Top Banner
EMH metering GmbH & Co. KG Neu-Galliner Weg 1 19258 Gallin GERMANY Tel. +49 38851 326-0 Fax +49 38851 326-1129 E-mail [email protected] Web www.emh-metering.com EN LZQJ-XC generation N Edition: 13.11.2012 LZQJXC-N-DAB-E-1.00 Design acc. to VDEW-Specifications 2.1 Exchangeable buffer battery Network analysis Optional with DLMS
2

LZQJ-XC - System 11EMH metering GmbH & Co. KG Neu-Galliner Weg 1 19258 Gallin GERMANY Tel. +49 38851 326-0 Fax +49 38851 326-1129 E-mail [email protected] Web EN LZQJ-XC generation

Mar 13, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: LZQJ-XC - System 11EMH metering GmbH & Co. KG Neu-Galliner Weg 1 19258 Gallin GERMANY Tel. +49 38851 326-0 Fax +49 38851 326-1129 E-mail info@emh-metering.com Web EN LZQJ-XC generation

EMH meteringGmbH & Co. KG

Neu-Galliner Weg 119258 GallinGERMANYTel. +49 38851 326-0Fax +49 38851 326-1129

E-mail [email protected] www.emh-metering.com

EN

LZQJ-XCgeneration N

Edition: 13.11.2012LZQJXC-N-DAB-E-1.00

Designacc.toVDEW-Specifications2.1

Exchangeablebufferbattery

Networkanalysis

OptionalwithDLMS

Page 2: LZQJ-XC - System 11EMH metering GmbH & Co. KG Neu-Galliner Weg 1 19258 Gallin GERMANY Tel. +49 38851 326-0 Fax +49 38851 326-1129 E-mail info@emh-metering.com Web EN LZQJ-XC generation

EMH metering GmbH & Co. KG • Neu-Galliner Weg 1 • 19258 Gallin • GERMANY • Tel. +49 38851 326-0 • [email protected] • www.emh-metering.com

4-Quadrant/Combi Meter - LZQJ-XC generation N

Direct connection version

Transformer connection version

Voltage 4-wiremeter 3x127/220V,3x220/380V,3x230/400V,3x240/415V

3x58/100V,3x63/110V,3x66,4/115V,3x115/200V,3x127/220V,3x220/380V,3x230/400V,3x240/415V

Current 5(60)A,10(60)A,5(100)A,10(100)A 5||1A,1(6)A,5A,1AFrequency 50Hz,60HzAccuracy activeenergy

reactiveenergyCl.A(Cl.2),optionalCl.B(Cl.1)

Cl.3,optionalCl.2Cl.B(Cl.1)orCl.C(Cl.0,5S)

Cl.2or1%(Cl.2)Measuring system designation compensatedcurrenttransformerMeasuring types activeenergy

reactiveenergyothers

+A,-A+R,-R,R1,R2,R3,R4

S,Ah,U2h,I2hMeter constants LED(Imp./kWh[kvarh])

output(Imp./kWh[kvarh])

configurationability

500...100010000...100000(dependingonmetertype)(dependingonmetertype)

250...5005000...50000(dependingonmetertype)(dependingonmetertype)aftercertificationbymeansofthecertificationrelevantlogbook

Energy registers maximumnumber 32tariffregisters+16tarifflessregisters,eachwith15historicalvaluesMaximum registers maximumnumber

measuringperiod32tariffregisters,eachwith15historicalvalues

1,5,10,15,30,60min,adjustableLoad profile maximumnumberofchannels

typicalmemorydepthat1channelregisteringperiodregisteringtype

32upto3yearswitharegisteringperiodlengthof15min

1,5,10,15,30,60min,adjustablepower,energy,energyfeed

Real Time Clock accuracysynchronisationrunningreservebattery

within±5ppmviadatainterfaces,controlinputorDCF-module

>10yearsRipple control receiver

numberofchannelstelegrams

6allcommontelegrams

Control inputs systemvoltage 0or2Data retention time withoutvoltageintheEEPROM,atleast10yearsDisplay displayversion

heightofdigitsreadingwithoutpowersupply

VDEW-display,84mmx24mm,illuminated8mm

byreadoutbatteryOperation mechanicalbuttons

opticalsensorforoperationofdisplayandreset(sealableunderhingedmodulecover)

foroperationofdisplayData interfaces opticaldatainterface

electricaldatainterfacedataprotocolsmaximumtransmissionrate

opticaldatainterfaceD0CL0orRS485(withoutshield)

IEC62056-21orDLMS(automaticprotocoldetection)9600baud(fixedorModeC/E)

Outputs maximumnumberOpto-MOSFETS0-output

0or5max.250VAC/DC,100mA(makecontact[NO])

max.27VDC,27mAEnergy supply switched-modepowersupply

mainsbufferingtime3-phase>200ms

Power consumption per phase (Basic meter)

voltagepathcurrentpath

<1,7VA/<1,1W<0,21VA

<1,7VA/<1,0W<0,004VA

EMC-characteristics isolationresistancesurgevoltage

resistanceagainstHF-fields

4kVAC,50Hz,1min10kV,impulse12Ω(measuringpaths)

6kV,impulse1,2/50µs,500Ω(outputs,inputs)10V/m(underload)

Temperature range specifiedoperatingrangelimitrangeforoperation,storageandtransport

-25°C...+55°C

-40°C...+70°CRelative humidity max.95%,non-condensingacc.toIEC62052-11,EN50470-1and

IEC60068-2-30Housing dimensions

classofprotectiondegreeofprotection:housingdegreeofprotection:terminalblockhousingmaterialfirecharacteristics

approx.180x285x80(WxHxD)mm,acc.toDIN43857II

IP51IP31

polycarbonateglass-fibrereinforced,withouthalogen,recyclableacc.toIEC62052-11

Environmental conditions

mechanicalelectromagneticintendedlocation

M1acc.toMeasuringInstrumentsDirective(2004/22/EC)E2acc.toMeasuringInstrumentsDirective(2004/22/EC)

indooracc.toEN50470-1Weight 1,3kg 1,1kg

Productspecificationsaresubjecttochangewithoutnotice!