GENERAL NOTES 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. ALL WORK SHALL CONFORM TO ALL APPLICABLE BUILDING CODES AND ALL STATE AND LOCAL AMENDMENTS. GENERAL NOTES, SYMBOLS LIST AND DETAILS ARE APPLICABLE TO ALL PLUMBING DRAWINGS. REFER TO ARCHITECTURAL PLANS FOR GENERAL CONSTRUCTION NOTES. DRAWINGS ARE DIAGRAMMATIC: THE CONTRACTOR SHALL DETERMINE LOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD, OFF OF ARCHITECTURAL AND STRUCTURAL PLANS. THE PLUMBING CONTRACTOR SHALL DETERMINE EXACT LOCATIONS OF EXISTING UTILITIES IN FIELD, WHETHER OR NOT SHOWN ON THE DRAWINGS. EXERCISE CAUTION AND IDENTIFY LOCATIONS OF UNMARKED UTILITY LINES AS NECESSARY TO PERFORM THIS WORK. THE PLUMBING CONTRACTOR SHALL PREPARE “SLEEVE AND INSERT” COORDINATION PLANS (LOCATING ALL ROOF, FLOOR AND WALL PENETRATIONS) AND SUBMIT TO ARCHITECT FOR REVIEW. EACH PENETRATION SHALL BE LOCATED WITH A MINIMUM OF (2) DIMENSIONS IN (2) DIRECTIONS. THE PLUMBING CONTRACTOR SHALL PREPARE “COORDINATION” DRAWNGS THAT COORDINATE THE PLUMBING WORK WITH ALL OTHER TRADES INCLUDING, BUT NOT LIMITED TO, ELECTRICAL, HVAC, PROCESS PIPING, SPRINKLER, STRUCTURAL AND GENERAL ARCHTIECTURE. ANY INTERFERENCE BETWEEN TRADES SHALL BE BROUGHT TO THE ATTENTION OF THE GENERAL CONTRACTOR/OWNER’S REPRESENTATIVE, AND SHALL BE RESOLVED PRIOR TO THE INSTALLATION OF THE WORK. ALL PIPE SLEEVES IN FLOORS SHALL EXTEND A MINIMUM OF TWO INCHES (2”) ABOVE THE FINISHED FLOOR UNLESS NOTED OTHERWISE. FILL ANNULAR SPACE WITH WATERPROOF, FIRE RETARDANT CAULKING PENETRATIONS. All PIPING PENETRATING CEILINGS AND WALLS SHALL BE INSTALLED WITH ESCUTCHEONS AT THE PENETRATION. ALL PIPING PENETRATING EXTERIOR WALLS AND ROOFS SHALL BE FLASHED IN AN APPROVED MANNER AND SHALL BE SEALED WEATHERTIGHT. PIPING PENETRATING FIRE RATED ASSEMBLIES SHALL BE PROVIDED WITH FIRE RATED SEALS AS REQUIRED BY CODE AUTHORITY HAVING JURISDICTION. TOPS OF ALL FLOOR DRAINS SHALL BE SET LEVEL AND FLUSH WITH FINISHED FLOOR. ALL PIPING ABOVE GRADE SHALL BE PROPERLY SUPPORTED BY THE BUILDING STRUCTURE AND SHALL NOT REST ON CEILING STRUCTURE OR COMPONENTS. ALL PLUMBING EQUIPMENT, PIPING, INSULATION, ETC., INSTALLED IN HVAC PLENUM SPACES SHALL MEET ALL CODE REQUIREMENTS FOR SMOKE AND COMBUSTIBILITY, PER ASTM E-84. THE PLUMBING CONTRACTOR SHALL PROVIDE SHUTOFF VALVES ON ALL BRACH PIPING AND ON ALL SUPPLIES TO INDIVIDUAL FIXTURES AND EQUIPMENT. PROVIDE FULL PORT BALL VALVES ON ALL WATER MAIN BRANCHES IN CORRIDORS AND WHERE INDICATED ON DRAWINGS. THE PLUMBING CONTRACTOR SHALL OBTAIN APPROVAL FROM THE STRUCTURAL ENGINEER PRIOR TO INSTALLING POWDER DRIVEN FASTENERS. COORDINATE ALL POST TENSIONED SLAB PENETRATIONS WITH