Micrologic Trip Unit for Masterpact and CompactSelection guide
Combine safety and performanceMasterpact and Compact Micrologic trip units provide outstanding protection as well as an integrated measurement unit to help you monitor power conditions and manage energy consumption.
Power metering and control > Advanced protection
> Alarming and programmable contact
> Cost allocation
> Diagnostic and maintenance
> Continuity of service
> Load trend monitoring
> Integration in a supervision and control system
through communication (SCADA, DCS, etc.)
> Management of energy quality.
Industry
Critical Power > Power availability
> Suitable for specific and advanced protection
> Diagnostic and maintenance
> Load trend monitoring
> Integration in a supervision and control system
through communication
> Management of energy quality.
IT
High current protection > Specific motor protection
> Total discrimination
> Diagnostic and maintenance
> Optimized size solution
> Integration in a supervision and control system
through communication (SCADA, DCS, etc.)
> Continuity of service.
Marine
Power management and monitoring > Optimize power consumption
> Cost allocation
> Integration in a Building Management System
through communication.
Building & Infrastructure
A = Current measurementE = Energy measurementP = Power measurementH = Harmonic measurementM = Motor protectionWithout = No measurement
L = Long time protectionS = Short time protectionI = Instantaneous protectionG = Ground fault protectionV = Earth Leakage protection
5 . 0 EType of measurement
Type of current protection
Version
M i c r o l o g i c Micrologic 2.0
.4.5.6
.7.8
.9.95.98
1
x Ir
22.5
3 4 56
8101.5
setting
Isd
.512
48
121620
instantaneous
long timealarmIr tr
(s)
x In at 6 Ir24
Micrologic 5.0 A
40
100%
%
menu
delay
short timetsd(s)
long timealarmtr
(s)
setting
.4.5.6
.7.8
.9.95.98
1
Ir
x In .512
4 8 121620
at 6 Ir24
x Ir
22.5
3 4 568
10
Isd
1.5on I2t
.2
.4 .4
.1
.3
.10
I i
x In
3
4
8
off2
.3
instantaneous
.26
15
1012
2100A
Micrologic 6.0 E
40
100%
%
delay
short time
on I2t
.2
.3.4 .4
.1
.2
.10
long timealarm
ground fault
setting
4
test
.4.5.6
.7.8
.9.95.98
1
Ir
x In .512
48
121620
tr(s)
at 6 Ir24
x Ir
22.5
3 4 568
10
Isd
1.5
tsd(s)
x In
3
68 10
1215
off2
BC
D E FGH
I
Ig
Aon I2t
.2
.3.4 .4
.1
.2.3
.10off
tg(s)
.1
.3instantaneous
I i
menu
MWh
_ _5.678
Micrologic 7.0 P
.4.5.6
.7.8
.9.95.98
1
delay
short timeI itsd
(s)
on I2t
.2
.3.4 .4
.1
.2.3
.10off
instantaneous
long timealarmIr
x In
settingx Ir
22.5
34 5
68
10
Isd
1.5
.512
48
121620
tr(s)
@ 6 Ir24
800
earth leakage
12
35 7
1020
30
∆t(ms)
60.5
140
230 350
I∆n(A)
x In
test
2
410
3
6 8
12
15off
4260AN 1 2 3
100
50
0
4200AN 1 2 3
100
50
0
Micrologic 5.0 H
without A E P H
2: Distribution L, I 2.0 2.0 2.0
5: Selective L, S, I 5.0 5.0 5.0 5.0 5.0
6: Selective and earth-fault protection L, S, I, G 6.0 6.0 6.0 6.0 6.0
7: Selective protection with earth-leakage protection L, S, I, V 7.0 7.0 7.0
Micrologic offer for Masterpact & Compact NS
5 . 3 EType of measurement
Type of current protection
Basic Frame Size
M i c r o l o g i c
M without A E
1: Motors I 1.3
2: Distribution L, I 2.2** – 2.3*
5: Selective L, S, I 5.2 – 5.3 5.2 – 5.3
6: Selective and earth-fault protection L, S, I, G 6.2 – 6.3 6.2* – 6.3*
Micrologic offer for Compact NSX
* Motor protection available – ** Generator and motor protection available
Combine safety and performanceMasterpact and Compact Micrologic trip units provide outstanding protection as well as an integrated measurement unit to help you monitor power conditions and manage energy consumption.
Power metering and control > Advanced protection
> Alarming and programmable contact
> Cost allocation
> Diagnostic and maintenance
> Continuity of service
> Load trend monitoring
> Integration in a supervision and control system
through communication (SCADA, DCS, etc.)
> Management of energy quality.
Industry
Critical Power > Power availability
> Suitable for specific and advanced protection
> Diagnostic and maintenance
> Load trend monitoring
> Integration in a supervision and control system
through communication
> Management of energy quality.
IT
High current protection > Specific motor protection
> Total discrimination
> Diagnostic and maintenance
> Optimized size solution
> Integration in a supervision and control system
through communication (SCADA, DCS, etc.)
> Continuity of service.
Marine
Power management and monitoring > Optimize power consumption
> Cost allocation
> Integration in a Building Management System
through communication.
Building & Infrastructure
07-2012EDCED112019EN
Make the most of your energy™www.schneider-electric.com
35, rue Joseph MonierCS 30323F- 92506 Rueil Malmaison Cedex
RCS Nanterre 954 503 439 Capital social 896 313 776 ewww.schneider-electric.com
Printed on ecological paper
Schneider Electric Industries SASAs standards, specifications and designs change from time to time, please ask for confirmationof the information given in this publication.
