IO-Link Interface Description

KQ1000KQ1001

IOD

D-P

DF

Cre

ator

V 2

.0.0

.84

ifm-0

0039

C-2

0190

806-

IOD

D1.

1, V

1.3.

14.2

9C

opyr

ight

201

9, B

uild

er: 4

.4.3

.1, T

ime:

06:

57:4

4

Page 2: IO-Link Interface Description - ifm

2/22

Table of Contents

1 Device variant ................................................................................ 3

2 Communication ................................................................................ 4

3 Parameter overview ................................................................................ 5

4 System Commands ................................................................................ 8

5 Identification ................................................................................ 9

6 Observation ................................................................................ 10

6.1 Process Data Input/Output ................................................................................ 10

7 Parameter ................................................................................ 11

7.1 Application Setup ................................................................................ 11

7.2 Output configuration ................................................................................ 11

7.3 Digital output 1 ................................................................................ 12

7.4 Digital output 2 ................................................................................ 12

7.5 Digital output 3 ................................................................................ 13

7.6 Fault Configuration ................................................................................ 14

7.7 Counter configuration ................................................................................ 14

7.8 Damping ................................................................................ 15

7.9 Setting of the sensor display ................................................................................ 15

7.10 Memory ................................................................................ 15

7.11 Setup ................................................................................ 16

8 Diagnosis ................................................................................ 17

8.1 Diagnosis ................................................................................ 17

9 Events ................................................................................ 20

10 Error types ................................................................................ 21

Page 3: IO-Link Interface Description - ifm

3/22

1 Device variant

KQ1000

Capacitive level sensor

KQ1001

Capacitive level sensor

Page 4: IO-Link Interface Description - ifm

4/22

2 Communication

Vendor ID 0x0136 310 d / Bytes 1d 54d

Device ID 0x00039C 924 d / Bytes 0d 3d 156d

Bit rate COM2

Minimum cycle time 7,2 ms

SIO mode supported Yes

Block parameterization Yes

Data storage Yes

Supported profiles Measuring SensorIdentification and Diagnosis

Support of IO-Link 1.0 Yes

NOTE:If the Vendor ID and Device ID is referenced in your PLC system, then it is ensured that- the connected Device type is correct- the IO-Link datastorage is enabled- your application is still able to work, even your Device has been exchanged with a successor model.

For process value update rate, as well as further information concerning sensor performance, see datasheet

Page 5: IO-Link Interface Description - ifm

5/22

3 Parameter overview

Parameter Index Subindex Type Factory settingDevice Access Locks 12 RecordT (16 Bit) false

Vendor name 16 StringT (19 Byte) ifm electronic gmbh

Vendor text 17 StringT (11 Byte) www.ifm.com

Product Name 18 StringT (6 Byte)

Product ID 19 StringT (6 Byte)

Product Text 20 StringT (23 Byte) Capacitive Level Sensor

Serial Number 21 StringT (16 Byte)

Hardware Version 22 StringT (8 Byte)

Firmware Version 23 StringT (8 Byte)

Application Specific Tag 24 StringT (32 Byte) ***

Function Tag 25 StringT (32 Byte) ***

Location Tag 26 StringT (32 Byte) ***

Device Status 36 UIntegerT (8 Bit) 0 (Device is OK)

Detailed Device Status 37 OctetStringT (3 byte) [10] 0x00,0x00,0x00

Process data input 40 RecordT (32 Bit)

OUT1 Counter 350 IntegerT (32 Bit) 0

OUT2 Counter 351 IntegerT (32 Bit) 0

OUT3 Counter 352 IntegerT (32 Bit) 0

P-n 500 UIntegerT (8 Bit) 0 (PnP)

dAP 510 UIntegerT (16 Bit) 0

dFo 530 UIntegerT (16 Bit) 1

FOU1 531 UIntegerT (8 Bit) 1 (OU)

