1 Harmonic Mitigation Selection This paper is a review of the methods available to reduce line current harmonics seen with AC motor drives. There are several methods that can reduce the Ithd, and by doing so, also reduce the Vthd on the secondary terminals of the transformer feeding the drive. However, each one impacts the power distribution system in a different way, and each one impacts the drive operation in a different way. This paper will review the effects along with the advantages and the disadvantages of each method. Included in this paper are test results of several of the harmonic mitigation methods using a 100hp 1336F drive. 1. Introduction to Harmonics 2. The Basic Drive System 3. AC Line Reactor 4. DC Link Choke 5. Pseudo 12-Pulse 6. Multi-Pulse Converter 7. Passive Filter 8. Active Filter 9. Active Front-End 10. Other Comparisons 11. Comparison Checklist 12. Summary Rules-of-Thumb Rick Hoadley April 2005 Acknowledgments: Special thanks to Nick Guskov, Gary Woltersdorf and John Streicher for engineering, technical and marketing assistance.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
This paper is a review of the methods available to reduce line current harmonics seen with AC motordrives. There are several methods that can reduce the Ithd, and by doing so, also reduce the Vthd on
the secondary terminals of the transformer feeding the drive. However, each one impacts the power
distribution system in a different way, and each one impacts the drive operation in a different way.This paper will review the effects along with the advantages and the disadvantages of each method.Included in this paper are test results of several of the harmonic mitigation methods using a 100hp
1336F drive.
1. Introduction to Harmonics
2. The Basic Drive System
3. AC Line Reactor4. DC Link Choke
5. Pseudo 12-Pulse
6. Multi-Pulse Converter
7. Passive Filter8. Active Filter
9. Active Front-End
10. Other Comparisons11. Comparison Checklist
12. Summary Rules-of-Thumb
Rick Hoadley
April 2005
Acknowledgments: Special thanks to Nick Guskov, Gary Woltersdorf and John Streicher for
When faced with the task of reducing line current harmonics caused by AC drives, there are severalalternatives available. How does one pick the best solution? What criteria should be used to weigh
the alternatives? This paper will deal with these topics.
1. Introduction to Harmonics
ConverterAC to DC
DC BusFilter
InverterDC to AC
AC Drive
A C
L i n e
I n p u t
A C
M o t or O u t p u t
Why do drives create current harmonics?
We know that an AC drive creates line currentharmonics because the line current does not look
like a sine wave. Why? Because the converter
within the drive takes the 3 phase AC line voltagesand converts them into DC that feeds a filter and the
inverter section. The inverter section is what then
takes the DC and creates the variable voltage,
variable frequency output for the motor. See Fig 1. Fig 1. Sections of a 6-Pulse AC drive
During the process of 3-phase AC to DC conversion,
the line current can resemble a pair of distinctpulses. VMab.V = f...
La.I = f(t, b...
Cbus.V = f(...
VMac.V = f...
VMan.V [V]...
81.50m
81.50m
93.50m
93.50m
82.50m
82.50m
85.00m
85.00m
87.50m
87.50m
90.00m
90.00m
92.50m
92.50m
100.0 -100.0
00.0
0 0
00.0 200.0
00.0 400.0
00.0 600.0
Vab Vac
Van
Vbus
Ia
VMab.V = f...
Cbus.V = f(...
VMac.V = f...
VMan.V [V]...
81.50
La.I = f(t, b...
m
81.50m
93.50m
93.50m
82.50m
82.50m
85.00m
85.00m
87.50m
87.50m
90.00m
90.00m
92.50m
92.50m
100.0 -100.0
00.0
0 0
00.0 200.0
00.0 400.0
00.0 600.0
Vab Vac
Van
Vbus
Ia
Vab Vac
Van
Vbus
Ia
Why does the current look like that? Remember,
current can only flow whenever the instantaneousline-to-line voltage exceeds the DC bus capacitor
voltage. So for phase A, when can current flow?
