SHOCK ARRESTOR SIZING TABLE PLUMBING GENERAL NOTES PLUMBING MATERIALS AND NOTES DOMESTIC WATER PIPING: 1. DOMESTIC WATER PIPING AND JOINTS BELOW GRADE : PROVIDE TYPE 'K' SOFT ANNEALED SEAMLESS COPPER TUBING (ASTM B 88) WITH NO JOINTS FOR PIPING 2 1/2" AND SMALLER. PROVIDE DUCTILE IRON PIPE AND FITTINGS (AWWA C151, AWWA C110) WITH RUBBER GASKET JOINTS AND RODS (AWWA C111) PIPING 3" AND LARGER. 2. DOMESTIC WATER PIPING AND JOINTS ABOVE GRADE : PROVIDE TYPE 'L' HARD DRAWN SEAMLESS COPPER TUBING (ASTM B 88) AND CAST COPPER ALLOY FITTINGS (ASME B16.18). JOINTS 1" AND SMALLER SHALL BE LEAD FREE 95-5 TIN/SILVER SOLDER JOINTS (ASTM B 32), JOINTS 1 1/4" AND LARGER SHALL BE BCUP SILVER/PHOSPHORUS/COPPER BRAZED JOINTS (AWS A5.8) OR PROVIDE COPPER PIPE AND FITTINGS AS SPECIFIED ABOVE EXCEPT WITH GROOVED ENDS (ASTM B 88, ASME B16.18) AND JOINTS UTILIZING GROOVED MECHANICAL COUPLINGS MEETING (ASTM F1476). 3. STERILIZE THE DOMESTIC WATER SYSTEM IN ACCORDANCE WITH THE AMERICAN WATER WORKS ASSOCIATION'S SPECIFICATIONS AND LOCAL HEALTH DEPARTMENT REGULATIONS. 4. INSULATE DOMESTIC WATER PIPING ABOVE GRADE (EXCEPT EXPOSED CONNECTIONS TO PLUMBING FIXTURES) WITH GLASS FIBER INSULATION HAVING A VAPOR BARRIER AND JACKET. PIPE INSULATION SHALL HAVE A CONDUCTIVITY NOT EXCEEDING 0.27 BTUH x SQ. FT. FOLLOW SCHEDULE BELOW: SERVICE TYPE PIPE SIZES INSULATION THICKNESS DOMESTIC HOT WATER & CIRCULATION 1/2" - 1 1/4" 1" DOMESTIC HOT WATER & CIRCULATION 1 1/2" - 4" 1 1/2" DOMESTIC COLD WATER 1/2" - 1 1/4" 1/2" DOMESTIC COLD WATER 1 1/2" - 4" 1" 5. DOMESTIC WATER PIPING INSULATION, JACKETS, COVERINGS, SEALERS, MASTICS AND ADHESIVES ARE REQUIRED TO MEET A FLAME-SPREAD RATING OF 25 OR LESS AND A SMOKE-DEVELOPED RATING OF 50 OR LESS, AS TESTED BY ASTM E84 (NFPA 255) METHOD AND SHALL BE PLENUM RATED. 6. PROVIDE FULL PORT, BALL TYPE SHUT-OFF VALVES AND INSTALL IN A LOCATION THAT PERMITS ACCESS FOR SERVICE WITHOUT DAMAGE TO THE BUILDING OR FINISHED MATERIALS. 7. PROTECT COPPER PIPING AGAINST CONTACT WITH DISSIMILAR METALS. ALL HANGERS, SUPPORTS, ANCHORS AND CLIPS SHALL BE COPPER OR COPPER PLATED. WHERE COPPER PIPING IS CARRIED ON TRAPEZE HANGERS WITH OTHER PIPING, PROVIDE A PERMANENT ELECTROLYTIC ISOLATION MATERIAL TO PREVENT CONTACT WITH DISSIMILAR OTHER METALS. 8. PROTECT COPPER PIPING AGAINST CONTACT WITH ALL MASONRY. WHERE COPPER IS SLEEVED THROUGH MASONRY, PROVIDE COPPER OR RED BRASS SLEEVES. WHERE COPPER MUST BE CONCEALED IN OR AGAINST MASONRY PARTITIONS, PROVIDE A HEAVY COATING OF ASPHALTIC ENAMEL ON THE COPPER PIPING AND 15# ASPHALT SATURATED FELT BETWEEN THE PIPING AND THE MASONRY PARTITION. 9. DOMESTIC WATER PIPING SHALL BE SLOPED FOR DRAINAGE WITH DRAIN VALVES INSTALLED AT LOW POINTS. SANITARY WASTE / VENT AND STORM PIPING: 1. SANITARY WASTE AND STORM DRAIN PIPING BELOW GRADE: PROVIDE SERVICE WEIGHT CAST IRON HUB AND SPIGOT PIPE (ASTM A 74) WITH COMPRESSION JOINTS (CISPI HSN) AND NEOPRENE GASKETS (ASTM C 564) OR NO-HUB PIPE AND FITTINGS (CISPI 301) WITH NEOPRENE GASKET/STAINLESS STEEL CLAMP JOINTS (CISPI 310) OR PROVIDE SCHEDULE 40 PVC PIPE AND SOCKET FITTINGS (ASTM D 2665) WITH SOLVENT WELD JOINTS (ASTM D2855). FOAM CORE PVC PIPE IS NOT APPROVED. 2. SANITARY WASTE/VENT AND STORM DRAIN PIPING ABOVE GRADE: PROVIDE SERVICE WEIGHT CAST IRON NO-HUB PIPE AND FITTINGS (CISPI 301) WITH NEOPRENE GASKET AND STAINLESS STEEL CLAMP JOINTS (CISPI 310). DO NOT INSTALL PVC PIPING IN RETURN AIR PLENUMS. 3. SLOPE SANITARY WASTE AND STORM DRAIN PIPING AT 1/4" PER FOOT MINIMUM FOR PIPING 2 1/2" AND SMALLER AND 1/8" PER FOOT MINIMUM FOR PIPING 3" AND LARGER UNLESS NOTED OTHERWISE. SLOPE ALL KITCHEN WASTE PIPING AT 1/4" PER FOOT MINIMUM. 