STRUCTURAL ENGINEER. PROVIDE CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS NECESSARY TO PREVENT STRESS ON PIPING. PROVIDE MANUFACTURED EXPANSION DEVICE OR FABRICATED EXPANSION LOOP ON ALL PIPING SYSTEMS CROSSING BUILDING EXPANSION JOINTS. ALL PIPE HANGERS ON INSULATED PIPING SHALL BE PROVIDED WITH HANGER SHIELDS. ALL VALVES, CLEANOUTS AND COMPONENTS REQUIRING ACCESS BEHIND WALLS OR INACCESSIBLE CEILING SHALL BE PROVIDED WITH ACCESS PANELS. COORDINATE WITH ARCHITECT FOR REQUIRED TYPE, LOCATION, AND FINISH. ALL P-TRAPS INSTALLED IN SPACES SUBJECT TO FREEZING SHALL BE INSULATED AND HEAT TRACED. TRAP PRIMERS ARE TO BE PROVIDED ON ALL FLOOR DRAINS AND HUB DRAINS WHICH DO NOT RECEIVE A CONTINUOUS DISCHARGE. REFER TO DRAINAGE DEVICE SCHEDULE AND FLOOR PLANS FOR TYPE AND MANUFACTURER. PROVIDE VENTS AT HIGH POINTS IN PIPING SYSTEMS AND DRAIN VALVES AT LOW POINTS. PROVIDE GAUGE FITTINGS AND THERMOMETER WELLS AT HOT WATER SUPPLY AND RETURN BRANCHES AND AT PUMP INLETS AND OUTLETS. SANITARY VENTS THROUGH THE ROOF MUST TERMINATE A MINIMUM OF 25 FEET AWAY FROM OUTSIDE AIR INTAKES, WHICH PROVIDE VENTILATION OR MAKE-UP AIR TO THE BUILDING. COORDINATE PROVISION FOR PROTECTING PIPING BENEATH HANDICAP LAVATORIES REQUIRED AND IDENTIFIED WITH TOILET ACCESSORIES. PLUMBING FIXTURES FOR “ADA” COMPLIANCE SHALL BE INSTALLED WITH THE HORIZONTAL AND VERTICAL CLEARANCES OUTLINED IN THE “AMERICANS WITH DISABILITIES ACT”. REFER TO ARCHITECTURAL PLANS FOR ELEVATIONS OF TOILET ROOMS. ALL WATER CLOSETS OR URINALS SHALL BE CENTERED BETWEEN RESPECTIVE TOILET PARTITIONS EXCEPT AS SPECIFICALLY NOTED OTHERWISE: THE CONTRACTOR SHALL COORDINATE ROUGHING IN WITH APPROVED TOILET PARTITION SHOP DRAWINGS. NEATLY INSTALL WHITE MILDEW-RESISTENT SILICONE SEALANT BEAD AROUND THE PERIPHERY OF ALL PLUMBING FIXTURES IN CONTACT WITH WALLS AND/OR FLOORS. MANUFACTURER’S MODEL NUMBERS ARE SPECIFIED SOLELY TO ESTABLISH STANDARD OF QUALITY FOR PERFORMANCE AND MATERIALS. INSTALLATION SHALL ADHERE TO MANUFACTURER’S RECOMMENDATIONS. THE PLUMBING CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL NEW PIPING THAT OCCURS IN THE CEILING SPACE OF THE TENANT BELOW WITH THE BUILDING MANAGEMENT, GENERAL CONTRACTOR AND ARCHITECT. RELOCATION OF ANY EXISTING PIPING/EQUIPMENT BELONGING TO THE TENANT/SPACE BELOW SHALL BE APPROVED BY BUILDING MANAGEMENT, GENERAL CONTRACTOR AND ARCHITECT PRIOR TO RELOCATION. THE PLUMBING CONTRACTOR SHALL COORDINATE “HOURS OF OPERATION” AVAILABLE FOR THIS WORK WITH BUILDING MANAGEMENT AND GENERAL CONTRACTOR. THE PLUMBING CONTRACTOR SHALL COORDINATE ALL NEW CORED OR CUT HOLES IN THE EXISTING CONCRETE STRUCTURE, INCLUDING FLOORS, WALLS AND ROOF, WITH