Only when the peak voltage between phases A and
B exceed the cap voltage, or only when the peak voltage between phases A and C exceed the cap
voltage. No current flows in phase A due to thepeak voltage between phases B and C. This is
easily seen in Fig 2.
VMab.V = f...The currents in phases B and C are the same, simply
phase shifted with respect to each other.La.I = f(t, b...
Cbus.V = f(...
VMac.V = f...
VMan.V [V]...
181.5m
181.5m
193.5m
193.5m
182.5m
182.5m
185.0m
185.0m
187.5m
187.5m
190.0m
190.0m
192.5m
192.5m
100.0 -100.0
00.0
0 0
00.0 200.0
00.0 400.0
00.0 600.0
Vab Vac
Van
Vbus
Ia
VMab.V = f...
Cbus.V = f(...
VMac.V = f...
VMan.V [V]...
181.5
La.I = f(t, b...
m
181.5m
193.5m
193.5m
182.5m
182.5m
185.0m
185.0m
187.5m
187.5m
190.0m
190.0m
192.5m
192.5m
100.0 -100.0
00.0
0 0
00.0 200.0
00.0 400.0
00.0 600.0
Vab Vac
Van
Vbus
Ia
Fig 3. Current in phase A with an increase inline impedance
Fig 2. Current in phase A with very little lineimpedance
If impedance is added to the circuit, either byadding a DC link choke, or an AC line reactor, the
current does not change as rapidly, causing thewaveform to change shape as seen in Fig 3.
What causes voltage distortion?
Since the current looks like these pulses and do notlook like a sine wave, when we analyze the current
waveform we will see that it is composed of afundamental sine wave along with a combination of
several harmonics. These are the harmonic currents
that cause voltage distortions on the powerdistribution system.
Rfund.V =...
Rharm.V ...
Rtotal.V =...
0
0
40.00
40.00
10.00
10.00
20.00
20.00
30.00m
30.00m
150.0 -150.
50.0
0
100.0 -100.
50.0 -50.0
0.0 50.0
00.0 100.0
The voltage distortions appear whenever currentharmonics flow through the impedance within the
transformer feeding the drive, and through anyimpedance in the wiring between the transformerand the drive. As you may realize, the voltage
distortion is least at the transformer terminals, and
greatest at the drive terminals. It is this voltage
distortion that causes problems for other pieces of equipment fed by that transformer.
Fig 4. The red line current is made up of thegreen fundamental current plus the blueharmonic currents
The next two figures show how the voltagedistortion will change depending on the size of the
transformer feeding a drive. Shown in Fig 5 is the
voltage waveform at the terminals of a 1500kVAtransformer, and the current waveform of a 75hp
AC drive. There is very little distortion in the line-
to-line voltage. However, Fig 6 shows the
waveforms at the terminals of a 75kVA transformer.There is a significant amount of flat-topping in the
distorted voltage. This amounts to about 10% Vthd.Fig 5. The red line current of a 75hp drivecauses little distortion seen in the blue line-to-line voltage at the 1500kVA xfmr sec terminals
How much is too much?
