COVER SHEET A0 VICINITY MAP PHOTO - EXISTING CONDITIONS NORTH GOLDEN APARTMENTS RENOVATION & REMODEL 2312 N. GOLDEN AVE., SAN BERNARDINO, CA 92404 SCOPE OF WORK SUMMARY NOTES SHEET INDEX OWNER/CLIENT HACSB HOUSING AUTHORITY OF THE COUNTY OF SAN BERNARDINO 715 E. BRIER DRIVE SAN BERNARDINO, CA 92408 [email protected]+ [email protected]ARCHITECT BASIS ARCHITECTURE & CONSULTING INC 2130 4TH STREET, STE. B SAN RAFAEL, CA 94915 Architect: Charles Pick 415-457-6035 [email protected]MECHANICAL/PLUMBING/ELECTRICAL GHASSAN SHREIM AME DESIGN GROUP INC. 2062 BUSINESS CTR. DRIVE SUITE 250 IRVINE, CA 92612 [email protected]PROJECT DATA WASTE MANAGEMENT PROGRAM: CONTRACTOR TO HAVE IN PLACE AT THE BEGINNING OF THE PROJECT A WASTE MANAGEMENT PROGRAM WITH COMPLIANCE FORMS AND SHEETS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PREPARING AND SUBMITTING THE CONSTRUCTION WASTE MANAGEMENT WORKSHEETS NECESSARY TO DOCUMENTING COMPLIANCE WITH THE WASTE MANAGEMENT PLAN. RECYCLE AN/OR SALVAGE FOR REUSE A MINIMUM OF 50% OF THE NON HAZARDOUS CONSTRUCTION AND DEMOLITION DEBRIS IN ACCORDANCE WITH REGULATIONS OR MEET A MORE STRINGENT LOCAL CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT ORDINANCE. THE CONTRACTOR IS RESPONSIBLE WITH PROVIDING TO THE CITY OF SAN DIEGO THE ABOVE COMPLIANCE FORMS AND IDENTIFY THE RECYCLING & WASTE HAULING COMPANY. HAZARDOUS MATERIALS IN EXISTING CONSTRUCTION BASIS ARCHITECTURE & CONSULTING ASSUMES NO RESPONSIBILITY FOR THE MANAGEMENT OF HAZARDOUS MATERIALS THAT MAY BE ON SITE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSURING THAT PERSONNEL WITHIN THE WORK AREA ARE PROTECTED FROM EXPOSURE TO HAZARDOUS MATERIALS. IF MATERIALS ARE DISCOVERED THAT MAY BE HAZARDOUS, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE OWNER AND CEASE WORK UNTIL CONDITIONS CAN BE MAINTAINED IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS. AN ABATEMENT PLAN FOR ASBESTOS CONTAINING STOR. STORAGE SL SKYLIGHT SCHEDULE SCHED. SHELF AND POLE S&P T.B. TOWEL BAR T.O.S. TOP OF SLAB UNIFORM BUILDING CODE U.B.C. RAIN WATER LEADER RWL PRESSURE TREATED PT MIR. MIRROR MODIFIED (M) MAT. MATERIAL LAMINATE LAM. HGR. HANGER H.A.R. HOT AIR REGISTER FX. FIXED FOOTING FTG. FR.C. FRENCH CASEMENT F.O.F. FACE OF FINISH EXT. EXTERIOR CTR. CENTER PLYWD. PLAM. Q.T. PSI (R) R DETAIL DET. D.F. DOWN DIAGONAL DIMENSION DIAMETER DOOR DOWNSPOUT DRAWING DN. DIM. DIA. DIAG. DR. D.S. DWG. DOUGLAS FIR RM. RO. SAD SEC. REQ'D REV. SQ. SIM. S.S. S.M.D. SHT. S.S.D. SPEC. EACH ELECTRICAL EXISTING EQUAL EXPOSED EA. (E) ELEC. EQ. EXP. ELEV. E.P. FINISH FLOOR FLASHING FLASH F.FLR. ELECTRICAL PANEL BUILDING ELEVATION STL. T&G TYP. TGL. STRUCT. SUSP. U.O.N. V.I.F. VERT. V.G. GAUGE GLASS GALVANIZED GA. GL. GALV. FACE OF STUD F.O.S. STD. W/ W.P. WD. WC GYPSUM HARDWOOD HEADER GYP. GWB. HDWD. HDR. HEIGHT HORIZONTAL HT. HVAC. HORZ. HEATING, VENTILATING GYPSUM WALL BOARD GR. GRADE REINF. INT. LAV. INSUL. INST. A.C. ACOUSTICAL ADJUSTABLE ALUMINIUM BOARD ANODIZED ALUM. A.F.F. ADJ. ACOUS. BD. ANOD. AIR CONDITIONING ABOVE FINISH FLOOR MIN. MTD. MTL. MISC. M.B. M.C. MAX. NO. (N) O.C. N.T.S. N.I.C. BOTTOM BLOCKING CABINET CEMENT CERAMIC BM. BOT. BLKG. CER. CEM. CAB. CEILING CORNER GUARD CENTER LINE CLEARANCE COLUMN CONCRETE CLR. CLG. C.L. C.G. CMU. CONC. COL. CONCRETE MASONRY UNIT BEAM O.H. PL. CONTRACTOR CERAMIC TILE COUNTERSINK DOUBLE CTSK. C.T. CONTR. DBL. CONSTRUCTION CONST. O.D. BLDG. BUILDING POUNDS/SQ. INCH RISER REPLACE QUARRY TILE PLYWOOD PLASTIC LAMINATE ROOM SECTION SHEET SQUARE SIMILAR STEEL TYPICAL WATER CLOSET WITH WOOD WATERPROOF VERIFY IN FIELD VERTICAL VERTICAL GRAIN TEMPERED GLASS TONGUE AND GROOVE SUSPENDED STRUCTURAL STANDARD SEE MECH. DRAWINGS SEE STRUCT. DRAWINGS STAINLESS STEEL SPECIFICATION SUPPLY AIR DUCT ROUGH OPENING REVISED REQUIRED REINFORCING UNLESS OTHERWISE NOTED INTERIOR LAVATORY MAXIMUM METAL MINIMUM NUMBER NEW PLATE INSULATION INSTALLATION OVER HEAD OUTSIDE DIAMETER ON CENTER NOT TO SCALE NOT IN CONTRACT MISCELLANEOUS MEDICINE CABINET MACHINE BOLT MOUNTED NTE NOT TO EXCEED DISABLED ACCESSIBLE DA ABBREVIATIONS TYPICAL EXISTING BUILDING TYPICAL EXISTING BUILDING FROM STREET EXISTING BUILDINGS: (3) TWO-STORY TOWNHOUSE APARTMENT BUILDINGS WITH ONE-STORY LAUNDRY / STORAGE BUILDINGS ATTACHED. CONSTRUCTION TYPE: V-A (NOTE: AUTOMATIC FIRE PROJECTION SPRINKLERS TO BE ADDED) EXISTING UNITS: 21 EXISTING TOWNHOUSES (2BR/2 BA) = 1208 SQ. FT. EACH PROPOSED UNITS: CONVERT 19 TOWNHOUSES INTO 38 FLATS: 19 UPPER FLOOR (1BR/1 BA) = +- 708 SQ. FT. (TYPE B) 17 LOWER FLOOR (1BR/1 BA) = +- 500 SQ. FT. (TYPE A) 2 LOWER LEVEL (1BR/1BA) = +- 500 SQ. FT. DISABLED UNIT (TYPE C) - (2 OF 38, 5%) CONVERT LOWER LEVELS OF 2 ADJACENT TOWNHOMES TO COMMON AREA SPACE = +- 1,200 S.F. EXISTING PARKING: 21 COVERED STALLS TOTAL = 21 PARKING SPACES PROPOSED PARKING: 21 COVERED STALLS (EXISTING NO CHANGE) 1 OPEN DISABLED VAN ACCESSIBLE SPACE TO BE ADDED TOTAL = 23 PARKING SPACES SITE AREA: NO CHANGE - 1.08 ACRES EXISTING LOT COVERAGE: NO CHANGE - 13,200 (APPROX.) EXISTING BUILDING HEIGHT: NO CHANGE - 22 FEET (APPROX.) EXISTING BUILDING SETBACKS: NO CHANGE PROPOSED WORK INCLUDES: · CONVERSION OF EXISTING 19 TOWNHOUSES INTO 38 FLATS (TWO OF THE CONVERTED GROUND LEVEL FLAT UNITS TO BE DISABLED ACCESSIBLE). · FIRE SPRINKLER SYSTEM, ADD TO EACH BUILDING. · SITE IMPROVEMENTS: REMOVE AND REPLACE EXISTING ASPHALT PAVING. · SITE ACCESS IMPROVEMENTS: PROVIDE CONFORMING PATH OF TRAVEL FROM DISABLED PARKING AND FROM STREET, TO GROUND LEVEL UNITS AND COMMON AREAS. · LAUNDRY ROOM BUILDING 2 (2324 NORTH GOLDEN): EXISTING LAUNDRY ROOM TO BE REMODELED FOR ACCESSIBILITY WITH 3 SETS OF CLOTHES WASHERS AND DRYERS, · BUILDING EXTERIORS: REPLACE ROOFING, REPAIR ROOF DRAINAGE, STUCCO AND EXTERIOR WOOD DRY ROT REPAIRS. · 1 EXISTING TOWNHOUSE TO REMAIN UNCHANGED FOR MANAGER'S UNIT. · 1 EXISTING TOWNHOUSE TO BE CONVERTED FOR LOWER FLOOR LEASE AND EXISTING LAUNDRY/STORAGE BUILDING PROJECT LOCATION SHEET TITLE: PROJECT LOCATION: PROJECT NAME: Copyright 2017 by Charles Pick, Architect and Basis Architecture & Consulting Inc. GOLDEN APARTMENTS CONVERSION OF TOWNHOMES TO FLAT UNIT APARTMENTS 2312 N. GOLDEN AVE. SAN BERNARDINO CALIFORNIA 92404 APN: 0155-183-27-0000 DRAWING REVISION LOG PLAN CHECK SUBMITTAL 12/12/17 Δ1 PLAN CHECK RESPONSE 03/30/18 POST-MOUNTED LIGHT LED WALL PACK PAVING IMPROVEMENTS (N) CONCRETE ANTICIPATED, V.I.F. (N) GRADING (E) WALL TO REMAIN (E) WALL TO BE REMOVED (N) INTERIOR PARTITION (N) 1 HOUR RATED WALL LEGEND CHARLES PICK, ARCHITECT 6-2017 ACCESSIBILITY NOTE: SECTION 504 APPLIES - 5% OF UNITS TO BE DISABLED ACCESSIBLE PER CBC IIB.233. TWO (2) DISABLED ACCESSIBLE UNITS TO BE PROVIDED (CONVERSION TO FLATS). THE OTHER SIXTEEN (16) GROUND LEVEL FLATS TO BE CBC IIB COMPLIANT, ADAPTABLE 2312 N GOLDEN ARCHITECTURAL A0 A0.1 A0.2 A1.0 A1.1 A1.2 A1.3 A5.2 A5.1 COVER SHEET DIAGRAMMATIC GROUND FLOOR PLAN DIAGRAMMATIC SECOND FLOOR PLAN TYPICAL UNIT EXISTING PLANS - DIMENSIONING AND NOTES GROUND FLOOR ACCESSIBLE UNIT GROUND AND SECOND FLOOR NON-ACCESSIBLE UNITS GROUND AND SECOND FLOOR EXISTING CONDITIONS AND DEMOLITION PLANS ACCESSIBILITY DETAILS EXTERIOR DETAILS A5.3 ACCESSIBILITY DETAILS INTERIOR A1.4 GROUND AND SECOND REMODELED PLANS, FINISH SCHEDULES AND NOTES A3.0 INTERIOR ELEVATIONS A6.0 DOOR AND WINDOW SCHEDULES DETAIL AND, FINISH SCHEDULE AND NOTES DETAIL PANS, FINISH SCHEDULES AND NOTES COMMUNITY ROOM AND MANAGER'S UNIT A4.0 TYPICAL EXTERIOR ELEVATIONS A3.1 INTERIOR ELEVATIONS A0.3 ROOF PLAN A3.2 EXISTING AND REMODELED STAIR PLANS AND SECTIONS SHT-4 SHT-5 DRAINAGE PLAN FIRE PROTECTION SHT-1 SHT-2 SHT-3 COVER SHEET, GENERAL NOTES, INDEX MAP DEMOLITION PLAN GRADING PLAN CIVIL DRAWINGS FIRE PROTECTION (DEFERRED SUBMITTAL) EXCEPT BATHROOM (INFEASIBLE). ONE (1) NEW VAN ACCESSIBLE PARKING STALL TO BE PROVIDED PER CBC IIB.208.2 TWENTY-ONE (21) EXISTING PARKING SPACES, LESS THAN ONE (1) PER UNIT, ONE (1) ACCESSIBLE STALL REQUIRED FOR 1 -25 TOTAL STALLS. SHT-6 SHT-7 