THE STRUCTURAL ENGINEER, PRIOR TO ANY WORK. PLUMBING ABBREVIATIONS AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AIP ABANDON IN PLACE AVS ACID VENT STACK AVTR ACID VENT THRU ROOF AW & V ACID WASTE & VENT AWS ACID WASTE STACK BPS BEDPAN SPRAY CFOI CONTRACTOR FURNISHED/OWNER INSTALLED CSSK CLINICAL SERVICE SINK CU COMBINATION WATER CLOSET/LAV UNIT CWR COLD WATER RISER DF DRINKING FOUNTAIN EC ELECTRICAL CONTRACTOR EWC ELECTRIC WATER COOLER F & I FURNISH & INSTALL FFE FINISHED FLOOR ELEVATION FGE FINISHED GRADE ELEVATION FPC FIRE PROTECTION CONTRACTOR GC GENERAL CONTRACTOR GVS GARAGE VENT STACK GVTR GARAGE VENT THRU ROOF GWS GARAGE WASTE STACK HVAC HVAC CONTRACTOR HWCR HOT WATER RECIRCULATION RISER HWR HOT WATER RISER ICS INCRAWL SPACE INV INVERT KEC KITCHEN EQUIPMENT CONTRACTOR KW & V KITCHEN WASTE & VENT KWS KITCHEN WASTE STACK LAV LAVATORY LPC LIMIT OF PLUMBING CONTRACT LVS LABORATORY VENT STACK LVTR LABORATORY VENT THRU ROOF LW & V LABORATORY WASTE & VENT LWS LABORATORY WASTE STACK MR MOP RECEPTOR NC NORMALLY CLOSED NIPC NOT IN PLUMBING CONTRACT NO NORMALLY OPEN NTS NOT TO SCALE OFCI OWNER FURNISHED/CONTRACTOR INSTALLED OFI OWNER FURNISHED & INSTALLED PC PLUMBING CONTRACTOR S & V SOIL & VENT "S=.01 SLOPE = 1/8"" PER FOOT" "S=.02 SLOPE = 1/4"" PER FOOT" "S=.05 SLOPE = 1/2"" PER FOOT" SHR SHOWER SK SINK SS SOIL STACK SSK SERVICE SINK SVS SEPERATOR VENT STACK SVTR SEPERATION VENT THRU ROOF TYP TYPICAL UR URINAL VS VENT STACK VTR VENT THRU ROOF W & V WASTE & VENT WC WATER CLOSET WS WASTE STACK SV STACK VENT NPCW NONPOTABLE COLD WATER PLUMBING LEGEND DOUBLE CHECK VALVE ASSEMBLY EXISTING PLUMBING FIXTURE TO BE REMOVED (SAMPLE) REDUCED PRESSURE BACKFLOW PREVENTER PRESSURE GAUGE WITH ISOLATION VALVE TEMPERATURE & PRESSURE RELIEF VALVE VACUUM RELIEF VALVE PG T & P GAS METER EXPANSION LOOP THERMOMETER WATER METER EX.LP T TB EXPANSION JOINT RPBFP EJ DCVA TRENCH DRAIN & TYPE CONCRETE THRUST BLOCK PLANTER DRAIN & TYPE PLAZA DRAIN & TYPE TD'A' TB PD'A' PTD'A' HEAT TRACE AND INSULATE [FREEZE PROTECTION] BACKWATER VALVE W/FLUSH CLEANOUT CHECK VALVE W/LEVER & WEIGHT ARROW INDICATES DIRECTION OF FLOW ARROW INDICATES DIRECTION OF SLOPE DOWN WATER HAMMER ARRESTOR (SHOCK ABSORBER) & TYPE HOT & COLD WATER HOSE BIBB EMERGENCY SHOWER EYEWASH COMBINATION UNIT BOTTOM DENOTES SERVICE TYPE CAPPED CONNECTION TOP DENOTES SIZE (INCHES) GARAGE DRAIN & TYPE AREA DRAIN & TYPE FLOOR DRAIN & TYPE ROOF DRAIN & TYPE GD'A' AD'A' RD'A' FD'A' EYEWASH RISER DESIGNATION EW DC WALL HYDRANT & TYPE EMERGENCY SHOWER ES/EW WH'A' ES HOSE BIBB STRAINER DRESSER COUPLING H/C HB HB DC TP AUTOMATIC TRAP PRIMER CAPPED PIPE WATERTIGHT SLEEVE SA'A' TP WTS UNION