4. PROVIDE CLEAN-OUTS AT THE BASE OF SANITARY WASTE STACKS AND STORM DRAIN RISERS AND AT EVERY TURN IN PIPING IN EXCESS OF 45° AND NO FURTHER THAN 100'-0" APART IN A LOCATION THAT PERMITS ACCESS FOR SERVICE WITHOUT DAMAGE TO THE BUILDING OR FINISHED MATERIALS. 5. PROVIDE FLOOR CLEANOUTS WITH TOPS DESIGNED TO MATCH SPECIFIC FLOOR FINISHES SUCH AS CARPET, TILE, ETC. YARD CLEANOUTS SHALL BE PROVIDED IN AN 18"x18"x6" CONCRETE PAD. 6. WHERE WASTE PIPING IS EXPOSED IN REST ROOM AREAS, PROVIDE CHROME PLATED BRASS PIPING, REMOVABLE P-TRAPS, MATCHING STOPS AND ESCUTCHEONS FOR ALL LAVATORIES. 7. INSULATE MECHANICAL ROOM FLOOR DRAIN BODIES, P-TRAP AND HORIZONTAL DRAIN PIPING ABOVE GRADE WITH 1" THICK GLASS FIBER INSULATION WITH VAPOR BARRIER AND JACKET. 8. INSULATE ROOF DRAIN BODIES AND HORIZONTAL PRIMARY AND SECONDARY STORM DRAIN PIPING ABOVE GRADE WITH 1" THICK GLASS FIBER INSULATION WITH VAPOR BARRIER AND JACKET. 9. PIPING INSULATION, JACKETS, COVERINGS, SEALERS, MASTICS AND ADHESIVES ARE REQUIRED TO MEET A FLAME-SPREAD RATING OF 25 OR LESS AND A SMOKE-DEVELOPED RATING OF 50 OR LESS, AS TESTED BY ASTM E84 (NFPA 255) METHOD. 10. SUMP PUMP DISCHARGE PIPING: PROVIDE SCHEDULE 40 GALVANIZED STEEL PIPE (ASTM A53) AND GALVANIZED 150 POUND MALLEABLE IRON FITTINGS (ASME B16.3) WITH THREADED JOINTS. SLOPE SUMP DISCHARGE LINE AT 1% SLOPE TOWARDS SUMP PUMP. NATURAL GAS PIPING: 1. NATURAL GAS PIPING AND FITTINGS ABOVE GRADE: SCHEDULE 40 BLACK STEEL PIPING, TYPE S, SEAMLESS, GRADE B (ASTM A 53) AND 150 PSI MALLEABLE BLACK IRON FITTINGS, GRADE 32510, (ASTM B 16.3) OR FORGED STEEL WELDING TYPE FITTINGS (ASTM A234). PROVIDE THREADED JOINTS FOR PIPE 2" AND SMALLER. PROVIDE WELDED JOINTS (ASME B31.9) FOR PIPE 2 1/2" AND LARGER. 2. NATURAL GAS PIPING AND FITTINGS OUTSIDE BELOW GRADE: SCHEDULE 40 BLACK STEEL, TYPE S, SEAMLESS, GRADE B (ASTM A 53) AND FORGED STEEL WELDING TYPE FITTINGS (ASTM A234) WITH (AWWA C105) POLYETHYLENE JACKET OR DOUBLE LAYER, HALF LAPPED 10 MIL POLYETHYLENE TAPE. PROVIDE WELDED JOINTS (ASME B31.9) FOR ALL UNDERGROUND PIPE. 3. SPACE GAS PIPING HANGER RODS 7'-0" ON CENTER MAXIMUM AND SPACE TRANSVERSE BRACING 20'-0" ON CENTER MAXIMUM. TRANSVERSE BRACING FOR ONE SECTION MAY ACT AS LONGITUDINAL BRACING FOR THE PIPE SECTION CONNECTED TO IT IF THE BRACING IS INSTALLED WITHIN 24" OF THE ELBOW OR TEE. COORDINATE HANGER LOCATIONS WITH STRUCTURAL DRAWING DETAILS. 4. PROVIDE A.G.A. CERTIFIED SHUT-OFF VALVES MINIMUM, 125 PSI RATED, NON- LUBRICATED PLUG TYPE WITH BRONZE BODY AND BRONZE PLUG, STRAINERS AND REGULATORS (AS RECOMMENDED BY THE EQUIPMENT MANUFACTURER) FOR ALL EQUIPMENT CONNECTED TO THE NATURAL GAS SYSTEM. 5. GAS PRESSURE REGULATORS SHALL BE CSA CERTIFIED (Z21.80) FOR 2 PSI INLET PRESSURE, OUTLET PRESSURE RANGE OF 7 TO 11 INCHES WATER COLUMN. WHEN USING VENTLESS REGULATORS, MOUNT REGULATOR IN A HORIZONTAL UPRIGHT POSITION. IF VENTED TYPE REGULATORS ARE USED, INSTALL VENT PIPING (FULL SIZE OPENING) FROM GAS PRESSURE REGULATORS TO OUTDOORS AND TERMINATE IN WEATHERPROOF HOOD. 6. PAINT ALL GAS PIPING WITH 2 COATS OF YELLOW ENAMEL PAINT APPLIED WITH A BRUSH (2 MIL THICKNESS MINIMUM). STENCIL "GAS" ON PIPE AT 12'-0" CENTERS FOR ALL LOW PRESSURE PIPING (0.5 PSI). STENCIL "2-PSI GAS" ON PIPE AT 6'-0" CENTERS FOR 2 PSI GAS PIPING. GENERAL REQUIREMENTS: 1. PLUMBING WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE COLORADO STATE PLUMBING CODE AND WITH THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION. 2. GENERAL AND SPECIAL CONDITIONS ARE HEREBY MADE AN INTEGRAL PART OF THE PLUMBING SPECIFICATIONS INSOFAR AS THE GENERAL AND SPECIAL CONDITIONS ARE APPLICABLE TO THE PLUMBING WORK, UNLESS OTHERWISE SPECIFIED. 3. SCOPE: PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT REQUIRED FOR THE COMPLETION AND OPERATION OF ALL PLUMBING SYSTEMS IN ACCORDANCE WITH ALL APPLICABLE CODES. 