DETAILS DETAILS A1.5 DETAIL PLAN AND ELEVATION MAILBOXES A5.0 WALL DETAILS A4.1 GOLDEN AVENUE EXTERIOR ELEVATIONS FP-1 CODE REQUIREMENTS ALL NEW UNITS ARE FOR PERMANENT SUPPORTIVE HOUSING. · · ELECTRICAL TO BE UPGRADED IN EACH UNIT. WITH ONE SET MEETING ACCESSIBILITY REQUIREMENTS. CIVIL ENGINEERING TODD MARTINELL LUDWIG ENGINEERING 109 EAST THRIRS STREET SAN BERNARDINO, CA 92410 909-884-8217 [email protected]STRUCTURAL SCE-STERLING CONSULTING ENGINEERS 188 TECHNOLOGY DRIVE SUITE #A IRVINE, CA 92618 415-457-6035 Principle: Bashar Abdelfattah 949-387-8650 [email protected]COMMUNITY ROOM AND MANAGER'S UNIT SCHEMATIC PLANS FOR KITCHEN AND BATHROOM EXHAUST, CEILING SUSPENSION SPECIFICATION A1.6 BUILDINGS 1, 2 + 3 COMMON AREA PLANS GENERAL NOTES FOR GENERAL NOTES SEE SHEET A0.2 COMMON AREA. ARE PROVIDED. ZONING MAP DEFERRED SUBMITTALS THE FIRE PROTECTION CALCULATIONS AND DRAWINGS WILL BE A DEFERRED SUBMITTAL PREPARED BY THE FIRE PROTECTION CONTRACTOR. THE CODE REQUIREMENTS FOR THE FIRE PROTECTION SYSTEM ARE DESCRIBED ON SHEET FP-1 TEAM INDEX STRUCTURAL S-1.0 S-3.0 GROUND LEVEL SLAB LAYOUTS UPPER ROOF EXISTING FRAMING PLANS S-2.0 SECOND FLOOR FRAMING PLANS SGN-1 STRUCTURAL GENERAL NOTES 1 OPEN STALL TO BE ADDED MECHANICAL M0.0 MECHANICAL LEAD SHEET M0.1 MECHANICAL EQUIPMENT SCHEDULES AND DETAILS M1.1 MECHANICAL GROUND PLAN M1.2 MECHANICAL SECOND PLAN M1.3 MECHANICAL ROOF PLAN M2.1 MECHANICAL UNIT PLANS M2.2 MECHANICAL GROUND & SECOND FLOOR REMODELED PLANS - MANAGERS UNIT & COMMUNITY ROOM M3.1 TITLE 24 PLUMBING P0.0 PLUMBING LEAD SHEET P0.1 PLUMBING CALCULATIONS P1.1 PLUMBING GROUND FLOOR PLAN P1.2 PLUMBING SECOND FLOOR PLAN P2.1 PLUMBING GROUND FLOOR ACCESSIBLE UNIT PLANS P2.2 PLUMBING GROUND & SECOND FLOORS NON- ACCESSIBLE UNIT PLANS P2.3 PLUMBING GROUND FLOOR DEMOLITION & REMODELED PLANS - MANAGERS UNIT, COMMUNITY ROOM & BLDG 2 COMMON AREA ELECTRICAL E-1.0 GENERAL NOTES, LEGEND AND FIXTURE SCHEDULE E-1.1 ELECTRICAL SITE PLAN E-2.0 BUILDING EXTERIOR LIGHTING PLAN E-2.1 BUILDING EXTERIOR LIGHTING AND ROOF PLAN E-3.0 ELECTRICAL UNIT PLAN E-3.1 ELECTRICAL MANAGER UNIT PLAN E-3.2 ELECTRICAL RECREATION UNIT PLAN E-4.0 UTILITY AND LAUNDRY ELECTRICAL PLAN E-5.0 ONE LINE DIAGRAM E-5.1 ONE LINE DIAGRAM PROJECT IS PUBLIC HOUSING PER CBC DEFINITION. A CODE DATA R2 OCCUPANCY, PUBLIC HOUSING APPLICABLE CODES: 2016 CALIFORNIA BUILDING CODE 2016 CALIFORNIA PLUMBING CODE 2016 CALIFORNIA MECHANICAL CODE 2016 CALIFORNIA ELECTRICAL CODE 2016 ENERGY STANDARDS 2016 CALIFORNIA GREEN BUILDING STANDARDS CODE A0.4 CONDITIONAL USE PERMIT COPY A0.5 CONDITIONAL USE PERMIT COPY A0.6 CONDITIONAL USE PERMIT COPY SHT-8 SHT-9 CONDITIONS OF APPROVAL CONDITIONS OF APPROVAL SHT-10 SECTIONS 2 PLAN CHECK RESPONSE 5-3-2018 (NFPA 13R FIRE SPRINKLER TYPE REQUIRED) 3 PLAN CHECK RESPONSE 5-17-2018 · PROVIDE (N) CATV, EACH UNIT. · (N) MEMBRANE ROOF WITH (N) CUTTERS AND DOWNSPOUTS AT TWO BUILDINGS. MATERIALS IS TO BE PROVIDED BY THE OWNER. CONVERT UPPER LEVELS OF SAME 2 UNITS FOR MANAGER'S UNIT ABOVE = +- 1,200 S.F. A OWNER REVISIONS 6-21-2018
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
COVER SHEET
A0VICINITY MAPPHOTO - EXISTING CONDITIONSNORTH
GOLDEN APARTMENTSRENOVATION & REMODEL
2312 N. GOLDEN AVE., SAN BERNARDINO, CA 92404
SCOPE OF WORK SUMMARY
NOTES
SHEET INDEX
OWNER/CLIENTHACSBHOUSING AUTHORITY OF THE COUNTY OF SAN BERNARDINO715 E. BRIER DRIVESAN BERNARDINO, CA [email protected] + [email protected]
ARCHITECTBASIS ARCHITECTURE & CONSULTING INC2130 4TH STREET, STE. BSAN RAFAEL, CA 94915Architect: Charles [email protected]
MECHANICAL/PLUMBING/ELECTRICALGHASSAN SHREIMAME DESIGN GROUP INC.2062 BUSINESS CTR. DRIVESUITE 250IRVINE, CA [email protected]
PROJECT DATA
WASTE MANAGEMENT PROGRAM:
CONTRACTOR TO HAVE IN PLACE AT THE BEGINNING OF THE PROJECT A WASTE MANAGEMENTPROGRAM WITH COMPLIANCE FORMS AND SHEETS. THE CONTRACTOR SHALL BE RESPONSIBLE FORPREPARING AND SUBMITTING THE CONSTRUCTION WASTE MANAGEMENT WORKSHEETS NECESSARY TODOCUMENTING COMPLIANCE WITH THE WASTE MANAGEMENT PLAN. RECYCLE AN/OR SALVAGE FORREUSE A MINIMUM OF 50% OF THE NON HAZARDOUS CONSTRUCTION AND DEMOLITION DEBRIS INACCORDANCE WITH REGULATIONS OR MEET A MORE STRINGENT LOCALCONSTRUCTION AND DEMOLITION WASTE MANAGEMENT ORDINANCE.THE CONTRACTOR IS RESPONSIBLE WITH PROVIDING TO THE CITY OF SAN DIEGO THE ABOVECOMPLIANCE FORMS AND IDENTIFY THE RECYCLING & WASTE HAULING COMPANY.
HAZARDOUS MATERIALS IN EXISTING CONSTRUCTION
BASIS ARCHITECTURE & CONSULTING ASSUMES NO RESPONSIBILITY FOR THE MANAGEMENT OFHAZARDOUS MATERIALS THAT MAY BE ON SITE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSURINGTHAT PERSONNEL WITHIN THE WORK AREA ARE PROTECTED FROM EXPOSURE TO HAZARDOUSMATERIALS. IF MATERIALS ARE DISCOVERED THAT MAY BE HAZARDOUS, THE CONTRACTOR SHALLIMMEDIATELY NOTIFY THE OWNER AND CEASE WORK UNTIL CONDITIONS CAN BE MAINTAINED INCOMPLIANCE WITH ALL APPLICABLE REGULATIONS. AN ABATEMENT PLAN FOR ASBESTOS CONTAINING
PROPOSED PARKING:21 COVERED STALLS (EXISTING NO CHANGE)1 OPEN DISABLED VAN ACCESSIBLE SPACE TO BE ADDED
TOTAL = 23 PARKING SPACES
SITE AREA: NO CHANGE - 1.08 ACRESEXISTING LOT COVERAGE: NO CHANGE - 13,200 (APPROX.)EXISTING BUILDING HEIGHT: NO CHANGE - 22 FEET (APPROX.)EXISTING BUILDING SETBACKS: NO CHANGE
PROPOSED WORK INCLUDES:
· CONVERSION OF EXISTING 19 TOWNHOUSES INTO 38 FLATS(TWO OF THE CONVERTED GROUND LEVEL FLAT UNITS TO BE DISABLED ACCESSIBLE).
· FIRE SPRINKLER SYSTEM, ADD TO EACH BUILDING.
· SITE IMPROVEMENTS: REMOVE AND REPLACE EXISTING ASPHALT PAVING.
· SITE ACCESS IMPROVEMENTS: PROVIDE CONFORMING PATH OF TRAVEL FROM DISABLEDPARKING AND FROM STREET, TO GROUND LEVEL UNITS AND COMMON AREAS.
· LAUNDRY ROOM BUILDING 2 (2324 NORTH GOLDEN): EXISTING LAUNDRY ROOM TO BEREMODELED FOR ACCESSIBILITY WITH 3 SETS OF CLOTHES WASHERS AND DRYERS,
· 1 EXISTING TOWNHOUSE TO REMAIN UNCHANGED FOR MANAGER'S UNIT.
· 1 EXISTING TOWNHOUSE TO BE CONVERTED FOR LOWER FLOOR LEASE AND
EXISTING LAUNDRY/STORAGE BUILDING PROJECT LOCATION
SHEET TITLE:
PROJECT LOCATION:
PROJECT NAME:
Copyright 2017 by Charles Pick, Architect and Basis Architecture & Consulting Inc.
GOLDENAPARTMENTS
CONVERSION OFTOWNHOMES TO FLAT
UNIT APARTMENTS
2312 N. GOLDEN AVE.SAN BERNARDINOCALIFORNIA 92404
APN: 0155-183-27-0000
DRAWING REVISION LOG
PLAN CHECK SUBMITTAL 12/12/17
Δ1 PLAN CHECK RESPONSE 03/30/18
POST-MOUNTED LIGHT
LED WALL PACK
PAVING IMPROVEMENTS
(N) CONCRETEANTICIPATED, V.I.F.
(N) GRADING
(E) WALL TO REMAIN
(E) WALL TO BE REMOVED
(N) INTERIOR PARTITION
(N) 1 HOUR RATED WALL
LEGEND
CHARLES PICK, ARCHITECT
6-2017
ACCESSIBILITY NOTE:
SECTION 504 APPLIES - 5% OF UNITS TO BE DISABLED ACCESSIBLE PER CBC IIB.233.TWO (2) DISABLED ACCESSIBLE UNITS TO BE PROVIDED (CONVERSION TO FLATS). THE OTHER SIXTEEN (16) GROUND LEVEL FLATS TO BE CBC IIB COMPLIANT, ADAPTABLE
2312 N GOLDEN
ARCHITECTURAL
A0
A0.1A0.2
A1.0A1.1
A1.2
A1.3
A5.2A5.1
COVER SHEET
DIAGRAMMATIC GROUND FLOOR PLANDIAGRAMMATIC SECOND FLOOR PLAN
TYPICAL UNIT EXISTING PLANS - DIMENSIONING AND NOTESGROUND FLOOR ACCESSIBLE UNIT
GROUND AND SECOND FLOOR NON-ACCESSIBLE UNITS
GROUND AND SECOND FLOOR EXISTING CONDITIONS AND DEMOLITION PLANS
ACCESSIBILITY DETAILS EXTERIORDETAILS
A5.3 ACCESSIBILITY DETAILS INTERIOR
A1.4 GROUND AND SECOND REMODELED PLANS, FINISH SCHEDULES AND NOTES
A3.0 INTERIOR ELEVATIONS
A6.0 DOOR AND WINDOW SCHEDULES
DETAIL AND, FINISH SCHEDULE AND NOTES
DETAIL PANS, FINISH SCHEDULES AND NOTES
COMMUNITY ROOM AND MANAGER'S UNIT
A4.0 TYPICAL EXTERIOR ELEVATIONS
A3.1 INTERIOR ELEVATIONS
A0.3 ROOF PLAN
A3.2 EXISTING AND REMODELED STAIR PLANS AND SECTIONS
SHT-4SHT-5
DRAINAGE PLANFIRE PROTECTION
SHT-1SHT-2SHT-3
COVER SHEET, GENERAL NOTES, INDEX MAPDEMOLITION PLANGRADING PLAN
CIVIL DRAWINGS
FIRE PROTECTION (DEFERRED SUBMITTAL)
EXCEPT BATHROOM (INFEASIBLE).
ONE (1) NEW VAN ACCESSIBLE PARKING STALL TO BE PROVIDED PER CBC IIB.208.2
TWENTY-ONE (21) EXISTING PARKING SPACES, LESS THAN ONE (1) PER UNIT,
ONE (1) ACCESSIBLE STALL REQUIRED FOR 1 -25 TOTAL STALLS.
