EMH metering GmbH & Co. KG • Südring 5 • 19243 Wittenburg • GERMANY • Tel. +49 38852 645-0 • [email protected] • www.emh-metering.com EMH metering GmbH & Co. KG Südring 5 19243 Wittenburg GERMANY Tel. Fax E-mail Web EN +49 38852 645-0 +49 38852 645-129 [email protected] www.emh-metering.com Edition: 05.08.2010 LZQJXC-DAB-E-2.30 Design acc. to VDEW-Specifications 2.1 Plugable communication module Exchangeable buffer battery Network analysis Optional with DLMS LZQJ-XC The LZQJ-XC fulfils the following standards: DIN 43857-2 Watthour meters in moulded insulation case without instrument transformers, up to 60 A rated maximum current; principal dimensions for poly-phase meters DIN 43857-4 Watthour meters in moulded insulation case without instrument transformers, up to 60 A rated maximum current; principal dimensions for meter terminal cover for poly-phase meters EN 50470-1 Electricity metering equipment (a.c.) - Part 1: General requirements, tests and test conditions - Metering equipment (class indexes A, B and C) EN 50470-3 Electricity metering equipment (a.c.) - Part 3: Particular requirements - Static meters for active energy (class indexes A, B and C) IEC 61000-... Electromagnetic compatibility (EMC) IEC 60529 Degrees of protection provided by enclosures (IP code) IEC 61038 Time switches for tariff and load control IEC 62052-11 Electricity metering equipment (AC) - General requirements, tests and test conditions - Part 11: Metering equipment IEC 62053-21 Electricity metering equipment (a.c.) - Particular Requirements - Part 21: Static meters for active energy (classes 1 and 2) IEC 62053-22 Electricity metering equipment (a.c.) - Particular requirements - Part 22: Static meters for active energy (classes 0,2 S and 0,5 S) IEC 62053-23 Electricity metering equipment (a.c.) - Particular requirements - Part 23: Static meters for reactive energy (classes 2 and 3) IEC 62056-21 Electricity metering - Data exchange for meter reading, tariff and load control - Part 21: Direct local data exchange IEC 62056-46 Electricity metering - Data exchange for meter reading, tariff and load control - Part 46: Data link layer using HDLC protocol IEC 62056-53 Electricity metering - Data exchange for meter reading, tariff and load control - Part 53: COSEM application layer IEC 62056-61 Electricity metering - Data exchange for meter reading, tariff and load control - Part 61: Object identification system (OBIS) IEC 62056-62 Electricity metering - Data exchange for meter reading, tariff and load control - Part 62: Interface classes DIN 66348-1 Interfaces and basic data link control procedures for serial measurement data communication; start-stop-transmission, point-to-point connection ITU-T V.11 Electrical characteristics for balanced double-current interchange circuits operating at data signalling rates up to 10 Mbit/s TIA/EIA-485 Electrical characteristics of generators & receivers for use in balanced digital multipoint systems ITU-T V.24 List of definitions for interchange circuits between data terminal equipment (DTE) and data circuit-terminating equipment (DCE) ITU-T V.28 Electrical characteristics for unbalanced double-current interchange circuits
2

The LZQJ-XC fulfils the following standards: LZQJ-XC - BTS · ITU-T V.24 List of definitions for interchange circuits between data terminal equipment (DTE) and ... installation check

Aug 21, 2018

Download

Documents

lyxuyen
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: The LZQJ-XC fulfils the following standards: LZQJ-XC - BTS · ITU-T V.24 List of definitions for interchange circuits between data terminal equipment (DTE) and ... installation check

EMH metering GmbH & Co. KG • Südring 5 • 19243 Wittenburg • GERMANY • Tel. +49 38852 645-0 • [email protected] • www.emh-metering.com

EMH meteringGmbH & Co. KG

Südring 519243 WittenburgGERMANYTel.Fax

E-mail Web

EN

+49 38852 645-0+49 38852 645-129

[email protected]

Edition: 05.08.2010LZQJXC-DAB-E-2.30

Designacc.toVDEW-Specifications2.1

Plugablecommunicationmodule

Exchangeablebufferbattery

Networkanalysis

OptionalwithDLMS

LZQJ-XCThe LZQJ-XC fulfils the following standards:

DIN43857-2 Watthourmetersinmouldedinsulationcasewithoutinstrumenttransformers, upto60Aratedmaximumcurrent;principaldimensionsforpoly-phasemeters

DIN43857-4 Watthourmetersinmouldedinsulationcasewithoutinstrumenttransformers, upto60Aratedmaximumcurrent;principaldimensionsformeterterminalcover forpoly-phasemeters

EN50470-1 Electricitymeteringequipment(a.c.)-Part1:Generalrequirements, testsandtestconditions-Meteringequipment(classindexesA,BandC)

EN50470-3 Electricitymeteringequipment(a.c.)-Part3:Particularrequirements- Staticmetersforactiveenergy(classindexesA,BandC)

IEC61000-... Electromagneticcompatibility(EMC)

IEC60529 Degreesofprotectionprovidedbyenclosures(IPcode)

IEC61038 Timeswitchesfortariffandloadcontrol

IEC62052-11 Electricitymeteringequipment(AC)-Generalrequirements,testsandtestconditions -Part11:Meteringequipment

IEC62053-21 Electricitymeteringequipment(a.c.)-ParticularRequirements -Part21:Staticmetersforactiveenergy(classes1and2)

IEC62053-22 Electricitymeteringequipment(a.c.)-Particularrequirements -Part22:Staticmetersforactiveenergy(classes0,2Sand0,5S)

IEC62053-23 Electricitymeteringequipment(a.c.)-Particularrequirements -Part23:Staticmetersforreactiveenergy(classes2and3)

IEC62056-21 Electricitymetering-Dataexchangeformeterreading,tariffandloadcontrol -Part21:Directlocaldataexchange

IEC62056-46 Electricitymetering-Dataexchangeformeterreading,tariffandloadcontrol -Part46:DatalinklayerusingHDLCprotocol

IEC62056-53 Electricitymetering-Dataexchangeformeterreading,tariffandloadcontrol -Part53:COSEMapplicationlayer

IEC62056-61 Electricitymetering-Dataexchangeformeterreading,tariffandloadcontrol -Part61:Objectidentificationsystem(OBIS)

IEC62056-62 Electricitymetering-Dataexchangeformeterreading,tariffandloadcontrol -Part62:Interfaceclasses

DIN66348-1 Interfacesandbasicdatalinkcontrolproceduresforserialmeasurement datacommunication;start-stop-transmission,point-to-pointconnection

ITU-TV.11 Electricalcharacteristicsforbalanceddouble-currentinterchangecircuits operatingatdatasignallingratesupto10Mbit/s

TIA/EIA-485 Electricalcharacteristicsofgenerators&receiversforuseinbalanceddigital multipointsystems

ITU-TV.24 Listofdefinitionsforinterchangecircuitsbetweendataterminalequipment(DTE) anddatacircuit-terminatingequipment(DCE)

ITU-TV.28 Electricalcharacteristicsforunbalanceddouble-currentinterchangecircuits

Page 2: The LZQJ-XC fulfils the following standards: LZQJ-XC - BTS · ITU-T V.24 List of definitions for interchange circuits between data terminal equipment (DTE) and ... installation check

Direct connection version5(60) A, 10(60) A, 5(100) A, 10(100) A

Transformer connection versionCl. B (Cl. 1)

Precision MeterCl. C (Cl. 0,5 S)

Precision MeterCl. 0,2 S

Voltage 4-wiremeter 3x127/220V...3x240/415V 3x58/100V...3x240/415V,3x400/690V 3x58/100V...3x240/415V,3x400/690VCurrent 5(60)A,10(60)A,5(100)A,10(100)A 5||1A,1(6)A,1(10)A,5A,1A,5(20)A 5||1A,1(6)A,1(10)A,5A,1A,5(20)AFrequency 50Hz,60Hz 50Hz,60Hz 50Hz,60HzAccuracy activeenergy

reactiveenergyCl.A(Cl.2),optionalCl.B(Cl.1)

Cl.3,optionalCl.2Cl.B(Cl.1)

Cl.2Cl.C(Cl.0,5S)

