COPYRIGHT PROJECT NO. DESIGNED BY DRAWN BY ISSUE DATE CHECKED BY SHEET NO. PHASE All rights reserved. Reproduction or translation of any part REVISION of this work without written permission of ARCHITECTS WEST INC. is unlawful and subject to criminal prosecution. 9-24-2019 100% BID SET ITD SECURITY LOBBY 19-100 ITD - COEUR D ALENE 600 W. PRAIRIE AVE. BUILDING 1002, COEUR D ALENE, IDAHO 83815 1859 MWM STRUCTURAL MECHANICAL ELECTRICAL TRINDERA 1130 W HAYDEN AVE, SUITE #101 HAYDEN, IDAHO 83835 208.676.8001 RL 2019 1130 W HAYDEN AVE, SUITE #101 HAYDEN, IDAHO 83835 (208) 676-8001 (208) 676-0100 THE SYMBOLS, ABBREVIATIONS AND NOTES ON THIS SHEET ARE INTENDED TO BE GENERAL AND COMPREHENSIVE AND DO NOT ALL APPLY TO THIS PROJECT GENERAL NOTES, ABBREVIATIONS, AND LEGENDS MWM E-001 GENERAL NOTES, ABBREVIATIONS, AND LEGENDS E-002 ELECTRICAL SPECIFICATIONS E-101 POWER & SYSTEMS PLAN - DEMO / EXISTING E-201 POWER & SYSTEMS PLAN - NEW / EXISTING RISER DIAGRAM E-801 LIGHTING SCHEDULE & ELECTRICAL DETAILS SHEET INDEX 1. "GENERAL NOTES" APPLY TO ALL DRAWINGS. "SHEET NOTES" APPLY TO ALL OF THE SHEETS ON WHICH THEY OCCUR. "KEYNOTES" APPLY ONLY WHERE CALLED OUT. 2. ALL EQUIPMENT SHOWN IN BOLD IS TO BE PROVIDED BY CONTRACTOR UNLESS OTHERWISE NOTED. 3. CONTRACTOR SHALL PROVIDE CONDUIT AND WIRE FROM ALL CONTROL DEVICES TO LUMINAIRES FOR CONTROL OF LUMINAIRES SHOWN. 4. LUMINAIRES SHOWN ON DRAWINGS FOR QUANTITY AND CIRCUITING ONLY. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS. 5. ALL FEEDERS AND BRANCH CIRCUITS SHALL CONTAIN AN EQUIPMENT GROUND CONDUCTOR SIZED PER NEC TABLE 250.122. ALL WIRING IS BASED ON CU COPPER PER NEC TABLE 310.15(B)(16), USING 75°C AMPACITIES FOR FEEDERS. IF ALUMINUM IS ALLOWED, CONTRACTOR IS RESPONSIBLE TO RE-SIZE ACCORDING TO NEC AMPACITIES FOR LOADS SHOWN ON DRAWINGS. 6. BRANCH CIRCUIT CONDUCTORS, NOT OTHERWISE IDENTIFIED SHALL BE A MINIMUM 12 AWG FOR RUNS 70 FEET OR LESS AND A MINIMUM 10 AWG FOR RUNS GREATER THAN 70 FEET. QUANTITY AND SIZE SHALL BE "AS REQUIRED" TO SERVE AND CONTROL DEVICE(S) OR EQUIPMENT WITH A MAXIMUM VOLTAGE DROP OF THREE PERCENT. WHERE CONTRACTOR CHOOSES TO RUN MORE THAN THREE CURRENT CARRYING CONDUCTORS WITHIN ONE RACEWAY OR CABLE, CONDUCTORS SHALL BE INCREASED IN SIZE TO COMPENSATE FOR THE DERATING REQUIRED PER NEC SECTION 310.15. CONDUCTOR AMPACITIES SHALL BE TAKEN FROM THE 75°C COLUMN. 7. MINIMUM CONDUIT IN EXTERIOR AND UNDERGROUND LOCATIONS TO BE 1". MINIMUM CONDUIT FOR INTERIOR BRANCH CIRCUITS TO BE 3/4". CONDUITS FROM LUMINAIRES TO LOCAL USER CONTROL DEVICES (SWITCHES, OCCUPANCY SENSORS, ETC.) MAY BE 1/2" OR AS INDICATED IN SPECIFICATIONS. PROVIDE ADDITIONAL CONDUCTOR FOR UNSWITCHED "HOT" TO LIGHTING LUMINAIRES WITH EMERGENCY POWER BATTERIES OR GENERATOR TRANSFER DEVICES. 8. WIRING FOR EMERGENCY LIGHTING CIRCUITS OR OTHER EMERGENCY EQUIPMENT SHALL BE KEPT ENTIRELY INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT AND SHALL MEET ALL REQUIREMENTS OF NEC SECTION 700.10. 9. CONTRACTOR SHALL PROVIDE CONDUIT AND WIRE FOR ALL CIRCUITS SHOWN ON DRAWINGS. 10. WHERE EQUIPMENT PART NUMBERS ARE SHOWN ON THESE PLANS THEY SHALL SUPERCEDE THE REQUIREMENTS OF THE SPECIFICATIONS. 11. ALL CONDUITS SHALL BE CONCEALED UNLESS OTHERWISE NOTED. 