> Pre Alarm Ir > Current measurement > Communication Modbus, Modbus TCP/IP
> Basic protection (LSIG), > Trip alarm, trip pre alarm > Current, voltage, power factor measurement > Power and energy metering > Power and current demand > "Quickview" function for the automatic cyclical display of the most useful values
> Programmable contacts (trip cause, pre alarm) > Maintenance information (load profile, operation counter, trip history)
> Communication Modbus, Modbus TCP/IP
Micrologic E + > Residual earth leakage protection (V) > IDMTL long time protection > Protection and functions advanced (over voltage, reverse power, load shedding, etc.)
> Programmable contacts (over consumption, rotation phase, max frequency, etc.)
> Maintenance information (wear contact, alarm history, etc.)
> Communication Modbus, Modbus TCP/IP
Micrologic P + > Power quality: Harmonic individual up to 31st order, fundamentals, THD, etc.)
> Wave form capture after fault, alarm or on request
> Enhanced alarm programming: thresholds and actions
> Communication Modbus, Modbus TCP/IP
t
I
Im
0
1.3-M Distribution and motors
Not Applicable
t
I
Isd
Ir
0
2.2 Distribution2.2 AB Service connection (public distribution)2.2 G Generators2.2 M Motors
2.3 Distribution2.3 AB Service connection (public distribution)2.3 M Motors
> Pre Alarm Ir > Current measurement > Communication Modbus, Modbus TCP/IP
> Basic protection (LSIG), > Trip alarm, trip pre alarm > Current, voltage, power factor measurement > Power and energy metering > Power and current demand > "Quickview" function for the automatic cyclical display of the most useful values
> Programmable contacts (trip cause, pre alarm) > Maintenance information (load profile, operation counter, trip history)
> Communication Modbus, Modbus TCP/IP
Micrologic E + > Residual earth leakage protection (V) > IDMTL long time protection > Protection and functions advanced (over voltage, reverse power, load shedding, etc.)
> Programmable contacts (over consumption, rotation phase, max frequency, etc.)
> Maintenance information (wear contact, alarm history, etc.)
> Communication Modbus, Modbus TCP/IP
Micrologic P + > Power quality: Harmonic individual up to 31st order, fundamentals, THD, etc.)
> Wave form capture after fault, alarm or on request
> Enhanced alarm programming: thresholds and actions
> Communication Modbus, Modbus TCP/IP
t
I
Im
0
1.3-M Distribution and motors
Not Applicable
t
I
Isd
Ir
0
2.2 Distribution2.2 AB Service connection (public distribution)2.2 G Generators2.2 M Motors
2.3 Distribution2.3 AB Service connection (public distribution)2.3 M Motors
> Pre Alarm Ir > Current measurement > Communication Modbus, Modbus TCP/IP
> Basic protection (LSIG), > Trip alarm, trip pre alarm > Current, voltage, power factor measurement > Power and energy metering > Power and current demand > "Quickview" function for the automatic cyclical display of the most useful values
> Programmable contacts (trip cause, pre alarm) > Maintenance information (load profile, operation counter, trip history)
> Communication Modbus, Modbus TCP/IP
Micrologic E + > Residual earth leakage protection (V) > IDMTL long time protection > Protection and functions advanced (over voltage, reverse power, load shedding, etc.)
> Programmable contacts (over consumption, rotation phase, max frequency, etc.)
> Maintenance information (wear contact, alarm history, etc.)
> Communication Modbus, Modbus TCP/IP
Micrologic P + > Power quality: Harmonic individual up to 31st order, fundamentals, THD, etc.)
> Wave form capture after fault, alarm or on request
> Enhanced alarm programming: thresholds and actions
> Communication Modbus, Modbus TCP/IP
t
I
Im
0
1.3-M Distribution and motors
Not Applicable
t
I
Isd
Ir
0
2.2 Distribution2.2 AB Service connection (public distribution)2.2 G Generators2.2 M Motors
2.3 Distribution2.3 AB Service connection (public distribution)2.3 M Motors
> Pre Alarm Ir > Current measurement > Communication Modbus, Modbus TCP/IP
> Basic protection (LSIG), > Trip alarm, trip pre alarm > Current, voltage, power factor measurement > Power and energy metering > Power and current demand > "Quickview" function for the automatic cyclical display of the most useful values
> Programmable contacts (trip cause, pre alarm) > Maintenance information (load profile, operation counter, trip history)
> Communication Modbus, Modbus TCP/IP
Micrologic E + > Residual earth leakage protection (V) > IDMTL long time protection > Protection and functions advanced (over voltage, reverse power, load shedding, etc.)
> Programmable contacts (over consumption, rotation phase, max frequency, etc.)
> Maintenance information (wear contact, alarm history, etc.)
> Communication Modbus, Modbus TCP/IP
Micrologic P + > Power quality: Harmonic individual up to 31st order, fundamentals, THD, etc.)
> Wave form capture after fault, alarm or on request
> Enhanced alarm programming: thresholds and actions
> Communication Modbus, Modbus TCP/IP
t
I
Im
0
1.3-M Distribution and motors
Not Applicable
t
I
Isd
Ir
0
2.2 Distribution2.2 AB Service connection (public distribution)2.2 G Generators2.2 M Motors
2.3 Distribution2.3 AB Service connection (public distribution)2.3 M Motors