INSTALLATION MANUAL VENTUM SERIES
41

INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Mar 16, 2023

Download

Documents

Khang Minh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

INSTALLATION MANUALVENTUM SERIES

Page 2: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Table of Contents

1. General Information 3

2. Installation 4

2.1 Unwrapping the Product 4

2.2 Assembly 4

2.3 Weights 5

2.4 Installation 5

2.4.1 Ceiling Mount 5

2.5 Installation of Accessories 7

2.5.1 Coupled Accessories 7

2.5.2 Decoupled Accessories 9

2.6 External Sensors 10

2.6.1 Supply Air Temperature Sensor 10

2.6.2 Pressure Sensor 10

2.6.3 CO2/VOC Sensor 11

2.6.4 Combination Temperature 12

/Humidity Sensor

3. Access Requirements 13

4. Lifting Requirements 13

5. Electrical Hook-Ups 14

5.1 Electrical Information 15

5.2 1PH Electrical Hook Up (2 Fans) 16

5.3 3PH Electrical Hook Up (2 Fans) 17

5.6 1PH Lite Electrical Hook Up (2 Fans) 18

5.7 3PH Lite Electrical Hook Up (2 Fans) 19

6.0 Wiring Diagrams 20

6.1 Ventum 240V, Single Phase, S1 21

6.2 Ventum 240V, Single Phase S2 22

6.3 Ventum, Three Phase, S1 23

6.4 Ventum, Three Phase, S2 24

6.5 Field Wiring, DX Coil, EKE 25

6.6 Field Wiring, DX Coil, Electric Reheat, EKE 26

6.7 Field Wiring, Electric Preheat, DX Coil 27 Electric Reheat, EKE

6.8 Field Wiring, Electric Preheat, DX Coil, EKE 28

6.9 Field Wiring, Damper Wiring 29

6.10 Field Wiring, Electric Reheat Wiring 30

6.11 Field Wiring, Electric Preheat, 31 Electric Reheat Wiring

6.12 Field Wiring, Electric Preheat Wiring 32

6.13 Field Wiring, Cooling Water Coil 33

6.14 Field Wiring, Humidity Control 34

6.15 Field Wiring, Combi Coil 35

6.16 Field Wiring, Hydronic Preheat 36

6.17 Field Wiring, Occupancy Mode 37

6.18 Field Wiring, Hydronic Reheat 38

6.19 Field Wiring, Fire Alarm 39

6.20 Field Wiring, DX Coil, Hydronic Reheat 40 EKE, Bypass 6.21 Field Wiring, CO2 Control, 41 External Bypass

Page 3: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

3

This manual includes important instructions for safe connection of the Heat Recovery Ventilator (HRV) or Energy Recovery Ventilator (ERV). Before connecting the unit, please read carefully and follow all of the instructions below! The manufacturer reserves the right to make changes, including changes in the technical documentation, without previous notification. Please keep this manual for future reference. Consider this manual a permanent part of the product.

This manual will show the manufacturers' recommended installation method. Please note that local codes and regulations may override these recommendations. The installation must follow local codes and standards.

The National Electric Code (NEC), the National Fire Protection Agency (NFPA), and the Canadian Electrical Code (CEC) must be followed. Installation of this product must be performed by a qualified and accredited professional in conformance with local and national codes, standards and licensing requirements.

Warnings and Caution

Warnings and cautions appear at the appropriate sections throughout this manual. Please read these sections carefully.

Warning

This sign indicates a potentially hazardous situation, which could result in death or serious injury if not avoided.

Caution

This sign indicates a potentially hazardous situation, which may result in minor or moderate injury if not avoided. It may also alert against unsafe practices.

Caution

This label indicates a situation that may result in equipment or property damage only accidents.

1.0 General Information

Page 4: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

4

2.1 Unwrapping the Product

When removing the shrink wrap, be cautious with knives and sharp tools to prevent scratching the paint.

The HMI, pressure sensor, external duct pressure sensor and all other optional field components will be found in the electrical box or fan compartment. They are secured there for transport and to easily find them on the job site.

2.2 Assembly

Remove the middle panel for wiring access. Fans and filters are accessible via the bottom doors. Fans should be pre-wired and no assembly is required.

Use the following steps to disassemble the fan section from the core section.

1. Remove the cover from the fan.

2. Undo the screw terminals that are holding the power wires and the communication wires. *See back of manual for electrical drawings.

3. Loosen the cable glands and pull the wires out of the motor.

4. Pull the pressure tube from the nozzle port on the fan bell mouth.

5. Push the pressure tube and all cables back into the core section, through the rubber grommets that are on the fan wall.

6. Repeat steps 1 ― 5 for the other fan.

2.0 Installation

1 2 43 5

Unit Wrapped

for Shipping

4x Corner

Page 5: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

5

2.3 Weights

Model Fan (A) lbs. Core (B) lbs. Total Weight lbs.

H05 27 13 450

H10 28.7 13 620

H15 37.5 22 720

H20 37.5 22 820

H25 48.5 64 1130

H30 48.5 64 1300

A

B

2.4 Installation

2.4.1 Ceiling Mount

Ventum is available exclusively for ceiling mount/horizontal applications with inner and outer brackets only. The hanging brackets are supplied loose with the necessary hardware to install them. They are not shipped assembled due to the variability of installation access on job sites. The front panel of the unit must be removed to slide the core into the unit.

Each hanging bracket is composed of two pieces: an inner component and an outer component. The units are designed to have four sets of brackets to support the unit.

Note Depending on the ducted opening location selected during the design phase, the location of the brackets will vary. Please consult your submittal drawings for specific locations.

Inner Bracket

OuterBracket

Warning

The unit must be installed with both the inner and outer bracket. Each unit must also have all four brackets installed to meet these guidelines.

Ceiling Mounted Unit

Page 6: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

6

Assembly of Hanging Brackets

1. Locate the position of the brackets on the outside of the unit.

2. Mark the 8 hole locations and drill to allow for the ¼" bolt. 32 - ¼" bolts, 32 - ¼" lock nut, 32 - ¼" washers and 64 - ¼" washers have been provided with the unit.

3. Assemble the hanging bracket by aligning the 8 holes of the outer bracket through the unit and with the inner bracket. Note: the inner component should be oriented so that its flange is pointing to the ceiling, and the outer bracket has the single hole pointing to the ceiling.

