Modern Control Systems (MCS) Dr. Imtiaz Hussain Assistant Professor email: [email protected] URL :http://imtiazhussainkalwar.weebly.co m/ Lecture-12-13-14-15 Lead Compensation
Feb 22, 2016
Modern Control Systems (MCS)
Dr. Imtiaz HussainAssistant Professor
email: [email protected] :http://imtiazhussainkalwar.weebly.com/
Lecture-12-13-14-15Lead Compensation
Lecture Outline
• Introduction to Lead Compensation
• Electronic Lead Compensator
• Electrical Lead Compensator
• Mechanical Lead Compensator
Lead Compensation
• Lead Compensation essentially yields an appreciable improvement in transient response and a small change in steady state accuracy.
• There are many ways to realize lead compensators and lag compensators, such as electronic networks using operational amplifiers, electrical RC networks, and mechanical spring-dashpot systems.
Lead Compensation
• Generally Lead compensators are represented by following transfer function
• or
, ()
, ()
Lead Compensation
, ()
-10 -8 -6 -4 -2 0-1
-0.5
0
0.5
1Pole-Zero Map
Real Axis
Imag
inar
y A
xis
-20
-15
-10
-5
0
Mag
nitu
de (d
B)
10-2
10-1
100
101
102
103
0
30
60Ph
ase
(deg
)
Bode Diagram
Frequency (rad/sec)
Electronic Lead Compensator• Following figure shows an electronic lead compensator using
operational amplifiers.
𝐸𝑜(𝑠)𝐸𝑖 (𝑠)
=𝑅2𝑅4
𝑅1𝑅3
𝑅1𝐶1𝑠+1𝑅2𝐶2𝑠+1
Electronic Lead Compensator
• This can be represented as
• Where,
• Then,
𝐸𝑜(𝑠)𝐸𝑖 (𝑠)
=𝑅2𝑅4
𝑅1𝑅3
𝑅1𝐶1𝑠+1𝑅2𝐶2𝑠+1
𝐸𝑜(𝑠)𝐸𝑖 (𝑠)
=𝑅4𝐶1
𝑅3𝐶2
𝑠+ 1𝑅1𝐶1
𝑠+ 1𝑅2𝐶2
𝑇=𝑅1𝐶1 𝑎𝑇=𝑅2𝐶2 𝐾 𝑐=𝑅4𝐶1
𝑅3𝐶2
, ()
𝑅1𝐶1>𝑅2𝐶2
Electronic Lead Compensator
• Pole-zero Configuration of Lead Compensator
𝑅1𝐶1>𝑅2𝐶2
Lead Compensation Techniques Based on the Root-Locus Approach.
• The root-locus approach to design is very powerful when the specifications are given in terms of time-domain quantities, such as
– damping ratio– undamped natural frequency– desired dominant closed-loop poles– maximum overshoot– rise time– settling time.
Lead Compensation Techniques Based on the Root-Locus Approach.
• The procedures for designing a lead compensator by the root-locus method may be stated as follows:
– Step-1: Analyze the given system via root locus.
Step-2
• From the performance specifications, determine the desired location for the dominant closed-loop poles.
Step-3• From the root-locus plot of the uncompensated system
(original system), ascertain whether or not the gain adjustment alone can yield the desired closed loop poles.
• If not, calculate the angle deficiency.
• This angle must be contributed by the lead compensator if the new root locus is to pass through the desired locations for the dominant closed-loop poles.
Step-4• Assume the Lead Compensator to be:
• Where α and T are determined from the angle deficiency.
• Kc is determined from the requirement of the open-loop gain.
Step-5• If static error constants are not specified, determine the
location of the pole and zero of the lead compensator so that the lead compensator will contribute the necessary angle.
• If no other requirements are imposed on the system, try to make the value of α as large as possible.
• A larger value of α generally results in a larger value of Kv, which is desirable.
• Larger value of α will produce a larger value of Kv and in most cases, the larger the Kv is, the better the system performance.
Step-6
• Determine the value of Kc of the lead compensator from the magnitude condition.
Final Design check
• Once a compensator has been designed, check to see whether all performance specifications have been met.
• If the compensated system does not meet the performance specifications, then repeat the design procedure by adjusting the compensator pole and zero until all such specifications are met.
Final Design check
• If the selected dominant closed-loop poles are not really dominant, or if the selected dominant closed-loop poles do not yield the desired result, it will be necessary to modify the location of the pair of such selected dominant closed-loop poles.
Example-1• Consider the position control system shown in following
figure.
• It is desired to design an Electronic lead compensator Gc(s) so that the dominant closed poles have the damping ratio 0.5 and undamped natural frequency 3 rad/sec.
Step-1 (Example-1)• Draw the root Locus plot of the given system.
)1(10)()(
ss
sHsG
• The closed loop transfer function of the given system is:
• The closed loop poles are
1010
)()(
2
sssRsC
1225.35.0 js
Step-1 (Example-1)• Determine the characteristics of given system using root loci.