The question we now ask is, “How much is toomuch?” This is where the recommendations found
in IEEE std 519-1992 come into play. Table 10.2
recommends that the voltage distortion be less than3% for hospitals and airports, less than 5% for all
other facilities, but may be as high as 10% if
converter loads are the only loads on a particulartransformer. This is shown in Fig 7. The location
for measuring the voltage distortion can be
anywhere in the facility where non-linear and linear
loads are connected together, typically at thesecondary terminals of distribution transformers. Fig 6. The red line current of a 75hp drive
causes significant distortion seen in the blueline-to-line voltage at the 75kVA xfmr sec
terminals
Why is there a concern for limiting the voltagedistortion? When motors are fed line voltages that
contain voltage distortion, there will be additional
heating in the motors and a loss of torque. It isdifficult to predict how much the motor needs to be
derated due to the level and content of the voltage
harmonics present. However, in NEMA MG1-1998,Revision 1, Part 30, Section 30.1.2.1, they define an
Harmonic Voltage Factor and a give a derating
chart. This was part of the consideration that IEEE
Application Maximum THD (%)
Special Applications - hospitals and airports 3.0%
General System 5.0%
Dedicated System - exclus ively converte r load 10.0%
Harmonic Voltage LimitsLow-Voltage Systems
Table 10.2
Application Maximum THD (%)
Special Applications - hospitals and airports 3.0%
General System 5.0%
Dedicated System - exclus ively converte r load 10.0%
Harmonic Voltage LimitsLow-Voltage Systems
Table 10.2
Fig 7. Table 10.2 from IEEE 519 showingrecommended Vthd limits for variousapplications
Even harmonics are limited to 25% of the odd harmonic limits above
Isc=maximum short circuit current at PCCIload=maximum demand load current (fundamental frequency component) at PCC
Maximum Harmonic Current Distortion in Percent of Iload
Table 10.3 puts limits on the current harmonics atthe place where multiple customers are connected tothe utility, usually at the metering point. See Fig 8.
This is the primary PCC (Point of Common
Coupling). Table 10.3 allows each customer
connected to the utility to draw some harmoniccurrent and thus create some voltage distortion
which everyone else needs to live with. However,
no one customer should draw so much harmoniccurrent so as to cause the voltage distortion at this
common connection point to exceed the
recommended limits at this point and causeproblems for the other customers.
Fig 8. Table 10.3 from IEEE 519 showingrecommended Ithd limits for various Isc/Iloadcategories
Within a customer’s plant, though, Table 10.3 does
not apply. Instead, only Table 10.2 applies –voltage distortion limits. The user should plan his
equipment type and placement and wiring to make
sure that the voltage distortion at any transformersecondary and at any point where linear and non-
linear loads are connected together are within thelimits in Table 10.2.
Fig 9. Diagram showing overview of whatvoltage distortion limits should be followed atvarious locations in multiple systems
If drives or other converters are the only load on atransformer, this table allows the voltage distortion
to be as high as 10%! For most users, the voltage
distortion should be less than 5%. For hospitals andairports (life-critical applications), the voltage
distortion should not exceed 3%. This is
diagrammed in Fig 9.
If, after a survey and harmonic estimation is made
of the plant, it is determined that there is a need to
reduce the harmonic current drawn by a drive or agroup of drives, several methods are available. We
will review these methods, compare their ability to
reduce the line current harmonics, list the pros andcons of each one, and discuss the effect each
method has on the operation of the drive and on the
power distribution system.
We will start with the characteristics of a basic,
The only drawback in the use of AC line reactors isthat it creates a drop in the DC bus voltage as full
load, full speed is approached. Fig 22 shows how
the DC bus voltage decreases as the load increases,comparing a basic drive to a drive with a 3% line
reactor, a drive with a 5% line reactor, and a drivewith a DC link choke. A 3% line reactor typicallycauses a 3% drop in bus voltage. A 5% line reactor
causes a 5% drop in bus voltage. The effect this has
on the drive system is that full power would not be
available from the motor because rated V/Hz couldnot be achieved from the drive. If full load, full
speed operation is not required, then this is not an
issue. However the user needs to be aware of thiseffect.
Vbus = 677Vdc
Ipk = 32A
Vbus = 587Vdc
Ipk = 120A
Vbus = 677Vdc
Ipk = 32A
Vbus = 587Vdc
Ipk = 120A
Fig 18. Operation during a power dip without anAC line reactor– green is the DC bus voltage,blue is the line-to-line voltage, red is the buscurrent
Vbus = 637Vdc
Ipk = 10A
Vbus = 545Vdc to 692Vdc
Ipk = 37A
Vbus = 637Vdc
Ipk = 10A
Vbus = 545Vdc to 692Vdc
Ipk = 37A
It is possible to place multiple drives on a singleline reactor. A rule of thumb for this is to select a
3% line reactor for 3 drives in parallel, or a 5% line
reactor for 5 drives in parallel. The hp rating of the
line reactor would be the total hp of the drivesconnected to it. Fig 23 diagrams this configuration.