12. PROVIDE DEDICATED NEUTRAL CONDUCTOR FOR ALL BRANCH CIRCUITS. GENERAL NOTES IP SECURITY CAMERA. CONTRACTOR TO PROVIDE JUNCTION BOX AND 3/4" CONDUIT WITH NYLON PULL STRING TO ACCESSIBLE CEILING SPACE. PTZ = PAN TILT ZOOM NOT SHADED = INDOOR SHADED = OUTDOOR A ACCESS CONTROL PANEL PTZ PTZ SPECIAL PURPOSE RECEPTACLE, RATING AS INDICATED / = TWISTLOCK STANDARD RECEPTACLES: 125V, 20A 18" AFF, UON. TYPES: SIMPLEX /DUPLEX /QUADRUPLEX /FLOOR DUPLEX /FLOOR QUADRUPLEX GFCI RECEPTACLES: 125V, 20A 18" AFF, UON. TYPES: SIMPLEX /DUPLEX /QUADRUPLEX X C = CEILING MOUNTED S = HALF SWITCHED I = ISOLATED GROUND TR = TAMPER RESISTANT a = LOWER CASE LETTER INDICATES SWITCH CONTROL 2" = MEASUREMENT INDICATES HEIGHT ABOVE BACKSPLASH/MILLWORK A = INDICATES MOUNT ABOVE BACKSPLASH/MILLWORK. COORDINATE HEIGHT WITH TRADES. USB = INDICATES 20A 120V DUPLEX RECEPTACLE WITH USB CHARGER. CT = SWITCHED RECEP, INDICATES FULL CONTROLLED DEDICATED 20A 125V DUPLEX CH = SWITCHED RECEP, INDICATES HALF CONTROLLED DEDICATED 20A 125V DUPLEX PROJECT SYMBOLS/LEGENDS/DESIGNATIONS POWER "1" "a" "NL" "E" INDICATES PANELBOARD AND CIRCUIT PROVIDING POWER TO SWITCHLEG INDICATED FOR LUMINAIRES CONTAINED IN SAME ROOM/AREA. INDICATES TYPE PER LUMINAIRE SCHEDULE. INDICATES NIGHT LIGHT LUMINAIRE. INDICATES CONTROL PER SWITCH. INDICATES POWER TO EMERGENCY LIGHTING CONTAINED IN SAME ROOM/AREA. 1 E NL a PNL-4 INDICATES CIRCUIT NUMBER. INDICATES POWER SOURCE. "PNL" "4" RECEPTACLE, TYPICAL: LUMINAIRE, TYPICAL: X-X a/E X-X E X-X a WIRELESS ACCESS PORT; SEE SPECIAL SYSTEMS CONNECTION SCHEDULE, WHEN INCLUDED ON PLANS. WALL MOUNTED SPEAKER/CLOCK COMBINATION WALL CLOCK - DIGITAL WALL OR CEILING MOUNTED SPEAKER CABLE TRAY TELEVISION OUTLET, 18" AFF UON. STUB 3/4" CO INTO ACCESSIBLE CEILING SPACE. RECESSED AUDIO FLOOR BACK BOX, OUTLET AND CONDUIT A/V SHORT THROW PROJECTOR. MOUNT AT 86" AFF. X-X ABBREVIATIONS AFC AFG AF AFCI AFF AIC AHJ ATS C CATV CB CCTV CL CO COMM DDC DP EC EM EMT ER FAAP FACP FATC FCIO FOIC GFCI GFP GND HTR IG IMC JBOX LCP LTG MCA MCB MCC MDP MGAP MLO MOCP MS MTD NAC NEC NIC NL NTS OC OH OS PIV PNL PS PVC R RCPT RMC SAC SB,SWBD SG SPD TEL TR TYP UON UL UG VD VFD W WP XFMR AVAILABLE FAULT CURRENT ABOVE FINISHED GRADE AMP FRAME ARC FLASH CIRCUIT INTERRUPTER ABOVE FINISHED FLOOR AMPERE INTERRUPTING CAPACITY AUTHORITY HAVING JURISDICTION AUTOMATIC TRANSFER SWITCH CONDUIT OR CEILING CABLE TELEVISION CIRCUIT BREAKER CLOSED CIRCUIT TELEVISION CONNECTOR LIGHTING CONDUIT ONLY COMMUNICATIONS DIRECT DIGITAL CONTROLS DISTRIBUTION PANELBOARD ELECTRICAL CONTRACTOR EMERGENCY ELECTRICAL METALLIC TUBING EXISTING TO REMAIN FIRE ALARM ANNUNCIATOR PANEL FIRE ALARM CONTROL PANEL FIRE ALARM TERMINAL CABINET FURNISHED BY CONTRACTOR, INSTALLED BY OWNER FURNISHED BY OWNER, INSTALLED BY CONTRACTOR GROUND FAULT CIRCUIT INTERRUPTER GROUND FAULT PROTECTION GROUND HEATER ISOLATED GROUND INTERMEDIATE METALLIC CONDUIT JUNCTION BOX LIGHTING CONTROL PANEL LIGHTING MINIMUM CIRCUIT AMPACITY MAIN CIRCUIT BREAKER MOTOR CONTROL CENTER MAIN DISTRIBUTION PANEL MEDICAL GAS ALARM PANEL MAIN LUGS ONLY MAXIMUM OVERCURRENT PROTECTION MOTOR STARTER MOUNTED NOTIFICATION APPLIANCE CABINET NATIONAL ELECTRICAL CODE NOT IN CONTRACT NIGHT LIGHT NOT TO SCALE ON CENTER OVERHEAD OCCUPANCY SENSOR POST INDICATOR VALVE PANEL POWER SUPPLY POLYVINYL CHLORIDE EXISTING TO BE REMOVED RECEPTACLE RIGID METAL CONDUIT SMALL