    WHO IS AN ENGINEER?

    According to USA President Herbert Hoover, who was an

    engineer before he became a politician, said:The great liability of the engineer compared to men of otherprofessionsis that his works are out in the open where allcan see them.

    His acts ..step by step are in hard substances.

    He cannot bury his mistakes in the grave like the DOCTORS.

    He cannot argue them into thin air..or blame the judge..likethe LAWYERS.

    He cannot, like the ARCHITECT, cover his figures with treesand vines.

    He cannot, like the politicians, screen his shortcomings byblaming his opponents.and hope the people will forget. The

    ENGINEER simply cannot deny he did it.If his works do not workhe is damned.

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    3/47

    A design engineers responsibility should includeassuring the structural safety of the design,details, checking shop drawing.

    Detailing is as important as design since proper

    detailing of engineering designs is an essential linkin the planning and engineering process as some ofthe most devasting collapses in history have beencaused by defective connections or DETAILING.There are many examples explained in the book"DESIGN AND CONSTRUCTION FAILURES by Dov

    Kaminetzky.Detailing is very important not only for the properexecution of the structures but for the safety of thestructures.

    Detailing is necessary not only for the steel

    structures but also for the RCC members as it is thetranslation of all the mathematical expressions andequations results.

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    4/47

    For the RCC members for most commonly used for buildings wecan divide the detailing for

    1. SLABS-WITH OR WITHOUT OPENINGS.(RECTANGULAR,CIRCULAR,NON-RECTANGULAR-PYRAMIDSLAB,TRIANGULAR ETC)

    -BALCONY SLAB,LOFT SLAB,CORNER SLAB etc

    2. BEAMS- WITH OR WITHOUT OPENIGS.(SHALLOW & DEEP BEAMS)

    3. COLUMNS.(RECTANGULAR,L-SHAPE,T-SHAPE,CIRCULAR,OCTAGONAL,CROSS SHAPE etc)

    4. FOUNDATIONS.

    Detailing for gravity loads is different from the lateral loadsspecially for the SEISMIC FORCES.

    Apart from the detailing for the above there is a differentdetailing required for the Rehabilitation and strengthening of

    damaged structures.

    We will now dwell on the DETAILING OF MEMBERS FOR THEGRAVITY AND SOME CODAL DETAILINGS AS PER IS CODE IS13920 AND IS 4326 AS REQUIRED FOR SEISMIC FORCES.

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    5/47

    DOS & DONOTS FOR DETAILING

    DOS-GENERAL

    1. Prepare drawings properly & accurately if possible label each bar

    and show its shape for clarity.

    12

    I dia@12c/c

    Cross section of retaining wall which collapsed immediately after placing of soil

    backfill because rather than 1-1/4 dia. were used. Error occurred because

    Correct rebar dia. Was covered by a dimension line.

    1- dia@12c/c

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    6/47

    2. Prepare bar-bending schedule , if necessary.

    3. Indicate proper cover-clear cover, nominal cover or

    effective cover to reinforcement.4. Decide detailed location of opening/hole and supplyadequate details for reinforcements around theopenings.

    5. Use commonly available size of bars and spirals.For a single structural member the number ofdifferent sizes of bars shall be kept minimum.

    6. The grade of the steel shall be clearly stated in thedrawing.

    7. Deformed bars need not have hooks at their

    ends.

    8. Show enlarged details at corners, intersections ofwalls, beams and column joint and at similarsituations.

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    7/47

    9. Congestion of bars should be avoided at points where

    members intersect and make certain that all rein. Can be

    properly placed.

    10. In the case of bundled bars, lapped splice of bundled barsshall be made by splicing one bar at a time; such

    individual splices within the bundle shall be staggered.

    11. Make sure that hooked and bent up bars can be placed

    and have adequate concrete protection.

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    8/47

    12. Indicate all expansion, construction and contraction joints

    on plans and provide details for such joints.

    13. The location of construction joints shall be at the point of

    minimum shear approximately at mid or near the mid points.

    It shall be formed vertically and not in a sloped manner.

    DOS BEAMS & SLABS:

    1. Where splices are provided in bars, they shall be , as far as

    possible, away from the sections of maximum stresses and

    shall be staggered.