Fig 19. Operation during a power dip with an ACline reactor – green is the DC bus voltage, blueis the line-to-line voltage, red is the bus current
Vbus = 677Vdc
Ipk = 32A
Vbus = 806Vdc
Ipk = 507A
Vbus = 677Vdc
Ipk = 32A
Vbus = 806Vdc
Ipk = 507A
% Vbus vs Load (Isc/Iload = 47)
94.00
95.00
96.00
97.00
98.00
99.00
100.00
101.00
102.00
0 10 20 30 40 50 60 70 80 90 100
unbuffered
buffered
3% line reactor
5% line reactor
1.35*Vac
% Vbus vs Load (Isc/Iload = 47)
94.00
95.00
96.00
97.00
98.00
99.00
100.00
101.00
102.00
0 10 20 30 40 50 60 70 80 90 100
unbuffered
buffered
3% line reactor
5% line reactor
1.35*Vac Fig 20. Operation during a ringing transientwithout an AC line reactor - green is the DC bus
Vbus = 637Vdc
Ipk = 10A
Vbus = 653Vdc
Ipk = 19A
Vbus = 637Vdc
Ipk = 10A
Vbus = 653Vdc
Ipk = 19A
Fig 22. Vbus vs Load – drop in DC bus voltageas the load is increased, showing the effect anAC line reactor has on this parameter
ge, red is thevoltage, blue is the line-to-line voltabus current
Transformer
xfmr% Z
Line Reactor
Drive
DC
AC
AC
DC
DC
AC
AC
DC
DC
AC
AC
DC
M
M
M
Fig 21. Operation during a ringing transient withan AC line reactor – green is the DC busvoltage, blue is the line-to-line voltage, red is thebus current
Fig 23. Diagram of multiple unbufferred driveson a single AC line reactor
equipped with a DC link choke as seen in Fig 24and 25. It usually is made up of two windings on a
common core, with one winding in each of the DCbus legs (one in the positive leg, one in the negativeleg) between the output of the converter bridge and
the bus caps.
Fig 24. Drive configuration with the addition ofDC link chokes (a buffered drive)
ConverterAC to DC
DC BusFilter
InverterDC to AC
AC Drive
A C
L i n e
I n p u t
A C
M o t or O u t p u t
Since this adds inductive impedance to the circuit,the rate of rise of the current into the caps is limited,
just like the effect seen by adding a line reactor to
the input to the converter bridge. There is adifference, though. During operation above about
25% load, the current in the link choke becomes
continuous (seen when the two pulses on the inputmerge into one pulse with two bumps, and the
current does not go to zero between the pairs of
pulses as compared to Fig 11). The line current will
typically look like what is shown in Fig 26. Fig 27shows the harmonic spectrum. Ithd is normally
between 30 to 40%. Since the impedance of a DC
link choke is usually selected to be about 4%, youcan see that this had the effect of further reducing
the 5th and 7th harmonics in the line current.
Fig 25. Details of drive configuration with DC
link chokes
La.I = f(t...
150.0
150.0
200.0
200.0
162.5
162.5
175.0
175.0
187.5
187.5
00.0 -400.
00.0
0 0
00.0 -200.