SLEEVE PIPE ALIGNMENT GUIDE PIPE ANCHOR PAG SL PA GCO WALL CLEANOUT DANDY CLEANOUT WCO DCO GRADE CLEANOUT FLUSH FLOOR CLEANOUT CLEANOUT PLUG OPEN END DRAIN W/TRAP GCO FCO CO OED BWV BWV WASTE & TRAP HOSE END DRAIN VALVE BACKWATER VALVE BWV W & T DV BWV CHECK VALVE SOLENOID VALVE VALVE IN VERTICAL CV CVLW SV VIV BALANCING VALVE PRESSURE REDUCING VALVE SHUT-OFF VALVE BV PRV SOV HTI - 4 S WM GM COLD WATER CW HOT WATER HW HOT WATER RETURN HWR SANITARY (BELOW GRADE) S SANITARY (ABOVE GRADE) S VENT V RAINLEADER (ABOVE GRADE) RL RAINLEADER (BELOW GRADE) RL RL RL EMERGENCY RAINLEADER ERL ERL PUMPED DISCHARGE PD PD WET FIRE PROTECTION FPW FPW DRY FIRE PROTECTION FPD FPD CONSULTING E aha-engineers.com 1801 Old Alabama Road Suite 125 Roswell, GA 30076 770.992.8585 NGI NE E RS SHEET TITLE CLIENT NAME PROJECT NAME CHECKED DRAWN DATE PROJECT NO. 1875, 1891, 1895, 1901 Peachtree Road Atlanta,Georgia 30309 P-001 2150432 07/06/2016 AJM CWH PLUMBING LEGEND, SYMBOLS, DETAILS AND NOTES CORNERSTONE MEDICAL BUILDING Cornerstone RH Medical Building SPE, LLC 3300 Preston Ridge Road, Suite 380 Alpharetta, GA 30005 GMP Set - 07-06-2016 Revision Schedule No. Description Date
31
Embed
GENERAL NOTES PLUMBING ABBREVIATIONS - … notes, symbols list and details are applicable to all plumbing drawings. refer to architectural plans for general construction notes.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
ALL WORK SHALL CONFORM TO ALL APPLICABLE BUILDING CODES AND ALLSTATE AND LOCAL AMENDMENTS.
GENERAL NOTES, SYMBOLS LIST AND DETAILS ARE APPLICABLE TO ALLPLUMBING DRAWINGS.
REFER TO ARCHITECTURAL PLANS FOR GENERAL CONSTRUCTION NOTES.
DRAWINGS ARE DIAGRAMMATIC: THE CONTRACTOR SHALL DETERMINELOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD, OFF OFARCHITECTURAL AND STRUCTURAL PLANS.
THE PLUMBING CONTRACTOR SHALL DETERMINE EXACT LOCATIONS OFEXISTING UTILITIES IN FIELD, WHETHER OR NOT SHOWN ON THE DRAWINGS.EXERCISE CAUTION AND IDENTIFY LOCATIONS OF UNMARKED UTILITY LINESAS NECESSARY TO PERFORM THIS WORK.
THE PLUMBING CONTRACTOR SHALL PREPARE “SLEEVE AND INSERT”COORDINATION PLANS (LOCATING ALL ROOF, FLOOR AND WALLPENETRATIONS) AND SUBMIT TO ARCHITECT FOR REVIEW. EACHPENETRATION SHALL BE LOCATED WITH A MINIMUM OF (2) DIMENSIONS IN (2)DIRECTIONS.
THE PLUMBING CONTRACTOR SHALL PREPARE “COORDINATION” DRAWNGSTHAT COORDINATE THE PLUMBING WORK WITH ALL OTHER TRADESINCLUDING, BUT NOT LIMITED TO, ELECTRICAL, HVAC, PROCESS PIPING,SPRINKLER, STRUCTURAL AND GENERAL ARCHTIECTURE.
ANY INTERFERENCE BETWEEN TRADES SHALL BE BROUGHT TO THEATTENTION OF THE GENERAL CONTRACTOR/OWNER’S REPRESENTATIVE,AND SHALL BE RESOLVED PRIOR TO THE INSTALLATION OF THE WORK.
