1 HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AND WATER COOLED AIR CONDITIONERS HORIZONTAL & VERTICAL MODELS 1/2 - 5 TONS GENERAL All Models - 5 tons ship as factory-charged packages. Horizontal (HWP) units are designed for suspended ceiling mounting. HWP models are shipped with ‘straight-through’ evaporator fan discharge as standard. Fan orientation is field convertible to side discharge. Vertical (VWP) units are designed for free- standing floor mounting. All units are completely factory wired and pre-piped. Water supply, water outlet, and condensate drain connections are via female pipe thread fittings. CABINET All cabinets are completely constructed of 18 Ga. corrosion resistant “Galvalume” coated steel. The HWP units are complete with integral hanger channels. The entire unit interior (both evaporator and condensing section) is insulated with 1/2” thick, 2 lb. density insulation. Service panels are equipped with lifting handles for ease of removal and handling. All units provide excellent service access to the reversing valve, thermal expansion valve, and compressor with the unit remaining in location. An integral duct collar is provided on the blower discharge opening. An optional discharge plenum is available for Vertical VWP models. REFRIGERANT CIRCUITS All models utilize hermetic rotary or reciprocating type compressors. Compressors are mounted on rubber isolators to minimize vibration transmission. Internal overload protection is provided. External high pressure and low pressure cutout switches are included in each compressor control circuit. Each refrigeration circuit includes an adjustable bi-flow thermal expansion valve (with external equalizer), bi-flow liquid line filter drier, and service gauge ports. The reversing valve is a pilot operated, sliding piston type with a replaceable magnetic solenoid coil. The refrigerant-to-air heat transfer coils are construct- ed of internally enhanced copper tubes mechanically bonded to enhanced aluminum plate fins. The evap- orator coil is employed in a draw-through configuration. Large evaporator coil face area minimizes potential water blow-off.
16
Embed
HIGH-EFFICIENCY WATER SOURCE HEAT PUMPSskymarkinternational.com/website_pdf/product4/prod1/Water Source Heat... · HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AND WATER COOLED AIR CONDITIONERS
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
1
HIGH-EFFICIENCYWATER SOURCE HEAT PUMPS
ANDWATER COOLED AIR CONDITIONERS
HORIZONTAL & VERTICAL MODELS1/2 - 5 TONS
GENERALAll Models 1⁄2 - 5 tons ship as factory-charged packages. Horizontal (HWP) units are designed for suspended ceiling mounting. HWP models are shipped with ‘straight-through’ evaporator fan discharge as standard. Fan orientation is field convertible to side discharge. Vertical (VWP) units are designed for free-standing floor mounting. All units are completely factory wired and pre-piped. Water supply, water outlet, and condensate drain connections are via female pipe thread fittings.
CABINETAll cabinets are completely constructed of 18 Ga. corrosion resistant “Galvalume” coated steel. The HWP units are complete with integral hanger channels. The entire unit interior (both evaporator and condensing section) is insulated with 1/2” thick, 2 lb. density insulation. Service panels are equipped with lifting handles for ease of removal and handling. All units provide excellent service access to the reversing valve, thermal expansion valve, and compressor with the unit
remaining in location. An integral duct collar is provided on the blower discharge opening. An optional discharge plenum is available for Vertical VWP models.
REFRIGERANT CIRCUITS
All models utilize hermetic rotary or reciprocating type compressors. Compressors are mounted on rubber isolators to minimize vibration transmission. Internal overload protection is provided. External high pressure and low pressure cutout switches are included in each compressor control circuit. Each refrigeration circuit includes an adjustable bi-flow thermal expansion valve (with external equalizer), bi-flow liquid line filter drier, and service gauge ports. The reversing valve is a pilot operated, sliding piston type with a replaceable magnetic solenoid coil.
The refrigerant-to-air heat transfer coils are construct-ed of internally enhanced copper tubes mechanically bonded to enhanced aluminum plate fins. The evap-orator coil is employed in a draw-through configuration. Large evaporator coil face area minimizes potential water blow-off.