00.0 200.0
Fig 26. Typical line current for this drive
configurationWhen operating, the voltage drop due to the DC
link choke is due to its DC resistance and not to itsinductive impedance. The result is that the DC bus
voltage does not drop as much as it would when
compared to a line reactor. See Fig 22. This is themain advantage of using a link choke instead of line
reactors. The other advantage is that they are
usually slightly less expensive than AC line reactors
since they only have two windings. An advantageof line reactors over link chokes is that they provide
better current sharing when paralleling diode
bridges.0
10
20
30
40
50
60
70
80
90
100
0 6 12 1 8 24 30 36 42 4 8 54 60 66 72 78
Harmonic Number
% H a r m o n i c C u r r e n
What is the overall effect of a link choke on a drive
and the power grid? Fig 28 to 31 will give yousome overall operational parameters with which to
compare various harmonic mitigation solutions.
Fig 27. Harmonic spectrum showing themagnitudes of the individual harmonicscontained in the line current
Fig 28 shows how the Arms of the total line current
varies with load. It is fairly linear. The current at
harmonicsare not totally cancelled. Fig 33. This is
accomplished by placing half of the hp load on adelta-wye transformer, and the other half on a delta-delta transformer (or a simple line reactor could be
used in place of the delta-delta transformer, with the
same impedance as the delta-wye transformer).
Fig 33. Pseudo 12-Pulse configuration with halfof the hp drive load on a delta-wye xfmr, and theother half on a delta-delta xfmr or line reactor
La1.I = f...
150.0m
150.0m
200.0m
200.0m
162.5m
162.5m
175.0m
175.0m
187.5m
187.5m
-1000.0 -1000.0
1000.0
0 0
-500.0 -500.0
500.0 500.0
The cancellation of the lower order harmonics will
be affected by the amount of load on each set of
drives. Any pre-existing harmonics present on thevoltage feeding these transformers will also affect
the harmonic cancellation.
Fig 34 shows the secondary current from the main
transformer when the drive on the delta-delta
transformer is at 100% load, the drive on the delta-
wye transformer is at 100% load.
Fig 34. Line current with 100% load on delta-delta and 100% load on delta-wye
La1.I = f...
150.0m
150.0m
200.0m
200.0m
162.5m
162.5m
175.0m
175.0m
187.5m
187.5m
-1000.0 -1000.0
1000.0
0 0
-500.0 -500.0
500.0 500.0
Fig 35 shows the secondary current from the main
transformer when the drive on the delta-deltatransformer is at 100% load, the drive on the delta-
wye transformer is at 75% load.
Fig 36 shows the secondary current from the main
transformer when the drive on the delta-deltatransformer is at 100% load, the drive on the delta-
wye transformer is at 50% load.
Fig 35. Line current with 100% load on delta-delta and 75% load on delta-wye
La1.I = f...
150.0m
150.0m
200.0m
200.0m
162.5m
162.5m
175.0m
175.0m
187.5m
187.5m
-1000.0 -1000.0
1000.0
0 0
-500.0 -500.0
500.0 500.0
Fig 37 shows the secondary current from the main
transformer when the drive on the delta-delta
transformer is at 100% load, the drive on the delta-
wye transformer is at 25% load.
Fig 38 shows the secondary current from the main
transformer when the drive on the delta-deltatransformer is at 100% load, the drive on the delta-
wye transformer is at 0% load. This is basically the
same as the current we saw in Fig 26.
Fig 36. Line current with 100% load on delta-delta and 50% load on delta-wye
Fig 49 shows how Iharm (the harmonic current)varies with load. It also shows the % Ithd as a
dashed line. This is the ratio of the harmonic
current to the fundamental current that is containedin the AC line current.
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
0 25 50 75 100
6p
18p
Fig 50 is a zoomed in detail of % Ithd vs % Load
from Fig 49. As you see, Ithd increases as the loaddecreases due to the different rates of change of the
harmonic current and the fundamental current. Per
IEEE 519, though, the critical point is at full load,which is the minimum point on the % Ithd curve.
