High Performance Unvented Attics with Fiberglass Insulation

Building Science Group, Sustainability Owens Corning

Page 2: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Acknowledgments

• Dr. William Miller – Oak Ridge National Laboratory

• Dr. Andre Desjarlais – Oak Ridge National Laboratory

• Mikael Salonvaara – Owens Corning

• Abe Cubano –Owens Corning

• Neil Freidberg – Owens Corning

Field Testing # 1

Field Testing # 2

Advanced Modeling

Mixed Climate

Hot-Cold-Humid

Hot-Dry Both Climates

2

Page 3: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Outline

• Moisture in above and below roof deck insulation

• Impact of vented and non-vented attics on moisture in attics

• Performance Results

• Discussion and Conclusions

3

Page 4: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Attic Types and Moisture Management

Sealed (Unvented) Attic Vented Attic

Ducts inside thermal boundary Ducts in unconditioned space

Attic is not living space and not intentionally conditioned

Attic is ventilated with outdoor air

4

Page 5: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Approach

• Focus on moisture performance

– Condensation, wetting and drying of roof deck

• Tools

– Simulations with hygrothermal models

– Field testing • Air tightness and temperature/humidity measurements

5

Page 6: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Typical Insulation in Unvented Attics

• Spray foam: Chemicals mixed, applied and cured on-site

– Open Cell • Low density (~0.5 pcf), Vapor permeable

– Closed Cell • High density (~2 pcf), Low vapor permeability

• Air permeable insulation

– Dense packed fibrous insulation

– Condensation control layer e.g. exterior foam may be needed

www.Insulatewithintegrity.com

6

Page 7: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Unvented Attics in Building Codes

International Residential Code (IRC) R806.5

• “Unvented attic and unvented enclosed rafter assemblies” – Requires air impermeable

insulation in direct contact with the roof sheathing

– If air permeable insulation is used

• The air permeable insulation has to be supplemented with a condensation control layer (air impermeable insulation) either on top of or under the roof sheathing.

Page 8: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Condensation Control - IRC

Table 3. Minimum R-values of Air-impermeable Insulation in Unvented

Attics. (IRC 2012 table R806.5)

Climate Zone Minimum rigid board or

air-impermeable insulation R-value

2B and 3B tile roof only None required

1, 2A, 2B, 3A, 3B, 3C R-5

4C R-10

4A, 4B R-15

5 R-20

6 R-25

7 R-30

8 R-35

8

Page 9: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

MEASURED AND SIMULATED TEMPERATURE & RELATIVE HUMIDITY

ORNL Test House – Model Calibration

Page 10: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Model Calibration

• Field Testing

– ORNL test house with Sealed Attic

• Structure

– Shingles

– Underlayment

– OSB

– 1” Closed Cell **

– ~5” Open Cell

– Spray-on fiber glass insulation 2”

10

Page 11: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Measured and Simulated Temperature

Temporary plastic

on top of roof

11

Page 12: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Measured and Simulated Relative Humidity

12

Page 13: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

ROOF DECK MOISTURE – MODELING OF DEMO HOUSE

Climate zones 3B

Page 14: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Roof Assembly

• The layers in the roof listed – from exterior to interior – are:

– Roof tile

– 1” Air gap

– Roofing underlayment

– ½” Roof sheathing (OSB) and

– Fiberglass insulation.

14

WUFI Model

ASHRAE 160

Page 15: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

OSB moisture content in Unvented and Vented attics

Climate zones 3B

15

More forgiveness in

Ventilated Attics

Fiberglass solution

Works well for

Unvented Attics

San Marcos, CA

Page 16: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Roof Deck Performance Results

• Unvented Attic

• Climate Zone and City

• Indoor moisture loads +4 g/m3

• Focus on Roof Deck Moisture (OSB)

1 Miami, FL

2 Houston, TX

3 Atlanta, GA

4 Baltimore, MD

16

Page 17: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Unvented Attic – Roof Deck Moisture

No water intrusion With water intrusion (1%)

Open Cell A2 (54 perm-in)

17

Page 18: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Unvented Attic – Roof Deck Moisture

No water intrusion With water intrusion (1%)

Open Cell A1 + Intumescent Coating (1-3 perms)