APPLIANCE CIRCUIT SWITCHBOARD SWITCHGEAR SURGE PROTECTIVE DEVICE TELEPHONE TAMPER RESISTANT TYPICAL UNLESS OTHERWISE NOTED UNDERWRITERS LABORATORIES UNDERGROUND VOLTAGE DROP VARIABLE FREQUENCY DRIVE WEATHERPROOF (WHILE IN USE) WEATHERPROOF TRANSFORMER RECEPTACLES SECURITY PHOTO ELECTRIC SENSOR LUMINAIRE CONTROLS # NEW LUMINAIRE CONTROL. SEE LIGHTING CONTROL LEGEND LOCATED ON LIGHTING SHEETS. COMMUNICATIONS CIRCUIT DESIGNATION PROXIMITY FOB READER OS CEILING MOUNTED OCCUPANCY SENSOR(S). PROVIDE SHOP DRAWINGS OF OCCUPANCY SENSOR SYSTEM AS PER PROJECT SPECIFICATION AS PART OF THE SUBMITTAL PROCESS PRIOR TO COMMENCEMENT OF LABOR. SEE LIGHTING CONTROL LEGEND LOCATED ON LIGHTING SHEETS. PE REFERENCE SYMBOLS DETAIL 1 XXX SCALE SECTION A XXX A XXX 2 XXX FAULT CURRENT TAG (AIC) KEY NOTE XX CONDUIT & WIRE TAG 1 SHEET WHERE DETAIL IS TAKEN FROM XX FIGURE OR PHOTO DETAIL NUMBER IF PHOTO, ARROW DENOTES DIRECTION TAKEN DETAIL AREA SHEET ON WHICH SECTION APPEARS SECTION LETTER SHEET WHERE SECTION IS TAKEN FROM SECTION LETTER SHEET WHERE SECTION IS TAKEN FROM DETAIL NUMBER 1 XXX (X) 2P 30A HH1 CONDUIT HOME RUN 3/4"C, 2#12 & 1#12 GND. UNLESS SHOWN OTHERWISE. (EXAMPLE SHOWN: TO PANEL P1, CIRCUIT 1) P1 P1-1 CONDUIT HOME RUN - SEE CONDUIT AND WIRE SCHEDULE. SWITCH 2 = DOUBLE POLE SWITCH 3 = THREE WAY SWITCH 4 = FOUR WAY SWITCH P = SWITCH AND PILOT LAMP K = KEY OPERATED SWITCH T = SWITCH WITH TIMER MS = MASTER SWITCH TO CONTROL ALL FIXED LUMINAIRES IN GUEST UNIT LUMINAIRE, SURFACE LUMINAIRE, RECESSED STRIP, SURFACE OR PENDANT AS INDICATED IN LUMINAIRE SCHEDULE LUMINAIRE, EMERGENCY LUMINAIRE, WALL MOUNT LIGHTED EXIT SIGN, ARROW INDICATES DIRECTION EMERGENCY WALL PACK LUMINAIRE, POLE MOUNTED SURFACE METAL RACEWAY WITH RECEPTACLE @ X" O.C. CONDUIT CONCEALED IN WALL, CEILING, UNDER FLOOR, IN FLOOR SLAB, OR ROUTED UNDERGROUND CONDUIT EXPOSED EXISTING CONDUIT ROUTED UNDERGROUND OVERHEAD ELECTRICAL EXTRA-HARD USAGE FLEXIBLE CORD CONDUIT FLEXIBLE. CONDUIT TURNED UP OR TOWARD CONDUIT TURNED DOWN OR AWAY CONDUIT CAPPED CONDUIT SEALS. CLASS . I DIV. 1 OR DIV 2 EXPLOSION PROOF CIRCUIT BREAKER, RATING/NO. OF POLES WITH THERMAL MAGNETIC CIRCUIT BREAKER TRIP, UNLESS OTHERWISE NOTED MANUAL OR AUTOMATIC TRANSFER SWITCH. JUNCTION BOX HANDHOLE WITH DESIGNATION EQUIPMENT TO BE REMOVED SHUNT TRIP PUSHBUTTON OR KEY-SWITCH PANELBOARD, SWITCHBOARD, OR SWITCHGEAR. DASHED BOX INDICATES CODE REQUIRED WORKING CLEARANCE HARDWIRED CONNECTION THERMOSTAT ST T IC SSS BP VFD SOLID STATE STARTER, REDUCED VOLTAGE WITH ISOLATION & BYPASS CONTACTORS VARIABLE FREQUENCY DRIVE CONDUCTORS NOT CONNECTED. CONDUCTORS CONNECTED. PULL OUT SWITCH/PLUG-RECEPTACLE CONNECTION NORMALLY OPEN CONTACT (WHEN DE-ENERGIZED) NORMALLY CLOSED CONTACT (WHEN DE-ENERGIZED) UNIT HEATER 200AS 200AS/ 100AF 60A 150W 3 CT - + M DISCONNECT SWITCH, FUSED 200=SWITCH RATING, 100=FUSE RATING DISCONNECT SWITCH, NON FUSED (60A) INDICATES AMPERAGE RATING MAGNETIC MOTOR STARTER W/DISCONNECT MAGNETIC MOTOR STARTER FVNR = FULL VOLTAGE NON-REVERSING FVR = FULL VOLTAGE REVERSING 2 = NEMA SIZE GENERATOR ELECTRIC HEATER, WATTAGE INDICATED EXHAUST OR SUPPLY FAN, NUMBER INDICATES H.P. MOTOR, NUMBER INDICATES HORSEPOWER CURRENT TRANSFORMER, NUMBER INDICATES NUMBER OF C.T.'S TRANSFORMER BATTERY GROUND ROD IN GROUND ROD BOX UTILITY WATT HOUR METER LIGHTING