4. PERMITS: APPLY AND PAY FOR ALL NECESSARY PERMITS, FEES AND INSPECTIONS REQUIRED BY ANY PUBLIC AUTHORITY HAVING JURISDICTION. ACREAGE CHARGES, FACILITIES CHARGES AND BOND PROPERTY ASSESSMENTS ARE NOT TO BE CONSTRUED TO BE A PART OF THIS CONTRACT. 5. WARRANTY: PROVIDE A ONE YEAR WARRANTY, FROM THE DATE OF ACCEPTANCE OF WORK BY THE OWNER, FOR ALL PLUMBING MATERIALS AND EQUIPMENT. 6. COORDINATE ALL PLUMBING PIPING LOCATIONS, ROUGH-IN LOCATIONS AND EQUIPMENT LOCATIONS WITH OTHER TRADES TO AVOID CONFLICTS AND INTERFERENCES. FINAL PIPING AND EQUIPMENT LOCATIONS SHALL BE A CODE COMPLIANT INSTALLATION FOR ALL TRADES. 7. FIELD VERIFY PROPER OPERATION OF EXISTING SYSTEMS BEFORE STARTING CONSTRUCTION. NOTIFY THE ARCHITECT / ENGINEER OF RECORD OF ANY PROBLEMS OR DISCREPANCIES BETWEEN THE CONSTRUCTION DOCUMENTS AND EXISTING CONDITIONS AND/OR ANY POTENTIAL PROBLEMS OBSERVED BEFORE CONTINUING WORK IN THE EFFECTED AREAS. 8. CUT WALLS, FLOORS AND CEILINGS AS REQUIRED FOR INSTALLATION OF PLUMBING WORK. ALL CUTTING SHALL BE HELD TO A MINIMUM. PATCH AND FINISH SURFACES TO MATCH ADJOINING SURFACES. 9. PLUMBING PLANS SHALL NOT BE SCALED. REFERENCE THE ARCHITECTURAL PLANS FOR ALL LOCATIONS OF PLUMBING FIXTURES, WALLS, DOORS, WINDOWS, ETC. 10. PLUMBING PIPING SHALL BE LOCATED CONCEALED IN WALLS, PARTITIONS OR ABOVE CEILINGS UNLESS NOTED OTHERWISE. PLUMBING PIPING IN EXPOSED AREAS SHALL BE RUN TIGHT TO UNDERSIDE OF STRUCTURE. 11. PLUMBING PIPING, VENTS, ETC. EXTENDING THROUGH EXTERIOR WALLS AND/OR THE ROOF SHALL BE FLASHED AND COUNTER FLASHED IN A WATERPROOF MANNER. COORDINATE FLASHING WITH THE GENERAL CONTRACTOR. 12. DO NOT INSTALL PLUMBING PIPING IN AREAS SUBJECT TO FREEZING TEMPERATURES. INSTALL PLUMBING PIPING SHOWN IN EXTERIOR WALLS ON THE CONDITIONED SIDE OF THE WALL INSULATION. 13. PROVIDE NON-CONDUCTING DIELECTRIC UNIONS WHENEVER CONNECTING DISSIMILAR METALS. 14. ATTACH HANGERS TO STRUCTURE, HANGERS SHALL NOT ATTACH TO THE DECK. 15. PROVIDE ACCESS DOORS FOR VALVES, WATER HAMMER ARRESTORS, TRAP PRIMERS, ETC. CONCEALED IN MASONRY WALLS, GYPBOARD WALLS AND/OR CEILINGS THAT WILL REQUIRE MAINTENANCE ACCESS. ACCESS DOORS SHALL BE LOCATED IN CEILILNG ONLY . 16. PLUMBING SYSTEMS INCLUDE, BUT ARE NOT LIMITED TO: PLUMBING FIXTURES AND EQUIPMENT, FIRE STOPPING, SEISMIC BRACING, PIPE IDENTIFICATION, DOMESTIC WATER SYSTEM, SANITARY WASTE AND VENT SYSTEM, STORM DRAIN SYSTEM, NATURAL GAS SYSTEM PLUMBING FIXTURES AND EQUIPMENT: 1. PROVIDE COMPLETE PLUMBING FIXTURES AND EQUIPMENT. INCLUDE SUPPLIES, STOPS, VALVES, FAUCETS, DRAINS, TRAPS, TAIL PIECES, ESCUTCHEONS, ETC. 2. PLUMBING FIXTURES AND EQUIPMENT SHALL BE INSTALLED PER THE MANUFACTURER'S RECOMMENDATIONS AND INSTALLATION INSTRUCTIONS. 3. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH SUBSTITUTIONS TO SPECIFIED PLUMBING FIXTURES AND EQUIPMENT INCLUDING BUT NOT LIMITED TO; PROVIDING MAINTENANCE ACCESS CLEARANCE, PIPING, ELECTRICAL, REPLACEMENT OF OTHER SYSTEM COMPONENTS, BUILDING ALTERATIONS, ETC. AND ANY MODIFICATIONS TO ASSOCIATED MECHANICAL, ELECTRICAL OR PLUMBING SYSTEMS REQUIRED BY THE EQUIPMENTS INSTALLATION INSTRUCTIONS. ALL COSTS ASSOCIATED WITH SUBSTITUTIONS SHALL BE INCLUDED IN THE ORIGINAL BASE BID. FIRE STOPPING: 1. FIRE STOP ALL PENETRATIONS, BY PIPING OR CONDUITS, OF FIRE RATED WALLS, FLOORS AND PARTITIONS. PROVIDE A DEVICE(S) OR SYSTEM(S) WHICH HAS BEEN TESTED AND LISTED AS COMPLYING WITH ASTM E-814 AND INSTALL IN ACCORDANCE WITH THE CONDITIONS OF THEIR LISTING. PROVIDE A DEVICE(S) OR SYSTEM(S) WITH AN 'F' RATING EQUAL TO THE RATING OF THE ASSEMBLY BEING PENETRATED. REFER TO ARCHITECTURAL PLANS FOR WALL AND FLOOR TYPES. SEISMIC BRACING: 1. PROPERLY SUPPORT AND BRACE VERTICALLY AND HORIZONTALLY ALL PIPING, APPARATUS, EQUIPMENT, ETC. IN ACCORDANCE WITH APPLICABLE CODES TO PREVENT EXCESSIVE MOVEMENT DURING SEISMIC CONDITIONS. PIPE IDENTIFICATION: 1. PIPE IDENTIFICATION SHALL MATCH THE FACILITY'S EXISTING STANDARD. IF NO STANDARD EXISTS, THEN THE PIPE IDENTIFICATION SHALL BE IN ACCORDANCE WITH ANSI A13.1. 