Fig 50. Detail of % Ithd vs % Load
0.00
1.00
2.00
3.00
4.005.00
6.00
7.00
8.00
9.00
10.00
0 25 50 75 100
6p
18p
Fig 51 is a zoomed in detail of Iharm vs % Loadfrom Fig 49. It is obvious that as the load decreases,
Iharm also decreases, meaning that the voltage
distortion will be decreasing, too.
Fig 52 is similar to Fig 32, showing how the
displacement power factor and distortion power
factor vary with load. The displacement powerfactor is again quite high throughout the load range.
But since there is so little harmonic current, the
distortion power factor is also very high throughoutthe load range.
Fig 51. Detail of Iharm vs % Load
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0 10 20 30 40 50 60 70 80 90 100
PF disp
PF dist
PF total
Overall, the 18-pulse converter has very little
impact on the power grid, and is very friendly to the
drive itself. Low harmonics, high power factor,good DC bus voltage at every load point. This is
almost an ideal type of converter.
A 12-pulse converter, on the other hand, would
cause the harmonics to increase 2 to 3 times. Since
there is very little cost difference between and 12-pulse transformer and diode bridge verses an 18-
pulse transformer and diode bridge, and since an
18-pulse converter is able to achieve 5% Ithd at the
input terminals of the drive system, there has been abig drop in demand for 12-pulse converters.
Fig 52. Power factor vs load - green isdisplacement PF, blue is distortion PF, pink istotal PF
NOTE: There are dozens of transformer andbridge configurations available to achieve 18-pulse operation. Each of these 18-pulseconverters have different characteristics withrespect to line current harmonics, power factor,efficiency, DC bus voltage, etc. The test resultsin this paper refer only to the 18-pulseconfiguration as defined in this section.
A 24-pulse or higher converter is able to furtherreduce the current harmonics, but only by a small
amount. The increased costs provide little payback.
However, due to the large currents involved, thiscould be beneficial for 1500hp drive systems and
factor current, and is most noticeable at no load.This is saying that when the drive is turned off, you
could have 30 to 50% of full load current flowing to
the passive filter.
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
0 25 50 75 100
6p
18p
P1
P2
P3
Fig 57 shows the total power factor associated withthe line current vs load. At full load, the powerfactor is very close to unity, but then approaches 0.2
to 0.4 leading power factor as the load decreases.
Again, this is due to the cap bank in the filter.Fig 60. Detail of % Ithd vs % Load
Fig 58 shows the change in the DC bus voltage as
the load is changed. 100% of nominal DC bus
voltage is again taken to be 1.35*Vac line-to-linevoltage. At no load, all of the filters provide some
boost in the DC bus voltage due to the cap bank. At
full load, there is a wide range of performance asthe DC bus voltage can be anywhere between 93%
and 102% of nominal. The design of the reactors in
the filter have the biggest impact on this parameter.This can cause the motor to operate at less than
rated V/Hz, causing overheating, if running above
93% of full speed.
0.00
1.00
2.00
3.00
4.005.00
6.00
7.00
8.00
9.00
10.00
0 25 50 75 100
6p
18p
P1
P2
P3
Fig 61. Detail of Iharm vs % Load
Fig 59 shows how Iharm and % Ithd vary with load.
They are all quite good. For more detail, we havethe next two figures.
Fig 50 is a zoomed in detail of % Ithd vs % Load
from Fig 59. At full load, they are all able to meet
IEEE 519 (which required 8% Ithd). As the load
decreased, the Ithd of the filters would rise veryslowly due to the capacitor bank current discussed
in Fig 56.
Fig 51 is a zoomed in detail of Iharm vs % Load
from Fig 49. This is the real test since this is what
creates the voltage distortion on the transformer. It
is obvious that as the load decreases, Iharm alsodecreases, meaning that the voltage distortion will
be decreasing, too. In the tests, the passive filters
were just a little worse than the 18-pulse drive.