SHT-6SHT-7
DETAILSDETAILS
A1.5 DETAIL PLAN AND ELEVATION MAILBOXES
A5.0 WALL DETAILSA4.1 GOLDEN AVENUE EXTERIOR ELEVATIONS
FP-1 CODE REQUIREMENTS
ALL NEW UNITS ARE FOR PERMANENT SUPPORTIVE HOUSING.·
· ELECTRICAL TO BE UPGRADED IN EACH UNIT.
WITH ONE SET MEETING ACCESSIBILITY REQUIREMENTS.
CIVIL ENGINEERINGTODD MARTINELLLUDWIG ENGINEERING109 EAST THRIRS STREETSAN BERNARDINO, CA [email protected]
SCHEMATIC PLANS FOR KITCHEN AND BATHROOM EXHAUST, CEILING SUSPENSION SPECIFICATIONA1.6 BUILDINGS 1, 2 + 3 COMMON AREA PLANS
GENERAL NOTES
FOR GENERAL NOTES SEE SHEET A0.2
COMMON AREA.
ARE PROVIDED.
ZONING MAP
DEFERRED SUBMITTALS
THE FIRE PROTECTION CALCULATIONS AND DRAWINGS WILL BE A DEFERRED SUBMITTALPREPARED BY THE FIRE PROTECTION CONTRACTOR.
THE CODE REQUIREMENTS FOR THE FIRE PROTECTION SYSTEM ARE DESCRIBED
ON SHEET FP-1
TEAM INDEX
STRUCTURAL
S-1.0
S-3.0
GROUND LEVEL SLAB LAYOUTS
UPPER ROOF EXISTING FRAMING PLANSS-2.0 SECOND FLOOR FRAMING PLANS
SGN-1 STRUCTURAL GENERAL NOTES
1 OPEN STALL TO BE ADDED
MECHANICALM0.0 MECHANICAL LEAD SHEETM0.1 MECHANICAL EQUIPMENT SCHEDULES AND DETAILSM1.1 MECHANICAL GROUND PLANM1.2 MECHANICAL SECOND PLANM1.3 MECHANICAL ROOF PLANM2.1 MECHANICAL UNIT PLANSM2.2 MECHANICAL GROUND & SECOND FLOOR REMODELED PLANS - MANAGERS UNIT & COMMUNITY ROOMM3.1 TITLE 24
PLUMBINGP0.0 PLUMBING LEAD SHEETP0.1 PLUMBING CALCULATIONSP1.1 PLUMBING GROUND FLOOR PLANP1.2 PLUMBING SECOND FLOOR PLANP2.1 PLUMBING GROUND FLOOR ACCESSIBLE UNIT PLANSP2.2 PLUMBING GROUND & SECOND FLOORS NON- ACCESSIBLE UNIT PLANSP2.3 PLUMBING GROUND FLOOR DEMOLITION & REMODELED PLANS - MANAGERS UNIT, COMMUNITY ROOM & BLDG 2 COMMON AREA
ELECTRICALE-1.0 GENERAL NOTES, LEGEND AND FIXTURE SCHEDULEE-1.1 ELECTRICAL SITE PLANE-2.0 BUILDING EXTERIOR LIGHTING PLANE-2.1 BUILDING EXTERIOR LIGHTING AND ROOF PLANE-3.0 ELECTRICAL UNIT PLANE-3.1 ELECTRICAL MANAGER UNIT PLANE-3.2 ELECTRICAL RECREATION UNIT PLANE-4.0 UTILITY AND LAUNDRY ELECTRICAL PLANE-5.0 ONE LINE DIAGRAME-5.1 ONE LINE DIAGRAM
PROJECT IS PUBLIC HOUSING PER CBC DEFINITION.
A
CODE DATA
R2 OCCUPANCY, PUBLIC HOUSING APPLICABLE CODES:2016 CALIFORNIA BUILDING CODE2016 CALIFORNIA PLUMBING CODE2016 CALIFORNIA MECHANICAL CODE2016 CALIFORNIA ELECTRICAL CODE2016 ENERGY STANDARDS2016 CALIFORNIA GREEN BUILDING STANDARDS CODE
A0.4 CONDITIONAL USE PERMIT COPYA0.5 CONDITIONAL USE PERMIT COPYA0.6 CONDITIONAL USE PERMIT COPY
SHT-8SHT-9
CONDITIONS OF APPROVALCONDITIONS OF APPROVAL
SHT-10 SECTIONS
2 PLAN CHECK RESPONSE 5-3-2018
(NFPA 13R FIRE SPRINKLER TYPE REQUIRED)
3 PLAN CHECK RESPONSE 5-17-2018
· PROVIDE (N) CATV, EACH UNIT.
· (N) MEMBRANE ROOF WITH (N) CUTTERS AND DOWNSPOUTS AT TWO BUILDINGS.
MATERIALS IS TO BE PROVIDED BY THE OWNER.
CONVERT UPPER LEVELS OF SAME 2 UNITS FOR MANAGER'S UNIT ABOVE = +- 1,200 S.F.A OWNER REVISIONS 6-21-2018
8'-3"
17'-7
"5
1/2"
17'-1
0"17
'-4"
3'-10
"17
'-4"
17'-9
"17
'-8"
9'-1"
17'-5
"16
'-1 3
/8"
15
1'-10"
18'-3
"8'-
10"
22'-8
"8
8" CMU
20'-0"8"
ROLL
ED U
P PA
VEM
ENT
REFUSE CONTAINER AREA
7 5/
8"1'-
2 7/
8" 5 5/
8"7
5/8"
7 5/
8"5
1/2"
STUCCO
7 5/
8"5
1/2"
7 5/
8"
EXIS
TING
PLA
NTER
WAL
LS ±
28" A
BOVE
GRA
DE
7 5/
8"
155"
AUTO
GATE
2'-0"
4'-0"
EXIS
TING
CONC
RETE
DIM
ENSI
ONS
5'-9" EXISTING
FENCE TO BEREMOVEDTYPICAL
5"
5 1/
2"
5 1/
2"
5 1/
2"
6 3/
4"
6 3/
4"
7 1/
2"
2 1/
2"
2 1/
2"
2 1/
2"
2 1/
2"
2 1/
2"
2 1/
2"
2 1/
2"
2 1/
2"
2 1/
2"
2 1/
2"
2 1/
2"
2 1/
2"
NOTE:ELEVATION MARKS SHOWNARE EXISTING DIFFERENCES
BETWEEN BOTTOM OF SILL ANDTOP OF CONCRETE WALK
NOTE:ELEVATION MARKS SHOWNARE EXISTING DIFFERENCES
SITE NOTES:1 SEE CIVIL DRAWINGS FOR DESCRIPTION OF EXISTING PROPERTY LINES AND
DIMENSIONS TO REMAIN WITH NO CHANGE
LIN
E O
F RO
OF
OVE
RHAN
G
EXISTING CARPORTSTO REMAIN
179.63' (PER SURVEY)
213.
25' (
PER
SURV
EY)
179.39' (PER SURVEY)
14'-6 7/16"
(PER SURVEY)
24'-11 1/4"
(PER SURVEY)EXISTING CARPORTSTO REMAIN
13"
(MEA
SURE
D) X
3 1
/2"
BEAM
ABO
VE (
TYP)
RETA
ININ
G W
ALL
WHE
EL S
TOP
2'-0"
9'-0"
8'-0"
2 SEE CIVIL DRAWINGS FOR EXISTING AND NEW ELEVATIONS TO TOP OFEXISTING AND NEW CONCRETE IN SITE IMPROVEMENTS
SEE CIVIL DRAWINGS FOR NEW ELEVATIONS TOTOP OF NEW CONCRETE WALKS
EXISTING COURTYARD
19'-0"
NOPARKING
4'-0"
EXIS
TING
PLA
NTER
WAL
LS ±
28" A
BOVE
GRA
DE
2 1/
2"
NEW RAMP DN117"
(EXI
STIN
G)
10'-0"
NEW HANDRAILS
MAILBOXES
MAILBOXESWHE
EL S
TOP
2'-0"
(E) T
RASH
ARE
A
12
3
4
56
7
8" CMU
9
10
STUCCO11
1213
14
EXISTING CARPORTSTO REMAIN
8" CMU
16
17
STUCCO18
1920
21
NEW VAN ACCESSIBLEPARKING SPACE
MAILBOXES
A1.12
A1.22
A1.42
A1.64
ROOMELECTRICAL
GAS METERS
EXISTINGELECTRICAL ROOM
DOMESTIC HOT WATERROOM
NEW FIRE PROTECTIONROOM
INACTIVE STORAGE
NEW FIRE PROTECTIONROOM
INACTIVE STORAGE
DOMESTIC HOT WATERROOM
EXISTINGELECTRICAL ROOM
EXISTING
REMODELED LAUNDRYROOM
NEW FIRE PROTECTIONROOM
DRI
VEW
AYIS
ONE
WAY
ACCE
SS
DRI
VEW
AYIS
ONE
WAY
ACCE
SS
3 THE SITE INFORMATION SHOWN ON THIS DRAWING IS FOR THE PURPOSE OFSHOWING THE GROUND FLOOR BUILDING PLANS (IN THEIR ENTIRETY) IN CONTEXT
LEGENDCROSS HATCHING INDICATES ACCESSIBLE UNIT ON ACCESSIBLE PATH OF TRAVEL
CARPORTS1 THE CARPORTS ARE EXISTING TO REMAIN, EXCEPT AS NOTED:
THE CONTRACTOR SHALL EXAMINE ALL 13" (MEASURED DIMENSION) X 3 1/2"BEAMS AT THE ROOF OVERHANGS FOR EVIDENCE OF DRY ROT.EXISTING BEAMS FOUND WITH DRY ROT TO BE REMOVED ANDREPLACED LIKE-FOR-LIKE.
THE CONTRACTOR SHALL EXAMINE THE FASCIAS FOR EVIDENCE OF DRY ROT.MATERIAL FOUND WITH DRY ROT TO BE REMOVED AND REPLACED LIK-FOR-LKIE.
ALL NEW MATERIAL TO BE PRIMED AND PAINTED.
A
B
C
NEW
TUB
E ST
EEL
FENC
E W
ITH
PAIN
TED
FINI
SHSE
E CI
VIL
DRAW
INGS
FOR
DET
AILS
SEE LANDSCAPEDRAWINGS FOR WORK
IN REAR YARDS
4'-3"
NEW OPENPARKING SPACE
4 ALL EXISTING UNLESS OTHERWISE NOTED: U.O.N.
PROVIDEROFFICES
SERVICE
COMMUNITY ROOM
SHEET TITLE:
PROJECT LOCATION:
PROJECT NAME:
Copyright 2017 by Charles Pick, Architect and Basis Architecture & Consulting Inc.
GOLDENAPARTMENTS
CONVERSION OFTOWNHOMES TO FLAT
UNIT APARTMENTS
2312 N. GOLDEN AVE.SAN BERNARDINOCALIFORNIA 92404
APN: 0155-183-27-0000
DRAWING REVISION LOG
PLAN CHECK SUBMITTAL 12/12/17
Δ1 PLAN CHECK RESPONSE 03/30/18
POST-MOUNTED LIGHT
LED WALL PACK
PAVING IMPROVEMENTS
(N) CONCRETEANTICIPATED, V.I.F.
(N) GRADING
(E) WALL TO REMAIN
(E) WALL TO BE REMOVED
(N) INTERIOR PARTITION
(N) 1 HOUR RATED WALL
LEGEND
CHARLES PICK, ARCHITECT
6-2017
DIAGRAMMATICGROUND FLOOR
PLAN
A0.1
3 PLAN CHECK RESPONSE 5-17-2018
3TYP
A
1'-2
7/8"
2312 N GOLDENUNIT 7
2312 N GOLDENUNIT 6
2312 N GOLDENUNIT 5
2312 N GOLDENUNIT 4
2312 N GOLDENUNIT 3
2312 N GOLDENUNIT 2
2312 N GOLDENUNIT 1
2334 N GOLDENUNIT 7 UNIT 6
2334 N GOLDENUNIT 5
2334 N GOLDENUNIT 3UNIT 4
2334 N GOLDEN 2334 N GOLDEN
EXISTING COURTYARD
EXISTING COURTYARD
2336 N GOLDENUNIT 7
2336 N GOLDENUNIT 6
2336 N GOLDENUNIT 5
2336 N GOLDENUNIT 4
2336 N GOLDENUNIT 3
2336 N GOLDENUNIT 2
2336 N GOLDENUNIT 1
EXISTING DRIVEWAY
EXISTING DRIVEWAY
EXIST
ING
COUR
TYAR
DEX
ISTIN
G DR
IVEW
AY
EXIS
TING
SID
EWAL
K
NORT
H GO
LDEN
AVE
NUE
EXIS
TING
PLA
NTIN
GEX
ISTI
NG P
LANT
ING
NORTH
DIAGRAMMATIC SECOND FLOOR PLANSCALE: 3 / 32 = 1'-0"
D W
A1.21
A1.21
A1.41
W/D
W/D
EXISTING HWFLUE THRU
ROOF
NEW DRYEREXHAUST
THRU ROOF
NEW DRYEREXHAUST
THRU ROOF
EXISTING HWFLUE THRU
ROOF
EXISTING HWFLUE THRU
ROOF
COMMONAREAROOF
COMMONAREAROOF
COMMONAREAROOF
LINE OF LOW ROOF
LINE OF LOW ROOF
LINE OF LOW ROOF
LINE OF LOW ROOF
DEFERRED SUBMITTALS
1. ALL WORK SHALL CONFORM TO APPLICABLE CODES AND ORDINANCES OF THE CITYOF SAN BERNARDINO, CALIFORNIA, INCLUDING:
2016 CALIFORNIA BUILDING CODE (CBC)2016 CALIFORNIA ELECTRICAL CODE (CEC)2016 CALIFORNIA PLUMBING CODE (CPC)2016 CALIFORNIA MECHANICAL CODE (CMC)2016 CALIFORNIA RESIDENTIAL CODE (CRC)2016 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN)UNIFORM HOUSING CODEUNIFORM SECURITY CODE
HOURS OF CONSTRUCTIONMONDAY - FRIDAY 7:00 AM - 5:00 PM
CONSTRUCTION NOISE GUIDELINES:CONTRACTOR SHALL OBTAIN A COPY OF THE CONSTRUCTION NOISE GUIDELINES ANDBECOME SELF AWARE OF ALL REQUIREMENTS AND BE SOLELY RESPONSIBLE FORCOMPLYING WITH THE GUIDELINES.
2. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, CONDITIONS & SHALL NOTIFYTHE ARCHITECT OF ANY DIMENSIONS & CONDITIONS, WHICH DIFFER FROM THOSESHOWN, BEFORE STARTING WORK. DIMENSIONS GIVEN AS (CLR.) ARE CODE REQUIRED& SHALL BE MAINTAINED.
3. ALL DIMENSIONS FOR NEW CONSTRUCTION ARE TO FACE OF STUD. ALL DIMENSIONSFROM EXISTING CONSTRUCTION ARE FROM FACE TO FINISH, UNLESS OTHER WISENOTED (U.O.N.).
4. DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALEDDIMENSIONS. DIMENSIONS FOR EXISTING CONDITIONS & ELEVATIONS MAY BEAPPROXIMATE.
5. ALL INSTALLATIONS TO BE IN ACCORDANCE WITH BEST INDUSTRY STANDARDS &MANUFACTURER'S REQUIREMENTS, SEE ATTACHED SPECIFICATIONS.
6. ALL THE DRAWINGS SHOW REPRESENTATIVE & TYPICAL ATTACHMENTS,CONNECTIONS, FASTENINGS & ETC. SHALL BE PROPERLY SECURED IN CONFORMANCEWITH BEST PRACTICE.
7. THE PLANS ARE NOT BASED ON A SURVEY & ARE INTENDED ONLY TO SHOW GENERALLAYOUT OF PROPERTY & WORK LOCATIONS. CONDITIONS SHOWN APPROXIMATE.
8. ALL WORK SUBJECT TO ASSOCIATED PROJECT MANUAL SPECIFICATIONS ANDINSTRUCTIONS BY ARCHITECT.
9. ALL CONDITIONS ARE EXISTING UNLESS OTHERWISE NOTED.
GENERAL NOTES
THE FIRE PROTECTION CALCULATIONS AND DRAWINGS WILL BE A DEFERRED SUBMITTALPREPARED BY THE FIRE PROTECTION CONTRACTOR.
THE CODE REQUIREMENTS FOR THE FIRE PROTECTION SYSTEM ARE DESCRIBEDON SHEET FP-1
LINE OF LOW ROOF
LINE OF LOW ROOF10. DRYER EXHAUST: SEE MECHANICAL SHEETS. EXHAUST TO BE +24" MIN HT
FROM ROOF WITHIN 10'.
MANAGER'SUNIT
SHEET TITLE:
PROJECT LOCATION:
PROJECT NAME:
Copyright 2017 by Charles Pick, Architect and Basis Architecture & Consulting Inc.
GOLDENAPARTMENTS
CONVERSION OFTOWNHOMES TO FLAT
UNIT APARTMENTS
2312 N. GOLDEN AVE.SAN BERNARDINOCALIFORNIA 92404
APN: 0155-183-27-0000
DRAWING REVISION LOG
PLAN CHECK SUBMITTAL 12/12/17
Δ1 PLAN CHECK RESPONSE 03/30/18
POST-MOUNTED LIGHT
LED WALL PACK
PAVING IMPROVEMENTS
(N) CONCRETEANTICIPATED, V.I.F.
(N) GRADING
(E) WALL TO REMAIN
(E) WALL TO BE REMOVED
(N) INTERIOR PARTITION
(N) 1 HOUR RATED WALL
LEGEND
CHARLES PICK, ARCHITECT
6-2017
DIAGRAMMATICSECOND FLOOR
PLAN
A0.2
A
A OWNER REVISIONS 6-21-2018
2312 N GOLDENUNIT 7
ACCESSIBLE
2312 N GOLDENUNIT 6
ACCESSIBLE
2312 N GOLDENUNIT 5
2312 N GOLDENUNIT 4
2312 N GOLDENUNIT 3
2312 N GOLDENUNIT 2
2312 N GOLDENUNIT 1
2334 N GOLDENUNIT 7
ACCESSIBLEUNIT 6
2334 N GOLDENUNIT 5
2334 N GOLDENUNIT 3UNIT 4
2334 N GOLDEN 2334 N GOLDENEX UNIT 1 & 2
2334 N GOLDEN 2334 N GOLDEN
MANAGER COMMUNITY RMACCESSIBLE
EXISTING COURTYARD
EXISTING COURTYARD
2336 N GOLDENUNIT 7
2336 N GOLDENUNIT 6
2336 N GOLDENUNIT 5
2336 N GOLDENUNIT 4
2336 N GOLDENUNIT 3
2336 N GOLDENUNIT 2
2336 N GOLDENUNIT 1
EXISTING DRIVEWAY
EXISTING DRIVEWAY
EXIST
ING
COUR
TYAR
DEX
ISTIN
G DR
IVEW
AY
NORT
H GO
LDEN
AVE
NUE
NORTH
ROOF PLANSCALE: 3 / 32 = 1'-0"
CARPORT ROOF
EXISTING GUTTER
EXISTING GUTTER
ELECSERVICE
CONDUITS
ELECSERVICE
CONDUITS
EXISTING GUTTER
ELECSERVICE
CONDUITS
RTUE
RTUE
RTUE
RTUE
RTUE
RTUE
RTUE
RTUE
RTUE
RTUE
RTUE
RTUE
RTUE
RTUE
RTU RTUE
RTUE
RTUE
CARPORT ROOF
EXISTING RTU TOBE REMOVED
COMPLETE ANDALL UTILITIES TERMINATED
EXISTING DUCTOPENING THRUROOF TO BEINFILLED AND
ROOF MEMBRANEPATCHED
BE REMOVEDCOMPLETE ANDALL UTILITIES TERMINATED
EXISTING DUCTOPENING THRUROOF TO BEINFILLED AND
ROOF MEMBRANEPATCHED
EXISTING RTU TO
EXISTING RTU TOBE REMOVED
COMPLETE ANDALL UTILITIES TERMINATED
EXISTING DUCTOPENING THRUROOF TO BEINFILLED AND
ROOF MEMBRANEPATCHED
KEN
KEN
KEN
ROOF MOUNTED EQUIPMENT
TEE
TEE
TEE
TEE
TEE
TEE
TEE
TEE
1 THE EXISTING RTUs ON UNIT 1, 2324 NORTH GOLDEN, THE NEW COMMUNITY ROOM TO BE REUSED IN REMODELED WORK.
PREVENTIVE MAINTENANCE SHALL BE PERFORMED ON THE UNIT AS PER THE ORIGINAL MANUFACTURER'SINSTRUCTIONS AND RECOMMENDED PREVENTIVE MAINTENANCE PLANS.
2 THE EXISTING RTUs ON UNIT 2, 2324 NORTH GOLDEN, THE MANAGER'S UNIT TO BE REUSED(NO INTERIOR WORK, ALL EXISTING TO REMAIN)
PREVENTIVE MAINTENANCE SHALL BE PERFORMED ON THE UNIT AS PER THE ORIGINAL MANUFACTURER'SINSTRUCTIONS AND RECOMMENCED PREVENTIVE MAINTENANCE PLANS.
3 ALL OTHER EXISTING RTUs TO BE REMOVED AND THE DUCT OPENINGS INFILLED NEW NEW ROOFSHEATHING FITTED TO THE OPENING, AND THE EXISTING ROOF MEMBRANE PATCHED TO PROVIDECONTINUITY IN THE WATERPROOFING.
ALL EXISTING KITCHEN AND BATHROOM EXHAUST THRU THE ROOF TO BE REUSED IN THE NEW WORKSHALL REMAIN AND THE ORIGINAL MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS FORPREVENTIVE MAINTENANCE SHALL BE PERFORMED.
ALL NEW KITCHEN AND BATHROOM EXHAUST TO BE PROVIDED IN THE NEW WORK SHALL SHALLHAVE ROOF CAPS AND PATCHING OF THE EXISTING ROOF MEMBRANE TO PROVIDE CONTINUITYIN THE WATERPROOFING..
THE CONTRACTOR SHALL VERIFY EXACT LOCATION OF ALL ROOF OPENINGS. ALL OPENINGS S ON THE ROOF PLAN AR DIAGRAMMATIC.
4
5
6
GENERAL NOTES FOR ROOF MEMBRANE AND
1A3.2
1A3.2
1A3.2
LOWER ROOF BELOW (TYP)LINE OF SECOND FLOOR ROOF OVERHANG
LOWER ROOF BELOW (TYP)LINE OF SECOND FLOOR ROOF OVERHANG
LOWER ROOF BELOW (TYP)LINE OF SECOND FLOOR ROOF OVERHANG
COMMONAREASROOFBELOW
COMMONAREASROOFBELOW
RTUE
RTUE
RTUE
JNEW CIRCUIT ON 24HR TIMER FROM EXISTINGBUILDING 3 (2312 N GOLDEN) ELECTRICAL RMFOR NEW ILLUMINATED SIGN
JNEW CIRCUIT ON 24HR TIMER FROM EXISTINGBUILDING 2 (2324 N GOLDEN) ELECTRICAL RMFOR NEW ILLUMINATED SIGN
JNEW CIRCUIT ON 24HR TIMER FROM EXISTINGBUILDING 1 (2336 N GOLDEN) ELECTRICAL RMFOR NEW ILLUMINATED SIGN
BUILDING 1
BUILDING 2
BUILDING 3
CONTRACTOR TO INSPECT, IDENTIFY DRYROT IN CANOPIES AND OVERHANGS. REPAIR AS NEEDED, RESTORE AND FINISH TO MATCH EXISTING.
7
(TYP. ALL)(TYP. ALL)
(TYP. ALL) (TYP. ALL)
(TYP. ALL)(TYP. ALL)
ROOF SERVICE AND REPAIR AS NEEDED
TPO ROOF
TPO ROOF
REPLACE ALL GUTTERS AND DOWNSPOUTS.8
UPPER:
EX UNIT 1 & 2
LOWER:
SHEET TITLE:
PROJECT LOCATION:
PROJECT NAME:
Copyright 2017 by Charles Pick, Architect and Basis Architecture & Consulting Inc.
GOLDENAPARTMENTS
CONVERSION OFTOWNHOMES TO FLAT
UNIT APARTMENTS
2312 N. GOLDEN AVE.SAN BERNARDINOCALIFORNIA 92404
APN: 0155-183-27-0000
DRAWING REVISION LOG
PLAN CHECK SUBMITTAL 12/12/17
Δ1 PLAN CHECK RESPONSE 03/30/18
POST-MOUNTED LIGHT
LED WALL PACK
PAVING IMPROVEMENTS
(N) CONCRETEANTICIPATED, V.I.F.
(N) GRADING
(E) WALL TO REMAIN
(E) WALL TO BE REMOVED
(N) INTERIOR PARTITION
(N) 1 HOUR RATED WALL
LEGEND
CHARLES PICK, ARCHITECT
6-2017
ROOF PLAN
A0.3
A
A OWNER REVISIONS 6-21-2018
GROUND FLOOR DEMOLITION UNITS 1 + 2 BUILDING 2 (2324 NORTH GOLDEN)SCALE: 1/4" = 1'-0"
2
MW
RK
GAS
EXISTINGLIVING ROOM100
EXISTINGKITCHEN102
EXISTINGDINING ROOM103
MW
RK
GAS
EXISTINGDINING ROOM103
UNIT 2
EXISTINGKITCHEN102
EXISTINGLIVING ROOM100
EXISTING UNIT 2 REMOVE SLIDING DOORCOMPLETE & PREPARE
NOTE:
BALANCE OF DIMENSIONS,NOTES, ELECTRICAL AND MECHANICAL INFORMATIONSIMILAR TO THAT SHOWN
UNIT 1
3'-0" 9"1'-8"7'-10"
15'-6"
1'-9"
REMOVE HANDRAIL ANDBRACKETS COMPLETE
REMOVE EXISTING STAIR
LINE OF EXISTING OPNGTHRU FLOOR ABOVE
IN TYPICAL UNIT
REMOVE EXTERIORSTORAGE CLOSETTYPICAL
FLOOR-TO-FLOORHEIGHT109 1/4" (9'-1 1/4")
REMOVE KITCHEN COMPLETECAP ALL UTILITIES ANDTERMINATE ALL ELECTRICAL
REMOVE CEILING EXPOSINGEXISTING FLOOR STRUCTUREABOVE TO REMAIN
REMOVE WALL CAP ON PARTIAL HEIGHT WALL
EXISTING KITCHEN CEILINGAT 84" AFF
NEW OPNG
3'-3" 3'-0"
EXISTING BEARING WALL
2'-0
"8'
-0"
REMOVE 8'-0" SECTIONOF (E) NON-BEARING WALL
REMOVE (E)POWDER ROOM. CAP
ALL UTILITIES AND TERMINATE ELECTRICAL
REMOVE SLIDING DOORCOMPLETE WITH HEADER,PREPARE ROUGH OPENINGFOR (N) DOOR & WINDOW
ROUGH OPENING FOR(N) WINDOW SHEET TITLE:
PROJECT LOCATION:
PROJECT NAME:
Copyright 2017 by Charles Pick, Architect and Basis Architecture & Consulting Inc.