    2. Were the depth of beams exceeds 750mm in case of beamswithout torsion and 450mm with torsion provide face rein.

    as per IS456-2000.

    3. Deflection in slabs/beams may be reduced by providing

    compression reinforcement.

    4. Only closed stirrups shall be used for transverse rein. Formembers subjected to torsion and for members likely to be

    subjected to reversal of stresses as in Seismic forces.

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    9/47

    5. To accommodate bottom bars, it is good practice to make secondarybeams shallower than main beams, at least by 50mm.

    Dos COLUMNS.

    1. A reinforced column shall have at least six bars of longitudinal

    reinforcement for using in transverse helical reinforcement.-forCIRCULAR sections.

    2. A min four bars one at each corner of the column in the case ofrectangular sections.

    3. Keep outer dimensions of column constant, as far as possible , forreuse of forms.

    4. Preferably avoid use of 2 grades of vertical bars in the same element.DONOTS-GENERAL:

    1. Reinforcement shall not extend across an expansion joint and thebreak between the sections shall be complete.

    2. Flexural reinforcement preferably shall not be terminated in a tensionzone.

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    10/47

    3. Bars larger than 36mm dia. Shall not be bundled.

    4. Lap splices shall be not be used for bars larger than

    36mm dia. Except where welded.

    5. Where dowels are provided, their diameter shall notexceed the diameter of the column bars by more than

    3mm.

    6. Where bent up bars are provided, their contribution

    towards shear resistance shall not be more than 50% of

    the total shear to be resisted. USE OF SINGEL BENT UPBARS(CRANKED) ARE NOT ALLOWED IN THE CASE

    OF EARTHQUAKE RESISTANCE STRUCTURES.

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    11/47

    DETAILING OF SLABS WITHOUT ANY CUT

    OR OPENINGS.

    The building plan DX-3 shows theslabs in different levels for the

    purpose of eliminating the inflow of

    rainwater into the room from the openterrace and also the sunken slab for

    toilet in first floor.

    The building plan DX-A3 is one inwhich the client asked the architect to

    provide opening all round.Refer the 3d

    elevation

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    12/47

    Different shapes of slabs used in the

    buildings. 6depression for OT &9 for sunken slabs.

    Portico slab in elevation

    19-6

    9-6suareopening

    5wide corridor all

    round

    Portico and other rooms

    roof slab in plan

    Portico slab in plan

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    13/47

    Minimum and max.reinforcement % in beams, slabs and

    columns as per codal provisions should be followed.

    SLABS:

    It is better to provide a max spacing of 200mm(8) for main

    bars and 250mm(10) in order to control the crack width and

    spacing.

    A min. of 0.24% shall be used for the roof slabs since it is

    subjected to higher temperature. Variations than the floor

    slabs. This is required to take care of temp. differences.

    It is advisable to not to use 6mm bars as main bars as this

    size available in the local market is of inferior not only with

    respect to size but also the quality since like TATA and SAILare not producing this size of bar.

    BEAMS:

    A min. of 0.2% is to be provided for the compression bars in

    order to take care of the deflection.

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    14/47

    The stirrups shall be min.size of 8mm

    in the case of lateral load resistance .

    The hooks shall be bent to 135degree .

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    15/47

    Ld/2Ld/2

    Ld

    crack

    INCORRECT

    CORRECT

    CLOSE

    STIRRUPS

    Ldt

    Ldt/2

    CANTILEVER BEAM

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    16/47

    NON PRISMATIC BEAM

    Ld/2 Ld/2Ld

    INCORRECT

    CORRECT

    CLOSE

    STIRRUPS

    crack

    Ldt/2

    Ldt

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    17/47

    GRID BEAMGRID BEAM

    INCORRECT

    1.5d1.5d1.5d

    Close rings

    Hanger bars

    Slope 1:10

    2#extra bars

    300300

    d

    CORRECT

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    18/47

    Details of Main & Secondary beams

    INCORRECT

    1.5d1.5d1.5d

    Close rings

    Hanger bars

    300300

    d

    CORRECT

    Secondary beam

    Main beam

    Secondary beam

    60degree

    Main beam

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    19/47

    d

    1/4OR

    1/5 SPAN

    1.5d

    CORRECT

    INCORRECT

    d/2+d/2Cot(t)