Overall, the passive filters do a good job reducing
the harmonic currents. The biggest drawbacks arethe leading power factor due to the cap bank in the
tuned section of the filter and the drop in DC bus
An active filter is a device that is quite remarkable
in its operation. See Fig 62 for a drive systemutilizing one. It is made up of an inverter bridge
section, like the output inverter section of a drive asshown in Fig 63. However, it is connected such thata cap bank is tied to the DC bus terminals, and the
3-phase terminals are connected to the AC line
through small line reactors and a notch filter. It
then has current sensors that monitor the AC currentgoing to the non-linear load, such as the AC drive.
Fig 62. Drive configuration with the addition ofan active filter
InverterDC to AC
DCBus
Active Filter
A C
L i n e
I n p u t
NotchFilter
fThe key to the operation of an active filter is that itwill supply the harmonic currents required by the
non-linear load. Since these currents have an
average power of zero (zero average watts areconsumed by the non-linear load due to the
harmonic currents), then the harmonic current
supplied by the active filter is absorbed by the drive
during one part of the cycle, and then it is returnedto the filter during the next part of the cycle. The
current simply flows back and forth between the
filter and the drive. It acts like a reservoir forharmonic currents. Most active filters are also able
to supply fundamental reactive current to help withthe displacement power factor.
Fig 63. Details of an active filter showing IGBTinverter section
Ia= f( S,...
-25.00m
-25.00m
24.90m
24.90m
0
0
-20.00m
-20.00m
-10.00m
-10.00m
10.00m
10.00m
20.00m
20.00m
-150.0 -150.0
150.0
0 0
-100.0 -100.0
-50.0 -50.0
50.0 50.0
100.0 100.0
The addition of an active filter to a drive circuitmeans that the transformer does not have to supply
the harmonic current s to the drive. The result is a
clean line current, with just a little ripple due to thecarrier frequency switching of the active filter
inverter section. The current waveform and
spectrum are seen in Fig 64 and 65. The notch filterhelps a great deal with removing the carrier from
the line current. A typical carrier frequency used
for active filters is between 10 and 20kHz.
Fig 64. Typical line current for driveconfiguration with an active filter
0
10
20
30
40
50
60
70
80
90
100
0 6 12 1 8 24 30 36 42 4 8 54 60 66 72 78
Harmonic Number
% H a r m o n i c C u r r e n
The effect on the power distribution system is
minimal, similar to an Active Front-End as will be
discussed in Section 9. There is a slight amount of real power consumed due to losses in the filter, but
this is less than ~ 2% of the filter power. The line
current supplied by the transformer will basically be just the fundamental current. The other big
advantage is that one active filter can be associated
with a transformer secondary, supplying whatever
Fig 65. Harmonic spectrum of the line currentfor the drive configuration with an active filter
The following are some rules-of-thumb to use when mitigating line current harmonics with AC Drives:
1. Identify the required PCC and apply techniques most cost effective for that
location.
2. Add a line reactor (or DC link choke if possible) to all unbuffered 6-pulse
drives.
3. Consider use of an active filter on a multiple drive system or MCC lineup tocorrect for harmonic distortion.
4. For an even number of equally sized drives, consider a pseudo 12-pulsesolution by placing half of the load on a phase shifting delta-wye (delta-star)
transformer.
5. Design the system to isolate linear and non-linear loads and create two systems
with 5% and 10% voltage distortion limits.
6. For passive filters on generator power, select a filter with a dropout contactorterminal block for the filter capacitors. This will limit the leading power factor at
no-load and stand-by operation.
7. Take time to understand the benefits and drawbacks of each type of mitigation
solution to assure you meet the requirements of the application and that you canlive with any negative effects created by the chosen harmonic solution.
8. Consider an active front-end if the application requires regenerative operationand harmonic compliance.
9. Perform a preliminary harmonic analysis on your system and explore theeffects of using various harmonic mitigation methods.
10. Never use power factor correction capacitors at the input (or output) of a
drive, or in parallel with passive filters.
These rules should lead you to a successful AC drive application.