ALL PIPE SLEEVES IN FLOORS SHALL EXTEND A MINIMUM OF TWO INCHES (2”)ABOVE THE FINISHED FLOOR UNLESS NOTED OTHERWISE. FILL ANNULARSPACE WITH WATERPROOF, FIRE RETARDANT CAULKING PENETRATIONS.
All PIPING PENETRATING CEILINGS AND WALLS SHALL BE INSTALLED WITHESCUTCHEONS AT THE PENETRATION. ALL PIPING PENETRATING EXTERIORWALLS AND ROOFS SHALL BE FLASHED IN AN APPROVED MANNER AND SHALLBE SEALED WEATHERTIGHT. PIPING PENETRATING FIRE RATED ASSEMBLIESSHALL BE PROVIDED WITH FIRE RATED SEALS AS REQUIRED BY CODEAUTHORITY HAVING JURISDICTION.
TOPS OF ALL FLOOR DRAINS SHALL BE SET LEVEL AND FLUSH WITHFINISHED FLOOR.
ALL PIPING ABOVE GRADE SHALL BE PROPERLY SUPPORTED BY THEBUILDING STRUCTURE AND SHALL NOT REST ON CEILING STRUCTURE ORCOMPONENTS.
ALL PLUMBING EQUIPMENT, PIPING, INSULATION, ETC., INSTALLED IN HVACPLENUM SPACES SHALL MEET ALL CODE REQUIREMENTS FOR SMOKE ANDCOMBUSTIBILITY, PER ASTM E-84.
THE PLUMBING CONTRACTOR SHALL PROVIDE SHUTOFF VALVES ON ALLBRACH PIPING AND ON ALL SUPPLIES TO INDIVIDUAL FIXTURES ANDEQUIPMENT. PROVIDE FULL PORT BALL VALVES ON ALL WATER MAINBRANCHES IN CORRIDORS AND WHERE INDICATED ON DRAWINGS.
THE PLUMBING CONTRACTOR SHALL OBTAIN APPROVAL FROM THESTRUCTURAL ENGINEER PRIOR TO INSTALLING POWDER DRIVENFASTENERS.
COORDINATE ALL POST TENSIONED SLAB PENETRATIONS WITHSTRUCTURAL ENGINEER.
PROVIDE CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES ASNECESSARY TO PREVENT STRESS ON PIPING.
PROVIDE MANUFACTURED EXPANSION DEVICE OR FABRICATED EXPANSIONLOOP ON ALL PIPING SYSTEMS CROSSING BUILDING EXPANSION JOINTS.
ALL PIPE HANGERS ON INSULATED PIPING SHALL BE PROVIDED WITHHANGER SHIELDS.
ALL VALVES, CLEANOUTS AND COMPONENTS REQUIRING ACCESS BEHINDWALLS OR INACCESSIBLE CEILING SHALL BE PROVIDED WITH ACCESSPANELS. COORDINATE WITH ARCHITECT FOR REQUIRED TYPE, LOCATION,AND FINISH.
ALL P-TRAPS INSTALLED IN SPACES SUBJECT TO FREEZING SHALL BEINSULATED AND HEAT TRACED.
TRAP PRIMERS ARE TO BE PROVIDED ON ALL FLOOR DRAINS AND HUBDRAINS WHICH DO NOT RECEIVE A CONTINUOUS DISCHARGE. REFER TODRAINAGE DEVICE SCHEDULE AND FLOOR PLANS FOR TYPE ANDMANUFACTURER.
PROVIDE VENTS AT HIGH POINTS IN PIPING SYSTEMS AND DRAIN VALVES ATLOW POINTS.
PROVIDE GAUGE FITTINGS AND THERMOMETER WELLS AT HOT WATERSUPPLY AND RETURN BRANCHES AND AT PUMP INLETS AND OUTLETS.
SANITARY VENTS THROUGH THE ROOF MUST TERMINATE A MINIMUM OF 25FEET AWAY FROM OUTSIDE AIR INTAKES, WHICH PROVIDE VENTILATION ORMAKE-UP AIR TO THE BUILDING.
COORDINATE PROVISION FOR PROTECTING PIPING BENEATH HANDICAPLAVATORIES REQUIRED AND IDENTIFIED WITH TOILET ACCESSORIES.