4. Install the 8 bolts. Caution - Do not over tighten and crush the panel.

5. Install 4 tek-screws in the flange portion of the inner bracket and secure it to the top casing of the unit.

6. Install 4 tek-screws in the lower flange of the outer bracket to secure it to the bottom frame of the unit.

7. Repeat steps 1 through 6 for the remainder of the brackets.

8. The hole in the outer brackets are designed for a ½" threaded rod to hang the units by.

Bracket Alignment

Page 7: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

7

2.5 Installation of Accessories

2.5.1 Coupled Accessories

Coupled Accessory with Ceiling Mounted Unit

Mounted Coupled Accessory

Page 8: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

8

Corner brackets come pre-installed with each Ventum unit. Accessories should be independently supported with Unistrut on the end farthest from the unit. Base mounted accessories that are connect to a duct connection in the lower position of the unit will come with matching base rails.

Accessories that are to be connected to a duct connection in the upper position will need to be supported externally.

1 2

Page 9: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

9

2.5.2 Decoupled Accessories

Ceiling hung decoupled accessories will not come with hanging brackets and can be supported in the ceiling with horizontal brackets and threaded rod or equivalent.

Page 10: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

10

2.6 External Sensors

2.6.1 Supply Air Temperature Sensor

TTH-6202 sensors are installed in the ventilation duct using the accompanying bracket, which must be attached to a firm, level surface by means of two screws. The supply voltage is provided via the Modbus connection. TTH-6202 has a pre-fitted cable,

which is equipped with a standard RJ12 connector. The cable may be extended up to 50 m using a Category 3 extension cable. The sensor must be mounted according to, and must be aligned parallel to the air flow in the center of the duct.

*Sensor must be installed a minimum of 5' from the heating or cooling module.

2.6.2 Pressure Sensor

Sensor must be installed ⅔ of the way down the duct in the duct path that would result in the most pressure drop.

Supply Air

Return Air

5'*

Supply Air

Page 11: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

11

2.6.3 CO2/VOC Sensor

VTH-6202 sensors are installed in the ventilation duct using the accompanying bracket, which must be attached to a firm, level surface by means of two screws. The 18-30 V DC supply voltage (24 V DC nominal voltage) is provided via the Modbus connection. VTH-6202 has a pre-fitted 7000 mm cable, which is equipped with a standard RJ12 connector. The cable may be extended to as much as 50 m without any negative effects on measuring accuracy. The surrounding EMC environment must, however, be taken into account and must be capable of being defined as

low. To extend the cable, use a crossover Category 3 extension cable, RJ12-RJ12, 6P6C. The sensor should be installed in such a way that the air flow in the duct can pass unhindered through the measuring hole at the end of the sensor, which should be aligned parallel to the air flow. Although the VTH-6202 is not affected by the position in which it is installed, it should not be installed in an upright position with the cable downwards as this may cause moisture to accumulate in the sensor.

The enclosure is opened without the use of tools by pressing the snap lock at the side of the tube connectors. PTH-6202 is attached onto a level surface by 2 screws, which are screwed into a solid surface. PTH-6202 can be fitted in all directions without accuracy being affected. PTH-6202 also functions with only one tube fitted to the connectors (+ or -). However, two tubes should always be fitted to ensure a suitable enclosure rating, if the connectors do not face downwards. Pressure is supplied to the measurement unit by tubes, the highest pressure being connected to the ‘+ connector’ and the lowest

pressure to ‘- connector’. The pressure tubes must be as short as possible and must be secured in position to prevent vibration. To obtain the best possible results, pressure must be measured where there is least risk of turbulence, i.e. in the center of the ventilation duct and at a distance of at least twice the width of the duct from bends and six times the width from branches. If there is a risk of condensation forming in connection tubes, PTH-6202 is to be located in such a way that condensate fluids cannot flow back into the pressure transmitter.

Supply Air

Return Air

In duct view

Page 12: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

12

2.6.4 Combination Temperature/ Humidity Sensor

HTH-6202 sensors are installed in the ventilation duct using the accompanying bracket, which must be attached to a firm, level surface by means of two screws. The 18-30 V DC supply voltage (24 V DC nominal voltage) is provided via the Modbus connection. HTH-6202 has a pre-fitted 7000 mm cable, which is equipped with a standard RJ12

connector. The cable may be extended to as much as 50 m without any negative effects on measuring accuracy. The surrounding EMC environment must, however, be taken into account and must be capable of being defined as low. To extend the cable, use a crossover Category 3 extension cable, RJ12-RJ12, 6P6C. The sensor should be installed in such a way that the air flow in the duct can pass unhindered through the measuring hole at the end of the sensor, which should be aligned parallel to the air flow. Although HTH-6202 is not affected by the position in which it is installed, it is advisable not to install the sensor in an upright position with the cable downwards as this may cause moisture to accumulate in the sensor. It is important that HTH-6202 is installed in such a way that the measuring hole is positioned at the center of the duct.

5'*

*Sensor must be installed a minimum of 5' from the heating or cooling module.

In duct view

Supply Air

Page 13: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

13

3.0 Access Requirements

Top of Unit

The National Electrical Code (NEC) requires 36 inches of clearance from an electrical connection. For Ventum, with a front-mounted electrical box, the 3’ must be measured from the front of the box. The unit should be mounted such that the bottom doors remain accessible.

4.0 Lifting RequirementsUnits can be lifted by mounting angles. Lifting directly from the frame is not recommended.

Door with removed hinge pinUnit with doors open

Page 14: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

14

Installation Manual Ventum Series

5.0 Electrical Hook Ups

Warning

Hazardous voltage, disconnect all electrical power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be accidentally re-engaged.

3 phase, 4 wire, 208V, 460V -10% - +15%, 60Hz

Recommended fuse diagram

1 phase, 3 wire, 240V -10% - +15%, 60Hz

Recommended fuse diagram

Unit Size 208V 460V

C24-ERV 25A 15A

C30-ERV 25A 15A

C24-FC 15A 15A

C30-FC 20A 15A

Unit Size 208V

A16-ERV 15A

B20-ERV 15A

A16-FC 15A

B20-FC 15A

Page 15: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

15

5.1 Electrical Information

Model

Airflow

Nom. V.

Motor

kW

SA

Fan

Qty.

SA

Fan

FLA

SA Fan

FLA

Total

RA

Fan

Qty.