SCHEMATIC PLAN CB 2 10 1/4 G T 60A DETAIL NUMBER SHEET ON WHICH DETAIL APPEARS E E OE X M MOTOR RATED SWITCH. WHERE "M" INDICATED, PROVIDE A MANUAL MOTOR STARTER W/OVERLOAD FIRE ALARM CONTROL PANEL FIRE ALARM ANNUNCIATOR FIRE ALARM REQUEST TO EXIT DUCT SMOKE DETECTOR SMOKE DETECTOR HEAT DETECTOR MANUAL PULL STATION HORN STROBE HORN STROBE CEILING MOUNT STROBE STROBE CEILING MOUNT SPEAKER STROBE WALL MOUNT S DOOR CONTACT MAGNETIC DOOR HOLD (SECURITY) ADA PUSH BUTTON WALL MOUNTED INTERCOM/CLOCK COMBINATION PULL STATION WITH CLEAR PLASTIC COVER ADDRESSABLE RELAY REMOTE ANNUNCIATOR KITCHEN HOOD FIRE SUPPRESSION SYSTEM FIRE SPRINKLER TAMPER SWITCH PRESSURE SWITCH FIRE SPRINKLER WATER FLOW SWITCH WATER FLOW BELL KNOX BOX PULL CORD STATION MAGNETIC DOOR HOLD (FIRE ALARM) M/C FFH FFJ NOTIFICATION APPLIANCE CIRCUIT PS N POST INDICATOR VALVE FIREFIGHTER 2-WAY VOICE COMMUNICATION SYSTEM HANDSET STATION ADDRESSABLE MODULE M = MONITOR C = CONTROL FIREFIGHTER 2-WAY VOICE COMMUNICATION SYSTEM JACK MAGNETIC LOCK MOTION DETECTOR OVERHEAD DOOR CONTACT WINDOW CONTACT VIDEO/INTERCOM W/ INTEGRAL FOB READER COMBINATION KEYPAD/FOB READER ELECTRIC STRIKE DOOR BELL CARD READER CIRCUIT BREAKER DISCONNECT (60A) INDICATES AMPERAGE RATING 60A 60A # # WALL MOUNTED TELECOMMUNICATIONS OUTLET. 18" AFF, UON. PROVIDE 4" BACKBOX AND 1"C ROUTED TO ACCESSIBLE CEILING SPACE OR DIRECTLY TO MDF ROOM. DATA CABLING INSTALLED IN FUTURE PHASE. WALL PHONE 43" AFF P FLOOR OR CEILING MOUNTED TELECOMMUNICATIONS OUTLET. # INDICATES QUANTITY OF VOICE AND DATA JACKS. PULLSTRING ALWAYS PROVIDED. SPECIAL OUTLET HEIGHTS ARE SHOWN ON THE ELECTRICAL DRAWINGS OR ON THE ARCHITECTURAL DRAWINGS. IF SPECIAL OUTLET HEIGHTS ARE NOT SHOWN OR REQUIRED, THEN LOCATE OUTLETS AS NOTED BELOW. OUTLET HEIGHTS ARE MEASURED FROM THE FINISHED FLOOR TO THE CENTERLINE OF THE OUTLET UNLESS OTHERWISE NOTED. RECEPTACLES 18 INCHES (460 mm) VERTICALLY MOUNTED LIGHT SWITCHES 42 INCHES (1200 mm) VERTICALLY MOUNTED CLOCK OUTLET 80 INCHES (2030 mm) PANELBOARDS 72 INCHES (1830 mm) TO TOP OF PANELBOARD TELECOM OUTLET, DESK HANDSET 18 INCHES (460 mm) VERTICALLY MOUNTED TELECOM OUTLET, WALL HANDSET 42 INCHES (1370 mm) VERTICALLY MOUNTED FIRE ALARM PULL STATION 42 INCHES (1200 mm) FIRE ALARM AUDIBLE NOTIFICATION DEVICES TOP EDGE NOT LESS THAN 90 INCHES (2300 mm) AFF AND NOT LESS THAN 6 INCHES (150 mm) BELOW CEILING. 6 INCHES (150 mm) BELOW CEILING SHALL TAKE PRECEDENCE WHERE CEILING HEIGHT DOES NOT ALLOW BOTH DIMENSIONS FIRE ALARM VISUAL AND COMBINATION AUDIBLE/VISUAL NOTIFICATION DEVICES BOTTOM EDGE SHALL BE AT 80 INCHES (2030 mm) AFF OR 6 INCHES (150 mm) BELOW CEILING HEIGHT, WHICHEVER IS LOWER FIRE ALARM CONTROL PANEL 72 INCHES (1830 mm) TO TOP OF PANELBOARD OUTLET MOUNTING HEIGHTS PHOTOCELL PC LUMINAIRE, PENDANT 100AF WAP C S C I C S TV DB FR KF R W D OD DH ML M VI ES FACP FAAP SD SD F C C F K KX D P PC F R A V T B M DOORBELL LIGHT SMOKE/FIRE DAMPER CONNECTION D EMERGENCY PUSH BUTTON SWTICH C SECURITY CONTROLLER
5
Embed
ITD SECURITY LOBBY 19-100...FIRE ALARM PULL STATION 42 INCHES (1200 mm) FIRE ALARM AUDIBLE NOTIFICATION DEVICES TOP EDGE NOT LESS THAN 90 INCHES (2300 mm) AFF AND NOT LESS THAN 6 INCHES
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
COPYRIGHT
PROJECT NO.DESIGNED BYDRAWN BYISSUE DATE
CHECKED BY
SHEET NO.