2. PROVIDE PIPING LABELS FOR ALL PLUMBING PIPING. PIPING LABELS SHALL BE ACRYLIC FACED, WRAP-AROUND TYPE. EACH LABEL SHALL INDICATE THE PIPING CONTENTS, DIRECTION OF FLOW AND SHALL BEAR THE MANUFACTURER'S STANDARD COLOR FOR THE SERVICE INDICATED. 61-113 33-60 12-32 1-11 D C B A 155-330 F E 114-154 1" 1 1/4" 1/2" 3/4" 2" 1 1/2" SA-D SA-C SA-B SA-A SA-F SA-E DRAWING SYMBOL FIXTURE UNITS PDI WH201 STANDARD DESIGNATION ARRESTOR SIZE - SIOUX CHIEF - WATTS - PPP INC. INSTALL SHOCK ARRESTORS PER PDI WH201 GUIDELINES REMARKS APPROVED MANUFACTURERS ESD G SD SD SA-# HOSE BIBB/WALL HYDRANT PRESSURE REDUCING/REGULATING VALVE BALANCING VALVE / CIRCUIT SETTER GAS COCK END OF LINE CLEAN OUT ROOF DRAIN STORM DRAIN PIPING - ABV. CEILING WALL CLEAN OUT YARD CLEAN OUT FLOOR CLEAN OUT NATURAL GAS PIPING CHECK VALVE HOT WATER RETURN PIPING STORM DRAIN PIPING - BEL. GRADE DESCRIPTION NEW PIPING SANITARY WASTE PIPING HOT WATER PIPING SANITARY VENT PIPING COLD WATER PIPING PIPE CONTINUES BALL VALVE FLOOR DRAIN ELBOW UP ELBOW DOWN PIPE REDUCER EMERGENCY STORM DRAIN PIPING SHOCK ARRESTOR - SUFFIX INDICATES PDI SIZE THERMOMETER PLUMBING LEGEND ABBR. CW HW HWR W V SD SD ESD G CV - - - - BV - PRV - FCO WCO CO YCO FD RD HB SA - PIPE CAP - ADDITIONAL ABBREVIATIONS PRESSURE GAUGE - IN-LINE PUMP - DIRECTION OF FLOW - ABV ABOVE AFF ABOVE FINISHED FLOOR AVTR ACID VENT THRU ROOF BAS BUILDING AUTOMATION SYSTEM BEL BELOW BF BARRIER FREE BFF BELOW FINISHED FLOOR BTUH BRITISH THERMAL UNIT / HOUR CFH CUBIC FEET PER HOUR CLG CEILING CONT CONTINUATION DFU DRAINAGE FIXTURE UNIT (WASTE) DN DOWN EX EXISTING FFE FINISHED FLOOR ELEVATION FIN FINISH FL FLOOR FR FROM FU FIXTURE UNITS GPM GALLONS PER MINUTE HP HORSE POWER INV INVERT ELEVATION IW INDIRECT WASTE KW KILOWATT LAV LAVATORY MBH 1,000 BTUH MH MOUNTING HEIGHT PH PHASE PSI POUNDS PER SQUARE INCH SF SQUARE FEET T&P TEMPERATURE AND PRESSURE TW TEMPERED WATER TYP TYPICAL UR URINAL VB VACUUM BREAKER VLV VALVE VTR VENT THRU ROOF WC WATER COLUMN EC ELECTRICAL CONTRACTOR FSEC FOOD SERVICE EQUIP. CONTRACTOR GC GENERAL CONTRACTOR MC MECHANICAL CONTRACTOR PC PLUMBING CONTRACTOR 1 A B C D E 3 4 5 6 2 Description Date Rev # Copyright 2014. All rights reserved. Printed or electronic drawings and documentation may not be reproduced in any form without written permission from ai Design Group, Inc. PROJECT NO: Revision Schedule DRAWN BY: CHECKED BY: SONIC DEVELOPMENT, LLC Charlotte, North Carolina E N G I N E E R I N G I N C Eng. of Record: License No.: M VEIGH MANGUM C & 1610 East Morehead Street, Suite 100 Charlotte, North Carolina 28207 Ph: (704) 547-9035 Fax: (704) 547-9036 email: [email protected]2/6/2015 11:56:11 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt 2/6/2015 11:56:11 AM 2015-02-06 13554 ISSUED FOR PERMIT MERCEDES-BENZ OF DENVER Street: Corner of E. Kentucky Ave. and South Colorado Boulevard Glendale, CO 80246 P-001 Author Checker PLUMBING NOTES & LEGENDS 48552 Larry P. McWilliams
11
Embed
PLUMBING LEGEND PLUMBING MATERIALS AND …rives.com/wp-content/uploads/2014/10/ALL-11-Total-Plumbing-2-MB.pdfplumbing materials and notes plumbing general notes ... before continuing
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
SHOCK ARRESTOR SIZING TABLE
PLUMBING GENERAL NOTESPLUMBING MATERIALS AND NOTESDOMESTIC WATER PIPING:
1. DOMESTIC WATER PIPING AND JOINTS BELOW GRADE : PROVIDE TYPE 'K' SOFT ANNEALED SEAMLESS COPPERTUBING (ASTM B 88) WITH NO JOINTS FOR PIPING 2 1/2" AND SMALLER. PROVIDE DUCTILE IRON PIPE ANDFITTINGS (AWWA C151, AWWA C110) WITH RUBBER GASKET JOINTS AND RODS (AWWA C111) PIPING 3"AND LARGER.