PLUMBING FIXTURES FOR “ADA” COMPLIANCE SHALL BE INSTALLED WITHTHE HORIZONTAL AND VERTICAL CLEARANCES OUTLINED IN THE“AMERICANS WITH DISABILITIES ACT”. REFER TO ARCHITECTURAL PLANSFOR ELEVATIONS OF TOILET ROOMS.
ALL WATER CLOSETS OR URINALS SHALL BE CENTERED BETWEENRESPECTIVE TOILET PARTITIONS EXCEPT AS SPECIFICALLY NOTEDOTHERWISE: THE CONTRACTOR SHALL COORDINATE ROUGHING IN WITHAPPROVED TOILET PARTITION SHOP DRAWINGS.
NEATLY INSTALL WHITE MILDEW-RESISTENT SILICONE SEALANT BEADAROUND THE PERIPHERY OF ALL PLUMBING FIXTURES IN CONTACT WITHWALLS AND/OR FLOORS.
MANUFACTURER’S MODEL NUMBERS ARE SPECIFIED SOLELY TO ESTABLISHSTANDARD OF QUALITY FOR PERFORMANCE AND MATERIALS.
INSTALLATION SHALL ADHERE TO MANUFACTURER’S RECOMMENDATIONS.
THE PLUMBING CONTRACTOR SHALL COORDINATE THE INSTALLATION OFALL NEW PIPING THAT OCCURS IN THE CEILING SPACE OF THE TENANTBELOW WITH THE BUILDING MANAGEMENT, GENERAL CONTRACTOR ANDARCHITECT. RELOCATION OF ANY EXISTING PIPING/EQUIPMENT BELONGINGTO THE TENANT/SPACE BELOW SHALL BE APPROVED BY BUILDINGMANAGEMENT, GENERAL CONTRACTOR AND ARCHITECT PRIOR TORELOCATION.
THE PLUMBING CONTRACTOR SHALL COORDINATE “HOURS OF OPERATION”AVAILABLE FOR THIS WORK WITH BUILDING MANAGEMENT AND GENERALCONTRACTOR.
THE PLUMBING CONTRACTOR SHALL COORDINATE ALL NEW CORED OR CUTHOLES IN THE EXISTING CONCRETE STRUCTURE, INCLUDING FLOORS,WALLS AND ROOF, WITH THE STRUCTURAL ENGINEER, PRIOR TO ANY WORK.
FURNISH TO OWNER (1) BACKFLOW PREVENTER TEST KIT AND SPARE PARTS KITW/OPERATING & TEST PROCEDURES.THIS CONTRACTOR SHALL ACT AS THE OWNERS AGENT IN SEEKING APROVAL FROMALL LOCAL & STATE AUTHORITIES. THIS CONTRACTOR SHALL SUBMIT ALL PLANS,SPECS. & APLICATIONS REQUIRED FOR APROVAL AND PAY ALL FEES.
FOR SIZING REFER TO THE DRAWING.TEST AND CERTIFY EACH INSTALLATION.
MAINTAIN 1'-0" CLEARANCE FROM WALL.
SEE FLOOR PLANS FOR SIZES.
6" CW FROM STREET
STRAINER (TYPICAL)
UNISTRUT SUPPORTSYSTEM TO SUIT
SHUT-OFF VALVE(TYPICAL)
TEST COCK (TYPICAL)
6" CW TO BUILDINGBFP-1
30" MAX
24" MAX
3" CW TO BUILDING
3" CW
3/4" CW
PRV-1PRV-2
SEAL ASSEMBLY SHALL BE MODULAR MECHANICAL TYPE CONSISTINGOF INTERLOCKING RUBBER LINKS SHAPED TO CONTINUOUSLY FILL INTHE ANNULAR SPACE BETWEEN PIPE & WALL OPENING PRESSUREPLATES SHALL BE DELRIN PLASTIC BOLTS & NUTS SHALL BE 18.8STAINLESS STEEL SEALING ELEMENT SHALL BE EPDM RUBBER
SEAL ASSEMBLY (SEE NOTE BELOW)
CARRIER PIPE (SIZE VARIES)
STANDARD WEIGHTSTEEL PIPE SLEEVE
NOTES:
WALL
PD
ELECTRICALOUTLET BY G.C.
ELEVATORPIT
1 1/4"BRONZE UNION
NIBCO T-4131 1/4"CHECK VALVE
BLEED HOLE 3/16"
2'-0"X2'-0"X2'0" DEEPSUMP BY G.C.