SA

Fan

FLA

SA Fan

FLA

Total

Tnsfmr

FLA

Fuse

Size

FLA

MCA

MROP

D

Rcmd

Fuse

H05 600 240 0.5 2.5 2.5 0.29 5.39 5.91 8.41 15A 3/10 5.29 5.91 8.41 15A

H10 1000 240 0.78 3.9 3.9 0.29 8.09 9.06 12.96 15A 3/10 8.09 9.06 12.96 15A

H15 1350 208 2.0 6.0 6.0 0.33 12.33 13.83 19.83 15A 4/10 12.33 13.83 19.83 15A

H15 1350 460 2.5 4.0 4.0 0.14 8.14 9.14 13.14 15A 3/16 8.14 9.14 13.14 15A

H20 1800 208 2.0 6.0 6.0 0.33 12.33 13.83 19.83 15A 4/10 12.33 13.83 19.83 15A

H20 1800 460 2.5 4.0 4.0 0.14 8.14 9.14 13.14 15A 3/16 8.14 9.14 13.14 15A

H25 2250 208 2.7 8.6 8.6 0.33 17.53 19.68 28.28 25A 4/10 17.53 19.68 28.28 25A

H25 2250 460 3.7 5.8 5.8 0.14 11.74 13.19 18.99 15A 3/16 11.74 13.19 18.99 15A

H30 3000 208 2.7 8.6 8.6 0.33 17.53 19.68 28.28 25A 4/10 18.33 20.58 29.58 25A

H30 3000 460 3.7 5.8 5.8 0.14 11.74 13.19 18.99 15A 3/16 10.94 12.29 17.69 15A

Page 16: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

16

Pieces:2021-02-11

Scale:

Drawn by:Approved by:Date:

Material:Weight:

Name:

Drawing number:

PM

FANMOTOR

FANMOTOR

DATA

CAB

LEDA

TA C

ABLE

0-10V

0-10V

L1 L2 L3GND

t t

t t

tENCLOSURE

4/10A for 208V3/16A for 460V

208V or 460V

24V

1/L1

3/L2

5/L3

2/T1

4/T2

6/T3

I> I> I>

1/L1

3/L2

5/L3

2/T1

4/T2

6/T3

I> I> I>

O28-05-0003-23

NOVA WIRING LAYOUT 3-PHASE

Pieces:2021-02-11

Scale:

Drawn by:Approved by:Date:

Material:Weight:

Name:

Drawing number:

PM

L1 240V

O28-05-0003-24

NOVA WIRING LAYOUT SINGLE PHASE

FANMOTOR

FANMOTOR

DATA

CAB

LEDA

TA C

ABLE

0-10V

0-10V

GND

t t

t t

tENCLOSURE

3/10A

24V

N

FAN I/0 R/ABOTTOM

FAN I/0 S/ATOP

6

5

3

4

1

7

8

POSITION PCsTYPE1234

6 15

COLOUR PART No.

11134

22/6 COMMUNICATION MODBUS

78 1

122/6 COMMUNICATION MODBUS

18/4 (3 PHASE/GRD) POWER18/4 (3 PHASE/GRD) POWER

18/2 (0-10V, GRD) COMMNS.18/2 (0-10V, GRD) COMMNS.

Pieces:2020-04-02

Scale:

Drawn by:Approved by:Date:

Material:Weight:

Name:

Drawing number:

O28-05-0003-01A

PMELE. BOX WIRING LAYOUT - 208V3-PHASE

1

FAN R/A(BOTTOM)

FAN S/A(TOP)

BLACKBLACKGRAYGRAYBLACKBLACKBLACKBLACK

LC LC

24V

TRANSFORMER

T1T2T3 SWITCH BODY

T1 T2

MMP1 MMP2

GREE

N

GREE

N

WHI

TE

BLAC

K

RED

WHI

TE

BLAC

K

REDFOR T1, T2 CONNECTION

SEE 208V TRANSFORMERWIRING DIAGRAM T1

BLA

CK

T2 B

LACK

C

T1 T2 T3

222

1

1

SINGLE WIRE 10Ga, L=9"SINGLE WIRE 10Ga, L=14"

9

9

9 2FAN JUMPER 18GaBLACK

WIP0010WIP0010

WIP0017WIP0018WIP0022WIP0021WIP0019WIP0020WIP0023

FOR WIRES CONNECTIONSEE 208V TRANSFORMER

WIRING DIAGRAM

Pre-heattemperature sensoris placed in top orbottom core bracket.

17-WHITE16-BLACK2-BLUE1-RED

3-PH

ASE

208V

PO

WER

SO

URCE

24V

TRANSFORMER

T1

18/3 (HOT, NEUTRAL, GROUND)

WHI

TE 1

WHI

TE 2

GREE

N 1

GREE

N 2

BLAC

K 1

BLAC

K 2

M9F1

M9F2

FOR T1CONNECTION

SEE 240VTRANSFORMER

WIRINGDIAGRAM

POWER BOXPOSITION PCsTYPE

1

34 1

COLOUR A16

11211

22/6 COMMUNICATION MODBUS56789 1

111

22/6 COMMUNICATION MODBUS18/2 0-10V, GRD COMMUNICATION18/2 0-10V, GRD COMMUNICATION

2

4

5

1 8

9

18/3 (HOT, NEUTRAL, GROUND)

Pieces:2020-04-02

Scale:

Drawn by:Approved by:Date:

Material:Weight:

Name:

Drawing number:

O28-05-0003-02A

PMELE. BOX WIRING LAYOUT - 240V SINGLE

PHASE

6

7

T1

C

SWITCH BODY

SINGLE WIRE 10Ga L=9"2 BLACK SINGLE WIRE 10Ga L=11"

BLACK

BLACKBLACK

BLACKBLACK

33

BLACK SINGLE WIRE 10Ga L=8"

GREYGREY

10 2SINGLE WIRE 18Ga, 1.5-InchBLACK WIP0023

10

10

FOR WIRESCONNECTIONAND JUMPERSETTING, SEE

240VTRANSFORMER

WIRINGDIAGRAM

DRAWING No.B20

WIP0004WIP0003

WIP0015WIP0001WIP0002WIP0010WIP0010WIP0010

WIP0014WIP0003

WIP0015WIP0012WIP0011WIP0010WIP0010WIP0010

FAN I/0 R/ABOTTOM

FAN I/0 S/ATOP

FAN R/A(BOTTOM)

FAN S/A(TOP)

17-WHITE16-BLACK Pre-heattemperature sensoris placed in top orbottom core bracket.

2-BLUE1-RED

WIP00021WIP00021

5.2 Single Phase Electrical Hook-Up (2 Fans)

Attention: Single phase electric consists of single Line, Neutral and Ground OR two hot lines and Ground (Line 1, Line 2 and Ground) based on voltage availability.

