Page 1: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

Major Components of Motor Drive Controllers

- for -

IEEE-IAS - by -

James S. Nasby

Columbia Engineering

Page 2: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 2

Items to be Covered Power Path Components Line Voltage Components Critical Path Items

Page 3: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 3

Model ECA A-T-L(D-O-L)

I/S

C/B

“M” Contactor

Emergency (Manual) Operator

Page 4: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 4

Model MCP Part

Winding

Current Transformers

Surge Arrestor Fuses

Control Unit

Digital Recorder

Balance Beam Dual Actuator

Motor Contactors "M1" & "M2"

Page 5: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 5

Common Power Path Components I/S: Isolating Switch (Means) C/B: Circuit Breaker (Disconnect Means) Contactor(s)

Running Starting

Current Transformers (Rigidly Mounted -vs- Tie Wrapped to Power Wiring)

Internal Wiring NEC® Table 310.16 -vs- 310.17 Single Hole Lugs -Often up to "F" Frame (217 Amps = 250A /

1.15) Two Hole Lugs "J" (400 amp) Frame and up 90°C or 75°C or 90°C Columns?? U.L. 60°C up to 100 amp & 75 °C @ FLA F.M. 90°C @ 1.25 x FLA E.g.: U.L. Greater < 100A and F.M. >100A

Note: Table 310-17 is for Conductors in Free Air, Not Bundled.

Page 6: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 6

Model ECP Part

Winding

Page 7: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 7

Internal Wiring and Contactor Currents Main = 1.00 x FLA Part Winding = 65% (M1) Reduced = 65% of FLA

Primary Reactor (Start) Primary Resistor (Start) Autotransformer (Start) Soft Start/Stop (Start)

Wye (Wye-Delta) = 57.7% of FLA (M1 & M2) Wye-Delta (Closed) Transition Wiring = 33% W- Closed Transition = FLA/(6x1.414)=11.8%* Wye (Autotransformer) = 25% (Includes Xfmr Saturation Current)

Variable Speed Wiring Bypass. R1 & R2 Contactors = 100% of FLA Link Reactor = Calculate (may exceed 100%)

* Proprietary Information

Page 8: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 8

Other Power Path Components

Transfer Switch 115% FLA Starting Reactors: Rating in FLA or Hp

Primary Reactors Neutral Reactors (Above 4800 Vac)

Note: Starting Reactors support numerous 10 Second starting attempts. Starting Resistors Sizing: Rating in Amps and

Watts Note that these have a limited duty cycle. W- Transition Resistors Sizing: (ditto) Autotransformer: Rated in Hp

Three Coil Two Coil

Soft Starter H.P. Rated? Continuous or Intermittent Duty Rated?

Page 9: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 9

Primary Reactor Transfer Swich Unit Combination Unit (285 FLA)

Page 10: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 10

Other Power Path Components

Variable VFD Fuses (Must be Selectively Coordinated with F.P. Breaker)

Medium Voltage Controllers Motor Fuses ("R" Rated) CPT Primary Fuses ("E" Rated)

Optional Terminal Blocks (UL Listed for Required WIC Rating)

Page 11: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 11

VFD Fuses

Page 12: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 12

Model ECHA"R" Rated

Motor Fuses

Page 13: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 13

Model ECHA Aux. CPT Primary "E" Rated Fuses

Page 14: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 14

Running ContactorsMust Be Sized for Either Motor Horsepower, or sized for the Greater of Running (FLA) Amps -or- Starting Amps

One Main (Run) Contactor: Motor Hp A-T-L & Variable Speed (Hp Rated) Primary Reactor, Resistor, Softstart Autotransformer

Part Winding: M1 & M2 M1 = 65% (Starting) M2 = 50% or 65%

Wye-Delta (W-): M1 & M2 M1 & M2 = 58% (1/3½)

Note: All of these are used for Manual Mechanical Starting.

Page 15: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 15

Starting ContactorsMust Be Sized for the Greater of Running Amps -or- Starting Amps

A-T-L & Variable Speed (Hp Rated) Part Winding (See Running) Resistor/Reactor/Soft Start = 65% W-

Wye = 33% FLA & LRC Tansition = FLA/(6x1.414)=11.8%*

A.T. Wye = 25% (Includes Xfmr Saturation Current)

* Proprietary Information

Page 16: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 16

Line Voltage Components All Power Path Components Control Power Transformers (CPT's)

Critical Path (Two or Three) Auxiliary Stepdown Transformers

• Cabinet Heaters, Aux. Power, Etc. Surge Arresters Sensors or Modules (Phase Rotation, etc.) Shunt Trip Circuitry & Coil** Note: Not all controllers protect against failures of any of

the three phases. Some provide no motor or controller or conductor protection if either L1 or L2 are lost, particularly with Manual Operator or welded contactor.

Page 17: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 17

Surge Arresters Most are NOT fused (coordination needed along

with higher voltage withstand ability). Many Still Connected on Service Terminals (I/S

Line Side Terminals) Special Option needed for:

Corner Grounded Delta Corner Grounded Wye Ungrounded Systems (Common in process plants to

permit first ground fault without shutting down the process - resulting in a Corner Ground System.)

Only one Mfr. Has UL/FM Option

Page 18: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 18

EC-LC Line Voltage Chassis,S/A Fuse Cover, Shop Current Test Cables

Page 19: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 19

Controllers Rated in Excess of 600 VAlso Called "High" Voltage and "Medium" Voltage*

Isolating Switch Interlocked w/ Contactor -or- Load Break Rated (per UL-347)

Vacuum Contactor Low Chop Motor Type -or- High Chop C/B Type (Suppression Needed)

Fuse Size Rules Door Interlocking Stress Cone Space

"High" Voltage = Old NFPA-20 Designation

"Medium" = Enclosed Switchgear above Low Voltage (600 Vac )

Page 20: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 20

Model ECHAIncoming Bus Bars (Tin Plated)

Shown w/ Shop Current Test Connections

Isolating Switch Stabs

Page 21: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 21

Model ECHAIncoming Bus Bars Cover in Place

Page 22: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 22

Model ECHASwing-outBay PartiallyClosed

Page 23: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 23

Model ECHA Motor Contactor -and- "R" Rated Silver/Sand Motor Fuses

Page 24: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 24

Model ECHA Interlocking

Page 25: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 25

Model ECHAEmergencyMechanicalManualOperator

Quick Make - Quick Break mechanism matches normal electrical operating speeds.

Page 26: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 26

Model ECHA Motor Terminals

Page 27: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 27

Model ECHAIsolatingSwitch

QMB Quick-Make Quick-Break Isolating Switch Mechanism

Includes Four Way Door, Contactor and Handle Interlocking

Page 28: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 28

Fully CoordinatedNote: Contactor is a "Low Chop" type vacuum contactor specifically designed for Motor Applications.

No special cable studies, capacitors or surge arresters required.

Note all Front Top or Bottom Access. Some Mfr's require Rear Access.

Page 29: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 29

Critical Path Items Anything Needed for Automatic Operation Controls

Processor Hardware & Programing Other Electronic Components Relays, Wiring, Connectors, etc.

Timers Lockouts (When Not Wanted) Sensors (False C/B Trip or False Single Phase

Start Protection Circuitry or Phase Reversal Circuitry

Anything that Can Prevent Starting

Page 30: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 30

Door Interlocks

Door Hooks

Interlock Bars

Page 31: IEEE-IAS 2012.02.18 Presentation - Major Components of Fire Pump Controllers

C.E. IEEE-IAS 31

Questions?