    INTRODUCTION

    This section briefly describes the Boiler and various auxiliaries in the Boiler

    Room.

    A boiler is an enclosed vessel that provides a means for combustion heat to be

    transferred to water until it becomes heated water or steam. The hot water or steam

    under pressure is then usable for transferring the heat to a process. Water is a useful

    and inexpensive medium for transferring heat to a process. When water at

    atmospheric pressure is boiled into steam its volume increases about 1,600 times,

    producing a force that is almost as explosive as gunpowder. This causes the boiler to

    be an equipment that must be treated with utmost care.

    The boiler system comprises of: a feed water system, steam system and fuel

    system. The feed water system provides water to the boiler and regulates it

    automatically to meet the steam demand. Various valves provide access for

    maintenance and repair. The steam system collects and controls the steam produced in

    the boiler. Steam is directed through a piping system to the point of use. Throughout

    the system, steam pressure is regulated using valves and checked with steam pressure

    gauges. The fuel system includes all equipment used to provide fuel to generate the

    necessary heat. The equipment required in the fuel system depends on the type of fuel

    used in the system.

    The water supplied to the boiler that is converted into steam is called feed

    water. The two sources of feed water are: (1) Condensate or condensed steam returned

    from the processes and (2) Makeup water (treated raw water) which must come from

    outside the boiler room and plant processes. For higher boiler efficiencies, an

    economizer preheats the feed water using the waste heat in the flue gas.

  • 8/11/2019 Mech Report Edit Final

    2/48

    TYPES OF BOILER

    This section describes the various types of boilers: Fire tube boiler, Water tube

    boiler, Packaged boiler, Fluidized bed combustion boiler, Stoker fired boiler,

    Pulverized fuel boiler, Waste heat boiler and Thermic fluid heater.

    2.1 FIRE TUBE BOILER

    In a fire tube boiler, hot gases pass through thetubesand boiler feed water in

    the shell side is converted into steam. Fire tube boilers are generally used for

    relatively small steam capacities and low to medium steam pressures. As a guideline,

    fire tube boilers are competitive for steam rates up to 12,000 kg/hour

    andpressures up to 18 kg/cm2. Fire tubeboilers are available for operation with

    oil, gas or solid fuels. For economic reasons,most fire tube boilers are of

    packaged construction (i.e. manufacturer erected) for all fuels.

  • 8/11/2019 Mech Report Edit Final

    3/48

    2.2 Water Tube Boiler

    In a water tube boiler, boiler feed water flows through the tubes and enters the

    boiler drum. The circulated water is heated by the combustion gases and converted

    into steam at the vapour space in the drum. These boilers are selected when the steam

    demand as well as steam pressure requirements are high as in the case of process cum

    power boiler / power boilers.

    Most modern water boiler tube designsare within the capacity range 4,500

    120,000 kg/hour of steam, at very high pressures. Many water tube boilers are of

    packaged construction if oil and /or gas are to be used as fuel. Solid fuel fired water

    tube designs are available but packaged designs are less common.

    The features of water tube boilers are:

    Forced, induced and balanced draft provision help to improve combustion

    efficiency.

    Less tolerance for water quality calls for water treatment plant.

    Higher thermal efficiency levels are possible

  • 8/11/2019 Mech Report Edit Final

    4/48

    2.3 Packaged Boiler

    The packaged boiler is so called because it comes as a complete package.

    Once delivered to a site, it requires only the steam, water pipe work, fuel supply and

    electrical connections to be made to become operational. Package boilers are

    generally of a shell type with a fire tube design so as to achieve high heat transfer

    rates by both radiation and convection.

    The features of packaged boilers are:

    Small combustion space and high heat release rate resulting in faster evaporation.

    Large number of small diameter tubes leading to good convective heat transfer.

    Forced or induced draft systems resulting in good combustion efficiency.

    Number of passes resulting in better overall heat transfer.

    Higher thermal efficiency levels compared with other boiler.

  • 8/11/2019 Mech Report Edit Final

    5/48

    These boilers are classified based on the number of passes - the number of

    times the hot combustion gases pass through the boiler. The combustion chamber is

    taken, as the first pass after which there may be one, two or three sets of fire-tubes.

    The most common boiler of this class is a three-pass unit with two sets of fire-tubes

    and with the exhaust gases exiting through the rear of the boiler.

    2.4 Fluidized Bed Combustion (FBC) Boiler

    Fluidized bed combustion (FBC) has emerged as a viable alternative and has

    significant advantages over a conventional firing system and offers multiple benefits

    compact boiler design, fuel flexibility, higher combustion efficiency and reduced

    emission of noxious pollutants such as SO2and NO2. The fuelsburnt in these boilers

    include coal, washer rejects, rice husk, biogases& other agricultural wastes. The

    fluidized bed boilers have a wide capacity range- 0.5 T/hr to over 100 T/hr.When an

    evenly distributed air or gas is passed upward through a finely divided bed of solid

    particles such as sand supported on a fine mesh, the particles are undisturbed at low

    velocity. As air velocity is gradually increased, a stage is reached when the individual

    particles are suspended in the air streamthe bed is called fluidized.

    With further increase in air velocity, there is bubble formation, vigorous

    turbulence, rapid mixing and formation of dense defined bed surface. The bed of solid

    particles exhibits the properties of a boiling liquid and assumes the appearance of a

    fluidbubbling fluidized bed.

    If sand particles in a fluidized state are heated to the ignition temperatures of

    coal, and coal is injected continuously into the bed, the coal will burn rapidly and the

    bed attains a uniform temperature. The fluidized bed combustion (FBC) takes place at

    about 8400c to 9500c. Since this temperature is much below the ash fusion

    temperature, melting of ash and associated problems are avoided.

    The lower combustion temperature is achieved because of high coefficient of

    heat transfer due to rapid mixing in the fluidized bed and effective extraction of heat

    from the bed through in-bed heat transfer tubes and walls of the bed. The gas velocity

    is maintained between minimum fluidization velocity and particle entrainment

  • 8/11/2019 Mech Report Edit Final

    6/48

    velocity. This ensures stable operation of the bed and avoids particle entrainment in

    the gas stream.

    Most operational boiler of this type is of the Atmospheric Fluidized Bed

    Combustion. (AFBC). This involves little more than adding a fluidized bed combustor

    to a conventional shell boiler. Such systems have similarly being installed in

    conjunction with conventional water tube boiler.

    Coal is crushed to a size of 1 10 mm depending on the rank of coal, type of

    fuel fed to the combustion chamber. The atmospheric air, which acts as both the

    fluidization and combustion air, is delivered at a pressure, after being preheated by the

    exhaust fuel gases. The in-bed tubes carrying water generally act as the evaporator.

    The gaseous products of combustion pass over the super heater sections of the boiler

    flowing past the economizer, the dust collectors and the air pre-heater before being

    exhausted to atmosphere.