Page 17: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

17

Pieces:2021-02-11

Scale:

Drawn by:Approved by:Date:

Material:Weight:

Name:

Drawing number:

PM

FANMOTOR

FANMOTOR

DATA

CAB

LEDA

TA C

ABLE

0-10V

0-10V

L1 L2 L3GND

t t

t t

tENCLOSURE

4/10A for 208V3/16A for 460V

208V or 460V

24V

1/L1

3/L2

5/L3

2/T1

4/T2

6/T3

I> I> I>

1/L1

3/L2

5/L3

2/T1

4/T2

6/T3

I> I> I>

O28-05-0003-23

NOVA WIRING LAYOUT 3-PHASE

Pieces:2021-02-11

Scale:

Drawn by:Approved by:Date:

Material:Weight:

Name:

Drawing number:

PM

L1 240V

O28-05-0003-24

NOVA WIRING LAYOUT SINGLE PHASE

FANMOTOR

FANMOTOR

DATA

CAB

LEDA

TA C

ABLE

0-10V

0-10V

GND

t t

t t

tENCLOSURE

3/10A

24V

N

FAN I/0 R/ABOTTOM

FAN I/0 S/ATOP

6

5

3

4

1

7

8

POSITION PCsTYPE1234

6 15

COLOUR PART No.

11134

22/6 COMMUNICATION MODBUS

78 1

122/6 COMMUNICATION MODBUS

18/4 (3 PHASE/GRD) POWER18/4 (3 PHASE/GRD) POWER

18/2 (0-10V, GRD) COMMNS.18/2 (0-10V, GRD) COMMNS.

Pieces:2020-04-02

Scale:

Drawn by:Approved by:Date:

Material:Weight:

Name:

Drawing number:

O28-05-0003-01A

PMELE. BOX WIRING LAYOUT - 208V3-PHASE

1

FAN R/A(BOTTOM)

FAN S/A(TOP)

BLACKBLACKGRAYGRAYBLACKBLACKBLACKBLACK

LC LC

24V

TRANSFORMER

T1T2T3 SWITCH BODY

T1 T2

MMP1 MMP2

GREE

N

GREE

N

WHI

TE

BLAC

K

RED

WHI

TE

BLAC

K

REDFOR T1, T2 CONNECTION

SEE 208V TRANSFORMERWIRING DIAGRAM T1

BLA

CK

T2 B

LACK

C

T1 T2 T3

222

1

1

SINGLE WIRE 10Ga, L=9"SINGLE WIRE 10Ga, L=14"

9

9

9 2FAN JUMPER 18GaBLACK

WIP0010WIP0010

WIP0017WIP0018WIP0022WIP0021WIP0019WIP0020WIP0023

FOR WIRES CONNECTIONSEE 208V TRANSFORMER

WIRING DIAGRAM

Pre-heattemperature sensoris placed in top orbottom core bracket.

17-WHITE16-BLACK2-BLUE1-RED

3-PH

ASE

208V

PO

WER

SO

URCE

24V

TRANSFORMER

T1

18/3 (HOT, NEUTRAL, GROUND)

WHI

TE 1

WHI

TE 2

GREE

N 1

GREE

N 2

BLAC

K 1

BLAC

K 2

M9F1

M9F2

FOR T1CONNECTION

SEE 240VTRANSFORMER

WIRINGDIAGRAM

POWER BOXPOSITION PCsTYPE

1

34 1

COLOUR A16

11211

22/6 COMMUNICATION MODBUS56789 1

111

22/6 COMMUNICATION MODBUS18/2 0-10V, GRD COMMUNICATION18/2 0-10V, GRD COMMUNICATION

2

4

5

1 8

9

18/3 (HOT, NEUTRAL, GROUND)

Pieces:2020-04-02

Scale:

Drawn by:Approved by:Date:

Material:Weight:

Name:

Drawing number:

O28-05-0003-02A

PMELE. BOX WIRING LAYOUT - 240V SINGLE

PHASE

6

7

T1

C

SWITCH BODY

SINGLE WIRE 10Ga L=9"2 BLACK SINGLE WIRE 10Ga L=11"

BLACK

BLACKBLACK

BLACKBLACK

33

BLACK SINGLE WIRE 10Ga L=8"

GREYGREY

10 2SINGLE WIRE 18Ga, 1.5-InchBLACK WIP0023

10

10

FOR WIRESCONNECTIONAND JUMPERSETTING, SEE

240VTRANSFORMER

WIRINGDIAGRAM

DRAWING No.B20

WIP0004WIP0003

WIP0015WIP0001WIP0002WIP0010WIP0010WIP0010

WIP0014WIP0003

WIP0015WIP0012WIP0011WIP0010WIP0010WIP0010

FAN I/0 R/ABOTTOM

FAN I/0 S/ATOP

FAN R/A(BOTTOM)

FAN S/A(TOP)

17-WHITE16-BLACK Pre-heattemperature sensoris placed in top orbottom core bracket.

2-BLUE1-RED

WIP00021WIP00021

5.3 Three-Phase Electrical Hook-Up (2 Fans)

Page 18: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

18

5.10 Fan Connection - Single Phase

WHI

TE

BLAC

K

BLAC

K

FAN BODY

Pieces:2020-04-02

Scale:

Drawn by:Approved by:Date:

Material:Weight:

Name:

Drawing number:O28-05-0003-10

PM240V FAN WIRING DIAGRAM

SINGLE PHASE

GREE

NW

HITE

BLAC

K

10V

GND

E1 D1 L1NPE

Page 19: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

19

5.11 Fan Connection - Three Phase

WHI

TE

BLAC

K WHI

TEBL

ACK

RED

GREEN*

BLAC

K

FAN BODY

Pieces:2020-04-02

Scale:

Drawn by:Approved by:Date:

Material:Weight:

Name:

Drawing number:O28-05-0003-09

PM208V, 460V FAN WIRING DIAGRAM

3-PHASE

24V

GND

E1 L3L2L1D1

* GROUND TERMINAL POSITION VARY. FOLLOW THE GROUND MARK

Page 20: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

20

Wiring Diagrams

Page 21: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

21

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-10-05 NTS 8" x 11.5" 1 of 1

NOVA/ 240V SINGLE PHASE/S1

028-05-0007-00DATE:

1.1

REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

1

OJ AIR2 MASTER

TERMINALS 20 TO 37

TERMINALS 1 TO 19

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

FAN IO 1

FAN IO 2

FANIO1

6

7

8

0-10V OUT

Alarm IN

A

B

C

RS485

RS485

RS485

FANIO2

9

10

1112

GND

GND

Temp. 1

GNDTemp. 2

6

7

8

0-10V OUT

Alarm IN

A

B

C

RS485

RS485

RS485

9

10

1112

GND

GND

Temp. 1

GNDTemp. 2

DIPS

DIPS

EXHAUST AIR TEMPERATURE

RETURN AIR TEMPERATURE

10VGNDE1D1

whtSUPPLY AIR FAN CONTROL

SUPPLY AIR TEMPERATURE

OUTDOOR AIR TEMPERATURE

10VGNDE1D1

whtRETURN AIR FAN CONTROL

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

SUPPLY AIR TEMPERATURE

(When optional Remote Duct Mount Temperature Sensor TTH-6202 and/or Humidity+Temp Sensor is Provided)