2. DOMESTIC WATER PIPING AND JOINTS ABOVE GRADE : PROVIDE TYPE 'L' HARD DRAWN SEAMLESS COPPERTUBING (ASTM B 88) AND CAST COPPER ALLOY FITTINGS (ASME B16.18). JOINTS 1" AND SMALLER SHALL BELEAD FREE 95-5 TIN/SILVER SOLDER JOINTS (ASTM B 32), JOINTS 1 1/4" AND LARGER SHALL BE BCUPSILVER/PHOSPHORUS/COPPER BRAZED JOINTS (AWS A5.8) OR PROVIDE COPPER PIPE AND FITTINGS ASSPECIFIED ABOVE EXCEPT WITH GROOVED ENDS (ASTM B 88, ASME B16.18) AND JOINTS UTILIZINGGROOVED MECHANICAL COUPLINGS MEETING (ASTM F1476).
3. STERILIZE THE DOMESTIC WATER SYSTEM IN ACCORDANCE WITH THE AMERICAN WATER WORKSASSOCIATION'S SPECIFICATIONS AND LOCAL HEALTH DEPARTMENT REGULATIONS.
4. INSULATE DOMESTIC WATER PIPING ABOVE GRADE (EXCEPT EXPOSED CONNECTIONS TO PLUMBINGFIXTURES) WITH GLASS FIBER INSULATION HAVING A VAPOR BARRIER AND JACKET. PIPE INSULATIONSHALL HAVE A CONDUCTIVITY NOT EXCEEDING 0.27 BTUH x SQ. FT. FOLLOW SCHEDULE BELOW:SERVICE TYPE PIPE SIZES INSULATION THICKNESSDOMESTIC HOT WATER & CIRCULATION 1/2" - 1 1/4" 1"DOMESTIC HOT WATER & CIRCULATION 1 1/2" - 4" 1 1/2"DOMESTIC COLD WATER 1/2" - 1 1/4" 1/2"DOMESTIC COLD WATER 1 1/2" - 4" 1"
5. DOMESTIC WATER PIPING INSULATION, JACKETS, COVERINGS, SEALERS, MASTICS AND ADHESIVES AREREQUIRED TO MEET A FLAME-SPREAD RATING OF 25 OR LESS AND A SMOKE-DEVELOPED RATING OF 50 OR LESS,AS TESTED BY ASTM E84 (NFPA 255) METHOD AND SHALL BE PLENUM RATED.
6. PROVIDE FULL PORT, BALL TYPE SHUT-OFF VALVES AND INSTALL IN A LOCATION THAT PERMITS ACCESSFOR SERVICE WITHOUT DAMAGE TO THE BUILDING OR FINISHED MATERIALS.
7. PROTECT COPPER PIPING AGAINST CONTACT WITH DISSIMILAR METALS. ALL HANGERS, SUPPORTS,ANCHORS AND CLIPS SHALL BE COPPER OR COPPER PLATED. WHERE COPPER PIPING IS CARRIED ONTRAPEZE HANGERS WITH OTHER PIPING, PROVIDE A PERMANENT ELECTROLYTIC ISOLATION MATERIAL TOPREVENT CONTACT WITH DISSIMILAR OTHER METALS.
8. PROTECT COPPER PIPING AGAINST CONTACT WITH ALL MASONRY. WHERE COPPER IS SLEEVED THROUGHMASONRY, PROVIDE COPPER OR RED BRASS SLEEVES. WHERE COPPER MUST BE CONCEALED IN ORAGAINST MASONRY PARTITIONS, PROVIDE A HEAVY COATING OF ASPHALTIC ENAMEL ON THE COPPERPIPING AND 15# ASPHALT SATURATED FELT BETWEEN THE PIPING AND THE MASONRY PARTITION.
9. DOMESTIC WATER PIPING SHALL BE SLOPED FOR DRAINAGE WITH DRAIN VALVES INSTALLED AT LOW POINTS.
SANITARY WASTE / VENT AND STORM PIPING:
1. SANITARY WASTE AND STORM DRAIN PIPING BELOW GRADE: PROVIDE SERVICE WEIGHT CAST IRON HUBAND SPIGOT PIPE (ASTM A 74) WITH COMPRESSION JOINTS (CISPI HSN) AND NEOPRENE GASKETS (ASTM C564) OR NO-HUB PIPE AND FITTINGS (CISPI 301) WITH NEOPRENE GASKET/STAINLESS STEEL CLAMP JOINTS(CISPI 310) OR PROVIDE SCHEDULE 40 PVC PIPE AND SOCKET FITTINGS (ASTM D 2665) WITH SOLVENT WELDJOINTS (ASTM D2855). FOAM CORE PVC PIPE IS NOT APPROVED.
2. SANITARY WASTE/VENT AND STORM DRAIN PIPING ABOVE GRADE: PROVIDE SERVICE WEIGHT CASTIRON NO-HUB PIPE AND FITTINGS (CISPI 301) WITH NEOPRENE GASKET AND STAINLESS STEEL CLAMP JOINTS(CISPI 310). DO NOT INSTALL PVC PIPING IN RETURN AIR PLENUMS.