    2.4.1Pressurized Fluidized Bed Combustion (PFBC) Boiler

    In Pressurized Fluidized Bed Combustion (PFBC) type, a compressor supplies

    the Forced Draft (FD) air and the combustor is a pressure vessel. The heat release rate

    in the bed is proportional to the bed pressure and hence a deep bed is used to extract

    large amounts of heat. This will improve the combustion efficiency and sulphur

    dioxide absorption in the bed. The steam is generated in the two tube bundles, one in

    the bed and one above it. Hot flue gases drive a power generating gas turbine. The

    PFBC system can be used for cogeneration (steam and electricity) or combined cycle

    power generation. The combined cycle operation (gas turbine & steam turbine)

    improves the overall conversion efficiency by 5 to 8 percent.

  • 8/11/2019 Mech Report Edit Final

    7/48

    2.4.2Atmospheric Circulating Fluidized Bed Combustion Boilers (CFBC)

    In a circulating system the bed parameters are maintained to promote solids

    elutriationfrom the bed.

    They are lifted in a relatively dilute phase in a solids riser, and a down-

    comerwith a cyclone provides a return path for thesolids.There are no steam

    generation tubes immersedin the bed. Generation and superheating of steam takes

    place in the convection section, water walls, at the exit of the riser.CFBC boilers are

    generally more economical than AFBC boilers for industrial application requiring

    more than 75100 T/hr of steam. For large units, the taller furnace characteristics of

    CFBC boilers offers better space utilization, greater fuel particle and sorbent

    residence time for efficient combustion and SO2 capture, and easier application of

    staged combustion techniques for NO2control than AFBC steam generators.

  • 8/11/2019 Mech Report Edit Final

    8/48

    2.5 Pulverized Fuel Boiler

    Most coal-fired power station boilers use pulverized coal, and many of the

    larger industrial water-tube boilers also use this pulverized fuel. This technology is

    well developed, and there are thousands of units around the world, accounting for

    well over 90 percent of coal-fired capacity.

    The coal is ground (pulverized) to a fine powder, so that less than 2 percent is

    +300 micrometre (m) and 70-75 percent is below 75 microns, for a bituminous coal.

    It should be noted that too fine a powder is wasteful of grinding mill power. On

    the other hand, too coarse a powder does not burn completely in the combustion

    chamber and results in higher unburnt losses.

    The pulverized coal is blown with part of the combustion air into the boiler

    plant through a series of burner nozzles. Secondary and tertiary air may also be added.

    Combustion takes place at temperatures from 1300-1700 C, depending largely on

    coal grade.Particle residence time in the boiler is typically 2 to 5 seconds, and the

    particles must be small enough for completecombustion to have taken place during

    this time.

  • 8/11/2019 Mech Report Edit Final

    9/48

    This system has many advantages such as ability to fire varying quality of

    coal, quick responses to changes in load, use of high pre-heat air temperatures etc.One

    of the most popular systems for firing pulverized coal is the tangential firing using

    four burners corner to corner to create a fireball at the centre of the furnace.

    2.6 Waste Heat Boiler

    Wherever the waste heat is available atmedium or high temperatures,

    a waste heat boiler can be installed economically.

    Wherever the steam demand is more than the steam generated during waste heat,auxiliary fuelburners are also used.If there is no direct use of steam, the steam may be

    let down in a steam turbine- generator setand power produced from it.It is widely used

    in the heat recovery from exhaust gases from gas turbineand diesel engine.

  • 8/11/2019 Mech Report Edit Final

    10/48

    BOILER INDUSTRY RAKHOH INDUSRIES PVT.LTD

    This section gives the details about RAKHOH INDUSRIES PVT.LTD. Its

    the location, mode of transport, capacity and establishment of plant.

    3.1 RAKHOH Boilers

    RAKHOH is a 30 years old an ISO 9001:2008 Certified Companyby TUV

    NORD. It is inprocess of obtaining U STAMP, S STAMP AND R STAMP

    THESAME WILL BE AN ADDED FEATHER TO THERE CAP and will further

    improve of capabilities to cater the Domestic as well as International market. It is

    engaged in manufacturing of wide range of Steam boilers with fuel range consisting

    of furnace Oil, LDO, Heavy Fuel Oil, Natural gas and solid fuels like Coal, Wood,

    Baggase, Rice Husks etc. It also manufacture Waste Heat Recovery Systems, Thermic

    Fluid heaters, Thermic Fluid Steam boiler & Hot Water Boilers, Coded Pressure

    Vessels, Storage Tanks, Structural, Water Tube Boiler Components like, Convection

    Tubes, Headers, Super Heater Coils, Economizer Coils, Drums, Boiler accessories

    like Economizers, Air pre-heaters, Wind Turbine equipments, carriers and High

    capacity Tower and Nacelle Lifting Jigs etc.

    3.2 Location

    Company is located in the heart of Punes Industrial Area with apresent

    working area of 1,00,000 Sq. ft. and is managed andcontrolled by experienced

    technocrats each of them follows the corporate philosophy, to achieve the desired goal

    and also satisfy the customers.The mainmanufacturing unit of RAKHOH is located at

    MIDC Bhosari,Pimrichinchwad,Pune.

    3.3. Testing facility

    a) Facilities available in house

    1). Hydraulic Test up to 500 Kg / Cm2.

    2). Pneumatic Test: up to 100 PSI

  • 8/11/2019 Mech Report Edit Final

    11/48

    3). Dye Penentrant Test

    4). Soap Bubble Test.

    5). Hardness Test.

    b) Facilities available on contract

    (Lloyds / IBR approved agency)

    1. Radiography

    2. Ultrasonic Test

    3. Magnetic Test

    4. Chemical Test

    5. Physical Test

    6. Heat- Treatment

    7. Mechanical Testing

    8. Normalizing

    9. Sand Blasting

    Rakhoh truly adherersto it tagline

    WHEN IT COMESTO FUEL ECONOMY. ITS RAKHOH

  • 8/11/2019 Mech Report Edit Final

    12/48

    Heat loss due to dr flue as

    Heat loss due to stem in flue gas

    Heat loss due to moisture in fuel

    Heat loss due to moisture in air

    Heat loss due to unburnt in residue

    Heat loss due to radiation & other

    Heat in steam

    Fuel

    CHAPTER 4

    ASSESSMENT OF A BOILER

    This section describes the Performance evaluation of boilers (through the

    direct and indirect method including examples for efficiency calculations), boiler

    blow down, and boiler water treatment.

    4.1. Performance Evaluation of a Boiler

    The performance parameters of a boiler, like efficiency and evaporation ratio,reduces with time due to poor combustion, heat transfer surface fouling and poor

    operation and maintenance. Even for a new boiler, reasons such as deteriorating fuel

    quality and water quality can result in poor boiler performance. A heat balance helps

    us to identify avoidable and unavoidable heat losses. Boiler efficiency tests help us to

    find out the deviation of boiler efficiency from the best efficiency and target problem

    area for corrective action.

    4.1.1 Heat balance

    The combustion process in a boiler can be described in the form of an

    energy flow diagram. This shows graphically how the input energy from the

    fuel is transformed into the various useful energy flows and into heat and

    energy loss flows.