FOU2 532 UIntegerT (8 Bit) 1 (OU)

FOU3 533 UIntegerT (8 Bit) 1 (OU)

Power cycles 541 IntegerT (32 Bit) 0

Operating hours 542 IntegerT (32 Bit) 0

Internal temperature 543 IntegerT (16 Bit)

Internal_Temperature_HiLo 544 RecordT (32 Bit)

Lo 544 1 IntegerT (16 Bit)

Hi 544 2 IntegerT (16 Bit)

Active Events 545 RecordT (32 Bit)

Param configuration fault 546 UIntegerT (32 Bit) [10] 0 (OK)

Hi 560 IntegerT (16 Bit)

Lo 561 IntegerT (16 Bit)

ou1 580 UIntegerT (8 Bit) 3 (Hno / Hysteresis fct normally open)

dS1 581 UIntegerT (16 Bit) 0

dr1 582 UIntegerT (16 Bit) 0

SP1 (FH1) 583 IntegerT (16 Bit) 25

rP1 (FL1) 584 IntegerT (16 Bit) 20

ou2 590 UIntegerT (8 Bit) 16 (OFF / Output Off)

dS2 591 UIntegerT (16 Bit) 0

dr2 592 UIntegerT (16 Bit) 0

SP2 (FH2) 593 IntegerT (16 Bit) 50

rP2 (FL2) 594 IntegerT (16 Bit) 45

ou3 600 UIntegerT (8 Bit) 16 (OFF / Output Off)

Page 6: IO-Link Interface Description - ifm

6/22

3 Parameter overview

Parameter Index Subindex Type Factory settingdS3 601 UIntegerT (16 Bit) 0

dr3 602 UIntegerT (16 Bit) 0

SP3 (FH3) 603 IntegerT (16 Bit) 75

rP3 (FL3) 604 IntegerT (16 Bit) 70

Sensitivity 924 UIntegerT (8 Bit) 2 (Hi / High)

LED mode 1400 UIntegerT (8 Bit) 3 (ALL_On)

Orientation 1500 UIntegerT (8 Bit) 0 (bottom / Connector at bottom)

Limitation of sensor el... 1501 RecordT (16 Bit)

Bottom 1501 1 UIntegerT (8 Bit) 0

Top 1501 2 UIntegerT (8 Bit) 0

Minimum recognition thr... 1502 IntegerT (16 Bit) 128

Level detection diagnos... 1503 RecordT (32 Bit)

Level edge 1503 1 UIntegerT (8 Bit)

Signal strength 1503 2 UIntegerT (8 Bit)

Filling edge sharpn... 1503 3 UIntegerT (8 Bit)

Installation quality 1503 4 UIntegerT (8 Bit)

MDC Descr 16512 RecordT (88 Bit)

Lower limit 16512 1 IntegerT (32 Bit) 0 (0)

Upper limit 16512 2 IntegerT (32 Bit) 100 (100)

Unit code 16512 3 UIntegerT (16 Bit) 1342 (%)

Scale 16512 4 IntegerT (8 Bit) 0 (0)

Page 7: IO-Link Interface Description - ifm

7/22

4 System Commands

System Command information- Address: Index 2, Subindex 0- Datatype: UInteger (8 Bit)- AccessRight: Write Only