PHASE
All rights reserved. Reproduction or translation of any part
REVISION
of this work without written permission ofARCHITECTS WEST INC.
is unlawful and subject to criminal prosecution.
9-24-2019100% BID SET
ITD
SECU
RITY
LOB
BY 1
9-10
0IT
D - C
OEUR
D A
LENE
600 W
. PRA
IRIE
AVE.
BUILD
ING
1002
, COE
UR D
ALE
NE, ID
AHO
8381
5
1859MWM
STRUCTURAL
MECHANICAL
ELECTRICALTRINDERA1130 W HAYDEN AVE, SUITE #101HAYDEN, IDAHO 83835208.676.8001
RL
2019
1130 W HAYDEN AVE, SUITE #101
HAYDEN, IDAHO 83835
(208) 676-8001 (208) 676-0100
THE SYMBOLS, ABBREVIATIONS AND NOTES ON THIS SHEET
ARE INTENDED TO BE GENERAL AND COMPREHENSIVE
AND DO NOT ALL APPLY TO THIS PROJECT
GENE
RAL N
OTES
, ABB
REVI
ATIO
NS, A
ND LE
GEND
S
MWM
E-001 GENERAL NOTES, ABBREVIATIONS, AND LEGENDS
E-002 ELECTRICAL SPECIFICATIONS
E-101 POWER & SYSTEMS PLAN - DEMO / EXISTING
E-201 POWER & SYSTEMS PLAN - NEW / EXISTING RISER DIAGRAM
E-801 LIGHTING SCHEDULE & ELECTRICAL DETAILS
S H E E T I N D E X
1. "GENERAL NOTES" APPLY TO ALL DRAWINGS. "SHEET NOTES"
APPLY TO ALL OF THE SHEETS ON WHICH THEY OCCUR.
"KEYNOTES" APPLY ONLY WHERE CALLED OUT.
2. ALL EQUIPMENT SHOWN IN BOLD IS TO BE PROVIDED BY
CONTRACTOR UNLESS OTHERWISE NOTED.
3. CONTRACTOR SHALL PROVIDE CONDUIT AND WIRE FROM ALL
CONTROL DEVICES TO LUMINAIRES FOR CONTROL OF
LUMINAIRES SHOWN.
4. LUMINAIRES SHOWN ON DRAWINGS FOR QUANTITY AND
CIRCUITING ONLY. SEE ARCHITECTURAL REFLECTED CEILING
PLANS FOR EXACT LOCATIONS.
5. ALL FEEDERS AND BRANCH CIRCUITS SHALL CONTAIN AN
EQUIPMENT GROUND CONDUCTOR SIZED PER NEC TABLE
250.122. ALL WIRING IS BASED ON CU COPPER PER NEC TABLE
310.15(B)(16), USING 75°C AMPACITIES FOR FEEDERS. IF
ALUMINUM IS ALLOWED, CONTRACTOR IS RESPONSIBLE TO
RE-SIZE ACCORDING TO NEC AMPACITIES FOR LOADS SHOWN
ON DRAWINGS.
6. BRANCH CIRCUIT CONDUCTORS, NOT OTHERWISE IDENTIFIED
SHALL BE A MINIMUM 12 AWG FOR RUNS 70 FEET OR LESS AND
A MINIMUM 10 AWG FOR RUNS GREATER THAN 70 FEET.
QUANTITY AND SIZE SHALL BE "AS REQUIRED" TO SERVE AND
CONTROL DEVICE(S) OR EQUIPMENT WITH A MAXIMUM VOLTAGE
DROP OF THREE PERCENT. WHERE CONTRACTOR CHOOSES TO
RUN MORE THAN THREE CURRENT CARRYING CONDUCTORS
WITHIN ONE RACEWAY OR CABLE, CONDUCTORS SHALL BE
INCREASED IN SIZE TO COMPENSATE FOR THE DERATING
REQUIRED PER NEC SECTION 310.15. CONDUCTOR AMPACITIES
SHALL BE TAKEN FROM THE 75°C COLUMN.
7. MINIMUM CONDUIT IN EXTERIOR AND UNDERGROUND
LOCATIONS TO BE 1". MINIMUM CONDUIT FOR INTERIOR BRANCH
CIRCUITS TO BE 3/4". CONDUITS FROM LUMINAIRES TO LOCAL
USER CONTROL DEVICES (SWITCHES, OCCUPANCY SENSORS,
ETC.) MAY BE 1/2" OR AS INDICATED IN SPECIFICATIONS.
PROVIDE ADDITIONAL CONDUCTOR FOR UNSWITCHED "HOT" TO
LIGHTING LUMINAIRES WITH EMERGENCY POWER BATTERIES OR
GENERATOR TRANSFER DEVICES.