TTH

PRE-HEATING COIL TEMPERATURE

HTH

AIR HUMIDITY/TEMPERATURE

240 VAC/1/60HZ

L1 N/ L2 GND

grn

blue

M

R/A Fan

M9F1

M

S/A FanM9F3

grn

M9F2

M9F4

F1

S1

T1

N

L1 T1

GND

blk

F2

L2 T2

6.1 V

entum 2

40V, S

ingle Phase, S

1

Page 22: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

22

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-10-05 NTS 8" x 11.5" 1 of 1

NOVA/ 240V SINGLE PHASE/ S2

028-05-0008-00DATE:

1.1

REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

1

OJ AIR2 MASTER

TERMINALS 20 TO 37

TERMINALS 1 TO 19

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

FAN IO 1

FAN IO 2

FANIO1

6

7

8

0-10V OUT

Alarm IN

A

B

C

RS485

RS485

RS485

FANIO2

9

10

1112

GND

GND

Temp. 1

GNDTemp. 2

6

7

8

0-10V OUT

Alarm IN

A

B

C

RS485

RS485

RS485

9

10

1112

GND

GND

Temp. 1

GNDTemp. 2

DIPS

DIPS

EXHAUST AIR TEMPERATURE

RETURN AIR TEMPERATURE

10VGNDE1D1

wht

SUPPLY AIR FAN CONTROL

SUPPLY AIR TEMPERATURE

OUTDOOR AIR TEMPERATURE

10VGNDE1D1

wht

RETURN AIR FAN CONTROL

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

PRE-HEATING COIL TEMPERATURE

SUPPLY AIR TEMPERATURE

(When optional Remote Duct Mount Temperature Sensor TTH-6202 and/or Humidity+Temp Sensor is Provided)

TTH

HTH

AIR HUMIDITY/TEMPERATURE

Wiring Diagram

240 VAC/1/60HZ

L1 N/ L2 GND

grn

blue

M

R/A Fan

M9F1

M

S/A FanM9F3

grn

M9F2

M9F4

F1

S1

T1

N

L1 T1

GND

blk

F2

L2 T2

6.2

Ventum

240

V, Single P

hase, S2

Page 23: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

23

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-04-05 NTS 8" x 11.5" 1 of 1

NOVA/ THREE PHASE/ S1

028-05-0009-00DATE:

1.0REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

1

F1

208 OR 460 VAC/3 HZ

L1 L2

blk

M

R/A Fan

T1

24VAC

OJ AIR2 MASTER

N

L3

red

M

S/A Fanred

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

FAN IO 1

FAN IO 2

FANIO1

6

7

8

0-10V OUT

Alarm IN

A

B

C

RS485

RS485

RS485

FANIO2

9

10

1112

GND

GND

Temp. 1

GNDTemp. 2

6

7

8

0-10V OUT

Alarm IN

A

B

C

RS485

RS485

RS485

9

10

1112

GND

GND

Temp. 1

GNDTemp. 2

blue

DIPS

DIPS

EXHAUST AIR TEMPERATURE

RETURN AIR TEMPERATURE

10VGNDE1D1

10VGNDE1D1

whtSUPPLY AIR FAN CONTROL

SUPPLY AIR TEMPERATURE

OUTDOOR AIR TEMPERATURE

10VGNDE1D1

10VGNDE1D1

whtRETURN AIR FAN CONTROL

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GND

GND

MDMD

T1 T2 T3

F2blk

MMP1MMP1

MMP2MMP2

grn

To Ground

grn

To Ground

Factory Jumper (blk)

PRE-HEATING COIL TEMPERATURE

SUPPLY AIR TEMPERATURE

(When optional Remote Duct Mount Temperature Sensor TTH-6202 and/or Humidity+Temp Sensor is Provided)

TTHTTH

HTHHTH

AIR HUMIDITY/TEMPERATURE

6.3 V

entum, Three P

hase, S1

Page 24: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

24

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-04-05 NTS 8" x 11.5" 1 of 1

NOVA/ THREE PHASE/ S2

028-05-0010-00DATE:

1.0REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

1

F1

208 OR 460 VAC/3 HZ

L1 L2

blk

M

R/A Fan

T1

24VAC

OJ AIR2 MASTER

L3

red

M

S/A Fanred

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

FAN IO 1

FAN IO 2

FANIO1

6

7

8

0-10V OUT

Alarm IN

A

B

C

RS485

RS485

RS485

FANIO2

9

10

1112

GND

GND

Temp. 1

GNDTemp. 2

6

7

8

0-10V OUT

Alarm IN

A

B

C

RS485

RS485

RS485

9

10

1112

GND

GND

Temp. 1

GNDTemp. 2

blue

DIPS

DIPS

10VGNDE1D1

10VGNDE1D1

wht

10VGNDE1D1

10VGNDE1D1

wht

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GND

GND

MDMD

T1 T2 T3

F2blk

MMP1MMP1

MMP2MMP2

grn

To Ground

grn

To Ground

Factory Jumper (blk)

EXHAUST AIR TEMPERATURE

RETURN AIR TEMPERATURE

SUPPLY AIR FAN CONTROL

SUPPLY AIR TEMPERATURE

OUTDOOR AIR TEMPERATURE

RETURN AIR FAN CONTROL

PRE-HEATING COIL TEMPERATURE

SUPPLY AIR TEMPERATURE

(When optional Remote Duct Mount Temperature Sensor TTH-6202 and/or Humidity+Temp Sensor is Provided)

TTHTTH

HTHHTH

AIR HUMIDITY/TEMPERATURE

6.4 V

entum, Three P

hase, S2

Page 25: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

25

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

VENTUM/ FIELD WIRING/ DX COIL (w/EKE)

028-05-0019-00DATE:

1.0

REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

1

T1

24VAC

OJ AIR2 MASTER

N

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

OUTDOOR UNIT PC BOARD

W CONTROLLER

Refer to standard wiring diagrams for panel wiring details.