• The damping ratio of the closed-loop poles is 0.158.
• The undamped natural frequency of the closed-loop poles is 3.1623 rad/sec.
• Because the damping ratio is small, this system will have a large overshoot in the step response and is not desirable.
1010
)()(
2
sssRsC
Step-2 (Example-1)• From the performance specifications, determine the
desired location for the dominant closed-loop poles.
• Desired performance Specifications are: It is desired to have damping ratio 0.5 and undamped natural
frequency 3 rad/sec.
939
2)()(
222
2
sssssRsC
nn
n
5981.25.1 js
Step-2 (Example-1)• Alternatively desired location of closed loop poles can also
be determined graphically
Desired ωn= 3 rad/sec
Desired damping ratio= 0.5
1cos
60)5.0(cos 1
Desired Closed Loop
Pole
60
Step-3 (Exampl-1)• From the root-locus plot of the uncompensated system
ascertain whether or not the gain adjustment alone can yield the desired closed loop poles.
Desired Closed Loop
Pole
Step-3 (Exampl-1)• If not, calculate the angle deficiency. • To calculate the angle of deficiency apply Angle Condition at desired
closed loop pole.
-1
5981.25.1 js Desired Closed Loop Pole
-1
-2
-2
120o100.8o
8.100120180d
89.40d
Step-3 (Exampl-1)
• Alternatively angle of deficiency can be calculated as.
5981.25.1 js Where are desired closed loop poles
5981.25.1)1(10180
jsd ss
5981.25.15981.25.1)1(10180
jsjsd ss
8.100120180d
89.40d
Step-4 (Exampl-1)• This angle must be contributed by the lead
compensator if the new root locus is to pass through the desired locations for the dominant closed-loop poles.
• Note that the solution to such a problem is not unique. There are infinitely many solutions.
Step-5 (Exampl-1)• Solution-1
– If we choose the zero of the lead compensator at s = -1 so that it will cancel the plant pole at s =-1, then the compensator pole must be located at s =-3. 89.40
Solution-1
Step-5 (Example-1)• If static error constants are not specified, determine the
location of the pole and zero of the lead compensator so that the lead compensator will contribute the necessary angle.
89.40
Solution-1
Step-5 (Example-1)• The pole and zero of compensator are determined as
89.40
=
1𝑇=1 yields
→𝑇=1
1𝛼𝑇=3yields
→𝛼=0.333
• The Value of can be determined as
Solution-1
Step-6 (Example-1)
89.40
• The Value of Kc can be determined using magnitude condition.
𝐺𝑐 (𝑠 )=0.9 𝑠+1𝑠+3
|𝐾 𝑐(𝑠+1)𝑠+3
10𝑠 (𝑠+1)|𝑠=− 1.5+ 𝑗2.5981
=1
|𝐾 𝑐10
𝑠(𝑠+3)|𝑠=−1.5+ 𝑗2.5981=1
𝐾 𝑐=|𝑠(𝑠+3)10 |𝑠=−1.5+ 𝑗 2.5981
=0.9
Solution-1
Final Design Check• The open loop transfer function of the designed system
then becomes
• The closed loop transfer function of compensated system becomes.
𝐺𝑐 (𝑠 )𝐺(𝑠)= 9𝑠 (𝑠+3)
𝐶 (𝑠)𝑅(𝑠)
= 9𝑠2+3 𝑠+9
Solution-1
Final Design Check
𝐺𝑐 (𝑠)𝐺(𝑠)= 9𝑠 (𝑠+3)
Solution-1
𝐺 (𝑠 )=10
𝑠 (𝑠+1)
-4 -3 -2 -1 0 1-5
0
5
0.158
0.158
3.16
3.16
Root Locus
Real Axis
Imag
inar
y Ax
is
-4 -3 -2 -1 0 1-5
0
5
0.5
0.5
3
3
Root Locus
Real Axis
Imag
inar
y Ax
is
Final Design Check• The static velocity error constant for original system is
obtained as follows.
• The steady state error is then calculated as
𝑒𝑠𝑠= 1𝐾 𝑣
=110=0.1
𝐾 𝑣= lim𝑠→ 0
𝑠𝐺(𝑠)
𝐾 𝑣= lim𝑠→ 0
𝑠 [ 10𝑠(𝑠+1) ]=10
Solution-1
Final Design Check Solution-1
0 2 4 6 8 10 12 140
0.2
0.4
0.6
0.8
1
1.2
1.4
Step Response
Time (sec)
Ampl
itude
Actual SystemCompensated System
Final Design Check• The static velocity error constant for the compensated
system can be calculated as
• The steady state error is then calculated as
𝑒𝑠𝑠= 1𝐾 𝑣
=13=0.333
𝐾 𝑣= lim𝑠→0
𝑠𝐺𝑐 (𝑠 )𝐺(𝑠)
𝐾 𝑣=lim𝑠→ 0
𝑠 [ 9𝑠(𝑠+3) ]=3
Solution-1
Step-5 (Exampl-1)• Solution-2
Solution-2
-1
-1
-2
-2
90o
49.2o
-3
89.40
Step-5 (Exampl-1)• Solution-2
-1
-1
-2
-2
90o
49.2o
-3
89.40
Solution-2
𝐺𝑐 (𝑠)=1.03 𝑠+1.5𝑠+3.6
Step-5 (Example-1)• If no other requirements are imposed on the system, try to make
the value of α as large as possible. A larger value of α generally results in a larger value of Kv, which is desirable.