    12.7% 8.1%

    100% BOILER 1.7%

    0.3% 2.4%

    0.3%

    73%

    Figure12.TypicalLossesfromCoalFiredBoiler

  • 8/11/2019 Mech Report Edit Final

    13/48

    The thickness of the arrows indicates the amount of energy contained in the

    respective A heat balance is an attempt to balance the total energy entering a boiler

    against that leaving the boiler in different forms. The following figure illustrates the

    different losses occurring for generating steam

    The energy losses can be divided in unavoidable and avoidable losses. The goal of a

    Cleaner Production and/or energy assessment must be to reduce the avoidable losses,

    i.e. to improve energy efficiency. The following losses can be avoided or reduced:

    Stack gas losses: Excess air (reduce to the necessary minimum which depends

    from burner technology, operation, operation (i.e. control) and maintenance).

    Stack gas temperature (reduce by optimizing maintenance (cleaning), load;

    better burner and boiler technology).

    Losses by unburnt fuel in stack and ash (optimize operation and

    maintenance; better technology of burner).

    Blow down losses (treat fresh feed water, recycle condensate)

    Condensate losses (recover the largest possible amount of condensate)

    Convection and radiation losses (reduced by better insulation of the boiler).

    Definition of Boiler Efficiency is The percentage of the total absorption heating

    value of outlet Steam in the total supply heating value.In other word, it is a rate

    how the boiler runs efficiently.

    There are two method of assessing boiler efficiency:

    1.The Direct Method: The energy gain of the working fluid (Water and Steam) is

    compared with the energy content of the boiler fuel.

    2.The indirect Method: The efficiency is the difference between the losses and the

    energy input.

  • 8/11/2019 Mech Report Edit Final

    14/48

    Methodology

    A. Direct Method of determining boiler efficiency

    This is also known as input output method due to that fact that it need only the

    useful output (steam) and the heat input (i.e. fuel) for evaluating the efficiency.

    This efficiency can be evaluated using the formula:

    Boiler efficiency = (heat output/heat input) *100

    Boiler efficiency = (Q *(hghf))/ (q*GCV)*100

    Parameters to be monitored for the calculation of boiler efficiency by direct methodare:

    Quantity of steam generated per hour (Q) in kg/hr.

    Quantity of fuel used per hour (q) in kg/hr.

    The working pressure (in kg /cm2(g) and superheat temperature (C) , if any

    The temperature of feed water (C0)

    Type of fuel and gross calorific value of the fuel (GCV) in kcal/ kg of fuel

    Boiler efficiency = {Qg*(hg- hf) / q* GCV} * 100

    and where

    HgEnthalpy of saturated steam in kcal/kg of steam

    HfEnthalpy of feed water in kcal/kg of water

    Example

    Find out the efficiency of the boiler by direct method with the the data given

    below:

    Type of boiler: - coal fired

    Quantity of steam (dry) generated 10TPH

    Steam pressure (gauge)/temp 10kg/cm2(g)/180 C

    Quantity of cola consumed 2.25TPH

  • 8/11/2019 Mech Report Edit Final

    15/48

    Feed water temperature 85

    GCV of coal 3200kcal/kg

    Enthalpy of steam at 10 kg/cm2pressure 665kcal/kg

    Enthalpy of feed water 85 kcal/kg

    Boiler efficiency

    = [8*(665-85)*1000] / [1.8* 3200*1000]*100 = 80%

    It should be noted that boiler may not generate 100% saturated dry steam, and there

    may be some amount of wetness in the steam

    Advantage of direct method

    Plant workers can evaluate quickly the efficiency of boiler

    Require few parameters for computations.

    Needs few instrument for monitoring.

    Easy to compare various evaporation accountable for various efficiency level.

    Disadvantage of direct method

    Does not give clue to the operator as to why efficiency of the system is lower

    Does not calculate various losses accountable for various efficiency level

    B. Indirect Method

  • 8/11/2019 Mech Report Edit Final

    16/48

    The reference standards for Boiler Testing at Site using indirect method namely

    British Standard, BS 845: 1987 and USA Standard is ASME PTC-4-1 Power

    Test Code Steam Generating Units.

    The Indirect method is also called as heat loss method. The efficiency can be

    arrived at, by subtracting the heat loss fractions from 100. The standards do not

    include blow down loss in the efficiency determination process. A detailed

    procedure for calculating boiler efficiency by indirect method is given below.

    However, it may be noted that the practicing energy mangers in industries prefer

    simpler calculation procedures .

    The principle losses that occur in a boiler are:

    Loss of heat due to dry flue gas.

    Loss of heat due to moisture in fuel and combustion air.

    Loss of heat due to combustion of hydrogen.

    Loss of heat due to radiation.

    Loss of heat due to unburnt.

    In the above, loss due to moisture in fuel and the loss due to combustion of

    hydrogen are dependent on the fuel, and cannot be controlled by design.

    The data required for calculation of boiler efficiency using indirect method are:

    Ultimate analysis of fuel (H2, O2, S, C, moisture content, ash content).

    Percentage of Oxygen or CO2 in the flue gas.

    Flue gas temperature in C0(Tf).

    Ambient temperature in C0(Ta) & humidity of air in kg/kg of dry air.

    GCV of fuel in kcal/kg.

    Percentage combustible in ash (in case of solid fuels).

    GCV of ash in kcal/kg (in case of solid fuels).

  • 8/11/2019 Mech Report Edit Final

    17/48

  • 8/11/2019 Mech Report Edit Final

    18/48

    = (M * {584 + Cp(Tf-Ta)}/ GCV of fuel *100

    Where,

    MKg of moisture in 1kg of fuel

    CpSpecific heat of superheated steam (0.45 kcal/kg) 0C

    d) Percentage heat loss due to moisture present in air

    = {AAS * humidity factor * Cp* (Tf-Ta)}*100/GCV of fuel

    CpSpecific heat of superheated steam (0.45 kcal/kg)

    e) Percentage heat loss due to unburnt in fly ash

    = (Total ash collected /kg of fuel burnt* GCV of fly ash)/

    GCV of fuel*100

    f) Percentage heat loss due to unburnt in bottom ash

    = (Total ash collected /kg of fuel burnt* GCV of bottom ash)/

    GCV of fuel *100

    g) Percentage heat loss due to radiation and other unaccounted loss

    The actual radiation and convection losses are difficult to assess because of

    particular emissivity of various surfaces, its inclination, air flow pattern etc. In a

    relatively small boiler, with a capacity of 10 MW, the radiation and unaccounted

    losses could amount to between 1% and 2% of the gross calorific value of the fuel,

    while in a 500 MW boiler, values between 0.2% to 1% are typical. The loss may be

    assumed appropriately depending on the surface condition.

  • 8/11/2019 Mech Report Edit Final

    19/48

    5) Boiler efficiency and Boiler evaporation ratio

    Efficiency of boiler = 100- (a+b+c+d+e+f+g)

    Evaporation ratio = heat utilized for steam generation/Heat addition to steam.

    Evaporation ratio means kilogram of steam generated per kilogram of fuel consumed.