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

28

29Dout3

30

31Dout4

32

33Dout5

34

35Dout6

36

37Dout4

remocon

outdoor

ON

/OFF

errorop

eration0

-10 V

P1

P2

F1F2

T1T2

C1

C2

C3

C4

C5

C6

W C

ON

TRO

LLER

TERM

INA

L BLO

CK

C/H

SELECTO

R

AB

C

X1A

X1M

ON

OFF

DS1 (A1P)

A5P

AH

U O

UTD

OO

R

UN

IT

A

C

Set DS-1 Switch On and Power Reset

HEATING DEMAND

0-10 DX COIL CONTROL

FAN SWITCH ON/OFF

TTH

SUPPLY AIR TEMPERATURE

(When optional Remote Duct Mount Temperature Sensor TTH-6202 and/or Humidity+Temp HTH Sensor is Provided)HTH

AIR HUMIDITY/TEMPERATURE

6.5

Field Wiring, D

X C

oil, EKE

Page 26: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

26

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

VENTUM/ FIELD WIRING/ DX COIL/ ELEC. RE-HEAT (w/EKE)

028-05-0019-01DATE:

1.0

REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

1

T1

24VAC

OJ AIR2 MASTER

N

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

LegendFactory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

OUTDOOR UNIT PC BOARD

W CONTROLLER

Refer to standard wiring diagrams for panel wiring details.

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

28

29Dout3

30

31Dout4

32

33Dout5

34

35Dout6

36

37Dout4

remocon

outdoorO

N/O

FFerror

operatio

n0

-10 V

P1P2

F1F2

T1T2

C1

C2

C3

C4

C5

C6

W C

ON

TRO

LLER

TERM

INA

L BLO

CK

C/H

SELEC

TOR

AB

C

X1A

X1M

ON

OFF

DS1 (A1P)

A5P

AH

U O

UTD

OO

R

UN

IT

A

C

Set DS-1 Switch On and Power Reset

FAN SWITCH

0-10 DX COIL CONTROL

SC

R

CO

NTR

OL

D21-PSSR OR D35

-

+

0-10 V input

+

GND RE-HEAT CONTROL

FAN SWITCH ON/OFF

HEATING DEMAND

TTH

SUPPLY AIR TEMPERATURE

(When optional Remote Duct Mount Temperature Sensor TTH-6202 and/or Humidity+Temp HTH Sensor is Provided)HTH

AIR HUMIDITY/TEMPERATURE

6.6

Field Wiring, D

X C

oil, Electric Re-H

eat, EKE

Page 27: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

27

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

VENTUM/ FIELD WIRING/ELEC. PRE-HEAT/ DX COIL/ELEC. RE-HEAT (w/EKE)

028-05-0019-02DATE:

1.0

REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

1

T1

24VAC

OJ AIR2 MASTER

N

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

OUTDOOR UNIT PC BOARD

W CONTROLLER

Refer to standard wiring diagrams for panel wiring details.

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

28

29Dout3

30

31Dout4

32

33Dout5

34

35Dout6

36

37Dout4

remocon

outdoorO

N/O

FFerror

operatio

n0

-10 V

P1P2

F1F2

T1T2

C1

C2

C3

C4

C5

C6

W C

ON

TRO

LLER

TERM

INA

L BLO

CK

C/H

SELEC

TOR

AB

C

X1A

X1M

ON

OFF

DS1 (A1P)

A5P

AH

U O

UTD

OO

R

UN

IT

A

C

Set DS-1 Switch On and Power Reset

FAN SWITCH

0-10 DX COIL CONTROL

SC

R

CO

NTR

OL

D21-PSSR OR D35

-

+

0-10 V input

+

GND

SC

R

CO

NTR

OL

D21-PSSR OR D35

-

+

0-10 V input

RE-HEAT CONTROL

FAN SWITCH ON/OFF

GND PRE-HEAT CONTROL

HEATING DEMAND

TTH

SUPPLY AIR TEMPERATURE

(When optional Remote Duct Mount Temperature Sensor TTH-6202 and/or Humidity+Temp HTH Sensor is Provided)HTH

AIR HUMIDITY/TEMPERATURE

6.7 Field W

iring, Electric Pre-H

eat, DX

Coil, Electric R

e-Heat, EK

E

Page 28: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

28

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

VENTUM/ FIELD WIRING/ELEC. PRE-HEAT/ DX COIL (w/EKE)

028-05-0019-03DATE:

1.0

REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

1

T1

24VAC

OJ AIR2 MASTER

N

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

OUTDOOR UNIT PC BOARD

W CONTROLLER

Refer to standard wiring diagrams for panel wiring details.

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

28

29Dout3

30

31Dout4

32

33Dout5

34

35Dout6

36

37Dout4

remocon

outdoorO

N/O

FFerror

operatio

n0

-10 V

P1P2

F1F2

T1T2

C1

C2

C3

C4

C5

C6

W C

ON

TRO

LLER

TERM

INA

L BLO

CK

C/H

SELEC

TOR

AB

C

X1A

X1M

ON

OFF

DS1 (A1P)

A5P

AH

U O

UTD

OO

R

UN

IT

A

C

Set DS-1 Switch On and Power Reset

FAN SWITCH

0-10 DX COIL CONTROL

SC

R

CO

NTR

OL

D21-PSSR OR D35

-

+

0-10 V input

FAN SWITCH ON/OFF

GND PRE-HEAT CONTROL

HEATING DEMAND

TTH

SUPPLY AIR TEMPERATURE

(When optional Remote Duct Mount Temperature Sensor TTH-6202 and/or Humidity+Temp HTH Sensor is Provided)HTH

AIR HUMIDITY/TEMPERATURE

6.8

Field Wiring, Electric P

re-Heat, D

X C

oil, EKE

Page 29: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

29

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

VENTUM/ FIELD WIRING/ DAMPERS (ON/OFF)

028-05-0020-00DATE:

1.0

REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

1

T1

24VAC

OJ AIR2 MASTER

N

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

Refer to standard wiring diagrams for panel wiring details.

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

28

29Dout3

30

31Dout4

32

33Dout5

34

35Dout6

36

37Dout4

DAMPER ACTUATOR

12

13

14

15

Ain1Ain2

+24V

COMMON

+ HOT

Blk (1)

Wht (2)wht

OUTDOOR AIR DAMPERLF TYPE

COMMON

+ HOT

Blk (1)

Wht (2)

EXHAUST AIR DAMPERLF TYPE

wht

TTH

SUPPLY AIR TEMPERATURE

(When optional Remote Duct Mount Temperature Sensor TTH-6202 and/or Humidity+Temp HTH Sensor is Provided)HTH

AIR HUMIDITY/TEMPERATURE

6.9

Field Wiring, D

amper W

iring

Page 30: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

30

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

VENTUM/ FIELD WIRING /ELECTRIC RE-HEAT

028-05-0020-01DATE:

1.0

REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

1

T1

24VAC

OJ AIR2 MASTER

N

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

Refer to standard wiring diagrams for panel wiring details.