Product TypeHWP = Horizontal Water Source Heat PumpVWP = Vertcial Water Source Heat Pump
Service Digit“Factory Assigned”
Production VariantA = Standard Heat PumpB = Heat Pump/Insulated Water CircuitC = Cooling Only Unit
Voltage12 = 208-230/1/6032 = 208-230/3/6034 = 460/3/6035 = 575/3/60Design Series
Model# HWP 036 A 32 A L - A
Product Nomenclature
ELECTRICAL/CONTROLSAll units are completely factory wired with all necessary operating controls. A 24 volt control circuit, with oversize transformer, is provided for field connection. Units are designed to operate with conventional thermostat control interface. The reversing valve solenoid coil shall be energized in cooling mode only. A manual reset is provided on each compressor control circuit in the event of high/low pressure cutout. A time delay relay for anti-short cycle protection is standard in all units. An optional condensate overflow switch is available, complete with an alarm output contact. An optional remote management package allows the unit to be controlled by an external source.
FILTERSAll models are shipped with 1 inch thick throw-away filters factory installed. Filters are accessible from either side of unit.
Unit ConfigurationL = Left Hand Return (Standard Horizontal)R = Right Hand Return (Standard Vertical)
The coaxial refrigerant-to-water heat exchangers feature a convoluted inner tube design for high heat transfer efficiency. Standard models feature a copper inner tube surrounded by a steel outer tube, and carry a 400 psig water side working pressure rating.
INDOOR FANS Forward curved, double inlet and double width direct-drive centrifugal blowers are used for evaporator air movement. Large diameter wheels are employed to provide required airflow performance at minimum noise levels. Blower wheels are fabricated of galvanized steel. Fan motors are PSC type, with minimum three speeds. The PSC motors feature permanently lubricated bearings and internal thermal overload protection.
NOTE:1) Performance calculated in accordance with ARI / ISO Standard 13256-1 for Water Loop Application2) Cooling capacities are rated at entering air conditions of 80.6 F db / 66.2 F wb, 86 F entering water temperature.3) Heating capacities are rated at entering air conditions of 68 F db / 59 F wb, 68 F entering water temperature.
COOLING HEATING
Min. Entering Water 50oF 40oF*
Max. Entering Water 110oF 80oF
Normal Entering Water 60-90oF 50-70oF
OPERATING LIMITS - Water Loop Application
* Heating operation below 55oF requires insulated water circuit.
4 5
COOLING
EWT GPM WPD EAT TC SC KW THR
(°F) (PSI) (db/wb) (MBH) (MBH) (MBH)
50
1.0 0.8
75/62 7.1 5.1 0.51 8.8
80/67 7.7 5.0 0.53 9.5
85/72 8.3 4.9 0.55 10.2
1.5 2.0
75/62 7.3 5.2 0.46 8.9
80/67 8.1 5.2 0.48 9.7
85/72 8.8 5.1 0.50 10.5
60
1.0 0.7
75/62 6.9 5.0 0.56 8.8
80/67 7.5 5.0 0.57 9.4
85/72 8.0 4.8 0.60 10.0
1.5 1.9
75/62 7.1 5.1 0.52 8.9
80/67 7.9 5.1 0.54 9.7
85/72 8.6 5.0 0.56 10.5
70
1.0 0.7
75/62 6.6 4.9 0.61 8.7
80/67 7.2 4.8 0.63 9.3
85/72 7.7 4.7 0.66 9.9
1.5 1.8
75/62 6.8 5.0 0.57 8.7
80/67 7.6 5.0 0.59 9.6
85/72 8.3 4.9 0.62 10.4
85
1.0 0.7
75/62 6.2 4.7 0.70 8.6
80/67 6.7 4.7 0.72 9.1
85/72 7.2 4.5 0.75 9.7
1.5 1.7
75/62 6.4 4.8 0.65 8.6
80/67 7.1 4.8 0.67 9.4
85/72 7.8 4.7 0.70 10.2
100
1.0 0.6
75/62 5.8 4.6 0.77 8.4
80/67 6.3 4.5 0.80 9.0
85/72 6.7 4.3 0.84 9.6
1.5 1.6
75/62 6.0 4.6 0.73 8.5
80/67 6.6 4.6 0.76 9.2
85/72 7.2 4.5 0.80 9.9
HWP/VWP 007 @ 200 CFM Nominal AirflowHEATING
EWT GPM EAT HC KW H Absrp.