3. SLOPE SANITARY WASTE AND STORM DRAIN PIPING AT 1/4" PER FOOT MINIMUM FOR PIPING 2 1/2" AND SMALLERAND 1/8" PER FOOT MINIMUM FOR PIPING 3" AND LARGER UNLESS NOTED OTHERWISE. SLOPE ALL KITCHENWASTE PIPING AT 1/4" PER FOOT MINIMUM.
4. PROVIDE CLEAN-OUTS AT THE BASE OF SANITARY WASTE STACKS AND STORM DRAIN RISERS AND AT EVERYTURN IN PIPING IN EXCESS OF 45° AND NO FURTHER THAN 100'-0" APART IN A LOCATION THAT PERMITS ACCESSFOR SERVICE WITHOUT DAMAGE TO THE BUILDING OR FINISHED MATERIALS.
5. PROVIDE FLOOR CLEANOUTS WITH TOPS DESIGNED TO MATCH SPECIFIC FLOOR FINISHES SUCH ASCARPET, TILE, ETC. YARD CLEANOUTS SHALL BE PROVIDED IN AN 18"x18"x6" CONCRETE PAD.
6. WHERE WASTE PIPING IS EXPOSED IN REST ROOM AREAS, PROVIDE CHROME PLATED BRASS PIPING,REMOVABLE P-TRAPS, MATCHING STOPS AND ESCUTCHEONS FOR ALL LAVATORIES.
7. INSULATE MECHANICAL ROOM FLOOR DRAIN BODIES, P-TRAP AND HORIZONTAL DRAIN PIPING ABOVEGRADE WITH 1" THICK GLASS FIBER INSULATION WITH VAPOR BARRIER AND JACKET.
8. INSULATE ROOF DRAIN BODIES AND HORIZONTAL PRIMARY AND SECONDARY STORM DRAIN PIPING ABOVEGRADE WITH 1" THICK GLASS FIBER INSULATION WITH VAPOR BARRIER AND JACKET.
9. PIPING INSULATION, JACKETS, COVERINGS, SEALERS, MASTICS AND ADHESIVES ARE REQUIRED TO MEET AFLAME-SPREAD RATING OF 25 OR LESS AND A SMOKE-DEVELOPED RATING OF 50 OR LESS, AS TESTED BYASTM E84 (NFPA 255) METHOD.
10. SUMP PUMP DISCHARGE PIPING: PROVIDE SCHEDULE 40 GALVANIZED STEEL PIPE (ASTM A53) ANDGALVANIZED 150 POUND MALLEABLE IRON FITTINGS (ASME B16.3) WITH THREADED JOINTS. SLOPE SUMPDISCHARGE LINE AT 1% SLOPE TOWARDS SUMP PUMP.
NATURAL GAS PIPING:
1. NATURAL GAS PIPING AND FITTINGS ABOVE GRADE: SCHEDULE 40 BLACK STEEL PIPING, TYPE S, SEAMLESS,GRADE B (ASTM A 53) AND 150 PSI MALLEABLE BLACK IRON FITTINGS, GRADE 32510, (ASTM B 16.3) OR FORGEDSTEEL WELDING TYPE FITTINGS (ASTM A234). PROVIDE THREADED JOINTS FOR PIPE 2" AND SMALLER. PROVIDEWELDED JOINTS (ASME B31.9) FOR PIPE 2 1/2" AND LARGER.
2. NATURAL GAS PIPING AND FITTINGS OUTSIDE BELOW GRADE: SCHEDULE 40 BLACK STEEL, TYPE S, SEAMLESS,GRADE B (ASTM A 53) AND FORGED STEEL WELDING TYPE FITTINGS (ASTM A234) WITH (AWWA C105)POLYETHYLENE JACKET OR DOUBLE LAYER, HALF LAPPED 10 MIL POLYETHYLENE TAPE. PROVIDE WELDEDJOINTS (ASME B31.9) FOR ALL UNDERGROUND PIPE.
3. SPACE GAS PIPING HANGER RODS 7'-0" ON CENTER MAXIMUM AND SPACE TRANSVERSE BRACING 20'-0" ONCENTER MAXIMUM. TRANSVERSE BRACING FOR ONE SECTION MAY ACT AS LONGITUDINAL BRACING FOR THEPIPE SECTION CONNECTED TO IT IF THE BRACING IS INSTALLED WITHIN 24" OF THE ELBOW OR TEE. COORDINATEHANGER LOCATIONS WITH STRUCTURAL DRAWING DETAILS.
4. PROVIDE A.G.A. CERTIFIED SHUT-OFF VALVES MINIMUM, 125 PSI RATED, NON- LUBRICATED PLUG TYPE WITHBRONZE BODY AND BRONZE PLUG, STRAINERS AND REGULATORS (AS RECOMMENDED BY THE EQUIPMENTMANUFACTURER) FOR ALL EQUIPMENT CONNECTED TO THE NATURAL GAS SYSTEM.
5. GAS PRESSURE REGULATORS SHALL BE CSA CERTIFIED (Z21.80) FOR 2 PSI INLET PRESSURE, OUTLET PRESSURERANGE OF 7 TO 11 INCHES WATER COLUMN. WHEN USING VENTLESS REGULATORS, MOUNT REGULATOR IN AHORIZONTAL UPRIGHT POSITION. IF VENTED TYPE REGULATORS ARE USED, INSTALL VENT PIPING (FULL SIZEOPENING) FROM GAS PRESSURE REGULATORS TO OUTDOORS AND TERMINATE IN WEATHERPROOF HOOD.
6. PAINT ALL GAS PIPING WITH 2 COATS OF YELLOW ENAMEL PAINT APPLIED WITH A BRUSH (2 MIL THICKNESSMINIMUM). STENCIL "GAS" ON PIPE AT 12'-0" CENTERS FOR ALL LOW PRESSURE PIPING (0.5 PSI). STENCIL"2-PSI GAS" ON PIPE AT 6'-0" CENTERS FOR 2 PSI GAS PIPING.
