EA
T2n
d S
TAG
E
BRN
GR
N
PRP
BLK
H M L
EQUIPMENTGROUND
BLK
RED/WHT{
208-
240
VA
C 6
0HZ
1 P
HA
SE
SU
PP
LY
24V
240VCOM
208V
XFORMER
BLOWERMOTOR
N.O.N.C.
COMBLOWERCONTROLRELAY
RE
D
GR
N
BLU
WH
T
BR
NBLO
WE
R C
ON
TRL
CO
IL
USE COPPER CONDUCTORS ONLY.IF ALUMINUM CONDUCTORS ARE PRESENT,ALL APPLICABLE LOCAL AND NATIONALCODES MUST BE FOLLOWED.
SEE INSTALLATION INSTRUCTIONS FOR PROPERLOW VOLTAGE FIELD WIRING CONNECTIONS.
WHEN INSTALLING HEATER KIT, BE SURE THE BLOWER SPEED IS SET TO THE SPEED SPECIFIED FOR THE AIR HANDLER/HEATER KITCOMBINATION ON THIS UNIT'S INSTALLATION INSTRUCTIONS.