GOLDENAPARTMENTS
CONVERSION OFTOWNHOMES TO FLAT
UNIT APARTMENTS
2312 N. GOLDEN AVE.SAN BERNARDINOCALIFORNIA 92404
APN: 0155-183-27-0000
DRAWING REVISION LOG
PLAN CHECK SUBMITTAL 12/12/17
Δ1 PLAN CHECK RESPONSE 03/30/18
POST-MOUNTED LIGHT
LED WALL PACK
PAVING IMPROVEMENTS
(N) CONCRETEANTICIPATED, V.I.F.
(N) GRADING
(E) WALL TO REMAIN
(E) WALL TO BE REMOVED
(N) INTERIOR PARTITION
(N) 1 HOUR RATED WALL
LEGEND
CHARLES PICK, ARCHITECT
6-2017
GROUNDEXISTING/DEMOLITION PLANS
MANAGER'S UNIT ANDCOMMUNITY ROOM
A1.3
2 PLAN CHECK RESPONSE 5-3-2018
3 PLAN CHECK RESPONSE 5-17-2018
A OWNER REVISIONS 6-21-2018
A
SECOND FLOOR AT UNITS 1 + 2 BUILDING 2 (2324 NORTH GOLDEN) - INCLUDES DEMOSCALE: 1/4" = 1'-0"
1
NOTE:
BALANCE OF DIMENSIONS, NOTES,ELECTRICAL AND MECHANICALINFORMATION SIMILAR TO THAT SHOWN IN TYPICAL UNIT
EXTERIOR STORAGECLOSETS TO BE REMOVED
TYPICAL
UNIT 2 UNIT 1
203HALLEXISTING
(E) CLOSET
201BATHROOMEXISTING MANAGER
201ASTORAGELAUNDRY/
203HALLEXISTING
204CLOSETEXISTING 204
CLOSETEXISTING
REMODELED GROUND FLOOR AT UNITS 1 + 2 BUILDING 2 (2324 NORTH GOLDEN)SCALE: 1/4" = 1'-0"
2
UNIT 2
NOTE:
BALANCE OF DIMENSIONS, NOTES,ELECTRICAL AND MECHANICALINFORMATION SIMILAR TO THAT SHOWN IN TYPICAL UNIT
UNIT 1
COMMON AREA KEYED NOTES
1.
2.
1
2
3
4
5
"EMPLOYEES ONLY" SIGN AT STAIRS
NEW ACCESSIBLE ENTRY DOOR
REMOVE EXISTING SLIDING GLASS DOORS, INFILL PORTION OF
INFILL FLOOR TO LEVEL
NEW PANTRY
EXISTING ROUGH OPENING FOR NEW WINDOW
PATCH AND REPAIR STUCCOAS REQD BY DEMOLITION OFEXTERIOR CLOSET
USER TOILET ROOMNEW ACCESSIBLE SINGLE
102
REMODELED BATHINTERIORELEVATIONS
16215
PATCH AND REPAIR STUCCOAS REQD BY DEMOLITION OF
EXTERIOR CLOSET
18
PANTRY103
A3.1
AND MEETING FOR LEASINGSERVICE PROVIDERS OFFICE
104
GAS
7
LEGENDCOMBINATION SMOKE AND CARBON MONOXIDE ALARM WITH PRIMARY POWERFROM BUILDING PERMANENT POWER SYSTEM (ALARM TO HAVE BATTERY BACK UP)
SMOKE ALARM WITH PRIMARY POWER FROM BUILDING PRIMARY POWER SYSTEM(ALARM TO HAVE BATTERY BACK UP)
VA COMBINATION VISUAL / AUDIBLE ALARM INTERCONNECTED TO SMOKE AND CARBONMONOXIDE ALARMS IN ACCESSIBLE UNITS 6 + 7 BUILDING 2 (2324 N. GOLDEN)AND UNITS 6 + 7 BUILDING 3 (2312 N. GOLDEN)
SM
SC
CLOSET
48" MIN. CLEAR
60"
6'-9" 4 1/2" 3'-0"
60"
1A3.1
8
W1
NEW WINDOW IN REWORKEDEXISTING ROUGH OPENING
PATCH AND REPAIR EXTERIOR STUCCOAND INTERIOR GYP BYRD AS RED
N
± ±6'-0"
± 8'-0"NEW RO
EXISTING RO
ROOM FINISH SCHEDULE
ROOM # ROOM DESCRIPTION FLOOR BASE WALLS CEILING NOTES
100 REMODELED NEW VINYL EXISTING EXISTINGON EXISTINGCONCRETESLAB ON
101 HALLWAY & EXISTING CEILING TO REMAIN
104 SERVICE PROVIDERS
GROUND FLOOR ACCESSIBLE COMMUNITY ROOM
COMMUNITY
OFFICE AND NEW VINYLON NEW PLYWOODSUBFLOOR
TO BEPAINTED
NEW WOODBASE TOMATCH
NEW 4"
AND NEWGYP BRDTO BE PAINTED
EXISTINGGYP BRDTO BE PAINTED
GYP BRDTO BE PAINTED
GYP BRDTO BEPAINTED
EXISTINGEXISTINGCOVE VINYL AT 7'-4" AFF
GYP BRDTO BE PAINTED
EXISTINGGYP BRDTO BE PAINTED
EXISTING
GRADE
102GYP BRDTO BE PAINTED
EXISTINGGYP BRDTO BE PAINTED
EXISTING
NEW VINYLON EXISTINGCONCRETESLAB ONGRADE
BASE
EXISTING
NEW VINYLON EXISTINGCONCRETESLAB ONGRADE
NEW WOODBASE TOMATCHEXISTING
ROOM
REMODELEDACCESSIBLETOILET ROOM
MEETING ROOM FORLEASING
EXISTING CEILING TO REMAINAT 8'-0" AFF
PATCH AND REPAIR CEILINGAS REQ'D
PATCH AND REPAIR CEILINGAS REQ'D
EXISTING CEILING TO REMAINAT 7'-4" AFF
ROOM FINISH SCHEDULE
ROOM # ROOM DESCRIPTION FLOOR BASE WALLS CEILING NOTES
200 MANAGER NEW VINYLON EXISTING
201
203 MANAGER
MANAGER'S UNIT (UPPER LEVEL)
LIVING
HALL
202
ROOM
MANAGERBEDROOMS
MANAGERBATHROOM
NEW OREXISTING
EXISTING ANDNEW TO BE
15'-6"
GENERAL NOTES FOR INTERIOR FINISHES:
1 ALL NEW PAINT COLORS TO BE SELECTED BY OWNER FROM STANDARD COLORS
WOOD BASE PAINTED TEXTURE
VA
SM
VA
SM
EXISTING CEILING TO REMAINAT 8'-0" AFFPATCH AND REPAIR CEILINGAS REQ'D FOR INSTALLATIONOF NEW ALARMS
4
OR NEWFRAMED
2
2
NEW CASED
9"
3/4"
T+G
PLY
WOO
DSU
BFLO
OROV
ER N
EW S
LEEP
ERS
ON E
XIST
ING
SLAB
SEE
DETA
IL 1
4, S
HT A
5.0
OPNG
6 6
VA
3"
±
2'-0
"8'
-0"
3'-0
"
6/A5.0
12/A5.0 (N) COMMUNITY ROOM100
(N) 4x10 HDR. DBL STUDSEACH END. WRAP DRYWALL,TAPE & TEXTURE TO MATCH (E)
NOTE:NEW TOILET EXHAUSTTO BE PROVIDED INLOCATION OF EXISTING.
PATCH AND REPAIR CEILINGAS REQUIRED FOR FITTINGNEW FAN HOUSING
EXISTING EXHAUST FAN TO REMAIN
RCP (N)ACCESSIBLE UNIT
CLG HT 7'-0" AFF
PTAC
(E) FLOOR
(N) FLOOR, INFILL
(E) SDG (SHOWN DASHED)
6'-8" A.F.F
(N) SINGLE HUNG WINDOW(N) WALL INFILL w/PTAC SLEEVE
DETAIL ELEVATION @ SERVICE PROVIDERS OFFICESCALE: 1/2" = 1'-0"
5
SHEET TITLE:
PROJECT LOCATION:
PROJECT NAME:
Copyright 2017 by Charles Pick, Architect and Basis Architecture & Consulting Inc.
GOLDENAPARTMENTS
CONVERSION OFTOWNHOMES TO FLAT
UNIT APARTMENTS
2312 N. GOLDEN AVE.SAN BERNARDINOCALIFORNIA 92404
APN: 0155-183-27-0000
DRAWING REVISION LOG
PLAN CHECK SUBMITTAL 12/12/17
Δ1 PLAN CHECK RESPONSE 03/30/18
POST-MOUNTED LIGHT
LED WALL PACK
PAVING IMPROVEMENTS
(N) CONCRETEANTICIPATED, V.I.F.