• Procedure to obtain a largest possible value for α.– First, draw a horizontal line passing through point P, the desired location for
one of the dominant closed-loop poles. This is shown as line PA in following figure.
– Draw also a line connecting point P and the origin O.
-1
-1
-2
-2
-3 O
AP
Solution-3
Step-5 (Example-1)• Bisect the angle between the lines PA and PO, as shown in following
figure.
-1
-1
-2
-2
-3 O
PA
2
2
Solution-3
Step-5 (Example-1)
• Draw two lines PC and PD that make angles with the the bisector PB.
• The intersections of PC and PD with the negative real axis give the necessary locations for the pole and zero of the lead network.
-1
-1
-2
-2
B
-3 O
PA
C
D
2d
2d
Solution-3
Step-5 (Example-1)• The lead compensator has zero at s=–1.9432 and pole at s=–4.6458.
• Thus, Gc(s) can be given as
-1
-1
-2
-2
B
-3 O
PA
C
D
2d
2d
=
Solution-3
Step-5 (Example-1)
• For this compensator value of is
• Also
=
1𝑇=1.9432 yields
→𝑇=0.514
1𝛼𝑇=4.6458 yields
→𝛼=0.418
Solution-3
Step-6 (Example-1)• Determine the value of Kc of the lead compensator from
the magnitude condition.
𝐺 (𝑠)𝐺𝑐 (𝑠 ) 𝐻 (𝑠)= 10𝐾 𝑐(𝑠+1.9432)𝑠(𝑠+1)(𝑠+4.6458)
| 10𝐾 𝑐 (𝑠+1.9432)𝑠(𝑠+1)(𝑠+4.6458)|𝑠=−1.5+ 𝑗 2.5981=1
Solution-3
Step-6 (Example-1)• The Kc is calculated as
• Hence, the lead compensator Gc(s) just designed is given by
𝐾 𝑐=1.2287
𝐺𝑐 (𝑠)=1.2287 𝑠+1.9432𝑠+4.6458
Solution-3
Final Design Check
Desired Closed Loop
Pole
Uncompensated System
Desired Closed Loop
Pole
Compensated System
Solution-3
Final Design Check• It is worthwhile to check the static velocity error
constant Kv for the system just designed.
• Steady state error is
94
𝐾 𝑣= lim𝑠→0
𝑠𝐺𝑐 (𝑠 )𝐺(𝑠)
𝐾 𝑣=lim𝑠→0
𝑠 [1.2287 𝑠+1.9432𝑠+4.6458
10𝑠(𝑠+1) ]=5.139
Solution-3
Final Design Check Solution-3
0 2 4 6 8 10 12 140
0.2
0.4
0.6
0.8
1
1.2
1.4
Step Response
Time (sec)
Ampl
itude
Actual SystemSolution-3
Final Design Check
0 2 4 6 8 10 12 140
0.2
0.4
0.6
0.8
1
1.2
1.4
Step Response
Time (sec)
Ampl
itude
Actual SystemSolution-1Solution-3
Solution-1
Solution-3
Mechanical Lead Compensator
• Figure shows the mechanical lead compensator.• Equations are obtained as
• Taking Laplace transform of these equations assuming zero initial conditions and eliminating Y(s), we obtain
Mechanical Lead Compensator
• By defining
• We obtain
Exampl-2• Design a mechanical lead compensator for following
system.
• The damping ratio of closed loop poles is 0.5 and natural undamped frequency 2 rad/sec. It is desired to modify the closed loop poles so that natural undamped frequency becomes 4 rad/sec without changing the damping ratio.
)2(4ss
Electrical Lead Compensator
𝑉 𝑜(𝑠)𝑉 𝑖 (𝑠) 𝑐
=𝑅2
𝑅1+𝑅2
𝑅1𝐶𝑠+1𝑅1𝑅2
𝑅1+𝑅2𝐶𝑠+1
𝑉 𝑜(𝑠)𝑉 𝑖 (𝑠 )
C 𝑎𝑇=𝑅1𝑅2𝐶𝑅1+𝑅2 1𝑎=
𝑅2
𝑅1+𝑅2
Example-3• Consider the model of space vehicle control system
depicted in following figure.
• Design an Electrical lead compensator such that the damping ratio and natural undamped frequency of dominant closed loop poles are 0.5 and 2 rad/sec.
END OF LECTURES-12-13-14-15
To download this lecture visithttp://imtiazhussainkalwar.weebly.com/