    tt

    Ld

    d/2

    d/2

    Ld

    LINE OF CRACK

    BEAM

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    20/47

    Continuous beam

    continuous beamSpan/4

    Span/4Span/4

    Span/4

    incorrect

    Span/4

    Span/4

    1.5d1.5d

    Span/4

    correct

    1.5d

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    21/47

    100%

    L1

    100% CRACKCRACK

    .08L2.08L1 L2

    SPAN/4 SPAN/4

    CONTINUOUS BEAM

    INCORRECT

    .08L1

    .08L1

    SPAN/4

    CRACK

    100%

    L1

    100%

    .15L2 L2

    L1/4 L2/4

    CORRECT

    0.1L1

    .15L1

    L1/4100%

    20%20%

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    22/47

    D

    D

    CRACK

    INCORRECT

    NONPRISMATIC

    SECTION OF BEAM

    D

    D

    DCORRECT

    D

    CLOSE RING

    CLOSE RING

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    23/47

    COLUMN

    INCORRECT

    CANTILEVER BEAM PROJECTING

    FROM COLUMN

    CORRECT

    NOT LESS THAN GREATER OF 0.5L OR Ld50mm

    0.25Ast

    NOT LESS

    THAN 0.5Ast

    COLUMN

    Ld

    Ld/3

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    24/47

    CRACK

    SLOPING BEAM

    CORRECT

    Ld

    Ld

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    25/47

    CRACKCRACK

    INCORRECT

    HAUNCH BEAMS

    CORRECTL/8 TO

    L/10 L/8 TO

    L/10

    L

    L

    Ld Ld

    Ld Ld

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    26/47

    STRESSES AT CORNERS

    C

    C-COMPRESSION

    T-TENSION

    t

    t

    C

    RESULTANT TENSILE STRESS FOR

    ACROSS CORNER(ONE PLANE)

    t

    c

    RESULTANT TENSILE STRESS FOR

    ACROSS CORNER(DIFFERENT PLANE)t

    c

    CRACK

    CRACK

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    27/47

    SHEAR AND TORSION REIN. IN

    BEAMS

    INCORRECT

    Min 0.2%bd to control deflection as

    well as for seismic requ.

    b

    D100 to

    200mm

    d

    D-n>500mm

    D/5

    Skin rein.10dia is

    required when depth

    exceeds 450mm(0.1%of web area distributed

    equally on two faces)

    Stirrups taken round outermost

    bars spacing

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    28/47

    CANTILEVER BEAM WITH

    POINT LOAD

    CORRECT

    INCORRECT

    2/3dd

    Shear rein.

    Extra ties

    Ld

    Ld

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    29/47

    opening

    CORRECT

    OPENING IN WEB OF BEAM

    crackcrack

    opening

    INCORRECT

    OPENING IN WEB OF BEAM

    Ld

    d/2 d/2

    Closed stps

    for d/2Closed stps

    for d/2

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    30/47

    BEAM COLUMN JUNCTION-EXTERIOR COLUMN

    CORRECT

    INCORRECT

    CLOSED STPS2max

    IN TENSION-Ld

    U TYPE BARS

    Ld

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    31/47

    CORRECT

    SPLICE DETAIL FOR COLUMN

    INCORRECT

    COVER

    CLOSE

    TIES @S/2

    S-SPACING

    SLOPE 1:6

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    32/47

    REDUCTION

    COLUMN BOTH

    SIDES

    INCORRECT

    CORRECT

    3NO.CLOSE TIES

    SPLICE

    CLOSE STPS SPACIN

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    33/47

    TERMINATION OF COLUMN BARS INSIDE BEAM

    INCORRECT

    CORRECT

    Ld

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    34/47

    BEAM COL. JUNCTION-EQ

    REGION

    EQREGION-BEAM-COL JN-EXTERIOR

    CORRECT

    BEAM COL. JUNCTION-EQ

    REGION

    INCORRECT

    END REGION

    END REGION

    COL.