(°F) (db) (MBH) (MBH)
50
1.0
60 7.2 0.59 5.2
70 7.2 0.63 5.0
80 7.1 0.67 4.8
1.5
60 7.5 0.60 5.4
70 7.4 0.64 5.2
80 7.3 0.68 5.0
60
1.0
60 8.1 0.62 5.9
70 8.0 0.66 5.7
80 7.9 0.70 5.5
1.5
60 8.4 0.63 6.2
70 8.3 0.67 6.0
80 8.2 0.71 5.8
70
1.0
60 9.2 0.65 7.0
70 9.1 0.69 6.7
80 9.0 0.73 6.5
1.5
60 9.5 0.66 7.3
70 9.4 0.70 7.0
80 9.3 0.74 6.7
80
1.0
60 10.1 0.68 7.8
70 10.0 0.72 7.5
80 9.8 0.76 7.2
1.5
60 10.5 0.69 8.1
70 10.3 0.73 7.8
80 10.2 0.77 7.5
All capacity data shown is NET - includes motor power/heat at design CFM and HI fan speed. Tabulated kW values do not include allowance for external pumping power.
NOTE:
TC = TOTAL COOLING CAPACITYSC = SENSIBLE COOLING CAPACITYTHR = TOTAL HEAT REJECTIONHC = TOTAL HEATING CAPACITYWPD = WATER PRESSURE DROP
AIRFLOW HEATING COOLING
% OFNominal CFM HC
InputPower
HeatAbsrp. TC SC
InputPower THR
80 160 0.986 1.058 0.969 0.966 0.893 0.992 0.971
90 180 0.993 1.029 0.985 0.983 0.947 0.996 0.986
100 200 1.000 1.000 1.000 1.000 1.000 1.000 1.000
110 220 1.007 0.977 1.014 1.011 1.049 1.004 1.011
115 230 1.010 0.965 1.021 1.017 1.074 1.006 1.016
AIR FLOW CORRECTION FACTORS
PERFORMANCE DATA
4 5
COOLING
EWT GPM WPD EAT TC SC KW THR
(°F) (PSI) (db/wb) (MBH) (MBH) (MBH)
50
1.35 1.4
75/62 9.1 7.0 0.55 11.0
80/67 10.0 6.9 0.56 11.9
85/72 10.8 6.7 0.57 12.7
2.25 3.5
75/62 9.2 7.0 0.53 11.0
80/67 10.2 7.0 0.54 12.0
85/72 11.1 6.8 0.56 13.0
60
1.35 1.4
75/62 8.8 6.8 0.61 10.9
80/67 9.7 6.8 0.62 11.8
85/72 10.5 6.6 0.64 12.7
2.25 3.5
75/62 8.9 6.9 0.58 10.9
80/67 9.9 6.8 0.59 11.9
85/72 10.7 6.7 0.61 12.8
70
1.35 1.4
75/62 8.5 6.7 0.66 10.7
80/67 9.3 6.6 0.67 11.6
85/72 10.1 6.5 0.69 12.4
2.25 3.5
75/62 8.6 6.8 0.64 10.8
80/67 9.5 6.7 0.65 11.7
85/72 10.4 6.6 0.66 12.6
85
1.35 1.4
75/62 8.0 6.5 0.74 10.5
80/67 8.8 6.4 0.75 11.3
85/72 9.6 6.3 0.78 12.3
2.25 3.5
75/62 8.1 6.5 0.73 10.6
80/67 9.0 6.5 0.74 11.5
85/72 9.8 6.4 0.77 12.4
100
1.35 1.4
75/62 7.5 6.3 0.82 10.3
80/67 8.3 6.2 0.84 11.2
85/72 9.0 6.1 0.87 12.0
2.25 3.5
75/62 7.6 6.3 0.81 10.4
80/67 8.4 6.3 0.83 11.2
85/72 9.1 6.2 0.86 12.0
HWP/VWP 009 @ 300 CFM Nominal AirflowHEATING
EWT GPM EAT HC KW H Absrp.