GENERAL REQUIREMENTS:
1. PLUMBING WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE COLORADO STATE PLUMBINGCODE AND WITH THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION.
2. GENERAL AND SPECIAL CONDITIONS ARE HEREBY MADE AN INTEGRAL PART OF THE PLUMBINGSPECIFICATIONS INSOFAR AS THE GENERAL AND SPECIAL CONDITIONS ARE APPLICABLE TO THEPLUMBING WORK, UNLESS OTHERWISE SPECIFIED.
3. SCOPE: PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT REQUIRED FOR THE COMPLETION ANDOPERATION OF ALL PLUMBING SYSTEMS IN ACCORDANCE WITH ALL APPLICABLE CODES.
4. PERMITS: APPLY AND PAY FOR ALL NECESSARY PERMITS, FEES AND INSPECTIONS REQUIRED BY ANYPUBLIC AUTHORITY HAVING JURISDICTION. ACREAGE CHARGES, FACILITIES CHARGES AND BONDPROPERTY ASSESSMENTS ARE NOT TO BE CONSTRUED TO BE A PART OF THIS CONTRACT.
5. WARRANTY: PROVIDE A ONE YEAR WARRANTY, FROM THE DATE OF ACCEPTANCE OF WORK BY THEOWNER, FOR ALL PLUMBING MATERIALS AND EQUIPMENT.
6. COORDINATE ALL PLUMBING PIPING LOCATIONS, ROUGH-IN LOCATIONS AND EQUIPMENT LOCATIONS WITHOTHER TRADES TO AVOID CONFLICTS AND INTERFERENCES. FINAL PIPING AND EQUIPMENT LOCATIONSSHALL BE A CODE COMPLIANT INSTALLATION FOR ALL TRADES.
7. FIELD VERIFY PROPER OPERATION OF EXISTING SYSTEMS BEFORE STARTING CONSTRUCTION. NOTIFYTHE ARCHITECT / ENGINEER OF RECORD OF ANY PROBLEMS OR DISCREPANCIES BETWEEN THECONSTRUCTION DOCUMENTS AND EXISTING CONDITIONS AND/OR ANY POTENTIAL PROBLEMS OBSERVEDBEFORE CONTINUING WORK IN THE EFFECTED AREAS.
8. CUT WALLS, FLOORS AND CEILINGS AS REQUIRED FOR INSTALLATION OF PLUMBING WORK. ALL CUTTINGSHALL BE HELD TO A MINIMUM. PATCH AND FINISH SURFACES TO MATCH ADJOINING SURFACES.
9. PLUMBING PLANS SHALL NOT BE SCALED. REFERENCE THE ARCHITECTURAL PLANS FOR ALL LOCATIONSOF PLUMBING FIXTURES, WALLS, DOORS, WINDOWS, ETC.
10. PLUMBING PIPING SHALL BE LOCATED CONCEALED IN WALLS, PARTITIONS OR ABOVE CEILINGS UNLESSNOTED OTHERWISE. PLUMBING PIPING IN EXPOSED AREAS SHALL BE RUN TIGHT TO UNDERSIDE OFSTRUCTURE.
11. PLUMBING PIPING, VENTS, ETC. EXTENDING THROUGH EXTERIOR WALLS AND/OR THE ROOF SHALL BE FLASHEDAND COUNTER FLASHED IN A WATERPROOF MANNER. COORDINATE FLASHING WITH THE GENERALCONTRACTOR.
12. DO NOT INSTALL PLUMBING PIPING IN AREAS SUBJECT TO FREEZING TEMPERATURES. INSTALL PLUMBINGPIPING SHOWN IN EXTERIOR WALLS ON THE CONDITIONED SIDE OF THE WALL INSULATION.
13. PROVIDE NON-CONDUCTING DIELECTRIC UNIONS WHENEVER CONNECTING DISSIMILAR METALS.
14. ATTACH HANGERS TO STRUCTURE, HANGERS SHALL NOT ATTACH TO THE DECK.15. PROVIDE ACCESS DOORS FOR VALVES, WATER HAMMER ARRESTORS, TRAP PRIMERS, ETC. CONCEALED IN
MASONRY WALLS, GYPBOARD WALLS AND/OR CEILINGS THAT WILL REQUIRE MAINTENANCE ACCESS. ACCESSDOORS SHALL BE LOCATED IN CEILILNG ONLY.
16. PLUMBING SYSTEMS INCLUDE, BUT ARE NOT LIMITED TO:PLUMBING FIXTURES AND EQUIPMENT, FIRE STOPPING, SEISMIC BRACING, PIPE IDENTIFICATION, DOMESTIC WATERSYSTEM, SANITARY WASTE AND VENT SYSTEM, STORM DRAIN SYSTEM, NATURAL GAS SYSTEM
PLUMBING FIXTURES AND EQUIPMENT:
1. PROVIDE COMPLETE PLUMBING FIXTURES AND EQUIPMENT. INCLUDE SUPPLIES, STOPS, VALVES,FAUCETS, DRAINS, TRAPS, TAIL PIECES, ESCUTCHEONS, ETC.
2. PLUMBING FIXTURES AND EQUIPMENT SHALL BE INSTALLED PER THE MANUFACTURER'SRECOMMENDATIONS AND INSTALLATION INSTRUCTIONS.
3. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH SUBSTITUTIONS TOSPECIFIED PLUMBING FIXTURES AND EQUIPMENT INCLUDING BUT NOT LIMITED TO; PROVIDING MAINTENANCEACCESS CLEARANCE, PIPING, ELECTRICAL, REPLACEMENT OF OTHER SYSTEM COMPONENTS, BUILDINGALTERATIONS, ETC. AND ANY MODIFICATIONS TO ASSOCIATED MECHANICAL, ELECTRICAL OR PLUMBINGSYSTEMS REQUIRED BY THE EQUIPMENTS INSTALLATION INSTRUCTIONS. ALL COSTS ASSOCIATED WITHSUBSTITUTIONS SHALL BE INCLUDED IN THE ORIGINAL BASE BID.