AUTOMATIC SUMP PUMP
ANGLE IRON GRATINGSUPPORT ALL AROUND
BY G.C.
2'-0"X2'-0" OPENGRATING NIPC
W/HOLE FORPOWER CORD &
PIPE DISCHARGEBY G.C.
3 PRONG PLUG
CUP TO WALL
PD
PD
GATE VALVE
FINISHED FLOOR
4" CHECK VALVE4" GATE VALVE
HIGH LEVEL ALARM
LAG PUMP ON
LEAD PUMP OFF
INSPECTION OPENING
6" DISCHARGE
ELEVATION
PLAN
INLET
SUMP PUMP RAILSYSTEM
SUMP PUMPSP-3 & 4
FLOOR
WALL
UNION (TYP.)
STRAP TO WALL
MOP SINK
IW
EXPANSION TANKA.O. SMITH No. V-5E
WALL BRACKET ANDSTEEL SHELF SUPPORT
SPILL FULL SIZE NON-FERROUSTEMPERATURE & PRESSURE RELIEF
& DRIP PAN WASTE TO SERVICE SINK
ELECTRIC WATERHEATER (WH-1 & 2)
DRAIN VALVE
SAFETY PAN
THERMOMETER
VACUUM RELIEFVALVE
COMBINATION TEMP. ANDPRESS. RELIEF VALVE
120°3/4"HW SUPPLY
NOTES:1. DRAWINGS FOR SCHEMATIC PURPOSES ONLY. ALL VALVES & EQUIPMENT MUST BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS.2. ENTIRE DOMESTIC HOT & COLD SHALL BE THOROUGHLY TESTED FOR TEMPERATURE & PRESSURE PRIOR TO TURNING BUILDING OVER TO OWNER.
3/4"CW SUPPLY
3/4"HWR SUPPLY
CHECK VALVE
CIRCULATION PUMP(CP-1 & 2)
THERMOSTAT
DOMESTIC WATERTO BLDG.
3/4"HOSE ENDDRAIN (TYP)FLOOR
TRIPLEX DOMESTIC WATERBOOSTER PUMP PACKAGE
SEE PUMP SCHEDULE FOR
PUMP CHARACTERISTICS
FULL SIZE VALVED BY-PASS(NORMALLY CLOSED)
FULL SIZE FLEXIBLE CONNECTORSTYPICAL (BY PLUMBING CONTRACTOR)
6" DOMESTIC WATER FROMWATER SERVICE ENTRY
4" HIGH CONCRETEPAD (BY GC)
5'
AF
F (M
AX
)
CO
NF
IRM
EX
AC
T
HE
IGH
T W
/ F
IRE
MA
RS
HA
LL
PRESSURE GAUGE W/SHUT-OFF VALVE
WATERFLOW SWITCH
OS&Y VALVE W/SUPERVISORY SWITCH
3
2
4
RISER1
FLOOR
INSPECTORS TEST VALVE
1" SIGHT GLASS
AUXILARY DRAIN VALVE
UNION ORIFICE
6
9
7
8
CHECK VALVE5
FLOOR
3" DRAIN RISER
TO SPRINKLER SYSTEM
CL
SS
COMBINATION STANDPIPE
WET PIPE SPRINKLER
RISER IN STAIR
FIRE RATED
PROTECTION
PACKING
2 1/2" FDV VALVE
W/ 1 1/2" REDUCER,
CAP AND CHAIN
NOTE: RISER
CLAMPS INSTALLED
AT ALL FLOORS
ROUTE DRAINS TO
INDIRECT WASTE
RECEPTOR OR TO GRADE
8 9
67
54
3
21
3" CAPPED HOSE
CONNECTION AND
ADAPTER
OS&Y VALVE WITHSUPERVISORY SWITCH
CHECK VALVE
FROM STANDPIPESYSTEM
STANDPIPE
SHUT-OFF VALVE
PRESSURE GAUGE
PRV-1 (SET @ 50 PSI)
PRESSURE GAUGE
SHUT-OFF VALVE
2 1/2" CW
3" CW
SHUT-OFF VALVE
PRESSURE GAUGE
PRV-2 (SET @ 60 PSI)
PRESSURE GAUGE
SHUT-OFF VALVE
3/4" CW3" CW
DOMESTICCW RISER
DOMESTICCW RISER
2 1/2" CW TOSERVE FLOOR
2 1/2" CW TOSERVE FLOOR
CONSULTINGE
aha-engineers.com
1801 Old Alabama RoadSuite 125
Roswell, GA 30076770.992.8585
NGINEERS
SH
EE
T T
ITLE
CLI
EN
T N
AM
EP
RO
JEC
T N
AM
E
CH
EC
KE
D
DR
AW
N
DA
TE
PR
OJ
EC
T N
O.