System Commands Text Description1 Upload Start Start block parameter upload

2 Upload End End block parameter upload

3 Download Start Start block parameter download

4 Download End Stop block parameter download

5 Store Finalize block parameterization and start Data Storage

6 Break Cancel block parameterization

130 Restore Factory Settings

161 Reset [Hi] and [Lo] memory

162 Reset [Lo] memory

163 Reset [Hi] memory

165 Reset [Hi.T] and [Lo.T] memory

166 Reset [Lo.T] memory

167 Reset [Hi.T] memory

170 Reset tank adjustments

195 Adjust SP1

196 Adjust SP2

197 Adjust rP1

198 Adjust rP2

208 Adjust empty tank

Page 8: IO-Link Interface Description - ifm

8/22

4 System Commands

System Commands Text Description209 Adjust full tank

210 Start dynamic tank adjustment

211 Stop dynamic tank adjustment

212 Cancel dynamic tank adjustment

213 Adjust SP3

214 Adjust rP3

222 Flash On

223 Flash Off

228 Reset counter to zero

240 IO-Link 1.1 system test command240, Event 8DFE appears

241 IO-Link 1.1 system test command241, Event 8DFE disappears

242 IO-Link 1.1 system test command242, Event 8DFF appears

243 IO-Link 1.1 system test command243, Event 8DFF disappears

Page 9: IO-Link Interface Description - ifm

9/22

5 Identification

Vendor name Index 16 Subindex 0 StringT (19 Byte) ReadOnlyFactory setting ifm electronic gmbh

Vendor text Index 17 Subindex 0 StringT (11 Byte) ReadOnlyFactory setting www.ifm.com

Product Name Index 18 Subindex 0 StringT (6 Byte) ReadOnly

Product Text Index 20 Subindex 0 StringT (23 Byte) ReadOnlyFactory setting Capacitive Level Sensor

Product ID Index 19 Subindex 0 StringT (6 Byte) ReadOnly

Serial Number Index 21 Subindex 0 StringT (16 Byte) ReadOnly

Hardware Version Index 22 Subindex 0 StringT (8 Byte) ReadOnly

Firmware Version Index 23 Subindex 0 StringT (8 Byte) ReadOnly

Application Specific Tag Index 24 Subindex 0 StringT (32 Byte) ReadWriteFactory setting ***

Function Tag Index 25 Subindex 0 StringT (32 Byte) ReadWrite

Plant designation, describes the device functionalityFactory setting ***

Location Tag Index 26 Subindex 0 StringT (32 Byte) ReadWrite

Location designation, identifies the device locationFactory setting ***

Page 10: IO-Link Interface Description - ifm

10/22

6 Observation

6.1 Process Data Input/Output

Process data input Index 40 Subindex 0 RecordT (32 Bit)

PDV1 IntegerT (16 Bit)

Current process data 1Value range [%] (0 To 100) * 1

32764 (NoData)

Device status UIntegerT (4 Bit)

Current device status, a copy of the parameter [Device Status, Index 36] in the process data channelValue range 0 (Device is OK)

1 (Maintenance required)2 (Out of specification)3 (Functional check)4 (Failure)

OUT3 BooleanT

Status depends on [OU3]Value range false (inactive)

true (active)

OUT2 BooleanT

Status depends on [OU2]Value range false (inactive)

true (active)

OUT1 BooleanT

Status depends on [OU1]Value range false (inactive)

true (active)

Process data displayed according device sort order.Please note: Siemens PLCs swap the high and low byte when using byte addressing.

Page 11: IO-Link Interface Description - ifm

11/22

7 Parameter

7.1 Application Setup

Orientation Index 1500 Subindex 0 UIntegerT (8 Bit) ReadWrite

Orientation of sensor installation

Factory setting 0 (bottom / Connector at bottom)Value range 0 (bottom / Connector at bottom)

1 (top / Connector on top)

Limitation of sensor elements Index 1501 Subindex 0 RecordT (16 Bit) ReadWrite

Deactivated sensor elements from bottom up/top down

Bottom Subindex 1 UIntegerT (8 Bit)

From bottom upFactory setting 0Value range (0 To 10)

Top Subindex 2 UIntegerT (8 Bit)

From top downFactory setting 0Value range (0 To 10)

Sensitivity Index 924 Subindex 0 UIntegerT (8 Bit) ReadWrite

Sensitivity of the sensor

Factory setting 2 (Hi / High)Value range 0 (Lo / Low)

2 (Hi / High)