Note: Closed Cell foam is even more vapor tight than the above

18

Page 19: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Unvented Attic – Roof Deck Moisture

No water intrusion With water intrusion (1%)

Fiberglass Insulation (100 perm-in) + Air sealing

19

Page 20: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Unvented Attic – Roof Deck Moisture

No water intrusion With water intrusion (1%)

Fiberglass Insulation (100 perm-in) +

Air sealing +10 perm VR

20

Page 21: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Climate Makes a Difference

• Hot to Cold, Wet to Dry climates (CZs 1-3)

Asphalt

FG

21

Page 22: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Climate vs Moisture Load

San Francisco

CZ3C, sensitive

San Diego, high moisture

load causes no problems

Asphalt shingles

22

Page 23: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

FIELD HOME – SAN MARCOS CALIFORNIA

KB Homes

Page 24: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Sealed Attic

24

Page 25: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Instrumentation Plan

•Roof surface temperatures

•Roof sheathing temperatures, humidity

and moisture content

• Attic air temperatures north and south

side of attic

•I ndoor air temperature at thermostat

•Weather conditions

•Whole-house energy use

•HVAC run time.

Campbell Scientific Model CR23X

and or CR10X micro-loggers

Building Electrical Monitoring Points Wattnode transducer Model WNA-1P-240-P Whole House Power

ACL1 Event counter OPTI-Line Monitor with DC power

supplied by data logger HVAC On Time 25

Page 26: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Computer Simulations

• Validation of AtticSim: Measured vs Simulated Attic T

AtticSim (version 12.6) 26

Page 27: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Energy Performance

• Ceiling heat flux

27

Page 28: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Air Pressure across attic floor varies ±1 Pa

Data collected August 26, 2013

Wind affects attic-to-indoor pressure gradient

Minimal air leakage at soffits 28

Page 29: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Attic and Indoor T and RH

29

Page 30: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Moisture Loads

Indoor=Air Return

Attic air has about the same moisture content as indoor air Attic/Indoor is drier than outdoors most of the year

30

Page 31: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

T/RH Under Roof Deck

North South

31

Page 32: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

T/RH Under Roof Deck

West East

32

Page 33: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

T/RH Over Roof Deck

33

Page 34: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Roof Deck Air Leakage

• Air leakage between attic and outdoors must be understood

– Is the attic ‘sealed’?

• Dual blower door testing is needed to separate component leakage

34

Page 35: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Air Tightness of the Attic

• Testing to separate Attic-to-Outdoors and Attic-to-Indoors air leakage characteristics

• Methods

– Dual Blower Door: = Blower door flow

– Multi-scenario tests at multiple pressure levels

-50Pa -50Pa

-50Pa

? Pa

-50Pa 0Pa

0Pa

35

Page 36: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Attic-to-Outdoors Air Leakage

• Fiberglass attics

– First house (San Marcos) cfm50=515

– Second house (Lancaster) cfm50=369

• SPF attic

– Knoxville, TN: cfm50=336

• First house was ‘test and learn’

• Second house shows fiberglass attic can be air sealed as well as a sprayfoam attic

36

Page 37: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Draped vs Boxed Netting

Thermal Performance with the same average thickness of 7.5”

37

Page 38: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Thermal Performance

• Draped Netting

• U-value = 0.044

• Truss cords exposed to attic – thermal bridge and cold spot (condensation)

• Boxed Netting

• U-value = 0.033 25% better

• Permits future vapor permeance tuned netting for controlling truss cord moisture 38

Page 39: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

Box Netting- evolved Wolf/Walden/Salonvaara

Unvented Attic # 2 39

Page 40: High Performance Unvented Attics with Fiberglass Insulation · 4/4/2014 · High Performance Unvented Attics with ... (IRC 2012 table R806.5) Climate Zone Minimum rigid board or ...

40

Summary:

1. Unvented Attic design # 1 (Drapped systems) has demonstrated

outstanding performance for a full year of monitoring.

2. Fiberglass is a cost effective solution with excellent performance.

3. No risk was found for the hygrothermal performance of the unvented

attic

4. Fiberglass is non-flammable, non VOC and mold resistant

5. Box netting results in superior thermal & moisture performance

Conclusions