(°F) (db) (MBH) (MBH)
50
1.35
60 8.2 0.62 6.0
70 8.1 0.66 5.8
80 8.0 0.70 5.6
2.25
60 8.6 0.64 6.5
70 8.5 0.68 6.2
80 8.4 0.72 6.0
60
1.35
60 8.8 0.65 6.6
70 8.7 0.69 6.3
80 8.6 0.73 6.1
2.25
60 9.7 0.68 7.4
70 9.6 0.72 7.1
80 9.4 0.76 6.8
70
1.35
60 10.6 0.71 8.1
70 10.4 0.76 7.8
80 10.3 0.81 7.5
2.25
60 11.3 0.74 8.7
70 11.1 0.79 8.4
80 11.0 0.84 8.1
80
1.35
60 11.8 0.76 9.2
70 11.6 0.81 8.8
80 11.4 0.86 8.5
2.25
60 12.3 0.78 9.7
70 12.1 0.83 9.3
80 12.0 0.88 9.0
AIRFLOW HEATING COOLING
% OFNominal CFM HC
InputPower
HeatAbsrp. TC SC
InputPower THR
80 240 0.986 1.058 0.969 0.966 0.893 0.992 0.971
90 270 0.993 1.029 0.985 0.983 0.947 0.996 0.986
100 300 1.000 1.000 1.000 1.000 1.000 1.000 1.000
110 330 1.007 0.977 1.014 1.011 1.049 1.004 1.011
115 345 1.010 0.965 1.021 1.017 1.074 1.006 1.016
PERFORMANCE DATA
All capacity data shown is NET - includes motor power/heat at design CFM and HI fan speed. Tabulated kW values do not include allowance for external pumping power.
NOTE:
TC = TOTAL COOLING CAPACITYSC = SENSIBLE COOLING CAPACITYTHR = TOTAL HEAT REJECTIONHC = TOTAL HEATING CAPACITYWPD = WATER PRESSURE DROP
AIR FLOW CORRECTION FACTORS
6 7
COOLING
EWT GPM WPD EAT TC SC KW THR
(°F) (PSI) (db/wb) (MBH) (MBH) (MBH)
50
1.8 2.1
75/62 13.2 10.0 0.80 15.9
80/67 14.4 9.9 0.83 17.2
85/72 15.4 9.6 0.89 18.4
3.0 5.3
75/62 13.4 10.1 0.76 15.9
80/67 14.7 10.0 0.78 17.3
85/72 16.0 9.8 0.80 18.7
60
1.8 2.0
75/62 12.7 9.8 0.88 15.7
80/67 13.8 9.7 0.90 16.8
85/72 14.9 9.4 0.96 18.1
3.0 5.1
75/62 13.0 9.9 0.85 15.9
80/67 13.9 9.8 0.88 16.9
85/72 15.5 9.6 0.92 18.6
70
1.8 1.9
75/62 12.3 9.6 0.96 15.5
80/67 13.4 9.5 1.00 16.8
85/72 14.4 9.3 1.04 17.9
3.0 4.8
75/62 12.5 9.7 0.91 15.6
80/67 13.7 9.6 0.95 16.9
85/72 14.9 9.4 0.98 18.2
85
1.8 1.8
75/62 11.5 9.3 1.08 15.1
80/67 12.6 9.2 1.11 16.3
85/72 13.6 9.0 1.16 17.5
3.0 4.6
75/62 11.8 9.4 1.03 15.3
80/67 13.0 9.3 1.06 16.6
85/72 14.1 9.2 1.11 17.8
100
1.8 1.7
75/62 10.8 9.0 1.20 14.8
80/67 11.8 8.9 1.25 16.0
85/72 12.7 8.7 1.31 17.1
3.0 4.4
75/62 11.1 9.1 1.16 15.0
80/67 12.1 9.0 1.21 16.2
85/72 13.2 8.8 1.26 17.5
HWP/VWP 012 @ 400 CFM Nominal AirflowHEATING
EWT GPM EAT HC KW H Absrp.
(°F) (db) (MBH) (MBH)
50
1.8
60 11.7 0.87 8.7
70 11.6 0.93 8.4
80 11.4 0.98 8.1
3.0
60 12.4 0.90 9.4
70 12.3 0.96 9.0
80 12.1 1.01 8.7
60
1.8
60 13.1 0.92 10.0
70 12.9 0.98 9.6
80 12.8 1.03 9.3
3.0
60 13.8 0.94 10.6
70 13.6 1.01 10.2
80 13.5 1.07 9.8
70
1.8
60 15.2 1.00 11.8
70 14.9 1.07 11.3
80 14.8 1.13 10.9
3.0
60 15.9 1.02 12.4
70 15.6 1.09 11.9
80 15.4 1.15 11.5
80
1.8
60 16.9 1.05 13.3
70 16.6 1.13 12.8
80 16.4 1.20 12.3
3.0
60 17.4 1.07 13.7
70 17.1 1.15 13.2
80 16.9 1.22 12.7
AIRFLOW HEATING COOLING
% OFNominal CFM HC
InputPower
HeatAbsrp. TC SC
InputPower THR
80 320 0.986 1.058 0.969 0.966 0.893 0.992 0.971
90 360 0.993 1.029 0.985 0.983 0.947 0.996 0.986
100 400 1.000 1.000 1.000 1.000 1.000 1.000 1.000
110 440 1.007 0.977 1.014 1.011 1.049 1.004 1.011
115 460 1.010 0.965 1.021 1.017 1.074 1.006 1.016
PERFORMANCE DATA
All capacity data shown is NET - includes motor power/heat at design CFM and HI fan speed. Tabulated kW values do not include allowance for external pumping power.