Minimum recognition threshold Index 1502 Subindex 0 IntegerT (16 Bit) ReadWrite

Minimum recognition threshold as from which the signals are recognised as valid

Factory setting 128Value range (64 To 3200)

7.2 Output configuration

ou1 Index 580 Subindex 0 UIntegerT (8 Bit) ReadWrite

Output configuration [OUT 1]

Factory setting 3 (Hno / Hysteresis fct normally open)Value range 3 (Hno / Hysteresis fct normally open)

4 (Hnc / Hysteresis fct normally closed)5 (Fno / Window fct normally open)6 (Fnc / Window fct normally closed)12 (dOU / Diagnostic output)16 (OFF / Output Off)

ou2 Index 590 Subindex 0 UIntegerT (8 Bit) ReadWrite

Output configuration [OUT 2]

Factory setting 16 (OFF / Output Off)Value range 3 (Hno / Hysteresis fct normally open)

4 (Hnc / Hysteresis fct normally closed)5 (Fno / Window fct normally open)6 (Fnc / Window fct normally closed)12 (dOU / Diagnostic output)16 (OFF / Output Off)

Page 12: IO-Link Interface Description - ifm

12/22

7 Parameter

ou3 Index 600 Subindex 0 UIntegerT (8 Bit) ReadWrite

Output configuration [OUT 3]

Factory setting 16 (OFF / Output Off)Value range 3 (Hno / Hysteresis fct normally open)

4 (Hnc / Hysteresis fct normally closed)5 (Fno / Window fct normally open)6 (Fnc / Window fct normally closed)12 (dOU / Diagnostic output)16 (OFF / Output Off)

P-n Index 500 Subindex 0 UIntegerT (8 Bit) ReadWrite

Output polarity for the switching outputs

Factory setting 0 (PnP)Value range 0 (PnP)

1 (nPn)

7.3 Digital output 1

SP1 (FH1) Index 583 Subindex 0 IntegerT (16 Bit) ReadWrite

Switch point 1. SP1 shall be above rP1. Min distance SP1...rP1 = 1 %. For details, see operating manual.

Factory setting 25Value range [%] (5 To 95) * 1

rP1 (FL1) Index 584 Subindex 0 IntegerT (16 Bit) ReadWrite

Reset point 1. Reset point 1. rP1 shall be below SP1. Min distance SP1...rP1 ===> see SP1.

Factory setting 20Value range [%] (4 To 94) * 1

dS1 Index 581 Subindex 0 UIntegerT (16 Bit) ReadWrite

Switching delay for [OUT 1]

Factory setting 0Value range [s] (0 To 43200) * 1

dr1 Index 582 Subindex 0 UIntegerT (16 Bit) ReadWrite

Reset delay for [OUT 1]

Factory setting 0Value range [s] (0 To 43200) * 1

7.4 Digital output 2

SP2 (FH2) Index 593 Subindex 0 IntegerT (16 Bit) ReadWrite

Switch point 2. SP2 shall be above rP2. Min distance SP2...rP2 = 1 %. For details, see operating manual.

Factory setting 50Value range [%] (5 To 95) * 1

Page 13: IO-Link Interface Description - ifm

13/22

7 Parameter

rP2 (FL2) Index 594 Subindex 0 IntegerT (16 Bit) ReadWrite

Reset point 2. Reset point 2. rP2 shall be below SP2. Min distance SP2...rP2 ===> see SP2.

Factory setting 45Value range [%] (4 To 94) * 1

dS2 Index 591 Subindex 0 UIntegerT (16 Bit) ReadWrite

Switching delay for [OUT 2]

Factory setting 0Value range [s] (0 To 43200) * 1

dr2 Index 592 Subindex 0 UIntegerT (16 Bit) ReadWrite

Reset delay for [OUT 2]

Factory setting 0Value range [s] (0 To 43200) * 1

7.5 Digital output 3

SP3 (FH3) Index 603 Subindex 0 IntegerT (16 Bit) ReadWrite

Switch point 3. SP3 shall be above rP3. Min distance SP3...rP3 = 1 %. For details, see operating manual.