8. WIRING FOR EMERGENCY LIGHTING CIRCUITS OR OTHER
EMERGENCY EQUIPMENT SHALL BE KEPT ENTIRELY INDEPENDENT
OF ALL OTHER WIRING AND EQUIPMENT AND SHALL MEET ALL
REQUIREMENTS OF NEC SECTION 700.10.
9. CONTRACTOR SHALL PROVIDE CONDUIT AND WIRE FOR ALL
CIRCUITS SHOWN ON DRAWINGS.
10. WHERE EQUIPMENT PART NUMBERS ARE SHOWN ON THESE
PLANS THEY SHALL SUPERCEDE THE REQUIREMENTS OF THE
SPECIFICATIONS.
11. ALL CONDUITS SHALL BE CONCEALED UNLESS OTHERWISE
NOTED.
12. PROVIDE DEDICATED NEUTRAL CONDUCTOR FOR ALL BRANCH
CIRCUITS.
G E N E R A L N O T E S
IP SECURITY CAMERA. CONTRACTOR TO PROVIDE
JUNCTION BOX AND 3/4" CONDUIT WITH NYLON PULL
STRING TO ACCESSIBLE CEILING SPACE.
PTZ = PAN TILT ZOOM
NOT SHADED = INDOOR
SHADED = OUTDOOR
A
ACCESS CONTROL PANEL
PTZ
PTZ
SPECIAL PURPOSE RECEPTACLE, RATING AS INDICATED
/ = TWISTLOCK
STANDARD RECEPTACLES: 125V, 20A 18" AFF, UON. TYPES:
SIMPLEX /DUPLEX /QUADRUPLEX /FLOOR DUPLEX /FLOOR
QUADRUPLEX
GFCI RECEPTACLES: 125V, 20A 18" AFF, UON. TYPES:
SIMPLEX /DUPLEX /QUADRUPLEX
X C = CEILING MOUNTED
S = HALF SWITCHED
I = ISOLATED GROUND
TR = TAMPER RESISTANT
a = LOWER CASE LETTER INDICATES SWITCH
CONTROL
2" = MEASUREMENT INDICATES HEIGHT ABOVE
BACKSPLASH/MILLWORK
A = INDICATES MOUNT ABOVE
BACKSPLASH/MILLWORK. COORDINATE
HEIGHT WITH TRADES.
USB = INDICATES 20A 120V DUPLEX RECEPTACLE
WITH USB CHARGER.
CT = SWITCHED RECEP, INDICATES FULL
CONTROLLED DEDICATED 20A 125V DUPLEX
CH = SWITCHED RECEP, INDICATES HALF
CONTROLLED DEDICATED 20A 125V DUPLEX
P
RO
JE
CT
S
YM
BO
LS
/L
EG
EN
DS
/D
ES
IG
NA
TI
ON
S
P O W E R
"1"
"a"
"NL"
"E"
INDICATES PANELBOARD AND CIRCUIT PROVIDING POWER
TO SWITCHLEG INDICATED FOR LUMINAIRES CONTAINED
IN SAME ROOM/AREA.
INDICATES TYPE PER LUMINAIRE SCHEDULE.
INDICATES NIGHT LIGHT LUMINAIRE.
INDICATES CONTROL PER SWITCH.
INDICATES POWER TO EMERGENCY LIGHTING
CONTAINED IN SAME ROOM/AREA.
1 E NL a
PNL-4
INDICATES CIRCUIT NUMBER.
INDICATES POWER SOURCE."PNL"
"4"
RECEPTACLE, TYPICAL:
LUMINAIRE, TYPICAL:
X-Xa/E
X-XE
X-Xa
WIRELESS ACCESS PORT; SEE SPECIAL SYSTEMS
CONNECTION SCHEDULE, WHEN INCLUDED ON PLANS.
WALL MOUNTED SPEAKER/CLOCK COMBINATION
WALL CLOCK - DIGITAL
WALL OR CEILING MOUNTED SPEAKER
CABLE TRAY
TELEVISION OUTLET, 18" AFF UON. STUB 3/4" CO INTO
ACCESSIBLE CEILING SPACE.
RECESSED AUDIO FLOOR BACK BOX, OUTLET AND CONDUITA/V
SHORT THROW PROJECTOR. MOUNT AT 86" AFF.