(N) GRADING
(E) WALL TO REMAIN
(E) WALL TO BE REMOVED
(N) INTERIOR PARTITION
(N) 1 HOUR RATED WALL
LEGEND
CHARLES PICK, ARCHITECT
6-2017
A1.5
RCP, DETAIL PLAN + ELEVMAILBOXES,
SCHEMATIC PLANS FORKITCHEN + BATH EXHAUST,
CLG SUSPENSION SPECIFICATION
1
3 PLAN CHECK RESPONSE 5-17-2018
33
3 PLAN CHECK RESPONSE 5-17-2018
A OWNER REVISIONS 6-21-2018
A
GROUND FLOOR ACCESSIBLE UNIT - LIVING ROOM & COMMUNITY ROOMSCALE: 3/8" =1'-0"
1
REMODELED LIVING ROOM WITH EXISTING STAIR BEYOND5'-0"
8'-0
"
NEW PAINTED WOOD BASE TO MATCH
EXISTING CONCRETE SLAB ON GRADE
EXISTING GYPSUM BOARD CEILINGREMAIN WITH NEW LAYER OFRESILIENT FURRING CHANNELS AND5/8" GYP BRD THROUGHOUT
FACE OF NEW GYPSUM BOARD TAPED AND TEXTURED TO MATCHEXISTING
TO BE PRIMED AND PAINTED INSTANDARD COLOR TO BE SELECTEDBY OWNER
EXISTING AND NEW GYP BRD4'
-0"
4'-0"
OPEN TO BEYOND
GROUND FLOOR ACCESSIBLE UNIT -KITCHENSCALE: 3/8" =1'-0"
2
2'-1
0"
29"
CLR
27"
CLR
℄
33"-
36"
18"
12" 24"
4'-2"
40"
24"
8" -
10"
BATHROOMSCALE: 3/8" =1'-0"
3 GROUND FLOOR ACCESSIBLE UNIT
SCALE: 3/8" =1'-0"
8'-0
"
± 6'-9"
SCALE: 3/8" =1'-0"
5
33"
- 36
"
8" -
10"
6
± 6'-9"
17"-
19"
54" MIN42" MIN
7"- 9"
15"
MIN
33"-
36"
± 9'-0 1/2" ± 9'-0 1/2"
1'-3
"
FACE OF NEW GYPSUM BOARD TAPED AND TEXTURED TO MATCHEXISTING
NEW PAINTED WOOD TRIMTO MATCH EXISTING
NOTE: ALL NEW SWITCHES ANDCONTROLS TO BE MOUNTEDAT 48" AFF
GFC
I ACRYLIC SURROUND
SEE SPECIFICATIONSFOR FIXTURE
NOTE: ALL NEWFAUCETS SHOWERCONTROLS, ETC, AREWATER CONSERVING
SCALE: 3/8" =1'-0"
7
SCALE: 3/8" =1'-0"
8
SCALE: 3/8" =1'-0"
9
SCALE: 3/8" =1'-0"
10
SCALE: 3/8" =1'-0"
11
8'-0
"
4 1/2"
7'-4
"
7'-4
"
EXISTING GYPSUM BOARD CEILING
AND REPAIRED AS REQUIRED FORNEW PAINTED FINISH IN COLORTO BE SELECTED BY OWNER
APPROXIMATE AREA OF PARTIALWALL TO BE INFILLED WITH NEWTO UNDERSIDE OF CEILING
EXISTING BASE CABINETSTO REMAINTO UNDERSIDE OF CEILING
5"
± 3'
-8"
INFI
LL W
ALL
8'-5 1/2"
EXIST
E
4'-4" OPEN
TOBEYOND
REFRIG
SPACE3'-0" EX
± 3'
-8"
EEE
3'-2"
REMOVE
REMOVE ANDREPLACE WALLCABINET WITH
NEW TO MATCHEXISTING
SCALE: 3/8" =1'-0"
12
SCALE: 3/8" =1'-0"
13
EXISTING STAIR BEYONDSHOWN IN HIDDEN LINESTYLE
24"
TO BE PRIMED AND PAINTED INSTANDARD COLOR TO BE SELECTEDBY OWNER
EXISTING AND NEW GYP BRD
EXISTING CONCRETE SLAB ON GRADE
BLOCKING FOR ATTACHMENTOF GRAB BARS
PROVIDE ALL NECESSARY
EXISTING BASE CABINETSTO REMAINTO UNDERSIDE OF CEILING
EXISTING WALL CABINETSTO REMAIN
EXISTING BASE CABINETSTO REMAIN
EXISTING WALL CABINETSTO REMAIN
REFRIG SPACE3/4" 3/4"
WORK SPACE
2'-6"
29" C
LEAR
SEE SPECIFICATIONS FOR ENERGYSTAR RATED APPLIANCES
NOTE:
30" UNDER CABINET RANGEHOOD WITH 3 1/4" X 10" DUCTTO ATMOSPHERE AND CONTROLSWITCH TO BE REWIRED TOWALL MOUNTED SWITCH ADJACENT
EXHAUST DUCT TOATMOSPHERE
GFCI
4'-0"
DIM
TO T
OP
COUN
TER
5'-8 1
/4"
1'-3"
5 1/2
"
GAS
2'-0 1/2"
36" (H) WALLCABINET
FIRST FLOOR
3A5.0
OF B
OTTO
M SH
ELF
END PANELSEACH SIDE
3A5.0
EXISTING GYPSUM BOARD CEILINGTO REMAIN TO THE MAXIMUM EXTENTPOSSIBLE
NEW COVE VINYL BASE IN REMODELED BATHROOMS
NEW COVE VINYL BASE IN REMODELED BATHROOMS
RECEPTACLE
EXISTING STEP DOWN
± 7'-0 1/2"
24"RANGE SPACE
2'-6"
2'-11"
30" CLEAR MIN
LAMINATEBACKSPLASH
4
1'-3"
5 1/2
"
5'-8 1
/4"
4'-0"
SIDESPALSH
WALL CABINET
3A5.0
UNDER CABINET RANGE HOOD
LAMINATE SIDESPLASH WITHCHAMFERED LEADING EDGE
GAS FUELED RANGE
NOTE: CONTROLS FOR RANGE HOODTO BE REWIRED TO WALL SWITCH
SCALE: 3/8" =1'-0"2A
BATHROOMGROUND FLOOR ACCESSIBLE UNIT BATHROOM
GROUND FLOOR ACCESSIBLE UNIT
BATHROOMGROUND FLOOR ACCESSIBLE UNIT
GROUND FLOOR NON-ACCESSIBLE UNITBATHROOM
GROUND FLOOR NON-ACCESSIBLE UNITBATHROOM
GROUND FLOOR NON-ACCESSIBLE UNITBATHROOM
GROUND FLOOR NON-ACCESSIBLE UNITBATHROOM
GROUND FLOOR NON-ACCESSIBLE UNITKITCHEN
GROUND FLOOR NON-ACCESSIBLE UNITKITCHEN
GROUND FLOOR NON-ACCESSIBLE UNITKITCHEN
SEE SIDESPLASH ELEVATION 2ATHIS SHEET
ALL NEW CLOSETS IN ACCESSIBLEROOMS OR SPACES TO HAVE NEW
CLOTHES SHELF AT 48" AFFAND CLOTHES ROD
EXISTING STAIR BEYOND SHOWN IN HIDDEN LINESTYLE
THE SPECIFIED REFRIG / FREEZERGE MODEL GPE12FSKSB HAS MORETHAN 54% OF THE FREEZER BELOW 54"AFF
SEE SHEET A3.2 FOR DETAILS ON WORKFOR EXISTING STAIR O REMAIN
NEW USG WALL-TO-WALL DRYWALLSUSPENSION SYSTEMALLOWABLE SPAN FOR "TEE" SPACINGAT 16" OC UP TO 7'-6" REQUIRES NOSUPPORTS.SEE SPECIFICATION SHEET ONSHEET A1.5
NEW EXHAUST DUCT TO BE ROUTEDBETWEEN UNDERSIDE OF EXISTING CEILINGAT TOP OF NEW DRYWALL SUSPENSION"TEE"
1'-0"
8'-0"
NEW FIXTURESEE ELECTRICAL
SEE DETAILS PLANS FOR SCHEMATICROUTING OF KITCHEN AND BATH EXHAUST TO EXISTING RISERS
NOTE:
EXISTING GYPSUM BOARD CEILINGTO REMAIN TO THE MAXIMUM EXTENTPOSSIBLE
NEW USG WALL-TO-WALL DRYWALLSUSPENSION SYSTEM AT 7'-0" AFF
NEW USG WALL-TO-WALL DRYWALLSUSPENSION SYSTEM
NEW USG WALL-TO-WALL DRYWALLSUSPENSION SYSTEM
7'-4"
EXIS
TIN
G C
LG H
EIG
HT
TO R
EMAI
N
AT 88" AFF TO BE PATCHED
BOTTOM OF EXISTING FLOOR JOISTSAT ± 96 1/2" AFF
8"
± FILLER
EXISTING15"NEW DOOR
NOTE:EXISTING WALL CABINET THAT OVERHANGSLOW WALL TO BE EXTENDED FULL HEIGHTTO BE MODIFIEDPROVIDE NEW FILLER IN FACE FRAMEOF CABINET. CUT AND FINISH EDGE OF EXISTINGOVERLAY DOOR TO MATCH EXISTINGAND RE-HANG DOOR
8" EXISTING GYPSUM BOARD CEILING
AND REPAIRED AS REQUIRED FORNEW PAINTED FINISH IN COLORTO BE SELECTED BY OWNER
AT 88" AFF TO BE PATCHED
BOTTOM OF EXISTING FLOOR JOISTSAT ± 96 1/2" AFF
21" (H) WALLCABINET
NEW POCKET DOOR AND TRIMTO MATCH EXISTING
8'-0"
EXISTING GYPSUM BOARD CEILINGTO REMAIN
EXISTING PARALLEL PARTITIONEXISTING 2" X 10" FLR JOISTS S-2.0
AEXISTING GYPSUM BOARD CEILINGREMAIN WITH NEW LAYER OFRESILIENT FURRING CHANNELS AND5/8" GYP BRD THROUGHOUTFIRST FLOOR
BWTEEWN 39" AND 42" MAX
NOTE:CONTRAOLS AND HANDHELD SHOWERHOSE 19" TO 27" FROM FOLDING SEATTHE HANDHEALD SHOWER HEAD SHALL
FIXED SHOWER HEAD ON THE
SINGLE LEVER SHOWER CONTROL LEVERLOCATED IN AREA SHOWN CROSS HATCHEDCENTERLINE OF LEVER TO BE LOCATED
HAVE A DIVERTER VALVE FROM THE
17"-
19"
15"
MIN
7"- 9"
18" TOWELBAR
48"
1/2" (MAX) BEVELEDTHRESHOLD
3'-6"± 1'-0 1/2"
VERIFY EXACTCLEAR DIM WITH
SURROUNDMFR
1/2" (MAX) BEVELEDTHRESHOLD
EXISTING PARALLEL PARTITIONEXISTING 2" X 10" FLR JOISTSS-2.0
A
1/2" (MAX) BEVELEDTHRESHOLD
EXISTING GYPSUM BOARD CEILINGTO REMAIN
EXISTIGN AND NEW GYP BRD SURFACESTO BE PRIMED AND PAINTED
NOTE:NO ELECTRICAL ROUGHINS TO BE LOCATEDIN FRAMING AREA OF DOOR POCKET
NEW COVE VINYL BASEALL AROUND
STANDARD FOXEDSHOWER HEAD
OPPOSITE WALL
8'-0
"
18"
NOTE:ALL TRIP LEVERS ON TOILETSTO BE LOCATED ON WIDE SIDE
NEW VINYL COVE BASE
GYP BRD SURFACES TO BEPRIMED AND PAINTED
ALL EXISTING AND / OR NEW
SCALE: 3/8" =1'-0"
BLOCKING FOR GRAB BAR PER CBC 11ABLKG FOR GRABBARS PER CBC 11A
BLKG FOR GRABBARS PER CBC 11A
PREFABRICATED SHOWER SURROUNDWITH NON-ABSORBANT FINISH AMIN OF 70" (H) PER CBC 807.13
BLKG FOR SEAT
BLKG FOR GRABBARS PER CBC 11A
18"
1'-0" NEW USG WALL-TO-WALL DRYWALL
SUSPENSION SYSTEMALLOWABLE SPAN FOR "TEE" SPACINGAT 16" OC UP TO 7'-6" REQUIRES NOSUPPORTS.SEE SPECIFICATION SHEET ONSHEET A1.5
1'-0"
SHOWER ROD
1/4"/1'-0" SLOPE-MAX.
SHOWER ROD
SHEET TITLE:
PROJECT LOCATION:
PROJECT NAME:
Copyright 2017 by Charles Pick, Architect and Basis Architecture & Consulting Inc.
GOLDENAPARTMENTS
CONVERSION OFTOWNHOMES TO FLAT
UNIT APARTMENTS
2312 N. GOLDEN AVE.SAN BERNARDINOCALIFORNIA 92404
APN: 0155-183-27-0000
DRAWING REVISION LOG
PLAN CHECK SUBMITTAL 12/12/17
Δ1 PLAN CHECK RESPONSE 03/30/18
POST-MOUNTED LIGHT
LED WALL PACK
PAVING IMPROVEMENTS
(N) CONCRETEANTICIPATED, V.I.F.
(N) GRADING
(E) WALL TO REMAIN
(E) WALL TO BE REMOVED
(N) INTERIOR PARTITION
(N) 1 HOUR RATED WALL
LEGEND
CHARLES PICK, ARCHITECT
6-2017
INTERIORELEVATIONS
A3.0
2 PLAN CHECK RESPONSE 5-3-2018
3 PLAN CHECK RESPONSE 5-17-2018
A OWNER REVISIONS 6-21-2018
A
SCALE: 1/4" = 1'-0"1 TYPICAL STAIR AT REMODELED SECOND FLOOR UNITS & COMMUNITY ROOM
34" T
O 38
"
3'-1"12'-10"14 EXISTING TREADS AT 11"
1'-2 1/2"
8'-0"
1'-1
1/4"
9'-1
1/4"
FIEL
D M
EASU
RED
DIM
ENSI
ON
TOTA
L EX
ISTI
NG R
ISE
15 E
QUAL
RIS
ERS
SCALE: 1/4" = 1'-0"2 TYPICAL STAIR AT REMODELED SECOND FLOOR UNITS & COMMUNITY ROOM
8'-0"
4'-6 1/2"
1'-1
1/4"
DIM
ENSI
ON 1"3'-0"5 1/2"
3'-6 1/2"
8'-0"
6'-2 1/4"
EXIS
TING
HEA
DROO
M (N
O CH
ANGE
)
EXIS
TING
3A5.0
EXISTING CEILING ON UNDERSIDEOF ROOF JOISTS TO REMAIN
EXISTING PARTITION TO REMAIN
NEW PARTITION CLOSES EXISTINGOPENING THRU FLOOR
NEW RESILIENTFURRING CHANNELSAND 5/8" GYP BRDON UNDERSIDE OFEXISTING CLG
EXISTING COMMON WALLTO REMAIN NO CHANGE
TOP OF EXISTING SECOND FLOOR
EXISTING PRECAST CONCRETE STAIRON STEEL STRINGERS TO REMAIN WITH NEWRISER BLOCKS
9'-1
1/4"
TOTA
L EX
ISTI
NG R
ISE
15 E
QUAL
RIS
ERS
SEE ROOF PLAN SHEET A0.3 FORALLOWANCE TO PATCH AND REPAIREXISTING ROOF MEMBRANE
EXISTING EXTERIOR STUCCO TO BEPAINTED. SEE SHEET A4.0 FORCOLOR LEGEND
UNDERSIDE OF EXISTING ROOFOVERHANGS TO BE PAINTEDAS REQUIRED
SEE ROOF PLAN SHEET A0.3 FORALLOWANCE TO PATCH AND REPAIREXISTING ROOF MEMBRANE
SEE ROOF PLAN SHEET A0.3 FORALLOWANCE TO REPAIR METALAS REQUIRED
UNDERSIDE OF EXISTING ROOFOVERHANGS TO BE PAINTEDAS REQUIRED
LINE OF EXISTING WING WALLTO REMAIN BEYOND
NEW FRAME AND DOOR IN EXISTINGROUGH OPENING
NEW WALL MOUNTED WOOD HANDRAIL WITH1 1/2" CLEAR DIMENSION FROM RAILING TOFACE OF WALL. SATIN NICKEL BRACKETS @
10
A5.1
TBD
A5.4
SEE DETAIL 10 SHEET A5.4 FOR NEWRISER BLOCKS
2
A3.2
EXISTING BEARING WALL SHOWNSHADED
NEW
RAI
LING
34" -
38"
ABOV
E ST
AIR
NOSI
NG
O.C. MAX MOUNTED TO STUDSSHEET TITLE:
PROJECT LOCATION:
PROJECT NAME:
Copyright 2017 by Charles Pick, Architect and Basis Architecture & Consulting Inc.
