Top Banner
Generator Set Transient Response How good should it be? How good is good enough?
15

Generator Set Transient Performance

Jan 14, 2017

Download

Engineering

michaeljmack
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Generator Set Transient Performance

Generator Set Transient Response

How good should it be?How good is good enough?

Page 2: Generator Set Transient Performance

Transient Performance

GenSet Performance

� Voltage Level is More Consistent than Utility

� Frequency Control is Poor Relative to Utility

� Load Changes Result in Frequency & Voltage Change

AVR

GOV MPU

ACTPWR EXC

ENGINE

Page 3: Generator Set Transient Performance

Transient Performance

The Energy Transfer Process

������������������

��

������� ���� ���� ��������

� Engine Provides HP to Rotate Alternator� Alternator “Converts” Mechanical to Electrical Energy� Motor “Re-converts” Electrical to Mechanical Energy to Rotate

Load� To start the motor (or any other load), engine must provide

HP(k/W)/torque needed, and alternator must provide Vars

Page 4: Generator Set Transient Performance

Transient Performance

GenSet Transient Performance

� Engine slows and voltage drops until fuel rate and/or excitation level increases– Governor and AVR can’t

predict change in load, so,

– Load change = V, Hz change

� Magnitude of changes depend on:– Size of load relative to

genset– How fast fuel rate and

excitation can be changed– AVR V/Hz function

AVR

ECMGOV

MPU

Fuel toEngine PWR to LOADS

EXC

ENGINE

Page 5: Generator Set Transient Performance

Transient Performance

What Does the Load Need?

� Resistive Loads– Sufficient kW to pick up load and recover speed

� Motor Starting:– Initial voltage dip not more than 35% (less is better)– Voltage recovery during acceleration (min. 90% per NEMA)

• Provides torque necessary to accelerate load

– Sufficient kW to operate load

� UPS– Will drop out on any nearly transient condition

• Typically depends on voltage range (± 10%), frequency range (± 3 Hz), AND slew rate (0.5 – 1.0 Hz/sec)

Page 6: Generator Set Transient Performance

Transient Performance

NFPA 110 Prototype Test Report

� Report documents compliance to NFPA 110 for Emergency power systems

� NFPA 110 compliance requires 0.8 PF test and allows 1.0 in field

� NFPA 110 has no performance requirements other than to recover

� 480V machine

Page 7: Generator Set Transient Performance

Transient Performance

What’s the voltage dip?

� 18%, right?

� Nope! This is alternator only!

VOLTAGE ROLLOFF

0

20

40

60

80

100

120

45 50 55 60 65

FREQUENCY%

VO

LTA

GE

Page 8: Generator Set Transient Performance

Transient Performance

Genset Database Development

Page 9: Generator Set Transient Performance

Transient Performance

Frequency Recovery

Page 10: Generator Set Transient Performance

Transient Performance

Voltage Recovery

Page 11: Generator Set Transient Performance

Transient Performance

160 VAC

4.2 Hz

� Figure 3: 2000kW generator set with 2000kW 0.8 power factor load applied. 33% voltage dip,

215 VAC

8.4 Hz

� Figure 4: Same generator set as Figure 3, but with 1.0 power factor load. 45% voltage dip.

Page 12: Generator Set Transient Performance

Transient Performance

Engine Fueling and Speed during TransientLOAD APPLIED

FUELLIMITED

STABLE ATFULL LOAD

� Engine begins to respond to speed change within 20 mS.

� Stable recovery ~4 sec

� Limited by turbo lag (ability to get air into engine)

Page 13: Generator Set Transient Performance

Transient Performance

Alternator Response Capability

� It takes time to build voltage in a machine after load is applied.

Page 14: Generator Set Transient Performance

Transient Performance

Slew Rate

� Typical allowable slew rates are very low relative to genset capability

� Genset frequency slew rated depends on load magnitude� Any load step may cause bypass to drop out or rectifier to switch

off� Most UPS ramps on: good for genset and system performance

4.2 Hz

0.5 Hz/Sec

Page 15: Generator Set Transient Performance

Transient Performance

Summary and Conclusions

� Performance of a genset depends on inertia in genset, energy stored in field (indicated by X”d), AVR performance, and engine fuel/air induction system performance

� There is some variation from machine to machine� Follow NFPA110 level 1: full load test at rated load and power

factor to demonstrate recovery; spec X”d; spec digital AVR and recovery kVA (to 90% voltage); spec voltage dip and recovery at 0.8 PF (and 1.0PF if desired to test in field)

� Best practice is to factory test gensets at 0.8PF and 1.0PF, and request strip chart recordings of performance at 25%, 50%, 75% and 100% on and off load tests.

� Test gensets at site with 1.0PF testing at the jobsite to verifyinstallation capability.