1875
, 189
1, 1
895,
190
1 P
each
tree
Roa
dA
tlant
a,G
eorg
ia 3
0309
P-501
2150
432
07/0
6/20
16
AJM
CW
HP
LUM
BIN
G D
ET
AIL
S
CO
RN
ER
ST
ON
E M
ED
ICA
L B
UIL
DIN
GC
orne
rsto
ne R
H M
edic
al B
uild
ing
SP
E, L
LC33
00 P
rest
on R
idge
Roa
d, S
uite
380
Alp
hare
tta, G
A 3
0005
GM
P S
et -
07-
06-2
016
SCALE: N.T.S.P-501
1 DOMESTIC WATER SERVICE ENTRYSCALE: N.T.S.P-501
2 WATERTIGHT SLEEVESCALE: N.T.S.P-501
3 ELEVATOR SUMP PUMP
SCALE: N.T.S.P-501
4 SUBMERSIBLE SUMP PUMP PITSCALE: N.T.S.P-501
5 ELECTRIC WATER HEATERSCALE: N.T.S.P-501
6 DOMESTIC BOOSTER PUMP
SCALE: N.T.S.P-501
7 FIRE DEPARTMENT AND FLOOR CONTROL VALVESSCALE: N.T.S.P-501
8 BASE OF STANDPIPE VALVE ASSEMBLYSCALE: N.T.S.P-501
9 PRV STATION
Revis
ion
Sch
ed
ule
No
.D
escri
pti
on
Date
PUMP SCHEDULE
DESIGNATIONBOOST
(PSI)LOCATION
FLOW(GPM)
TOTAL HEAD(FEET)
DOMESTIC BOOSTERPUMP (DBP-1)
REMARKS
7.5 (EA)121 FIRE PUMP ROOM
P1-106 15450 (TL)158 (EA)
TRIPLEX, 70% REDUNDANCY, END SUCTION,VARIABLE SPEED, 480 VOLT / 3 PHASE COORDINATE
1. PROVIDE WATTS SERIES MMV THERMOSTATIC MIXING VALVES AT ALL SINKS/LAVS THAT RECIEVE HOT WATER.2. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION AND MOUNTING HEIGHTS OF ALL PLUMBING FIXTURES AND FITTINGS.3. PC TO COORDINATE COLORS AND FINISHES OF ALL PLUMBING FIXTURES AND FITTINGS WITH ARCHITECT PRIOR TO CONSTRUCTION.
WC-2WATERCLOSET(PUBLIC)
4" 2" 1" -WATER CLOSET: WALL MOUNTED ADA HEIGHT 1.28 GPFFLUSH VALVE: CHROME FINISH, SENSOR TYPE, 1.28 GPFSEAT: OPEN FRONT
WATER CLOSET: KOHLER K-4325FLUSH VALVE: KOHLER K-7531SEAT: CHURCH 9500CT
UR-1 URINAL 2" 2" 3/4" -
SINK: CHINA DROP-IN TYPE, WHITEFAUCET: CHROME PLATED, 1.0 GPM AERATOR
SINK: KOHLER K-2907-1FAUCET: KOHLER K-7514-CP
ELECTRIC WATER HEATER SCHEDULE
COORDINATE VOLTAGES WITH ELECTRICAL PLANS AO SMITH DEL-10
DESIGNATIONSTORAGE
(GAL)LOCATION
RECOVERY RATE
(90 DEG. RISE)REMARKS
VOLTS
ELECTRICAL REQUIREMENTSTEMP
SETTING (°F) KW PHASE
WH-1 10 7 GPH 120 1.5JAN ROOM
SPECIFICATION
460 1
COORDINATE VOLTAGES WITH ELECTRICAL PLANS AO SMITH DEL-10WH-2 10 7 GPH 120 1.5JAN ROOM 460 1