NOTE:
TC = TOTAL COOLING CAPACITYSC = SENSIBLE COOLING CAPACITYTHR = TOTAL HEAT REJECTIONHC = TOTAL HEATING CAPACITYWPD = WATER PRESSURE DROP
AIR FLOW CORRECTION FACTORS
6 7
COOLING
EWT GPM WPD EAT TC SC KW THR
(°F) (PSI) (db/wb) (MBH) (MBH) (MBH)
50
2.75 2.3
75/62 18.4 14.6 1.01 21.9
80/67 20.2 14.4 1.04 23.8
85/72 21.8 14.1 1.07 25.5
4.50 5.7
75/62 18.7 14.7 0.96 22.0
80/67 20.6 14.5 0.98 24.0
85/72 22.3 14.3 1.02 25.8
60
2.75 2.2
75/62 17.8 14.3 1.10 21.6
80/67 19.6 14.2 1.12 23.4
85/72 21.2 13.9 1.16 25.2
4.50 5.5
75/62 18.0 14.4 1.07 21.7
80/67 20.0 14.3 1.09 23.7
85/72 21.6 14.0 1.12 25.4
70
2.75 2.1
75/62 17.1 14.0 1.21 21.2
80/67 18.9 13.9 1.24 23.2
85/72 20.3 13.6 1.28 24.7
4.50 5.2
75/62 17.4 14.1 1.16 21.4
80/67 19.2 14.0 1.19 23.3
85/72 20.8 13.8 1.22 25.0
85
2.75 2.0
75/62 16.1 13.6 1.37 20.8
80/67 17.8 13.5 1.40 22.6
85/72 19.2 13.2 1.45 24.2
4.50 4.9
75/62 16.3 13.7 1.33 20.9
80/67 18.1 13.6 1.35 22.7
85/72 19.6 13.4 1.38 24.3
100
2.75 1.9
75/62 15.1 13.2 1.55 20.4
80/67 16.6 13.0 1.58 22.0
85/72 17.9 12.8 1.65 23.5
4.50 4.7
75/62 15.3 13.3 1.51 20.5
80/67 17.0 13.2 1.54 22.3
85/72 18.4 12.9 1.59 23.8
HWP/VWP 0018 @ 600 CFM Nominal AirflowHEATING
EWT GPM EAT HC KW H Absrp.
(°F) (db) (MBH) (MBH)
50
2.75
60 16.2 1.13 12.4
70 16.0 1.20 11.9
80 15.8 1.28 11.5
4.50
60 16.9 1.14 13.0
70 16.7 1.22 12.5
80 16.5 1.30 12.1
60
2.75
60 18.5 1.20 14.4
70 18.2 1.28 13.8
80 17.9 1.36 13.3
4.50
60 19.4 1.23 15.2
70 19.1 1.31 14.6
80 18.8 1.39 14.1
70
2.75
60 21.1 1.28 16.8
70 20.8 1.37 16.1
80 20.5 1.46 15.5
4.50
60 22.2 1.32 17.7
70 21.8 1.41 17.0
80 21.5 1.50 16.4
80
2.75
60 23.4 1.37 18.7
70 23.0 1.46 18.0
80 22.7 1.55 17.4
4.50
60 24.4 1.39 19.7
70 24.0 1.49 18.9
80 23.6 1.59 18.2
AIRFLOW HEATING COOLING
% OFNominal CFM HC
InputPower
HeatAbsrp. TC SC
InputPower THR
80 480 0.986 1.058 0.969 0.966 0.893 0.992 0.971
90 540 0.993 1.029 0.985 0.983 0.947 0.996 0.986
100 600 1.000 1.000 1.000 1.000 1.000 1.000 1.000
110 660 1.007 0.977 1.014 1.011 1.049 1.004 1.011
115 690 1.010 0.965 1.021 1.017 1.074 1.006 1.016
PERFORMANCE DATA
All capacity data shown is NET - includes motor power/heat at design CFM and HI fan speed. Tabulated kW values do not include allowance for external pumping power.