    CORE*

    SPACING OF

    LATERAL

    TIES

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    35/47

    EQ REGION CONTINUOUS BEAM

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    36/47

    EQ-REGION-CONTINUOUS BEAM

    INCORRECT

    Ld

    A=L1/3

    CONTINUOUS BARS NOT LESS THAN

    AREA OF BARS AT COL.FACE

    A=L1/3 A=L1/3

    2d

    50mmmax

    Stirrup spacing=d/4 or

    100mm or 8dia which

    ever is the least

    2d2d 2dstp@maxd/2 stp@maxd/2

    CORRECT

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    37/47

    INCORRECT

    FOOTING-DETAILS(INDEPENDENT)

    CORRECT

    COVER TO

    STARTER

    STARTER

    BARS

    COLUMN

    BARS

    NATURAL

    G.L

    Ldt

    Lb3 SIDE COVER

    LdtCOVER50mm

    IF p.c.c below

    or 75mm

    Min.300

    TYPICAL REIN DETAILS OF

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    38/47

    TYPICAL REIN DETAILS OF

    HAMMER FOUNDATION BLOCKINCORRECT

    CORRECT

    Ld

    Ld

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    39/47

    SECTION OF TRENCH

    CRACK

    INCORRECTINCORRECT

    CORRECT

    LdLd

    Ld

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    40/47

    STAIRCASE-WITH WAIST SLAB

    INCORRECT

    CORRECT

    Ld(min)Extra bar

    Ld(min)

    Ld(min)

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    41/47

    Main bar

    Dist.

    Main bar

    Alternate 1

    SLABLESS STAIRCASE

    S SS S C S

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    42/47

    Main bar

    Alternate 2

    A=0.25L

    L=horizontal span

    SLABLESS STAIRCASE

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    43/47

    DEVELOPMENT LENGTH OF BARS

    SLNO BAR DIA. TENSIONmm COMPRESSION REMARKS

    1 8 376.0 301.0

    2 10 470.0 376.0

    3 12 564.0 451.0

    4 16 752.0 602.0

    5 20 940.0 752.0

    6 22 1034.0 827.0

    7 25 1175.0 940.0

    8 28 1316.0 1053.0

    9 32 1504.0 1203.0

    FOR A CONCRETE GRADE M20 &STEEL STRENGTH Fy=415

    APPROXIMATELY USE 50Xdia FOR TENSION

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    44/47

    CONCLUSION:

    Before concluding I will show some more details drawnin autocad exported in wwf format

    As there is no time to elaborately explaining ,the following topics are notcovered :

    1. Flat slabs, Folded plates, shell structures-cylindrical shells, silos,

    2. Staircases- helical staircase, central beam type, cantilever type etc.

    3. Different types of foundations-raft, pile foundation, strap foundation etc.

    4. Retaining wall structures,

    5. Liquid retaining structures.

    6. Deep beams.

    7. Shear wall, walls.

    Hope that I have enlighten some of the detailing technique for the mostcommonly encountered RCC members in buildings.

    In the above statements if my senior colleagues and ACCE members

    can find different method or any new detailing system it will be of immensehelp not only for me but to other young engineers who should learn in wrightways and not wrong lessons.

    REFERENCES

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    45/47

    REFERENCES:

    1. HANDBOOK ON CONCRETE REINFORCEMENT ANDDETAILING-SP:34(S&T)-1987.

    2. MANUAL OF ENGINEERING & PLACING DRAWINGSFOR REINFORCED CONCRETE STRUCTURES-

    (ACI 315-80

    3. MANUAL OF STANDARD PRACTICE CONCRETEREINFORCING STEEL INSTITUTE.

    4. TWARD BOARD MANUAL FOR RURAL WATER SUPPLYSCHEMES.

    5. DESIGN PRINCIPLES AND DETAILING OF CONCRETESTRUCTURES. By D.S.PRAKASH RAO.

    6. SIMPLIFIED DESIGN-RC BUILDINGS OF MODERATESIZE AND HEIGHT-BY PORTLAND CEMENT

    ASSOCIATION,USA.7. DESIGN AND CONSTRUCTION FAILURES BY DOV

    KAMINETZKY.

  • 8/8/2019 Guide for Reinforced Concretet Detailing

    46/47

    8. IS:2502-1963 CODE OF PRACTICE FOR BENDING AND

    FIXING OF BARS FOR CONCRETE REINFORCEMENT.

    9. IS:1893:2000.

    10. IS:4326.11. IS:456:2000

    12. REINFORCED HAND BOOK BY REYNOLD.