Factory setting 75Value range [%] (5 To 95) * 1

rP3 (FL3) Index 604 Subindex 0 IntegerT (16 Bit) ReadWrite

Reset point 3. Reset point 3. rP3 shall be below SP3. Min distance SP3...rP3 ===> see SP3.

Factory setting 70Value range [%] (4 To 94) * 1

dS3 Index 601 Subindex 0 UIntegerT (16 Bit) ReadWrite

Switching delay for [OUT 3]

Factory setting 0Value range [s] (0 To 43200) * 1

dr3 Index 602 Subindex 0 UIntegerT (16 Bit) ReadWrite

Reset delay for [OUT 3]

Factory setting 0Value range [s] (0 To 43200) * 1

Page 14: IO-Link Interface Description - ifm

14/22

7 Parameter

7.6 Fault Configuration

FOU1 Index 531 Subindex 0 UIntegerT (8 Bit) ReadWrite

[OUT 1] behaviour in case of fault

Factory setting 1 (OU)Value range 1 (OU)

2 (On)4 (OFF)

FOU2 Index 532 Subindex 0 UIntegerT (8 Bit) ReadWrite

[OUT 2] behaviour in case of fault

Factory setting 1 (OU)Value range 1 (OU)

2 (On)4 (OFF)

FOU3 Index 533 Subindex 0 UIntegerT (8 Bit) ReadWrite

[OUT 3] behaviour in case of fault

Factory setting 1 (OU)Value range 1 (OU)

2 (On)4 (OFF)

dFo Index 530 Subindex 0 UIntegerT (16 Bit) ReadWrite

Delay time of outputs after fault

Factory setting 1Value range [s] (0 To 43200) * 1

7.7 Counter configuration

OUT1 Counter Index 350 Subindex 0 IntegerT (32 Bit) ReadOnly

Output 1, Switching process counter

Factory setting 0Value range (0 To 2000000000)

OUT2 Counter Index 351 Subindex 0 IntegerT (32 Bit) ReadOnly

Output 2, Switching process counter

Factory setting 0Value range (0 To 2000000000)

OUT3 Counter Index 352 Subindex 0 IntegerT (32 Bit) ReadOnly

Output 3, Switching process counter

Factory setting 0Value range (0 To 2000000000)

Page 15: IO-Link Interface Description - ifm

15/22

7 Parameter

7.8 Damping

dAP Index 510 Subindex 0 UIntegerT (16 Bit) ReadWrite

Damping of the measured signal

Factory setting 0Value range [s] (0 To 3600) * 1

7.9 Setting of the sensor display

LED mode Index 1400 Subindex 0 UIntegerT (8 Bit) ReadWrite

LED mode

Factory setting 3 (ALL_On)Value range 0 (ALL_OFF)

1 (STAT)2 (STAT_OUT)3 (ALL_On)

7.10 Memory

Lo Index 561 Subindex 0 IntegerT (16 Bit) ReadOnly

Minimum memory value

Value range [%] (0 To 100) * 132764 (NoData)

Hi Index 560 Subindex 0 IntegerT (16 Bit) ReadOnly

Maximum memory value

Value range [%] (0 To 100) * 132764 (NoData)

Internal temperature Index 543 Subindex 0 IntegerT (16 Bit) ReadOnly

Current internal temperature of the device

Value range [°C] (-100 To 300) * 132764 (NoData)

Internal_Temperature_HiLo Index 544 Subindex 0 RecordT (32 Bit) ReadOnly

Internal temperature memory

Lo Subindex 1 IntegerT (16 Bit)

Internal minimum [Lo.T] temperatureValue range [°C] (-100 To 300) * 1

32764 (NoData)

Hi Subindex 2 IntegerT (16 Bit)