EXISTING GYPSUM BOARD TO REMAIN.PATCH AND REPAIR TO LIKE NEW CONDITION.MATCH EXISTING TEXTURING (IF ANY) IN ALL NEWPATCHING.
NEW INSULATION AS REQUIRED IN STUD CAVITIESFOR ALL OPENINGS TO BE INFILLED
INFILL OPINING WITH NEW FRAMING ASREQUIRED
EXISTING 2" X 4" WOOD FRAMING
EXISTING EXTERIOR STUCCO, WATER RESISTANTBARRIER AND UNDERLAYMENT
INTERIOREXTERIOR
1 HOUR FIRE RATING FOR LOAD OR NON-LOAD BEARINGBASED UPON IBC TABLE 720.1 (2), ITEM 15-1.3
STC 33
INSULATION
INFILL INTERIOR AND EXTERIOR WITH NEW TOMATCH EXISTING
± IN
FILL
OPE
NIN
G
DETAIL PLAN OF NEW EXTERIOR DOORSSCALE: 3/4" =1'-0"
12
1 HOUR RATED WITH STC 38SCALE: 3/4" =1'-0"
2 EXISTING CONCRETE FLOOR SLAB ON GRADE
VARIES
NOTE:
EXISTING CONCRETESLAB O GRADE OVERCOMPACTED BASE
CONTRACTOR TO PROVIDE ALLNECESSARY CUTTING, MATERIALREMOVAL, TRENCHING AND PATCHING AS REQUIRED FOR NEWROUTING AND PLUMBING CONNECTIONS BELOW TOP OFEXISTING SLAB
PER CBC 1207.61 ALLNOTE:
FLLOR/CEILING ASSEMBLIESSEPARATING DWELLING UNITSREQUIRE A 1 HR FIRE SEPARATION
NOTE:PER CBC 707.1 ALL ANNULARSPACE AROUND ANY PENETRATINGITEM SHALL BE FIRE-STOPPED
NEW PENETRATING ITEM
EXIS
TIN
G
EXISTING GYP BRD CEILING
NEW RC-1 RESILIENT CHANNELSPERPENDICULAR TO SPAN OFJOIST AT 24" OC
NEW LAYER 5/8" TYPE X GYPSUMBOARD WITH JOINTS TAPED ANDSANDED READY FOR PRIMER ANDPAINT
EXISTING ROOF JOISTS
ROOF SHEATHING
NOTES:
PER CALIFORNIA CODE OF REGULATIONSTITLE8, SECTION 3235 (b) A EXITDOOR SHALL BE NOT LESS THAN 3'-0"IN WIDTH AND 6'-8" HIGH.
PER 3214 (1) STAIRS LESS THAN 44MAY HAVE ONE HANDRAIL.
PER 3213 (B) (1) STAIRWAYS SERVING ANOCCUPANT LOAD OF LESS THAN 50 MAYBE 36" WIDE.
ALL ACCESSIBLE SPACE UNDER EXISTING OF NEW STAIRS USED ASA REQUIRED EXITWAY SHALL HAVEWALLS, OR UNDERSTAIR SURFACESPROTECTED WITH 5/8" TYPE X GYPSUMBOARD
3'-1" 11"
EXISTING EXISTINGTREADS
3'-0
"1"
9"3'
-0"
4'-6 1/2" 2'-3 1/2"
FIRST FLOOR CEILING AT 8'-0" AFF FIRST FLOOR CEILINGSLOPES UP
OPENING THRUFLOOR ABOVE
3'-6
1/2
"
WID
TH O
F EX
ISTI
NG
OPE
NIN
GTH
RU F
LOO
R AB
OVE
1/2"
FRO
M E
XIST
ING
OPE
NIN
GTO
FAC
E O
F N
EW W
ALL
BELO
W
NEW
1 H
R PA
RTIT
ION
SEE
DETA
IL T
HIS
SH
EET
1'-8
"
3"
3'-0"
± 10
1 8"
3'-0
"±
10"
4'-0
"
± 7'
-10"
EXIS
TIN
G R
OU
GH
OPE
NIN
G F
OR
EXIS
TIN
GW
INDO
W T
O B
E RE
MO
VE
NEW
WIN
DOW
NEW
DO
OR
WALL TYPE 7
WALL TYPE 6
SCALE: 3/4" =1'-0"5 POCKET DOOR FOR 2" X 4" WALL
NEW LAYER 1/2" GYPSUM BOARD EACH
NEW 2" X 4" WOOD STUDS AT 16" OC
FINISHED FACE
SEE DOOR SCHEDULE FOR DEPTH OF POCKETREQUIRED FOR NEW DOOR,, AND PLAN FOR LOCATIONOF POCKET WITH RESPECT TO OPENING
NOTE:SLIDING DOOR HARDWARE TO BE ACCOMMODATEDIN WALL TO BE BY JOHNSON HARDWARE
3 1/2"
(OR EQUAL) 2511 SERIES POCKET DOOR FRAMEKIT FOR 2" X 4" WALL
± 3'
-0"
POCK
ET
INTERIOR PARTITION (1 HR RATED)SCALE: 3/4" =1'-0"
6 TYPICAL NEW NON-BEARING STAIR
NEW 1/2" TYPE "X" GYPSUM BOARD TO BETAPED AND SANDED (TEXTURED IF NEEDED TO MATCHEXISTING ADJACENT).
NEW 2" X 4" WOOD FRAMING AT 16" OC WITHDOUBLE TOP PLATES AND SILL PLATES IN CONTACTWITH CONCRETE TO BE PRESSURE TREATED
ALL NEW GYPSUM BOARD TO BE PRIMED AND PAINTEDIN STANDARD COLOR TO BE SELECTED BY OWNER
1 HOUR FIRE RATING FOR LOAD OR NON-LOAD BEARINGUL DESIGN NUMBER U305
BASED UPON
INSIDE FACE OF NEW GYP BRD TO ALIGNWITH FACE OF EXISTING STAIR OPENINGTHRU WALL ABOVE
NEW FURRING STRIPS CUT TO DIMENSION REQUIREDFOR ENCLOSING EXISTING STAIR WITH RESPECT TOEXISTING OPENING THRU FLOOR
WALL TYPE 9
WALL TYPE 9 SIMILARFOR NEW WALL
MISCELLANEOUS NEW HEADER OR LOOSE LINTELS1 FOR OPENINGS IN BEARING OR NON-BEARING WALLS
UP TO 4'-0" USE 4" X 8" (OR 2 - 2" X 8" WITH 1/2" PLYWOODFLITCH PLATE) BEARING ON A MINIMUM OF 2 -2" X 4"WOOD STUD EACH END
2 FOR OPENINGS IN BEARING OR NON-BEARING WALLSFROM 4'-1" TO 6'-0" USE 4" X 10" (OR 2 - 2" X 10" WITH 1/2" PLYWOODFLITCH PLATE) BEARING ON A MINIMUM OF 2 -2" X 4"WOOD STUD EACH END
SEE
NO
TES
FOR
NEW
LIN
TELS
INDUSTRY STANDARD PTAC AIR CONDITIONER WALL SLEEVE(DIMENSIONS 42" (W) X 14 1/8" (D) X 16 1/16" (H)SHOWN IN HIDDEN LINESTYLE
± REMOVE TEXTURINGTO MIN EXTENT REQUIREDTO FASTEN FURRINGCHANNEL LEG TO UNIFORM SURFACE
1/2" GYPSUM BOARD TO BE TO BE TAPEDAND SANDED (TEXTURED IF NEEDED TO MATCHEXISTING ADJACENT) ON FINISHED FACE
NEW 2" X 4" WOOD FRAMING AT 16" OC
ALL NEW GYPSUM BOARD TO BE PRIMED AND PAINTEDIN STANDARD COLOR TO BE SELECTED BY OWNER
RAISED FLOOR IN EXISTING DINING ROOMSCALE: 3/4" =1'-0"
14
TOP OF EXISTING SLAB IN KITCHEN
3/4" T + G PLYWOOD GLUED AND SCREWED TO
± 5"
2" X 4" JOISTS AT 16" OC ON PRESSURE TREATEDSHIMS FOR A SMOOTH TRANSITION BETWEENEXISTING AND NEW
TOP OF DINING ROOM SLAB
NOTE: DROPPED CEILING SIMILAR (INFILL FLOOR SIMILAR)
WALLDETAILS
A5.0
SHEET TITLE:
PROJECT LOCATION:
PROJECT NAME:
Copyright 2017 by Charles Pick, Architect and Basis Architecture & Consulting Inc.
GOLDENAPARTMENTS
CONVERSION OFTOWNHOMES TO FLAT
UNIT APARTMENTS
2312 N. GOLDEN AVE.SAN BERNARDINOCALIFORNIA 92404
APN: 0155-183-27-0000
DRAWING REVISION LOG
PLAN CHECK SUBMITTAL 12/12/17
Δ1 PLAN CHECK RESPONSE 03/30/18
POST-MOUNTED LIGHT
LED WALL PACK
PAVING IMPROVEMENTS
(N) CONCRETEANTICIPATED, V.I.F.
(N) GRADING
(E) WALL TO REMAIN
(E) WALL TO BE REMOVED
(N) INTERIOR PARTITION
(N) 1 HOUR RATED WALL
LEGEND
CHARLES PICK, ARCHITECT
6-2017
2 PLAN CHECK RESPONSE 5-3-2018
3 PLAN CHECK RESPONSE 5-17-2018
A OWNER REVISIONS 6-21-2018
A
WALKING SURFACE.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REINSTALLING ALL WINDOW COVERINGS TO ALLOW FOR NEW WORK.THE CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING ALL TENANT'S FURNITURE A MINIMUM OF 5' IN EVERY DIRECTION FROM THE WORK AREA
THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROJECTION OF THE EXISTING FINISHES ANDTHE TENANT'S FURNISHINGS.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR CLEANING REFUSE REMOVAL AND THE END OF EACHWORK DAY.
2
3
4
WINDOW NOTES - CONTRACTOR TO NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO WINDOW ORDERIN ADDITION TO REQUIRED MEANS OF EGRESS ALL EXISTING SLEEPING ROOMS HAVE ONE EMERGENCY EGRESSWINDOW WITH A MINIMUM CLEAR OPENING OF 5.7 SQUARE FEET (EXCEPT THE MINIMUM NET CLEAROPENING FOR EMERGENCY ESCAPE AND RESCUE GRADE FLOOR OPENINGS COULD BE 5 SQUARE FEET).
THE MINIMUM NET CLEAR OPENING DIMENSIONS ARE GREATER THAN 24 INCHES (H) AND 20 INCHES (W). THE NETCLEAR OPENING DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF THE OPENING.
THE MAXIMUM HEIGHT FROM THE FLOOR FOR EMERGENCY EGRESS WINDOWS IS NOT GREATER THAN44 INCHES.ALL WINDOWS IN THE DWELLING UNITS ABOVE THOSE AT GRADE SHALL BE EQUIPPED WITH A CHILDPROOFLATCH THAT WILL NOT ALLOW THE WINDOW TO BE OPENED MORE THAN 4 INCHES.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL EXISTING ROUGH OPENINGS DIMENSIONS FORNEW REPLACEMENT WINDOWS IN EXISTING OPENINGS AND MAKE ALL NECESSARY ADJUSTMENTS FOR THEFIELD VERIFIED DIMENSIONS IN THE SHOP DRAWING SUBMITTAL REQUIRED FOR REPLACEMENT WINDOWS.
WINDOW GLAZING IN HAZARDOUS LOCATIONS REQUIRE SAFETY GLAZING MATERIALS, EITHER TEMPEREDGLASS OR LAMINATED SAFETY GLASS. WIRED GLASS IS NOT PERMITTED.
GLAZING NOTESTHE FOLLOWING ARE CONSIDERED HAZARDOUS LOCATIONS REQUIRING SAFETY GLAZING:
GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT TO A DOOR WHERE THE NEAREST EXPOSEDEDGE OF THE GLAZING IS WITHIN A 24 INCH ARC OF EITHER VERTICAL EDGE OF THE DOOR IN A CLOSEDPOSITION AND WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS THAN 60 INCHES ABOVE THE
1
3
4
1
2
WINDOW DEMOLITION NOTES
1
CONTRACTOR PRIOR TO WINDOW ORDER TO PROVIDE FIXED PANEL LOCATIONS AS REQ'D FOR CONFORMING VENTINGCLEARANCES AT RELOCATED GAS METERS & NEW HOT WATER HEATER LOCATIONS.
5
DOOR SCHEDULE
DOOR SIZE DOORTYPE
HARDWAREFUNCTION NOTES
1
WINDOW SCHEDULE
OPERATIONWINDOWS DIMENSIONSCONTRACTOR TO VIF
GLAZING
CONTRACTOR TO VIF ALL SIZES FOR NEW DOORS IN EXISTING ROUGH OPENINGS
LOCATION
NOTES
W1
*
CONTRACTOR TO VIF ALL SIZES & REPLACEMENTS(R) = REPLACE EXISTING(N) = NEW
2
ALL NEW WINDOWS TO BE MILGARD STYLINE. SEE SPECIFICATIONS.