    Typical Ex: Coal fired boiler: 6 (1 kg of coal can generate 6 kg of steam)

    Oil fired boiler: 13(1 kg of oil can generate 13 kg of steam)

    However, this figure will depend upon type of boiler, calorific value of the fuel and

    associated efficiencies.

    Example:

    The following are the data collected for a typical oil fired boiler. Find

    out the efficiency of the boiler by indirect method and Boiler Evaporation

    ratio.

    Type of boiler : Oil fired

    Ultimate analysis of Oil

    C: 84.0 % H2: 12.0%

    S: 3.0 % O2: 1.0 %

    GCV of Oil : 1020kcal/kg

    Steam Generation Pressure: 7kg/cm2 (g)

    -saturated

    Enthalpy of steam : 660 Kcal/kg

    Feed water temperature: 60oC

  • 8/11/2019 Mech Report Edit Final

    20/48

    Percentage of Oxygen in flue gas: 7

    Percentage of CO2 in flue gas : 11

    Flue gas temperature (Tf : 220 0C

    Ambient temperature (Ta): 27 0C

    Humidity of air: 0.018 kg/kg of Dry air

    Solution:-

    Step-1: Find the theoretical air requirement

    = [(11.6*C) + {34.8*(H2-O2/8)} + (4.35*S)]/100 kg/kg of oil

    = [(11.6*84) + {34.8*(12-1/8)} + (4.35*3)]/100 kg/kg of oil

    = 14 kg of air /kg of fuel

    Step-2: Find the %Excess air supplied

    Excess air supplied (EA) = (O2%)/ (21-O2%)*100

    = 7 %/( 21-7)*100

    = 50%

    Step-3: Find the Actual mass of air supplied

    Actual mass of air supplied /kg of fuel = [1 + EA/100] x Theoretical Air

    (AAS) = [1 + 50/100] x 14

    = 1.5 x 14

    = 21 kg of air/kg of oil

    Step-4: Estimation of all losses

  • 8/11/2019 Mech Report Edit Final

    21/48

    i. Dry flue gas loss

    Percentage heat loss due to dry flue gas = {m*Cp*(Tf-Ta)}/GCV of fuel * 100

    m= mass of CO2 + mass of SO2 + mass of N2 + mass of O2

    m = (0.84*44/12) + (0.03*64)/32+ (21*77)/100+ ((21-4)*(23/100)7)

    m= 21 kg /kg of oil

    = (21*0.23*(220-27))/10200*100

    =9.57%

    ii. Heat loss due to evaporation of water formed due to H2 in fuel

    =[(9*H2*{584+Cp(Tf-Ta)})/GCV of fuel] /100

    Where,

    H2percentage of H2in fuel

    = [(9*12*{584+0.45(220-27)})/10200] /100

    =7.10%

    iii. Heat loss due to moisture present in air

    = [(AAS*humidity *Cp*(TfTa))/GCV of fuel]/100

    = [(21*0.018*0.45*(220-27)/10200]*100

    =0.322

    iv. Heat loss due to radiation and other unaccounted losses

    For a small boiler it is estimated to be 2%

  • 8/11/2019 Mech Report Edit Final

    22/48

    5) Boiler Efficiency and boiler evaporation ratio

    i. Heat loss due to dry flue gas: 9.14%

    ii. Heat loss due to evaporation of water formed due to H2 in fuel: 7.10 %

    iii. Heat loss due to moisture present in air: 0.322 %

    iv. Heat loss due to radiation and other unaccounted loss: 2%

    Boiler Efficiency

    = 100- [9.14+7.10+0.322+2]

    = 10018.56 = 81 (app)

    EvaporationRatio

    =Heatutilizedforsteamgeneration/Heatadditiontothesteam

    =10200x0.83/(660-60)

    =14.11(comparedto13foratypicaloilfiredboiler)

    CHAPTER 5

  • 8/11/2019 Mech Report Edit Final

    23/48

    ENERGY EFFICIENCY OPPORTUNITIES

    This section includes energy efficiency opportunities related to combustion,heat transfer, avoidable losses, auxiliary power consumption, water quality and blow

    down. Energy losses and therefore energy efficiency opportunities in boilers can be

    related to combustion, heat transfer, avoidable losses, high auxiliary power

    consumption, water quality and blow down.

    The various energy efficiency opportunities in a boiler system can be related

    to:

    1.

    Stack temperature control

    2.

    Feed water preheating using economizers

    3.

    Combustion air pre-heating

    4.

    Incomplete combustion minimization

    5.

    Excess air control

    6.

    Radiation and convection heat loss avoidance

    7.

    Automatic blow down control

    8.

    Reduction of scaling and soot losses9.

    Reduction of boiler steam pressure

    10.

    Variable speed control for fans, blowers and pumps

    11.

    Controlling boiler loading

    12.

    Proper boiler scheduling

    13.

    Boiler replacement

    These are explained in the sections below.

    5.1 Stack Temperature Control

    The stack temperature should be as low as possible. However, it should not be

    so low that water vapour in the exhaust condenses on the stack walls. This is

    important in fuels containing significant sulphur as low temperature can lead to

  • 8/11/2019 Mech Report Edit Final

    24/48

    sulphur dew point corrosion. Stack temperatures greater than 200C indicates

    potential for recovery of waste heat. It also indicates the scaling of heat

    transfer/recovery equipment and hence the urgency of taking an early shut down for

    water / flue side cleaning.

    5.2Feed Water Preheating using Economizers

    Typically, the flue gases leaving a modern 3-pass shell boiler are at temperatures

    of 200 to300 oC. Thus, there is a potential to recover heat from these gases. The flue

    gas exit temperature from a boiler is usually maintained at a minimum of 200 oC, so

    that the sulphuroxides in the flue gas do not condense and cause corrosion in heattransfer surfaces. When a clean fuel such as natural gas, LPG or gas oil is used, the

    economy of heat recovery must be worked out, as the flue gas temperature may be

    well below 200 oC.

    The potential for energy savings depends on the type of boiler installed and the

    fuel used. For a typically older model shell boiler, with a flue gas exit temperature of

    260 oC, an economizer could be used to reduce it to 200 oC, increasing the feed water

    temperature by 15 oC. Increase in overall thermal efficiency would be in the order of 3

    percent. For a modern 3-pass shell boiler firing natural gas with a flue gas exit

    temperature of 140 oC a condensing economizerwould reduce the exit temperature to

    65 oC increasing thermal efficiency by 5 percent.

    5.3Combustion Air Preheating

    Combustion air preheating is an alternative to feed water heating. In order to

    improve thermal efficiency by 1 percent, the combustion air temperature must be

    raised by 20oC. Most gas and oil burners used in a boiler plant are not designed for

    high air-preheat temperatures.Modern burners can withstand much higher combustion

    air preheat, so it is possible to consider such units as heat exchangers in the exit flue

    as an alternative to an economizer, when either space or a high feed water return

    temperature make it viable.