Internal maximum [Hi.T] temperatureValue range [°C] (-100 To 300) * 1

32764 (NoData)

Page 16: IO-Link Interface Description - ifm

16/22

7 Parameter

Power cycles Index 541 Subindex 0 IntegerT (32 Bit) ReadOnly

Number of power cycles since delivery

Factory setting 0Value range (0 To 1000000)

Operating hours Index 542 Subindex 0 IntegerT (32 Bit) ReadOnly

Counter of the operating hours since delivery

Factory setting 0Value range [h] (0 To 500000) * 1

7.11 Setup

Device Access Locks Index 12 Subindex 0 RecordT (16 Bit) ReadWrite

Local Parameterization Lock bitOffset 2 BooleanTFactory setting false

MDC Descr Index 16512 Subindex 0 RecordT (88 Bit) ReadOnly

Description of the measurement data channel

Lower limit Subindex 1 IntegerT (32 Bit)

Lower value measurement rangeFactory setting 0 (0)Value range 0 (0)

Upper limit Subindex 2 IntegerT (32 Bit)

Upper value measurement rangeFactory setting 100 (100)Value range 100 (100)

Unit code Subindex 3 UIntegerT (16 Bit)

Unit code of the measurement dataFactory setting 1342 (%)Value range 1342 (%)

Scale Subindex 4 IntegerT (8 Bit)

Range shifting (10 scale)Factory setting 0 (0)Value range 0 (0)

Page 17: IO-Link Interface Description - ifm

17/22

8 Diagnosis

8.1 Diagnosis

Device Status Index 36 Subindex 0 UIntegerT (8 Bit) ReadOnlyFactory setting 0 (Device is OK)Value range 0 (Device is OK)

1 (Maintenance required)2 (Out of specification)3 (Functional check)4 (Failure)(5 To 255) (Reserved)

Detailed Device Status Index 37 Subindex 0 OctetStringT (3 byte) [10] ReadOnlyFactory setting 0x00,0x00,0x00

Active Events Index 545 Subindex 0 RecordT (32 Bit) ReadOnly

Bit mask for current pending events

Bit_31 bitOffset 31 BooleanT

Test Event 2. Device Status = 1 (Maintenance required)Factory setting 0 (noEv)Value range 0 (noEv)

1 (0x8DFF)

Bit_30 bitOffset 30 BooleanT

Test Event 1. Device Status = 1 (Maintenance required)Factory setting 0 (noEv)Value range 0 (noEv)

1 (0x8DFE)

Bit_29 bitOffset 29 BooleanT

Flash sequence active. Device Status = 1 (Maintenance required)Factory setting 0 (noEv)Value range 0 (noEv)

1 (0x8CDB)

Bit_16 bitOffset 16 BooleanT

Plausibility error. Device Status = 2 (Out of specification)Factory setting 0 (noEv)Value range 0 (noEv)

1 (0x8CA4)

Bit_11 bitOffset 11 BooleanT

Signal fault. Device Status = 2 (Out of specification)Factory setting 0 (noEv)Value range 0 (noEv)

1 (0x8CC0)

Bit_10 bitOffset 10 BooleanT

Maintenance required - CleaningFactory setting 0 (noEv)Value range 0 (noEv)

1 (0x8C40)

Bit_3 bitOffset 3 BooleanT

Parameter missingFactory setting 0 (noEv)Value range 0 (noEv)

1 (0x6321)

Page 18: IO-Link Interface Description - ifm

18/22

8 Diagnosis

Active Events Index 545 Subindex 0 RecordT (32 Bit) ReadOnly

Bit_2 bitOffset 2 BooleanT

Short circuitFactory setting 0 (noEv)Value range 0 (noEv)

1 (0x7710)

Bit_1 bitOffset 1 BooleanT

Parameter errorFactory setting 0 (noEv)Value range 0 (noEv)

1 (0x6320)

Bit_0 bitOffset 0 BooleanT

Device hardware faultFactory setting 0 (noEv)Value range 0 (noEv)