1%(Cl.2)Cl.0,2S

0,5%(Cl.2)Measuring system designation compensatedcurrenttransformer compensatedcurrenttransformerMeasuring types activeenergy

reactiveenergyothers

+A,-A+R,-R,R1,R2,R3,R4

S,Ah,U2h,I2h

+A,-A+R,-R,R1,R2,R3,R4

S,Ah,U2h,I2hMeter constants LED(Imp./kWh[kvarh])

output(Imp./kWh[kvarh])configurationability

500...1000(dependingonmetertype)10000...100000(dependingonmetertype)250...500(dependingonmetertype)5000...50000(dependingonmetertype)

aftercertificationbymeansofthecertificationrelevantlogbook

10000...100000(dependingonmetertype)5000...50000(dependingonmetertype)

aftercertificationbymeansofthecertificationrelevantlogbookEnergy registers maximumnumber 32tariffregisters+16tarifflessregisters,eachwith15historicalvalues 32tariffregisters+16tarifflessregisters,eachwith15historicalvaluesMaximum registers maximumnumber

measuringperiod32tariffregisters,eachwith15historicalvalues

1,5,10,15,30,60min,adjustable32tariffregisters,eachwith15historicalvalues

1,5,10,15,30,60min,adjustableLoad profile maximumnumberofchannels

typicalmemorydepthat1channelregisteringperiodregisteringtype

32upto3yearswitharegisteringperiodlengthof15min

1,5,10,15,30,60min,adjustablepower,energy,energyfeed

32upto3yearswitharegisteringperiodlengthof15min

1,5,10,15,30,60min,adjustablepower,energy,energyfeed

Real Time Clock accuracysynchronisationrunningreservebattery/capacitor

within±5ppmviadatainterfaces,controlinputorDCF-module

>20years/>10days

within±5ppmviadatainterfaces,controlinputorDCF-module

>20years/>10daysRipple control receiver numberofchannels

telegrams6

allcommontelegrams6

allcommontelegramsControl inputs S0-input/systemvoltage max.1/max.5

(intotalmax.5inputspossible)max.2/max.9

(intotalmax.10inputspossible)max.2/max.9

(intotalmax.10inputspossible)Data retention time withoutvoltageintheEEPROM,atleast10years withoutvoltageintheEEPROM,atleast10yearsDisplay displayversion

heightofdigitsalternativedisplayreadingwithoutpowersupply

VDEW-display,84mmx24mm8mm

alphanumericaldisplay4x20characters;70,4mmx20,8mm;heightofdigits4mmbybufferbattery(optional)

VDEW-display,84mmx24mm8mm

alphanumericaldisplay4x20characters;70,4mmx20,8mm;heightofdigits4mmbybufferbattery(optional)

Operation mechanicalbuttonsopticalsensor

foroperationofdisplayandreset(sealableunderhingedmodulecover)foroperationofdisplay

foroperationofdisplayandreset(sealableunderhingedmodulecover)foroperationofdisplay

Data interfaces opticaldatainterfaceelectricaldatainterfacedataprotocolsmaximumtransmissionrate

opticaldatainterfaceD0RS485,RS232orCL0IEC62056-21orDLMS

upto19200baud(fixedorModeC/E)

opticaldatainterfaceD0RS485,RS232orCL0IEC62056-21orDLMS

upto19200baud(fixedorModeC/E)Communication module (plugable)

modeminterfacemoduledataprotocolsmaximumtransmissionrate

GSM/GPRS,Ethernet,PSTN(analog)RS485,RS232

IEC62056-21orDLMSupto19200baud(fixedorModeC/E)

GSM/GPRS,Ethernet,PSTN(analog)RS485,RS232

IEC62056-21orDLMSupto19200baud(fixedorModeC/E)

Outputs maximumnumberOpto-MOSFETS0-outputrelayshighloadrelay

8max.250VAC/DC,100mA(makecontact[NO]orbreakcontact[NC])

max.27VDC,27mAmax.250VAC/DC,100mA(max.2makecontacts[NO])max.250VAC/DC,10A(max.2makecontacts[NO])

8max.250VAC/DC,100mA(makecontact[NO]orbreakcontact[NC])

max.27VDC,27mAmax.250VAC/DC,100mA(max.2makecontacts[NO])max.250VAC/DC,10A(max.2makecontacts[NO])