  • 8/11/2019 Mech Report Edit Final

    25/48

    5.4Incomplete Combustion Minimization

    Incomplete combustion can arise from a shortage of air or surplus of fuel or poor

    distribution of fuel. It is usually obvious from the colour or smoke, and must be

    corrected immediately.In the case of oil and gas fired systems, CO or smoke (for oil

    fired systems only) with normal or high excess air indicates burner system problems.

    A more frequent cause of incomplete combustion is the poor mixing of fuel and air at

    the burner. Poor oil fires can result from improper viscosity, worn tips, carbonization

    on tips and deterioration of diffusers or spinner plates.With coal firing, unburned

    carbon can comprise a big loss. It occurs as grit carry-over or carbon-in-ash and may

    amount to more than 2 percent of the heat supplied to the boiler. Non-uniform fuel

    size could be one of the reasons for incomplete combustion. In chain grate stokers,

    large lumps will not burn out completely, while small pieces and fines may block the

    air passage, thus causing poor air distribution. In sprinkler stokers, stoker grate

    condition, fuel distributors, wind box air regulation and over-fire systems can affect

    carbon loss. Increase in the fines in pulverized coal also increases carbon loss.

    5.5Excess Air Control

    The table below gives the theoretical amount of air required for combustion of

    various types of fuel.Excess air is required in all practical cases to ensure complete

    combustion, to allow for the normal variations in combustion and to ensure

    satisfactory stack conditions for some fuels. The optimum excess air level for

    maximum boiler efficiency occurs when the sum of the losses due to incomplete

    combustion and loss due to heat in flue gases is minimized. This level varies with

    furnace design, type of burner, fuel and process variables. It can be determined by

    conducting tests with different air fuel ratios.

  • 8/11/2019 Mech Report Edit Final

    26/48

    THEORETICAL COMBUSTION DATA

    COMMON BOILER FUELS

    (National Productivity Council, field experience)

    Fuel kg of air req./kg

    of fuel

    CO2 percent in flue gas

    achieved in practice

    Solid Fuels

    3.3 10-12

    Bagasse

    Coal (bituminous) 10.7 10-13

    Lignite 8.5 9 -13

    Paddy Husk 4.5 14-15

    Wood 5.7 11.13

    Liquid Fuels 13.8 9-14

    Furnace Oil

    LSHS 14.1 9-14

    TYPICAL VALUES OF EXCESS AIR

    LEVELS FOR DIFFERENT FUELS

    (National Productivity Council, field

    experience)

    Fuel Type of Furnace or

    Burners

    Excess Air

    (percent by

    wt)

    Pulverized coal Completely water-cooled furnace for

    slag-tap or dry-ash removal

    15-20

    Partially water-cooled furnace for 15-40

  • 8/11/2019 Mech Report Edit Final

    27/48

    dry-ash removal

    Coal Spreader stoker 30-60

    Water-cooler vibrating-grate stokers 30-60

    Chain-grate and traveling-grate

    stokers

    15-50

    Underfeed stoker 20-50

    Fuel oil Oil burners, register type 15-20

    Multi-fuel burners and flat-flame 20-30

    Natural gas High pressure burner 5-7

    Wood Dutch over (10-23 percent through

    grates) and Hofft type

    20-25

    Bagasse All furnaces 25-35

    Black liquor Recovery furnaces for draft and soda-

    pulping processes

    30-40

    Controlling excess air to an optimum level always results in reduction in flue gas

    losses; for every 1 percent reduction in excess air there is approximately 0.6 percent

    rise in efficiency.

    Various methods are available to control the excess air:

    1.

    Portable oxygen analyzers and draft gauges can be used to make periodic

    readings to guide the operator to manually adjust the flow of air for optimum

    operation. Excess air reduction up to 20 percent is feasible.

    2.

    The most common method is the continuous oxygen analyzer with a

    local readoutmounted draft gauge, by which the operator can adjust air flow.

    A further reduction of 10- 15 percent can be achieved over the previous

    system.

    3.

    The same continuous oxygen analyzer can have a remote controlled pneumatic

  • 8/11/2019 Mech Report Edit Final

    28/48

    damper positioner, by which the readouts are available in a control room. This

    enables an operator to remotely control a number of firing systems

    simultaneously.

    4.

    The most sophisticated system is the automatic stack damper control, whose

    costis really justified only for large systems.

    5.6 Radiation and Convection Heat Loss Avoidance

    The external surfaces of a shell boiler are hotter than the surroundings. The

    surfaces thus lose heat to the surroundings depending on the surface area and the

    difference in temperature between the surface and the surroundings.

    The heat loss from the boiler shell is normally a fixed energy loss, irrespective of

    the boiler output. With modern boiler designs, this may represent only 1.5 percent on

    the gross calorific value at full rating, but will increase to around 6 percent, if the

    boiler operates at only 25 percent output.Repairing or augmenting insulation canreduce heat loss through boiler walls and piping.

    5.7 Automatic Blow down Control

    Uncontrolled continuous blow down is very wasteful. Automatic blow down

    controls can be installed that sense and respond to boiler water conductivity and pH.

    A 10 percent blow down in a 15 kg/cm2 boiler results in 3 percent efficiency loss.

    5.8

    Reduction of Scaling and Soot Losses

    In oil and coal-fired boilers, soot build-up on tubes acts as an insulator against

    heat transfer. Any such deposits should be removed on a regular basis. Elevated stack

    temperatures may indicate excessive soot build-up. Also same result will occur due to

  • 8/11/2019 Mech Report Edit Final

    29/48

    scaling on the water side. High exit gas temperatures at normal excess air indicate

    poor heat transfer performance. This condition can result from a gradual build-up of

    gas-side or waterside deposits. Waterside deposits require a review of water treatment

    procedures and tube cleaning to remove deposits.

    An estimated 1 percent efficiency loss occurs with every 22oC increase in stack

    temperature.

    Stack temperature should be checked and recorded regularly as an indicator of

    soot deposits. When the flue gas temperature rises to about 20 oC above the

    temperature for a newly cleaned boiler, it is time to remove the soot deposits. It is

    therefore recommended to install a dial type thermometer at the base of the stack to

    monitor the exhaust flue gas temperature.

    It is estimated that 3 mm of soot can cause an increase in fuel consumption by 2.5

    percent due to increased flue gas temperatures. Periodic off-line cleaning of radiant

    furnace surfaces, boiler tube banks, economizers and air heaters may be necessary to

    remove stubborn deposits.

    5.9 Reduction of Boiler Steam Pressure

    This is an effective means of reducing fuel consumption, if permissible, by as

    much as 1 to 2 percent. Lower steam pressure gives a lower saturated steam

    temperature and without stack heat recovery, a similar reduction in the temperature of

    the flue gas temperature results.

    Steam is generated at pressures normally dictated by the highest pressure /

    temperature requirements for a particular process. In some cases, the process does not

    operate all the time, and there are periods when the boiler pressure could be reduced.

    But it must be remembered that any reduction of boiler pressure reduces the specific

    volume of the steam in the boiler, and effectively derates the boiler output. If the

    steam load exceeds the rerated boiler output, carryover of water will occur. The

    energy manager should therefore consider the possible consequences of pressure

  • 8/11/2019 Mech Report Edit Final

    30/48

    reduction carefully, before recommending it. Pressure should be reduced in stages,

    and no more than a 20 percent reduction should be considered.