1 (0x5000)

Param configuration fault Index 546 Subindex 0 UIntegerT (32 Bit) [10] ReadOnly

Displays the incorrectly set parameters

Factory setting 0 (OK)Value range 0 (OK)

786432 (Device Access Locks, Index = 12)32768000 (P-n, Index = 500)33423360 (dAP, Index = 510)34734080 (dFo, Index = 530)34799616 (FOU1, Index = 531)34865152 (FOU2, Index = 532)34930688 (FOU3, Index = 533)38010880 (ou1, Index = 580)38076416 (dS1, Index = 581)38141952 (dr1, Index = 582)38207488 (SP1 (FH1), Index = 583)38273024 (rP1 (FL1), Index = 584)38666240 (ou2, Index = 590)38731776 (dS2, Index = 591)38797312 (dr2, Index = 592)38862848 (SP2 (FH2), Index = 593)38928384 (rP2 (FL2), Index = 594)39321600 (ou3, Index = 600)39387136 (dS3, Index = 601)39452672 (dr3, Index = 602)39518208 (SP3 (FH3), Index = 603)39583744 (rP3 (FL3), Index = 604)60555264 (Sensitivity, Index = 924)91750400 (LED mode, Index = 1400)98304000 (Orientation, Index = 1500)98369536 (Limitation of sensor elements, Index = 1501)98369537 (Limitation of sensor elements, Index = 1501, Subindex = 1)98369538 (Limitation of sensor elements, Index = 1501, Subindex = 2)98435072 (Minimum recognition threshold, Index = 1502)

Level detection diagnostic data Index 1503 Subindex 0 RecordT (32 Bit) ReadOnly

diagnostic data: Level edge, Signal strength, Filling edge sharpness, Installation quality

Level edge Subindex 1 UIntegerT (8 Bit)

Index of level edgeValue range (0 To 13)

255 (NoData)

Signal strength Subindex 2 UIntegerT (8 Bit)

Signal strength referred to the dynamic rangeValue range (0 To 100)

255 (NoData)

Page 19: IO-Link Interface Description - ifm

19/22

8 Diagnosis

Level detection diagnostic data Index 1503 Subindex 0 RecordT (32 Bit) ReadOnly

Filling edge sharpness Subindex 3 UIntegerT (8 Bit)

Filling edge sharpnessValue range (0 To 100)

255 (NoData)

Installation quality Subindex 4 UIntegerT (8 Bit)

Installation quality referred to the dynamic rangeValue range (0 To 100)

255 (NoData)

Page 20: IO-Link Interface Description - ifm

20/22

9 Events

Code Device status PQ* Class Name Description0x500020480d

4 (Failure) invalid Error Device hardware fault Device Exchange

0x632025376d

3 (Functional check) invalid Error Parameter error Check data sheet and values

0x632125377d

3 (Functional check) valid Error Parameter missing Check data sheet

0x771030480d

3 (Functional check) valid Error Short circuit Check installation

0x8C4035904d

unchanged valid Notification Maintenance required - Cleaning Clean device

0x8CA436004d

2 (Out of specification) valid Warning Plausibility error. Device Status = 2(Out of specification)

Check Measurement

0x8CC036032d

2 (Out of specification) valid Warning Signal fault. Device Status = 2 (Outof specification)

Please check your application

0x8CDB36059d

1 (Maintenancerequired)

valid Warning Flash sequence active. DeviceStatus = 1 (Maintenance required)

Deactivate flash sequence

0x8DFE36350d

1 (Maintenancerequired)

valid Warning Test Event 1. Device Status = 1(Maintenance required)

Event appears by setting index 2 to value240, Event disappears by setting index 2 tovalue 241

0x8DFF36351d

1 (Maintenancerequired)

valid Warning Test Event 2. Device Status = 1(Maintenance required)