Energy supply switched-modepowersupplymainsbufferingtime

3-phase>500ms

3-phase>500ms

Auxiliary voltage supply long-range --- 48...300VAC/DC(optional) 48...300VAC/DC(optional) 48...300VAC/DCPower consumption per phase (Basic meter)

voltagepathwithauxiliaryvoltagewithoutauxiliaryvoltagecurrentpathauxiliaryvoltage

---<1,2VA/<0,75W

<0,01VA---

<0,02VA/<0,01W(3x58/100V)<1,2VA/<0,75W

<0,004VA<4,2VA...<2,5VA

<0,02VA/<0,01W(3x58/100V)<1,2VA/<0,75W

<0,004VA<4,2VA...<2,5VA

EMC-characteristics isolationresistancesurgevoltage

resistanceagainstHF-fields

4kVAC,50Hz,1min8kV,impulse1,2/50µs,2Ω(measuringpaths,auxiliaryvoltage)

6kV,impulse1,2/50µs,500Ω(outputs:Opto-MOSFET,relays;inputs:systemvoltage)30V/m(underload)

4kVAC,50Hz,1min8kV,impulse1,2/50µs,2Ω(measuringpaths,auxiliaryvoltage)

6kV,impulse1,2/50µs,500Ω(outputs:Opto-MOSFET,relays;inputs:systemvoltage)30V/m(underload)

Temperature range specifiedoperatingrangelimitrangeforoperation,storageandtransport

-25°C...+55°C

-40°C...+70°C

-25°C...+55°C

-40°C...+70°CRelative humidity 95%,non-condensingacc.toIEC62052-11,EN50470-1andIEC60068-2-30 95%,non-condensingacc.toIEC62052-11,EN50470-1andIEC60068-2-30Housing dimensions

classofprotectiondegreeofprotection:housingdegreeofprotection:terminalblockhousingmaterialfirecharacteristics

approx.180x285x80(WxHxD)mm,acc.toDIN43857II

IP51(optionalIP54)IP31

polycarbonateglass-fibre-reinforced,withouthalogen,recyclableacc.toIEC62052-11

approx.180x285x80(WxHxD)mm,acc.toDIN43857II

IP51(optionalIP54)IP31

polycarbonateglass-fibre-reinforced,withouthalogen,recyclableacc.toIEC62052-11

Weight 1,4kg 1,2kg 1,2kgFurther features measuringofinstantaneousvalues

installationcheckopticalfibreinterfacebufferbattery

manipulationrecognition

networkanalysis

P,Q,S(perphaseandsum),U,I,powerfactor(perphase),linefrequency,phasefailuresviainstantaneousvalues(servicedata)possible

forconnectionofupto4opticalfibreseparationboxesexchangeablebufferbatteryforreadingoutthemeterviatheopticalinterfaceand

readingthedisplaywithoutpowerwithopeningofthemeter-andterminalcoverand

recognitionofelectromagneticinterferencemonitoringofU,I,THD,f,flicker,harmonicsacc.toDINEN50160

P,Q,S(perphaseandsum),U,I,powerfactor(perphase),linefrequency,phasefailuresviainstantaneousvalues(servicedata)possible

forconnectionofupto4opticalfibreseparationboxesexchangeablebufferbatteryforreadingoutthemeterviatheopticalinterfaceand

readingthedisplaywithoutpowerwithopeningofthemeter-andterminalcoverand

recognitionofelectromagneticinterferencemonitoringofU,I,THD,f,flicker,harmonicsacc.toDINEN50160

MetersfromtheseriesLZQJ-XCaredesignedforuni-versalapplicationsaccordingtoVDEW-specifications2.1.Duetothetheapplicationofatriedandtestedmeasuringprocedurethemeterisdistinguishedbyitshighreliability.Thehighperformingprocessorsystemguaranteesasolidbasisforfurtherextensions.

TheLZQJ-XCfunctionscanbeextentedwiththefollowingaccessories:

Productspecificationsaresubjecttochangewithoutnotice!

MetermodemVARIOMOD-XC(GSM/GPRS,Ethernet,PSTN)

Interfacemodule(RS232,RS485)

DCF-AerialDCF77-TH2

GPS-Antenna

OpticalfibreseparationboxLTR

Communication-andparameterisationsoftware

Networkanalysis(optional)