NOTE:
TC = TOTAL COOLING CAPACITYSC = SENSIBLE COOLING CAPACITYTHR = TOTAL HEAT REJECTIONHC = TOTAL HEATING CAPACITYWPD = WATER PRESSURE DROP
AIR FLOW CORRECTION FACTORS
8 9
COOLING
EWT GPM WPD EAT TC SC KW THR
(°F) (PSI) (db/wb) (MBH) (MBH) (MBH)
50
3.5 3.3
75/62 25.5 19.9 1.25 29.8
80/67 28.3 19.8 1.26 32.6
85/72 30.9 19.5 1.27 35.2
6.0 8.0
75/62 26.1 20.2 1.15 30.0
80/67 29.0 20.1 1.17 33.0
85/72 31.8 19.9 1.19 35.9
60
3.5 3.2
75/62 24.3 19.4 1.41 29.1
80/67 26.9 19.3 1.43 31.8
85/72 29.4 19.0 1.45 34.4
6.0 7.7
75/62 25.0 19.7 1.33 29.6
80/67 27.8 19.6 1.35 32.4
85/72 30.2 19.3 1.37 34.9
70
3.5 3.0
75/62 23.1 18.9 1.55 28.4
80/67 25.6 18.8 1.58 31.0
85/72 27.8 18.5 1.62 33.3
6.0 7.3
75/62 23.8 19.2 1.48 28.9
80/67 26.5 19.1 1.51 31.7
85/72 28.8 18.8 1.54 34.1
85
3.5 2.9
75/62 21.1 18.1 1.75 27.1
80/67 23.4 18.0 1.79 29.5
85/72 25.4 17.7 1.85 31.7
6.0 6.9
75/62 21.5 18.2 1.70 27.3
80/67 24.3 18.3 1.75 30.3
85/72 26.4 18.0 1.79 32.5
100
3.5 2.7
75/62 19.0 17.2 1.95 25.7
80/67 21.1 17.1 2.00 27.9
85/72 22.7 16.8 2.06 29.7
6.0 6.6
75/62 19.3 17.3 1.91 25.8
80/67 21.7 17.3 1.97 28.4
85/72 23.6 17.1 2.03 30.5
HWP/VWP 0024 @ 800 CFM Nominal AirflowHEATING
EWT GPM EAT HC KW H Absrp.
(°F) (db) (MBH) (MBH)
50
3.5
60 21.0 1.43 16.1
70 20.7 1.53 15.5
80 20.5 1.62 14.9
6.0
60 21.8 1.46 16.9
70 21.5 1.56 16.2
80 21.3 1.65 15.6
60
3.5
60 23.8 1.50 18.6
70 23.4 1.61 17.9
80 23.1 1.71 17.3
6.0
60 25.1 1.54 19.9
70 24.7 1.65 19.1
80 24.4 1.75 18.4
70
3.5
60 27.8 1.61 22.3
70 27.3 1.73 21.4
80 26.9 1.84 20.6
6.0
60 29.5 1.66 23.8
70 29.0 1.78 22.9
80 28.5 1.89 22.1
80
3.5
60 30.7 1.69 25.0
70 30.2 1.81 24.0
80 29.7 1.92 23.1
6.0
60 34.0 1.61 28.5
70 33.3 1.73 27.4
80 32.7 1.84 26.4
AIRFLOW HEATING COOLING
% OFNominal CFM HC
InputPower
HeatAbsrp. TC SC
InputPower THR
80 640 0.986 1.058 0.969 0.966 0.893 0.992 0.971
90 720 0.993 1.029 0.985 0.983 0.947 0.996 0.986
100 800 1.000 1.000 1.000 1.000 1.000 1.000 1.000
110 880 1.007 0.977 1.014 1.011 1.049 1.004 1.011
115 920 1.010 0.965 1.021 1.017 1.074 1.006 1.016
PERFORMANCE DATA
All capacity data shown is NET - includes motor power/heat at design CFM and HI fan speed. Tabulated kW values do not include allowance for external pumping power.