Event appears by setting index 2 to value242, Event disappears by setting index 2 tovalue 243

Events are raised by the device itself to notify irregular device statesPQ* = Process data quality

nnnnnnnnnnnnnnnnnnn nnnnnnnn1 (Maintenancerequired)

valid Warning

Page 21: IO-Link Interface Description - ifm

21/22

10 Error types

Code Name Description0x800032768d

Device application error - no details Service has been refused by the device application and no detailed information of theincident is available

0x801132785d

Index not available Access occurs to a not existing index

0x801232786d

Subindex not available Access occurs to a not existing subindex

0x802032800d

Service temporarily not available Parameter is not accessible due to the current state of the device application

0x802132801d

Service temporarily not available -local control

Parameter is not accessible due to an ongoing local operation at the device

0x802232802d

Service temporarily not available -device control

Parameter is not accessible due to a remote triggered state of the device application

0x802332803d

Access denied Write access on a read-only parameter

0x803032816d

Parameter value out of range Written parameter value is outside its permitted value range

0x803332819d

Parameter length overrun Written parameter length is above its predefined length

0x803432820d

Parameter length underrun Written parameter length is below its predefined length

0x803532821d

Function not available Written command is not supported by the device application

0x803632822d

Function temporarily unavailable Written command is not available due to the current state of the device application

0x804032832d

Invalid parameter set Written single parameter collides with other actual parameter settings

0x804132833d

Inconsistent parameter set Parameter inconsistencies were found at the end of block parameter transfer, deviceplausibility check failed

0x808232898d

Application not ready Read or write service is refused due to a temporarily unavailable application

Error types are used for the ISDU response. Values unequal '0' indicate the cause of a failed ISDU read or writeservice.

Page 22: IO-Link Interface Description - ifm

22/22

Additional device-specific information On delivery, the unit is not operational! First of all the sensor has to be adjusted to the application / the tank (see

operating instructions). Only carry out the tank adjustment when the unit is installed!

The sensor calculates the level based on the measured capacitances of its individual measuring segments. To ensure

correct calculation the measured capacitances have to be comparable. This means that in some applications

additional grounding may become necessary (see operating instructions, chapter Troubleshooting).

Note! The tank adjustment is not part of the data storage!

After unit replacement, adjustment has to be made again manually via IO-Link. Only when the tank adjustment has

been carried out successfully does the unit revert to the cyclical process data transmission.

Note!

After a factory reset, the factory settings are restored.

The unit is not operational!

Adjustment options (standard commands)

Adjust empty tank: The process value of the unit is adjusted to an empty tank.

"Empty" means the level is below the detection range.

Adjust full tank: The process value of the unit is adjusted to a full tank.

"Full" means the level is above the detection range.

Dynamic tank adjustment: The process value of the unit is adjusted to the level in the measurement range

during the time window (start to stop). During the entire time window, the level has

to be in the measuring range! The dynamic adjustment does not have a timeout and

therefore always has to be stopped or aborted via IO-Link.

For non-changing products, the highest operational reliability is obtained by carrying out empty and full adjustments.

These two adjustments are also recommended for adhering products if they remain unchanged.

Deposits can only be detected when empty and full adjustments have been made!

For changing products (with extremely different dielectric constants) only the adjustment to the empty tank should

be made.

Causes of events

Event Meaning 0x5000 The unit is faulty / has to be replaced. 0x6320 The parameter value is outside the permissible range. Check the data sheet and the values. 0x6321 Adjustment or parameter missing. Make a tank adjustment or check the data sheet. 0x7710 Short-circuit on a switching output. Check the installation. 0x8C40 Deposits in the detection range were detected. Clean the detection range / inner wall of the tank. 0x8CA4 Several levels were found in the detection range. Check the installation and the inside of the tank for bubbles,

voids or deposits. 0x8CC0 The signal strength is too low or to too high. Increase or decrease the sensitivity of the unit (see operating

instructions).