    5.10

    Variable Speed Control for Fans, Blowers and Pumps

    Variable speed control is an important means of achieving energy savings.

    Generally, combustion air control is affected by throttling dampers fitted at forced and

    induced draft fans. Though dampers are simple means of control, they lack accuracy,

    giving poor control characteristics at the top and bottom of the operating range. In

    general, if the load characteristic of the boiler is variable, the possibility of replacing

    the dampers by a VSD should be evaluated.

    5.11

    Controlling Boiler Loading

    The maximum efficiency of the boiler does not occur at full load, but at about

    two-thirds of the full load. If the load on the boiler decreases further, efficiency also

    tends to decrease. At zero output, the efficiency of the boiler is zero, and any fuel

    fired is used only to supply the losses. The factors affecting boiler efficiency are:

    1.

    As the load falls, so does the value of the mass flow rate of the flue gases

    through thetubes. This reduction in flow rate for the same heat transfer area

    reduces the exit flue gas temperatures by a small extent, reducing the sensible

    heat loss.

    2.

    Below half load, most combustion appliances need more excess air to

    burn the fuelcompletely. This increases the sensible heat loss.

    In general, efficiency of the boiler reduces significantly below 25 percent of the

    rated load and operation of boilers below this level should be avoided as far as

    possible.

  • 8/11/2019 Mech Report Edit Final

    31/48

    5.12Proper Boiler Scheduling

    Since, the optimum efficiency of boilers occurs at 65-85 percent of full load, it is

    usually more efficient, on the whole, to operate a fewer number of boilers at higher

    loads, than to operate a large number at low loads.

    5.13Boiler Replacement

    The potential savings from replacing a boiler depend on the anticipated change

    in overall efficiency. A change in a boiler can be financially attractive if the existing

    boiler is:

    1.

    Old and inefficient

    2.

    Not capable of firing cheaper substitution fuel

    3.

    Over or under-sized for present requirements4.

    Not designed for ideal loading conditions

    The feasibility study should examine all implications of long-term fuel availability

    and company growth plans. All financial and engineering factors should be

    considered. Since boiler plants traditionally have a useful life of well over 25 years,

    replacement must be carefully studied.

    CHAPTER6

    OPTION CHECKLIST

    This section includes the most common options for improving a boilers

    energy efficiency.

  • 8/11/2019 Mech Report Edit Final

    32/48

    6.1Periodic tasks and checks outside of the boiler

    1. All access doors and plate work should be maintained air tight with effective

    gaskets.

    2. Flue systems should have all joints sealed effectively and be insulated where

    appropriate.

    3.

    Boiler shells and sections should be effectively insulated. Is existing insulation

    adequate?If insulation was applied to boilers, pipes and hot water cylinders

    several years ago, it is almost certainly too thin even if it appears in good

    condition. Remember, it was installed when fuel costs were much lower.

    Increased thickness may well be justified.

    4.

    At the end of the heating season, boilers should be sealed thoroughly, internal

    surfaceseither ventilated naturally during the summer or very thoroughly

    sealed with tray of desiccant inserted. (Only applicable to boilers that will

    stand idle between heating seasons)

    6.2

    Boilers: extra items for steam raising and hot water boilers

    1. Check regularly for build-up of scale or sludge in the boiler vessel or check

    TDS of boiler water each shift, but not less than once per day. Impurities in

    boiler water are concentrated in the boiler and the concentration has limits that

    depend on type of boiler and load. Boiler blow down should be minimized, but

    consistent with maintaining correct water density. Recover heat from blow

    down water.

    2. With steam boilers, is water treatment adequate to prevent foaming or

    priming andconsequent excessive carryover of water and chemicals into the

    steam system?

    3. For steam boilers:- are automatic water level controllers operational? The

    presence of inter-connecting pipes can be extremely dangerous.

    4.

    Have checks been made regularly on air leakages round boiler

  • 8/11/2019 Mech Report Edit Final

    33/48

    inspection doors, orbetween boiler and chimney? The former can reduce

    efficiency; the latter can reduce draught availability and may encourage

    condensation, corrosion and smutting.

    5. Combustion conditions should be checked using flue gas analyzers at

    least twice perseason and the fuel/air ratio should be adjusted if required.

    6.

    Both detection and actual controls should be labeled effectively and checked

    regularly.

    7. Safety lockout features should have manual re-set and alarm features.

    8. Test points should be available, or permanent indicators should be fitted to oil

    burners to give operating pressure/temperature conditions.

    9. With oil-fired or gas-fired boilers, if cables of fusible link systems for

    shutdown due to fire or overheating run across any passageway accessible to

    personnel, they should be fitted above head level.

    10.The emergency shut down facility is to be situated at the exit door of the boiler

    house.

    11.In order to reduce corrosion, steps should be taken to minimize the periods

    when water return temperatures fall below dew point, particularly on oil and

    coal fired boilers.

    12.

    Very large fuel users may have their own weighbridge and so can operate a

    direct checkon deliveries. If no weighbridge exists, occasionally ask your

    supplier to run via a public weighbridge (or a friendly neighbor with a

    weighbridge) just as a check? With liquid fuel deliveries check the vehicles

    dipsticks?

    13.

    With boiler plant, ensure that the fuel used is correct for the job. With solid

    fuel, correct grading or size is important, and ash and moisture content should

    be as the plant designeroriginally intended. With oil fuel, ensure that viscosity

    is correct at the burner, and check the fuel oil temperature.

    14.The monitoring of fuel usage should be as accurate as possible. Fuel stock

    measurementsmust be realistic.

    15.With oil burners, examine parts and repairs. Burner nozzles should be changed

    regularly and cleaned carefully to prevent damage to burner tip.

    16.Maintenance and repair procedures should be reviewed especially for burner

    equipment,controls and monitoring equipment.

    17.Regular cleaning of heat transfer surfaces maintains efficiency at the highest

  • 8/11/2019 Mech Report Edit Final

    34/48

    possible level.

    18.Ensure that the boiler operators are conversant with the operational

    procedures, especiallyany new control equipment.

    19.Have you investigated the possibility of heat recovery from boiler exit gases?

    Modern heat exchangers/ remunerators are available for most types and sizes

    of boiler.

    20.Do you check feed and header tanks for leaking make up valves, correct

    insulation or loss of water to drain?

    21.The manufacturer may have originally provided the boiler plant with

    insulation. Is thisstill adequate with todays fuel costs? Check on optimum

    thickness.

    22.

    If the amount of steam produced is quite large, invest in a steam meter.

    23.Measure the output of steam and input of fuel. The ratio of steam to fuel is the

    main measure of efficiency at the boiler.

    24.

    Use the monitoring system provided: this will expose any signs of

    deterioration.

    25.Feed water should be checked regularly for both quantity and purity.

    26.

    Steam meters should be checked occasionally as they deteriorate with time

    due to erosion of the metering orifice or pilot head. It should be noted that

    steam meters only give correct readings at the calibrated steam pressure.