X-X
AB
BR
EV
IA
TI
ON
S
AFC
AFG
AF
AFCI
AFF
AIC
AHJ
ATS
C
CATV
CB
CCTV
CL
CO
COMM
DDC
DP
EC
EM
EMT
ER
FAAP
FACP
FATC
FCIO
FOIC
GFCI
GFP
GND
HTR
IG
IMC
JBOX
LCP
LTG
MCA
MCB
MCC
MDP
MGAP
MLO
MOCP
MS
MTD
NAC
NEC
NIC
NL
NTS
OC
OH
OS
PIV
PNL
PS
PVC
R
RCPT
RMC
SAC
SB,SWBD
SG
SPD
TEL
TR
TYP
UON
UL
UG
VD
VFD
W
WP
XFMR
AVAILABLE FAULT CURRENT
ABOVE FINISHED GRADE
AMP FRAME
ARC FLASH CIRCUIT INTERRUPTER
ABOVE FINISHED FLOOR
AMPERE INTERRUPTING CAPACITY
AUTHORITY HAVING JURISDICTION
AUTOMATIC TRANSFER SWITCH
CONDUIT OR CEILING
CABLE TELEVISION
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CONNECTOR LIGHTING
CONDUIT ONLY
COMMUNICATIONS
DIRECT DIGITAL CONTROLS
DISTRIBUTION PANELBOARD
ELECTRICAL CONTRACTOR
EMERGENCY
ELECTRICAL METALLIC TUBING
EXISTING TO REMAIN
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
FURNISHED BY CONTRACTOR, INSTALLED
BY OWNER
FURNISHED BY OWNER, INSTALLED BY
CONTRACTOR
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT PROTECTION
GROUND
HEATER
ISOLATED GROUND
INTERMEDIATE METALLIC CONDUIT
JUNCTION BOX
LIGHTING CONTROL PANEL
LIGHTING
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION PANEL
MEDICAL GAS ALARM PANEL
MAIN LUGS ONLY
MAXIMUM OVERCURRENT PROTECTION
MOTOR STARTER
MOUNTED
NOTIFICATION APPLIANCE CABINET
NATIONAL ELECTRICAL CODE
NOT IN CONTRACT
NIGHT LIGHT
NOT TO SCALE
ON CENTER
OVERHEAD
OCCUPANCY SENSOR
POST INDICATOR VALVE
PANEL
POWER SUPPLY
POLYVINYL CHLORIDE
EXISTING TO BE REMOVED
RECEPTACLE
RIGID METAL CONDUIT
SMALL APPLIANCE CIRCUIT
SWITCHBOARD
SWITCHGEAR
SURGE PROTECTIVE DEVICE
TELEPHONE
TAMPER RESISTANT
TYPICAL
UNLESS OTHERWISE NOTED
UNDERWRITERS LABORATORIES
UNDERGROUND
VOLTAGE DROP
VARIABLE FREQUENCY DRIVE
WEATHERPROOF (WHILE IN USE)
WEATHERPROOF
TRANSFORMER
RECEPTACLES
S E C U R I T Y
PHOTO ELECTRIC SENSOR
LUMINAIRE CONTROLS
#
NEW LUMINAIRE CONTROL. SEE LIGHTING CONTROL LEGEND
LOCATED ON LIGHTING SHEETS.
C O M M U N I C A T I O N S
CIRCUIT DESIGNATION
PROXIMITY FOB READER
OS CEILING MOUNTED OCCUPANCY SENSOR(S). PROVIDE SHOP
DRAWINGS OF OCCUPANCY SENSOR SYSTEM AS PER
PROJECT SPECIFICATION AS PART OF THE SUBMITTAL
PROCESS PRIOR TO COMMENCEMENT OF LABOR. SEE
LIGHTING CONTROL LEGEND LOCATED ON LIGHTING
SHEETS.
PE
RE
FE
RE
NC
E
SY
MB
OL
S
DETAIL
1
XXX
SCALE
SECTION
A
XXX
A
XXX
2
XXX
FAULT CURRENT TAG (AIC)
KEY NOTE
XX CONDUIT & WIRE TAG
1
SHEET WHERE DETAIL
IS TAKEN FROM
XX
FIGURE OR PHOTO
DETAIL NUMBER
IF PHOTO, ARROW DENOTES
DIRECTION TAKEN
DETAIL AREA
SHEET ON WHICH
SECTION APPEARS
SECTION LETTER
SHEET WHERE SECTION
IS TAKEN FROM
SECTION LETTER
SHEET WHERE SECTION
IS TAKEN FROM
DETAIL NUMBER
1
XXX
(X)
2P
30A
HH1
CONDUIT HOME RUN 3/4"C, 2#12 & 1#12
GND. UNLESS SHOWN OTHERWISE.
(EXAMPLE SHOWN: TO PANEL P1, CIRCUIT
1)
P1
P1-1
CONDUIT HOME RUN - SEE CONDUIT AND
WIRE SCHEDULE.
SWITCH
2 = DOUBLE POLE SWITCH
3 = THREE WAY SWITCH
4 = FOUR WAY SWITCH
P = SWITCH AND PILOT LAMP
K = KEY OPERATED SWITCH
T = SWITCH WITH TIMER
MS = MASTER SWITCH TO CONTROL ALL FIXED
LUMINAIRES IN GUEST UNIT
LUMINAIRE, SURFACE
LUMINAIRE, RECESSED
STRIP, SURFACE OR PENDANT AS
INDICATED IN LUMINAIRE SCHEDULE
LUMINAIRE, EMERGENCY
LUMINAIRE, WALL MOUNT
LIGHTED EXIT SIGN, ARROW
INDICATES DIRECTION
EMERGENCY WALL PACK
LUMINAIRE, POLE MOUNTED
SURFACE METAL RACEWAY WITH RECEPTACLE @ X" O.C.
CONDUIT CONCEALED IN WALL, CEILING,
UNDER FLOOR, IN FLOOR SLAB, OR
ROUTED UNDERGROUND
CONDUIT EXPOSED
EXISTING CONDUIT ROUTED
UNDERGROUND
OVERHEAD ELECTRICAL
EXTRA-HARD USAGE FLEXIBLE CORD
CONDUIT FLEXIBLE.
CONDUIT TURNED UP OR TOWARD
CONDUIT TURNED DOWN OR AWAY
CONDUIT CAPPED
CONDUIT SEALS. CLASS . I DIV. 1 OR DIV
2 EXPLOSION PROOF
CIRCUIT BREAKER, RATING/NO.