NOTE:
TC = TOTAL COOLING CAPACITYSC = SENSIBLE COOLING CAPACITYTHR = TOTAL HEAT REJECTIONHC = TOTAL HEATING CAPACITYWPD = WATER PRESSURE DROP
All capacity data shown is NET - includes motor power/heat at design CFM and HI fan speed. Tabulated kW values do not include allowance for external pumping power.
NOTE:
TC = TOTAL COOLING CAPACITYSC = SENSIBLE COOLING CAPACITYTHR = TOTAL HEAT REJECTIONHC = TOTAL HEATING CAPACITYWPD = WATER PRESSURE DROP
All capacity data shown is NET - includes motor power/heat at design CFM and HI fan speed. Tabulated kW values do not include allowance for external pumping power.
NOTE:
TC = TOTAL COOLING CAPACITYSC = SENSIBLE COOLING CAPACITYTHR = TOTAL HEAT REJECTIONHC = TOTAL HEATING CAPACITYWPD = WATER PRESSURE DROP
All capacity data shown is NET - includes motor power/heat at design CFM and HI fan speed. Tabulated kW values do not include allowance for external pumping power.
NOTE:
TC = TOTAL COOLING CAPACITYSC = SENSIBLE COOLING CAPACITYTHR = TOTAL HEAT REJECTIONHC = TOTAL HEATING CAPACITYWPD = WATER PRESSURE DROP
All capacity data shown is NET - includes motor power/heat at design CFM and HI fan speed. Tabulated kW values do not include allowance for external pumping power.
NOTE:
TC = TOTAL COOLING CAPACITYSC = SENSIBLE COOLING CAPACITYTHR = TOTAL HEAT REJECTIONHC = TOTAL HEATING CAPACITYWPD = WATER PRESSURE DROP
AIR FLOW CORRECTION FACTORS
12 13
BLOWER PERFORMANCE / ELECTRICAL DATA
BLOWER PERFORMANCE External Static Pressure (in w.g.)
Units are shipped pre-wired for Medium speed.All airflow ratings are at lowest voltage rating of dual rating (ie. 208 volt)Airflow ratings include resistance of wet coil and clean air filters.
ELECTRICAL DATA MODEL SUPPLY COMPRESSOR BLOWER MIN. CCT. MAX FUSE /
Series VOLTAGE QTY RLA LRA HP FLA AMPACITY CCT. BKR. AMP
007 208-230/1/60 1 @ 2.8 17.7 0.10 0.9 4.35 15
009 208-230/1/60 1 @ 3.4 23.0 0.10 0.9 5.15 15
012 208-230/1/60 1 @ 4.8 26.3 0.17 1.4 7.40 15
018 208-230/1/60 1 @ 9.6 49.0 0.17 1.4 13.40 20
024 208-230/1/60 1 @ 10.4 49.0 0.25 1.5 14.50 20
030208-230/1/60 1 @ 12.4 61.0 0.33 2.6 18.10 30
208-230/3/60 1 @ 7.7 55.0 0.33 2.6 12.23 15
036
208-230/1/60 1 @ 15.3 82.0 0.50 3.2 22.33 35
208-230/3/60 1 @ 10.0 68.0 0.50 3.2 15.70 25
460/3/60 1 @ 4.8 34.0 0.50 2.5 8.50 15
048
208-230/1/60 1 @ 19.0 105.0 0.75 4.9 28.65 45
208-230/3/60 1 @ 14.0 91.0 0.75 4.9 22.40 35
460/3/60 1 @ 5.9 42.0 0.75 2.2 9.58 15
575/3/60 1 @ 4.8 34.0 0.75 1.8 7.80 15
060
208-230/1/60 1 @ 24.6 132.0 1.00 5.1 35.85 60
208-230/3/60 1 @ 16.0 97.0 1.00 5.1 25.10 40
460/3/60 1 @ 8.2 50.0 1.00 3.2 13.45 20
575/3/60 1 @ 5.0 44.0 1.00 2.6 8.85 15
14 15
HORIZONTAL HWP DIMENSIONAL DATA
14 15
VERTICAL VWP DIMENSIONAL DATA
16
City of New YorkDepartment of Buildings
MEA
Skymark maintains a continuous product improvement policy, therefore specifications are subject to change without notice.