    Recalibration may be required.

    27.Check all pipe work, connectors and steam traps for leaks, even in inaccessible

    spaces.

    28.

    Pipes not in use should be isolated and redundant pipes disconnected.

    29.Is someone designated to operate and generally look after the installation?

    This work should be included in their job specification.

    30.

    Are basic records available to that person in the form of drawings,

    operationalinstructions and maintenance details?

    31.Is a log book kept to record details of maintenance carried out, actual

    combustion flue gas readings taken, fuel consumption at weekly or monthly

    intervals, and complaints made?

    32.Ensure that steam pressure is no higher than need be for the job. When night

    load is materially less than day load, consider a pressure switch to allow

    pressure to vary over a much wider band during night to reduce frequency of

  • 8/11/2019 Mech Report Edit Final

    35/48

    burner cut-out, or limit the maximum firing rate of the burner.

    33.Examine the need for maintaining boilers in standby conditionsthis is

    often anunjustified loss of heat. Standing boilers should be isolated on the

    fluid and gas sides.

    34.Keep a proper log of boiler house activity so that performance can be

    measured against targets. When checking combustion, etc. with portable

    instruments, ensure that this is done regularly and that load conditions are

    reported in the log: percentage of CO2 at full flame/half load, etc.

    35.Have the plant checked to ensure that severe load fluctuations are not caused

    by incorrect operation of auxiliaries in the boiler house, for example, ON/OFF

    feed control, defective modulating feed systems or incorrect header design.

    36.

    Have hot water heating systems been dosed with an anti-corrosion additive

    and is this checked annually to see that concentration is still adequate? Make

    sure that this additives NOT put into the domestic hot water heater tank, it will

    contaminate water going to taps at sinks and basins.

    37.Recover all condensate where practical and substantial savings are possible.

    6.3

    Boiler rooms and plant rooms

    1.

    Ventilation openings should be kept free and clear at all times and the

    opening area should be checked to ensure this is adequate.

    2.

    Plant rooms should not be used for storage, airing or drying purposes.

    3.

    Is maintenance of pumps and automatic valves carried out in accordance

    with the manufacturers instructions?

    4.

    Are run and standby pump units changed over approximately once per month?

    5.

    Are pump isolating valves provided?

    6. Are pressure/heat test points and/or indicators provided on each side of the

    pump?

    7. Are pump casings provided with air release facilities?

    8. Are moving parts (e.g. couplings) guarded?

    9.

    Ensure that accuracy of the instruments is checked regularly.10.Visually inspect all pipe work and valves for any leaks.

  • 8/11/2019 Mech Report Edit Final

    36/48

    11.

    Check that all safety devices operate efficiently.

    12.

    Check all electrical contacts to see that they are clean and secure.

    13.

    Ensure that all instrument covers and safety shields are in place.

    14.

    Inspect all sensors, make sure they are clean, unobstructed and not exposed to

    unrepresentative conditions, for example temperature sensors must not be

    exposed to direct sunlight nor be placed near hot pipes or a process plant.

    15.Ensure that only authorized personnel have access to control equipment.

    16.Each section of the plant should operate when essential, and should

    preferably be controlled automatically.

    17.

    Time controls should be incorporated and operation of the whole plant should,

    preferably, be automatic.

    18.

    In multiple boiler installations, isolate boilers that are not required on the

    waterside and, ifsafe and possible, on the gas side. Make sure these boilers

    cannot be fired.

    19.Isolation of flue system (with protection) also reduces heat losses.

    20.In multiple boiler installations the lead/lag control should have a change round

    facility.

    21.

    Where possible, reduction of the system operating temperature should be made

    with devices external to the boiler and with the boiler operating under a normal

    constant temperature range.

    6.4Water and steam

    1. Water fed into the boilers must meet the specifications given by the

    manufacturers. The water must be clear, colorless and free from suspended

    impurities.

    2.

    Hardness nil. Max. 0.25 ppm CaCO3.

    3. pH of 8 to 10 retard forward action or corrosion. pH less than 7 speeds up

    corrosion due to acidic action.

    4.

    Dissolved O2 less than 0.02 mg/l. Its presence with SO2 causes corrosion

    problems.

  • 8/11/2019 Mech Report Edit Final

    37/48

    5. CO2 level should be kept very low. Its presence with O2 causes corrosion,

    especially in copper and copper bearing alloys.

    6.

    Water must be free from oilit causes priming

    6.5Blow down (BD) procedure

    A conventional and accepted procedure for blowing down gauge is as follows:

    Close water lock

    Open drain cock (note that steam escapes freely)

    Close drain cock

    Close steam cock

    Open water cock

    Open drain cock (note that water escapes freely)

    Close drain cock

    Open steam cock

    Open and then close drain cock for final blow through.

    Operators should blow these down regularly in every shift, or at least once per day

    where boilers are steamed less than 24 hours a day.

    6.5 Boiler water

    1.

    Water must be alkalinewithin 150 ppm of CaCO3 and above 50 ppm of

    CaCO3 at pH.

    2.

    Alkalinity number should be less than 120.3. Total solids should be maintained below the value at which contamination of

  • 8/11/2019 Mech Report Edit Final

    38/48

    steam becomes excessive, in order to avoid cooling over and accompanying

    danger of deposition on super heater, steam mains and prime movers.

    4.

    Phosphate should be no more than 25 ppm P2 O5.

    5.

    Make up feed water should not contain more than traces of silica. There must

    be less than 40 ppm in boiler water and 0.02 ppm in steam, as SiO2. Greater

    amounts may be carried to turbine blades.

    6. Water treatment plants suitable for the application must be installed to ensure

    water purity, and a chemical dosing arrangement must be provided to furthe

    Maximum Boiler Water Concentrations

    recommended by the American Boiler

    Manufacturers Association

    Boiler Steam Pressure (ata) Maximum Boiler Water

    Concentration (ppm)

    0-20 3500

    20-30 3000

    30-40 2500

    40-50 2000

  • 8/11/2019 Mech Report Edit Final

    39/48

    control boiler water quality. Blow downs should be resorted to when

    concentration increases beyond the permissible limits stipulated by the

    manufacturers.

    7.

    Alkalinity should not exceed 20 percent of total concentration. Boiler water

    level should be correctly maintained. Normally, 2 gauge glasses are provided

    to ensure this.