OF POLES WITH THERMAL
MAGNETIC CIRCUIT BREAKER
TRIP, UNLESS OTHERWISE
NOTED
MANUAL OR AUTOMATIC
TRANSFER SWITCH.
JUNCTION BOX
HANDHOLE WITH DESIGNATION
EQUIPMENT TO BE REMOVED
SHUNT TRIP PUSHBUTTON OR
KEY-SWITCH
PANELBOARD, SWITCHBOARD, OR
SWITCHGEAR. DASHED BOX INDICATES
CODE REQUIRED WORKING CLEARANCE
HARDWIRED CONNECTION
THERMOSTAT
ST
T
IC
SSS
BP
VFD
SOLID STATE STARTER, REDUCED
VOLTAGE WITH ISOLATION & BYPASS
CONTACTORS
VARIABLE FREQUENCY DRIVE
CONDUCTORS NOT CONNECTED.
CONDUCTORS CONNECTED.
PULL OUT SWITCH/PLUG-RECEPTACLE
CONNECTION
NORMALLY OPEN CONTACT (WHEN
DE-ENERGIZED)
NORMALLY CLOSED CONTACT (WHEN
DE-ENERGIZED)
UNIT HEATER
200AS
200AS/
100AF
60A
150W
3
CT
- +
M
DISCONNECT SWITCH, FUSED
200=SWITCH RATING, 100=FUSE
RATING
DISCONNECT SWITCH, NON
FUSED (60A) INDICATES
AMPERAGE RATING
MAGNETIC MOTOR STARTER
W/DISCONNECT
MAGNETIC MOTOR STARTER
FVNR = FULL VOLTAGE
NON-REVERSING
FVR = FULL VOLTAGE
REVERSING
2 = NEMA SIZE
GENERATOR
ELECTRIC HEATER, WATTAGE
INDICATED
EXHAUST OR SUPPLY FAN,
NUMBER INDICATES H.P.
MOTOR, NUMBER INDICATES
HORSEPOWER
CURRENT TRANSFORMER,
NUMBER INDICATES NUMBER OF
C.T.'S
TRANSFORMER
BATTERY
GROUND ROD IN GROUND ROD
BOX
UTILITY WATT HOUR METER
LIGHTING
SCHEMATIC PLAN
CB
2
10
1/4
G
T
60A
DETAIL NUMBER
SHEET ON WHICH
DETAIL APPEARS
E E
OE
X
M
MOTOR RATED SWITCH. WHERE
"M" INDICATED, PROVIDE A
MANUAL MOTOR STARTER
W/OVERLOAD
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR
FIRE ALARM
REQUEST TO EXIT
DUCT SMOKE DETECTOR
SMOKE DETECTOR
HEAT DETECTOR
MANUAL PULL STATION
HORN STROBE
HORN STROBE CEILING MOUNT
STROBE
STROBE CEILING MOUNT
SPEAKER STROBE WALL MOUNT
S
DOOR CONTACT
MAGNETIC DOOR HOLD (SECURITY)
ADA PUSH BUTTON
WALL MOUNTED INTERCOM/CLOCK COMBINATION
PULL STATION WITH CLEAR PLASTIC COVER
ADDRESSABLE RELAY
REMOTE ANNUNCIATOR
KITCHEN HOOD FIRE SUPPRESSION SYSTEM
FIRE SPRINKLER TAMPER SWITCH
PRESSURE SWITCH
FIRE SPRINKLER WATER FLOW SWITCH
WATER FLOW BELL
KNOX BOX
PULL CORD STATION
MAGNETIC DOOR HOLD (FIRE ALARM)
M/C
FFH
FFJ
NOTIFICATION APPLIANCE CIRCUIT PS
N
POST INDICATOR VALVE
FIREFIGHTER 2-WAY VOICE COMMUNICATION
SYSTEM HANDSET STATION
ADDRESSABLE MODULE M = MONITOR
C = CONTROL
FIREFIGHTER 2-WAY VOICE
COMMUNICATION SYSTEM JACK
MAGNETIC LOCK
MOTION DETECTOR
OVERHEAD DOOR CONTACT
WINDOW CONTACT
VIDEO/INTERCOM W/ INTEGRAL FOB READER
COMBINATION KEYPAD/FOB READER
ELECTRIC STRIKE
DOOR BELL
CARD READER
CIRCUIT BREAKER DISCONNECT
(60A) INDICATES AMPERAGE
RATING
60A
60A
#
#
WALL MOUNTED TELECOMMUNICATIONS OUTLET. 18" AFF,
UON. PROVIDE 4" BACKBOX AND 1"C ROUTED TO ACCESSIBLE
CEILING SPACE OR DIRECTLY TO MDF ROOM. DATA CABLING
INSTALLED IN FUTURE PHASE.
WALL PHONE 43" AFFP
FLOOR OR CEILING MOUNTED TELECOMMUNICATIONS OUTLET.
# INDICATES QUANTITY OF VOICE AND DATA JACKS.
PULLSTRING ALWAYS PROVIDED.
SPECIAL OUTLET HEIGHTS ARE SHOWN ON THE ELECTRICAL DRAWINGS OR ON THE ARCHITECTURAL DRAWINGS. IF SPECIAL OUTLET HEIGHTS ARE NOT SHOWN OR
REQUIRED, THEN LOCATE OUTLETS AS NOTED BELOW. OUTLET HEIGHTS ARE MEASURED FROM THE FINISHED FLOOR TO THE CENTERLINE OF THE OUTLET UNLESS