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

28

29Dout3

30

31Dout4

32

33Dout5

34

35Dout6

36

37Dout4

SC

R

CO

NTR

OL

D21-PSSR OR D35

-

+

0-10 V input+

GND RE-HEAT CONTROL

SSR HEATER

NOTE: Refer to standard wiring diagrams for default controls wiring.

TTH

SUPPLY AIR TEMPERATURE

(When optional Remote Duct Mount Temperature Sensor TTH-6202 and/or Humidity+Temp HTH Sensor is Provided)HTH

AIR HUMIDITY/TEMPERATURE

6.10

Field Wiring, Electric R

eheat Wiring

Page 31: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

31

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

VENTUM/ FIELD/ ELECTRIC PRE-HEAT/ ELECTRIC RE-HEAT

028-05-0020-02DATE:

1.0

REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

1

T1

24VAC

OJ AIR2 MASTER

N

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

Refer to standard wiring diagrams for panel wiring details.

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

28

29Dout3

30

31Dout4

32

33Dout5

34

35Dout6

36

37Dout4 S

CR

C

ON

TRO

L

D21-PSSR OR D35

-

+

0-10 V input+

GND

SC

R

CO

NTR

OL

D21-PSSR OR D35

-

+

0-10 V input

RE-HEAT CONTROL

GND PRE-HEAT CONTROL

SSR HEATER

NOTE: Refer to standard wiring diagrams for default controls wiring.

TTH

SUPPLY AIR TEMPERATURE

(When optional Remote Duct Mount Temperature Sensor TTH-6202 and/or Humidity+Temp HTH Sensor is Provided)HTH

AIR HUMIDITY/TEMPERATURE

6.11 Field W

iring, Electric Preheat, Electric R

eheat Wiring

Page 32: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

32

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

VENTUM/ FIELD WIRING/ELECTRIC PRE-HEAT

028-05-0020-03DATE:

1.0

REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

1

T1

24VAC

OJ AIR2 MASTER

N

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

Refer to standard wiring diagrams for panel wiring details.

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

28

29Dout3

30

31Dout4

32

33Dout5

34

35Dout6

36

37Dout4

SC

R

CO

NTR

OL

D21-PSSR OR D35

-

+

0-10 V input

GND PRE-HEAT CONTROL

SSR HEATER

NOTE: Refer to standard wiring diagrams for default controls wiring.

TTH

SUPPLY AIR TEMPERATURE

(When optional Remote Duct Mount Temperature Sensor TTH-6202 and/or Humidity+Temp HTH Sensor is Provided)HTH

AIR HUMIDITY/TEMPERATURE

6.12

Field Wiring, Electric P

reheat Wiring

Page 33: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

33

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

DATE:

REVISION:

CONTROLLER:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

028-05-0020-041.0

OJ

Controller DetailsWiring Diagram

T1

24VAC

N

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

0

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

TTH

GNDGND

SUPPLY AIR TEMPERATURE

Refer to standard wiring diagrams for panel wiring details.

COOLING VALVE ACTUATOR

VENTUM/ FIELD WIRING/HYDRONIC COOLING WATER COIL

NOTE: Refer to standard wiring diagrams for default controls wiring.

VALVE ACTUATOR

MG0G

YM

UZ

1

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

28

29Dout3

30

31Dout4

32

33Dout5

34

35Dout6

36

37Dout4

12

13

14

15

Ain1Ain2

+24V

POSITION SIGNAL 0-10 VDC/ 4-20 mA

(When optional Remote Duct Mount Temperature Sensor TTH-6202 and/or Humidity+Temp Sensor is Provided)

HTH

AIR HUMIDITY/TEMPERATURE

6.13 Field W

iring, Hydronic C

ooling Water C

oil

Page 34: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

34

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

DATE:

REVISION:

CONTROLLER:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

028-05-0020-051.0

OJ

Controller DetailsWiring Diagram

T1

24VAC

N

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

Refer to standard wiring diagrams for panel wiring details.

VENTUM/ FIELD WIRING/HUMIDITY CONTROL

NOTE: Refer to standard wiring diagrams for default controls wiring.

VALVE ACTUATOR

1

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

28

29Dout3

30

31Dout4

32

33Dout5

34

35Dout6

36

37Dout4

12

13

14

15

Ain1Ain2

+24V

HTH

AIR HUMIDITY/TEMPERATURE

DEWPOINT TEMPERATURE

6.14 Field W

iring, Hum

idity Control

Page 35: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

35

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

DATE:

REVISION:

CONTROLLER:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

028-05-0020-061.0

OJ

Controller DetailsWiring Diagram

T1

24VAC

N

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

0

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

Refer to standard wiring diagrams for panel wiring details.

COMBI-COIL VALVE ACTUATOR

VENTUM/ FIELD WIRING/COMBI-COIL

NOTE: Refer to standard wiring diagrams for default controls wiring.

VALVE ACTUATOR

MG0G

YM

UZ

1

OJ AIR2 MASTER

224VAC

3

4

5

Din1

Din2

A

B

C

RS485

RS485

RS485

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

28

29Dout3

30

31Dout4

32

33Dout5

34

35Dout6

36

37Dout4

12

13

14

15

Ain1Ain2

+24V

POSITION SIGNAL 0-10 VDC/ 4-20 mA

HEATING DEMAND SIGNAL

6.15

Field Wiring, C

ombi C

oil

Page 36: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

36

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

VENTUM/ FIELD WIRING/HYDRONIC PRE-HEAT

028-05-0020-07DATE:

1.1

REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

T1

24VAC

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

Refer to standard wiring diagrams for panel wiring details.

GND

NOTE: Refer to standard wiring diagrams for default controls wiring.

PRE-HEAT COIL RETURN WATER TEMP.

1

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

28

29Dout3

30

31Dout4

32

33Dout5

34

35Dout6

36

37Dout4

12

13

14

15

Ain1Ain2

+24V

PRE-HEAT CONTROLVALVE

MG0G

YM

UZ

VALVE CONTROL 0-10 VDC

+ 24 VDC

VALVE ACTUATOR

6.16

Field Wiring, H

ydronic Pre-H

eat

Page 37: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

37

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

DATE:

REVISION:

CONTROLLER:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

028-05-0020-081.0

OJ

Controller DetailsWiring Diagram

T1

24VAC

N

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

Refer to standard wiring diagrams for panel wiring details.

VENTUM/ FIELD WIRING/OCCUPANCY MODE

NOTE: PIR SENSOR (Occupancy Sensor) AUTOMATICALLY START OR INCREASE VENTILATION TO THE HIGH SPEED SETPOINT WHEN OCCUPANCY IS DETECTED.