    50-60 1500

    60-70 1250

    70-100 1000

  • 8/11/2019 Mech Report Edit Final

    40/48

    CHAPTER 7

    WORKSHEETSANDOTHERTOOLS

    This section includes worksheets (Boiler Performance; Data Collection

    Sheet ;FuelAnalysis Sheet) and other tools (Boiler Performance Checklist ; Rules

    of Thumb; Dos and Donts)

    7.1 Worksheets

    7.1.1.Worksheet Boiler:- BOILER PERFORMANCE

    No. Parameter reference Units Readings

    1 Ultimate Analysis

    Carbon percent 48.54

    Hydrogen percent 3.35

    Oxygen percent 4.42

    Sulphur percent 0.27

    Nitrogen percent 0.88

    Moisture percent 9

    Ash percent 33.662 GCV of Fuel K Cal/kg 4200

    3 Oxygen in Flue Gas percent 7

    4 Flue Gas Temperature(Tf) 0

    230

    5 Ambient Temperature(Ta) 0

    30

    6 Humidity in Air Kg/kg of dry0.018

    7 Combustible in Ash percent 17.91

    8 GCV of Ash K Cal/kg452.95(Fly ash)

    600 (Bottom ash)

  • 8/11/2019 Mech Report Edit Final

    41/48

    9 Excess Air

    Supplied(EA)(O2x100)/

    percent 31.25

    10 Theoretical air requirement (TAR)

    [11xC+{34.5x(H2O2/8)}+4.32xS]/100

    kg/kg of fuel 6.316

    11 Actual mass of air supplied

    {1+EA/100}x theoretical air

    kg/kg of fuel 9.474

    12 Percentage heat loss due to dry flue gas

    {k x (TfTa)}/percentCO2

    Where,K (Seigertconst.)

    = 0.65 for Coal

    = 0.56 for Oil

    percent 13

    13 Percentage heat loss due to evaporation of

    water formed due to H2 in fuel

    [9xH2{584+0.45(TfTa)}]/GCV of Fuel

    percent 4.89

    14 Percentage heat loss due to evaporation

    of moisture present in fuel

    [M x{584+0.45x(TfTa)}]/GCV of Fuel

    percent 1.68

    15 Percentage heat loss due to moisture present in

    air

    {AASxHumidityx0.45(TfTa)x100}/GCV of

    percent 1.2983

    16 Percentage heat loss due to combustibles in ash

    {Ash x(100

    percent 8.42

    17 Total Losses percent 31.28

    18 Efficiency percent 68.72

  • 8/11/2019 Mech Report Edit Final

    42/48

    7.1.2 Worksheet Boiler 3 : FUEL ANALYSIS SHEET

    No. Parameter reference Units Readings

    1 Ultimate Analysis

    Carbon Percent 48.54

    Hydrogen percent 3.35

    Oxygen percent 4.42

    Sulphur percent 0.27

    Nitrogen percent 0.88

    Moisture percent 9

    Ash percent 33.66

    2 GCV of Fuel K Cal/kg 4200

    7.1.3 Boiler Periodic Checklist

    BD and Water

    Treatment

    Check BD

    valves.Do not

    -

    Make sure

    solids do

    -

  • 8/11/2019 Mech Report Edit Final

    43/48

    Feed Water

    System

    Check and

    correctUnsteady

    water level.

    Ascertain

    Cause ofunsteady

    water

    Check controls by

    Stopping the

    feed water pump

    and

    Allow control to

    stop fuel

    Nil Condensate

    receiver, de-aerator

    system pumps.

    Flue Gases Check temp. at

    two

    different points

    Measure temp.

    andCompare

    composition at

    Selected firings

    andAd ust

    Same as

    weekly.

    Compare

    with previous

    readin s.

    Same as weekly

    Record

    references.

    Combustion Air

    Supply

    Check

    adequate

    Openings exist

    Burners Check control sare

    Operating

    properly. May

    Clean burners ,pilot

    assemblies, check

    condition of spark

    Same as

    weekly

    Same as weekly,

    Clean and

    recondition

    Boiler operating

    Characteristics

    Observe flame

    Failure and

    Relief Valve Check for leakages Remove and

    Recondition

    Steam Pressure Check for excess

  • 8/11/2019 Mech Report Edit Final

    44/48

    Loads which will

    Cause

    excessive

    Fuel System

    Check pumps,

    Pressure

    gauges,

    transfer lines.

    Clean and

    Recondition system

    Belt for gland

    Packing

    Check

    damages.

    Checkgland

    packing

    Air leaks in water

    Side and

    fireside

    Clean surface as per

    manufacturers

    recommendation

    Air leaks Check for leaks

    Around access

    openings and flame

    Refractories on

    fuel side

    Repair

    Elec. System

    Clean panels

    Outside

    Inspect panels

    inside

    Clean ,repair

    Terminals and

    contactsetc.

  • 8/11/2019 Mech Report Edit Final

    45/48

    Hydraulic and

    Pneumatic valves

    Clean

    equipment,

    Oil spillages

    to bear rested

    Repair all defects

    And check for

    proper operation

  • 8/11/2019 Mech Report Edit Final

    46/48

    7.2.General rules (Rules of Thumb)

    5percentreductioninexcessairincreasesboilerefficiencyby1percent(or1percentre

    duction ofresidualoxygeninstackgasincreasesboilerefficiencyby1percent).

    22Creductioninfluegastemperature increasestheboiler efficiencyby1percent.

    6Criseinfeedwatertemperaturebroughtaboutbyeconomizer/condensaterecover

    ycorrespondstoa1percentsavingsinboilerfuelconsumption.

    20Cincreaseincombustionairtemperature,pre-heatedbywaste heat

    recovery,resultsina1percentfuelsaving.

    A3mmdiameterholeinapipecarrying7kg/cm2steamwouldwaste32,650litersoffu

    eloil peryear.

    100mofbaresteampipewithadiameterof 150 mm

    carryingsaturatedsteamat8kg/cm2wouldwaste25000litersfurnace oilinayear.

    70 percent of heat losses can be reduced by floating a layer of 45 mm

    diameterpolypropylene(plastic)ballsonthesurfaceofa90Chotliquid/condensate.

    A0.25mmthickairfilmoffersthesameresistancetoheattransferasa330mmthickCopp

    erwall.

    A3mmthicksootdepositonaheattransfersurfacecancausea2.5percentincreaseinf

    uelconsumption.

    A1mmthickscaledepositonthewatersidecouldincreasefuelconsumptionby5to8per

    cent.

  • 8/11/2019 Mech Report Edit Final

    47/48

    CHAPTER8

    CONCLUSION AND DISCUSSION

    A case study on boiler efficiency manufactured by RAKHOH INDUSTRIES

    PVT.LTD ,PUNE have been presented. From the case study following conclusion

    are drawn:

    1.Boiler efficiency is 68.72 %.

    2. 2% of heat is unaccounted during process.

    3. Percentage heat loss due to dry flue gas is 13 %.

    4. Percentage heat loss due to evaporation of water formed due

    toH2 in fuel is 4.89 %.

    5.Percentage heat loss due to evaporation of moisture present in fuel

    is 1.68 %.

    6. Percentage heat loss due to moisture present in air is 1.29 %.

    7. Percentage heat loss due to combustibles in ash is 8.42 %.

    8. Total losses are 31.28% .

    It is clear from the above efficiency that the energy transferred in form heat

    from fuel to the water has a difference of about 10%. So there is scope to improve the

    efficiency of boiler.

    Suggestions:-

  • 8/11/2019 Mech Report Edit Final

    48/48

    1. Coal of higher grade must be used.

    2. Coal must be dried before feeding for firing.

    3.

    Moisture in the air supplied must be removeed by using air preheater or

    using one more air preheater.

    4. Quantity of excess air must be optimized.