SCALE: 1 /4" = 1'-0"
5
OPENING
4
6'-8
"
WINDOW TYPES
6'-8
"
3'-0"
6'-8
"
3'-0"
AND FRAME IN EXISTINGNEW UNIT ENTRY DOOR
SEE PLAN FOR HAND OFALL DOORS
DOOR VIEWER AT 48"
SEE PLAN FOR HAND OFALL DOORS
6'-8
"DOOR VIEWER AT 48"
NEW DOOR AND FRAMEWITH CASING TRIM TOMATCH EXISTING
1
ON INTERIOR FACE
4
6'-8
"
3'-0"
6'-8
"
SEE PLAN FOR HAND OFALL DOORS
3
NEW DOOR AND FRAMEWITH CASING TRIM TOMATCH EXISTING
SEE SPECS FOR HARDWAREINCLUDING LATCH FUNCTION
6'-8
"6'
-8"
6
#
UNIT 3'-0" X 6'-8" X 1 3/4"DOOR AND FRAME IN EXISTING OPENING
HINGED ENTRY FURNISH WITH ADA CONFORMING LEVERHARDWARE, THRESHOLD AND DOOR VIEWERENTRY
OUT-SWING
3'-0" X 6'-8" X 1 3/8"DOOR AND FRAME INNEW OPENING
HINGED PASSAGE FURNISH WITH ADA CONFORMING LEVERHARDWARE, AND ROBE HOOK ON INTERIOR
TYPICALUNITBATHROOM FACE
DOOR TYPESSCALE: 1 /4" = 1'-0"
REPLACEMENT WINDOW
± 4'-0" X 6'-8" SLIDINGDOOR OPENING
FIXED/SLIDER DUAL
W1
WITH LOW EGLASS
CONTRACTOR TO VERIFY
GLAZEDFIRSTFLOOR
W2 REPLACEMENT WINDOWIN ± 4'-0" X 4'-6" ROUGHOPENING
FIXED/SLIDER DUAL
WITH LOW EGLAZED
NOTES:
W3 REPLACEMENT WINDOW
OPENING
FIXED/SLIDER DUAL
WITH LOW EGLAZED
W4 REPLACEMENT WINDOWIN ± 3'-0" X 4'-0" EXISTINGOPENING
FIXED/SLIDER DUAL
WITH LOW EGLAZED
CONTRACTOR TO VERIFY EXACT ROUGH OPENINGS AND PORTION TO BE INFILLED
EXISTING ROUGH OPENING WITH
GROUND FLOOR
BEDROOM DOOR (NEW)3
6'-3
"6'
-3"
3'-0
"
± 8'-0"
EXISTINGVIF
W2
REPLACEMENT WIDOWIN REWORKED ROUGHOPENING.
EXACT EXISTING OPENINGDIMENSIONS IN FIELD
GROUND FLOOR
INFILL PORTION OF WALLCONSTRUCTION WHERE EXISTINGSLIDING GLASS DOOR IS REMOVED
NOTE:
MATCH EXISTING
NEW OUT-SWING ENTRY DOOR IN
LOCKED HINGES
NOTE:
WEATHERSTRIP OPENING
ADA COMPLIANT THRESHOLD
6'-8
"
3'-0"
6'-8
"
NEW UNIT ENTRY DOORAND FRAME IN EXISTINGOPENING
DOOR VIEWER AT 48"
SEE PLAN FOR HAND OFALL DOORS
2 NEW ENTRY DOOR IN NEW ROUGH OPENINGIN-SWING
NOTE:
WEATHERSTRIP OPENING
ADA COMPLIANT THRESHOLD
NEW 1 3/8" ACCESSIBLEBATHROOM DOOR
NOTE:
6'-8
"
1'-6"
6'-8
"
NEW DOOR AND FRAMEWITH CASING TRIM TO
SEE PLAN FOR HAND OFALL DOORS
5
SEE SPECS FOR HARDWARE
CLOSET DOOR
INCLUDING LATCH FUNCTION
NOTE:
CLOSET DOOR
6'-8
"6'
-8"
7
NEW SLIDING DOORSIN CASED GYPSUMBOARD OPENING
8'-0"
CLOSET DOORS
6'-8
"
3'-0"
6'-8
" 3" (MIN H) CONTRASTINGOFFICE LOCKSET
SEE PLAN FOR HAND OFALL DOORS
8
ON INTERIOR FACE
NEW DOOR AND FRAMEWITH CASING TRIM TOMATCH EXISTING
NEW ACCESSIBLEOFFICE DOOR
NOTE:
6'-8
"
3'-0"
6'-8
"
KICKPLATE BOTH FACES
9
ON INTERIOR FACE
NEW DOOR AND FRAMEWITH CASING TRIM TOMATCH EXISTING
EXTERIOR IN-SWINGFIRE PROTECTION ROOM
6CLOSET
7SLIDING DOORS IN8'-0" X 6'-8" CASED
SLIDING - -CLOSET
83'-0" X 6'-8 X 1 3/8" HINGED OFFICE -COMMUNITY
NOTE
9HINGED VERIFYFIRE
SPRINKLER
1
PATCH AND REPAIR ALL STUCCO AS REQUIRED FOR NEW DOORS IN EXISTING OR NEW ROUGH OPENINGS2
3'-0" X 6'-8" X 1 3/4"DOOR AND FRAME IN NEW OPENING
UNIT 3'-0" X 6'-8" X 1 3/4"DOOR AND FRAME IN NEW OPENING
ENTRY FURNISH WITH ADA CONFORMING LEVERHARDWARE, THRESHOLD AND DOOR VIEWERENTRY
IN-SWING
NOTE:FOR SINGLE USER TOILET ROOM DOORS INCOMMUNITY ROOM PROVIDE CLOSER AND PRIVACYLOCKSET
CLOSET 1'-6" X 6'-8" X 1 3/8"DOOR AND FRAME INNEW OPENING
HINGED PASSAGE
3'-0" X 6'-8" X 1 3/8"DOOR AND FRAME INNEW OPENING
HINGED PASSAGEBEDROOM
GYP BRD OPENING
ROOMOFFICE
DOOR AND FRAME IN NEW OPENING
5"
6'-8
"
FLOOR IN EXISTING DININGROOM TO BE RAISED ± 5" TOALIGN FOR A SMOOTH TRANSITIONTO EXISTING ADJACENT FLOORHEIGHT
4'-6
"
± 4'-0"
6'-8
"
2'-2
"
W3 GROUND FLOOR
4'-6
"
± 3'-0"
6'-8
"
2'-2
"
W4 LAUNDRY
± 3'
-0"
± 4'-0"
EXIS
TIN
GVI
F
6'-8
"
3'-8
"
EXIS
TVI
F
LOCATION
IN ± 3'-0" X 4'-8" ROUGH
FIRSTFLOOR
FIRSTFLOOR
LAUNDRY
LIGHT
VENT
14.0 SF
7.0 SF
LIGHT
VENT
14.8 SF
7.4 SF
LIGHT
VENT
10.6 SF
5.3 SF
LIGHT
VENT
9.4 SF
4.7 SF
INFILL PORTION OF WALLCONSTRUCTION WHEREWINDOW IS REMOVED
NO WORK SHALL PROCEED WITHOUT PRIOR REVIEW AND APPROVAL OF SHOP DRAWING SUBMITTAL
NEW PTAC UNITSTHE NEW OPENINGS THRU THE EXISTING EXTERIOR WALLS FOR THE SLEEVE AND PTAC UNITARE TO BE VERIFIED WIT RESPECT TO THE EXISTING SILL HEIGHT WITH A SHOP DRAWINGSUBMITTAL FOR REVIEW AND APPROVAL.
1
FOR THESE OPENINGS
10
10
6'-8
"
2'-6"
6'-8
"
11
EXISTING DOOR AND FRAMEFRAME
LOUVER
BEDROOM DOOR
6'-8
"6'
-8"
2'-6"
6'-8
"
12
NEW DOOR AND FRAMEFRAME
BEDROOM DOOR
SEE PLAN FOR HAND OFALL DOORS
NOTE:
SEE PLAN FOR HAND OFALL DOORS
NOTE:
11EXISTING DOOR HINGED PASSAGE
BEDROOM
122'-6" X 6'-8" X 1 3/8"DOOR AND FRAME INNEW OPENING
HINGED PASSAGEBEDROOM
6'-8
"6'
-8"
2'-6"
6'-8
"
13
NEW 1 3/4" (1 HR RATED) DOOR IN FULLY RABBETED FRAME
STOREROOM LOCK FUNCTION
1 HR RATED ACCESS DOOR
SEE PLAN FOR HAND OFALL DOORS
NOTE:
13NOT USED
THRU WALL SLEEVE FORPTAC UNITDIMENSIONS42" (W) X 14 1/8" (D) X 16 1/6" (H)
5 1/
2"
1'-4
"
THRU WALL FANSEE MECHANICAL
2'-6"
1'-4
"
THRU WALL FANSEE MECHANICAL
LAUNDRY
AND FRAME
± 6'-0" ±
WINDOW ABOVE
ALIGN NEW WINDOWWITH EXISTING ABOVE
3'-0" X 6'-0'IN EXISTING TO ALIGN WITH EXISTING WINDOW ABOVE
6'-8
"
3'-0" X 6'-8" X 1 3/4" HINGED
3'-0"
6'-8
"
THE SWEEP PERIOD OF THE CLOSER SHALL BE ADJUSTED
STORAGE
SO THAT FROM AN OPEN POSITION OF 70 DEGREES
KICKPLATE BOTH FACESON INTERIOR FACE
NEW DOOR AND FRAMEWITH CASING TRIM TOMATCH EXISTING
LAMINATED SAFETY GLASS
EXTERIOR IN-SWINGLAUNDRY ROOM DOOR
NOTE: OVERHEAD DOORCLOSER TO BE PROVIDED ON INTERIOR
DOOR AND FRAME IN EXISTING OPENING
VERIFY
NOTE:THE DOOR CLOSER TO COMPLY WITH ADA 4.13.10 SO THAT
A POINT 3 INCHES FROM THE LATCH, MEASURED TO THE THE DOOR SHALL TAKE AT LEAT 3 SECONDS TO MOVE TO
SEE NOTE ON COMPLIANCE REQUIREMENTS
THE OPERABLE PORTION OF THE WINDOWS IS TO BE PROTECTED
LEADING EDGE OF THE DOOR
FOR CLOSER
WITH INSECT SCREENS
FIRE RISER INSIDE
LETTERS AT 5'-0" AFFON OUTSIDE FACE
ROOM
VERIFY KEYING REQUIREMENTS WITHSAN BERNARDINO COUNTY FIRE DEPT
# UNIT ENTRY DOORS SIGNAGE
100
5'-0
"
EXTERIOR FACE
ADA COMPLIANT UNITENTRY SIGNAGE2" (H) FONT + BRAILLE
NOTE:A SHOP DRAWING SUBMITTALTO SIGNAGE IS REQUIRED FORREVIEW AND APPROVAL
6'-8
"
3'-0"
6'-8
"
SEE PLAN FOR HAND OFALL DOORS
14
NEW POCKET DOOR AND FRAMEWITH CASING TRIM TOMATCH EXISTING
NEW 1 3/8" ACCESSIBLEBATHROOM DOOR
NOTE:
POCKET
14ACCESSIBLEUNITBATHROOM
3'-0" X 6'-8" X 1 3/8"DOOR AND FRAME INNEW OPENING
POCKET PASSAGE FURNISH WITH ADA CONFORMING PULL
15
6'-8
"6'
-8"
2'-6"
CLOSET DOORS
2'-6"
NEW SLIDING DOORSIN CASED GYPSUMBOARD OPENING
15SLIDING DOORS IN5'-0" X 6'-8" CASED
SLIDING - -CLOSET
GYP BRD OPENING
6'-8
"
2'-0"
6'-8
"
NEW DOOR AND FRAMEWITH CASING TRIM TOMATCH EXISTING
SEE PLAN FOR HAND OFALL DOORS
SEE SPECS FOR HARDWAREINCLUDING LATCH FUNCTION
NOTE:
2'-0" X 6'-8" X 1 3/8"DOOR AND FRAME INNEW OPENING
HINGED PASSAGE
TEMPERED
SIGN TO READ:MAINTENANCEACCESS ONLY
INSULATEDFIBERGLASS
HINGEDINSULATEDFIBERGLASS
MASONITE
MASONITE
MASONITE
MASONITE
MASONITE
MASONITE
MASONITE
MASONITE
MASONITE
INSULATEDFIBERGLASS
INSULATEDFIBERGLASS
MASONITE
W5 SERVICE PROVIDERS
4'-0
"
± 3'-6"
6'-8
"
2'-8
"
INFILL PORTION OF WALLCONSTRUCTION WHEREWINDOW IS REMOVED
PTAC UNDER
5 1/
2"
5" FLOOR IN EXISTING DININGROOM TO BE RAISED ± 5" TOALIGN FOR A SMOOTH TRANSITIONTO EXISTING ADJACENT FLOORHEIGHT
OFFICE
W5 NEW WINDOW IN ± (N) 3'-6" X 4'-0" OPENING
SLIDER DUAL
WITH LOW EGLAZED
SERVICE LIGHT
VENT
9.68 SF
5.21 SFPROVIDERSOFFICE
WINDOW AND DOORSCHEDULES
A6.0
SHEET TITLE:
PROJECT LOCATION:
PROJECT NAME:
Copyright 2017 by Charles Pick, Architect and Basis Architecture & Consulting Inc.