OCCUPANCY MODE:

FAN SPEED MUST BE SET TO “WEEKLY PROGRAM” AND ALL PRESET ON/OFF TIME MUST BE DELETED. PIR SENSOR TO DETERMINE WHEN UNIT WILL START.

MINIMUM RUN TIME CAN BE SET UNDER INSTALLER=> OPERATING => EXTERNAL HIGH INPUT.

1

OJ AIR2 MASTER

224VAC

3

4

5

Din1

Din2

A

B

C

RS485

RS485

RS485

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

12

13

14

15

Ain1Ain2

+24V

Occupancy Sensor Signal

6

7

8

Din3

Din4

9

10

11

Din5

Din6 HIGH SPEED

6.17 Field W

iring, Occupancy M

ode

Page 38: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

38

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

VEMTUM/ FIELD WIRING / HYDRONIC RE-HEAT ONLY

028-05-0020-09DATE:

1.1

REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

T1

24VAC

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

Refer to standard wiring diagrams for panel wiring details.

GND

NOTE: Refer to standard wiring diagrams for default controls wiring.

RE-HEAT COIL RETURN WATER TEMP.

1

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

28

29Dout3

30

31Dout4

32

33Dout5

34

35Dout6

36

37Dout4

12

13

14

15

Ain1Ain2

+24V

RE-HEAT CONTROLVALVE

MG0G

YM

UZ

VALVE CONTROL 0-10 VDC

+ 24 VDC

VALVE ACTUATOR

6.18

Field Wiring, H

ydronic Re-H

eat

Page 39: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

39

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

DATE:

REVISION:

CONTROLLER:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

028-05-0020-101.0

OJ

Controller DetailsWiring Diagram

T1

24VAC

N

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

Refer to standard wiring diagrams for panel wiring details.

VENTUM/ FIELD WIRING/FIRE ALARM

FIRE ALARM SEQUENCE: FIRE ALARM SIGNAL IS NORMALLY CLOSED CONTACT. IN THE EVENT OF FIRE, CONTACT OPENS AND UNIT IS SHUT DOWN. AN “EXTERNAL FIRE” ALARM WILL BE DISPLAYED ON HMI.

1

OJ AIR2 MASTER

224VAC

3

4

5

Din1

Din2

A

B

C

RS485

RS485

RS485

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

12

13

14

15

Ain1Ain2

+24V

Fire Alarm Signal (NC)

6

7

8

Din3

Din4

9

10

11

Din5

Din6

EXTERNAL FIRE THERMOSTAT (STOP)

6.19

Field Wiring, Fire A

larm

Page 40: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

40

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-09-29 NTS 8" x 11.5" 1 of 2

VENTUM/ FIELD WIRING/ DX COIL/ HYDRONIC RE-HEAT (w/EKE)+ HEAT RECOVERY

CUSTOM210929DATE:

1.0

REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

1

T1

24VAC

OJ AIR2 MASTER

N

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

LegendFactory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

OUTDOOR UNIT PC BOARD

W CONTROLLER

Refer to standard wiring diagrams for panel wiring details.

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

28

29Dout3

30

31Dout4

32

33Dout5

34

35Dout6

36

37Dout4

remocon

outdoorO

N/O

FFerror

operatio

n0

-10 V

P1P2

F1F2

T1T2

C1

C2

C3

C4

C5

C6

W C

ON

TRO

LLER

TERM

INA

L BLO

CK

C/H

SELEC

TOR

AB

C

X1A

X1M

ON

OFF

DS1 (A1P)

A5P

AH

U O

UTD

OO

R

UN

IT

A

C

Set DS-1 Switch On and Power Reset

FAN SWITCH

0-10 DX COIL CONTROL

FAN SWITCH ON/OFF

HEATING DEMAND

TTH

SUPPLY AIR TEMPERATURE

(When optional Remote Duct Mount Temperature Sensor TTH-6202 and/or Humidity+Temp HTH Sensor is Provided)HTH

AIR HUMIDITY/TEMPERATURE

RE-HEAT COIL WATER TEMP.

20 22 23

12

13

14

15

Ain1Ain2

+24V

14

15BYPASS & RE-HEAT VALVE POWER (SEE PAGE 2)

TO PAGE 2

RE-HEAT CONTROL

BYPASS CONTROL

6.2

0 Field W

iring, DX

Coil, H

ydronic Coil, EK

E, Bypass

Page 41: INSTALLATION MANUAL VENTUM SERIES - Oxygen8

Installation Manual Ventum Series

41

DRAWING TITTLE:

DRAWING NUMBER:

SCALE: SIZE: SHEET:

DRAWN BY:

APPROVED:

IP

2021-09-30 NTS 8" x 11.5" 1 of 1

VENTUM/ FIELD WIRING/CO2 CONTROL+ EXTERNAL BYPASS

CUSTOM210930DATE:

1.1

REVISION:

CONTROLLER:

OJ

Controller DetailsWiring Diagram

1

T1

24VAC

OJ AIR2 MASTER

N

TERMINALS 20 TO 37

TERMINALS 1 TO 19

blk

OJ AIR2 MASTER

224VAC

16

17

18

19

Tin1

Tin2

A

B

C

RS485

RS485

RS485

Legend

Factory wired

Communication/ RJ12

Enclosed unit

Field wiring required

GNDGND

Refer to standard wiring diagrams for panel wiring details.

20

21

22

23

Aout1

Aout2

Aout3

24

25Dout1

26

27Dout2

28

29Dout3

30

31Dout4

32

33Dout5

34

35Dout6

36

37Dout4

DAMPER ACTUATOR

12

13

14

15

Ain1Ain2

+24V

VTH

CO2 SENSOR

VTH-6202 SENSOR TO BE INSTALLED IN RETURN AIR DUCT.

CO2

TO FANIO 1 EXT. PORT.(See Standard Wiring Diagram)

COMMON

+ HOT

Blk (1)

Red (2)

Y1 INPUT

Y2 INPUT

Wht (1)

Wht (2)

U OUTPUTWht (2)

0-10 VDCBYPASS CONTROL 0-10 VDC/ HEAT RECOVERY

COMMON

+ HOT

Blk (1)

Red (2) BYPASS DAMPER 1MTF TYPE - NO

Y1 INPUT

Y2 INPUT

Wht (1)

Wht (2)

U OUTPUTWht (2)

wht

0-10 VDC

BYPASS CONTROL 0-10 VDC/ HEAT RECOVERY

BYPASS DAMPER 2MTF TYPE - NC

6.2

1 Field Wiring, C

O2

Control, External B

ypass