FIRE STOPPING:
1. FIRE STOP ALL PENETRATIONS, BY PIPING OR CONDUITS, OF FIRE RATED WALLS, FLOORS AND PARTITIONS.PROVIDE A DEVICE(S) OR SYSTEM(S) WHICH HAS BEEN TESTED AND LISTED AS COMPLYING WITH ASTM E-814AND INSTALL IN ACCORDANCE WITH THE CONDITIONS OF THEIR LISTING. PROVIDE A DEVICE(S) OR SYSTEM(S)WITH AN 'F' RATING EQUAL TO THE RATING OF THE ASSEMBLY BEING PENETRATED. REFER TO ARCHITECTURALPLANS FOR WALL AND FLOOR TYPES.
SEISMIC BRACING:
1. PROPERLY SUPPORT AND BRACE VERTICALLY AND HORIZONTALLY ALL PIPING, APPARATUS, EQUIPMENT,ETC. IN ACCORDANCE WITH APPLICABLE CODES TO PREVENT EXCESSIVE MOVEMENT DURING SEISMICCONDITIONS.
PIPE IDENTIFICATION:
1. PIPE IDENTIFICATION SHALL MATCH THE FACILITY'S EXISTING STANDARD. IF NO STANDARD EXISTS, THENTHE PIPE IDENTIFICATION SHALL BE IN ACCORDANCE WITH ANSI A13.1.
2. PROVIDE PIPING LABELS FOR ALL PLUMBING PIPING. PIPING LABELS SHALL BE ACRYLIC FACED,WRAP-AROUND TYPE. EACH LABEL SHALL INDICATE THE PIPING CONTENTS, DIRECTION OF FLOW ANDSHALL BEAR THE MANUFACTURER'S STANDARD COLOR FOR THE SERVICE INDICATED.
61-113
33-60
12-32
1-11
D
C
B
A
155-330 F
E114-154
1"
1 1/4"
1/2"
3/4"
2"
1 1/2"
SA-D
SA-C
SA-B
SA-A
SA-F
SA-E
DRAWINGSYMBOL
FIXTURE UNITSPDI WH201STANDARDDESIGNATION
ARRESTORSIZE
- SIOUX CHIEF- WATTS- PPP INC.
INSTALL SHOCK ARRESTORSPER PDI WH201 GUIDELINES
REMARKS
APPROVEDMANUFACTURERS
ESD
G
SD
SD
SA-#HOSE BIBB/WALL HYDRANT
PRESSURE REDUCING/REGULATING VALVE
BALANCING VALVE / CIRCUIT SETTER
GAS COCK
END OF LINE CLEAN OUT
ROOF DRAIN
STORM DRAIN PIPING - ABV. CEILING
WALL CLEAN OUT
YARD CLEAN OUT
FLOOR CLEAN OUT
NATURAL GAS PIPING
CHECK VALVE
HOT WATER RETURN PIPING
STORM DRAIN PIPING - BEL. GRADE
DESCRIPTIONNEW PIPING
SANITARY WASTE PIPING
HOT WATER PIPING
SANITARY VENT PIPING
COLD WATER PIPING
PIPE CONTINUES
BALL VALVE
FLOOR DRAIN
ELBOW UP
ELBOW DOWN
PIPE REDUCER
EMERGENCY STORM DRAIN PIPING
SHOCK ARRESTOR - SUFFIX INDICATES PDI SIZE
THERMOMETER
PLUMBING LEGENDABBR.
CW
HW
HWR
W
V
SD
SD
ESD
G
CV
-
-
-
-
BV
-
PRV
-
FCO
WCO
CO
YCO
FD
RD
HB
SA
-
PIPE CAP-
ADDITIONAL ABBREVIATIONS
PRESSURE GAUGE-
IN-LINE PUMP-
DIRECTION OF FLOW-
ABV ABOVEAFF ABOVE FINISHED FLOORAVTR ACID VENT THRU ROOFBAS BUILDING AUTOMATION SYSTEMBEL BELOWBF BARRIER FREEBFF BELOW FINISHED FLOORBTUH BRITISH THERMAL UNIT / HOURCFH CUBIC FEET PER HOURCLG CEILINGCONTCONTINUATIONDFU DRAINAGE FIXTURE UNIT (WASTE)DN DOWNEX EXISTINGFFE FINISHED FLOOR ELEVATIONFIN FINISHFL FLOORFR FROMFU FIXTURE UNITSGPM GALLONS PER MINUTEHP HORSE POWERINV INVERT ELEVATIONIW INDIRECT WASTE
KW KILOWATTLAV LAVATORYMBH 1,000 BTUHMH MOUNTING HEIGHTPH PHASEPSI POUNDS PER SQUARE INCHSF SQUARE FEETT&P TEMPERATURE AND PRESSURETW TEMPERED WATERTYP TYPICALUR URINALVB VACUUM BREAKERVLV VALVEVTR VENT THRU ROOFWC WATER COLUMN
EC ELECTRICAL CONTRACTORFSEC FOOD SERVICE EQUIP. CONTRACTORGC GENERAL CONTRACTORMC MECHANICAL CONTRACTORPC PLUMBING CONTRACTOR
1
A
B
C
D
E
3 4 5 62
DescriptionDateRev #
Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.
PROJECT NO:
Revision Schedule
DRAWN BY: CHECKED BY:
SONIC DEVELOPMENT, LLC
Charlotte, North Carolina
E N G I N E E R I N G I N C
Eng. of Record: License No.:
M VEIGH MANGUMC &1610 East Morehead Street, Suite 100
Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036
2/6/2015 11:56:11 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt
2/6/2015 11:56:11 AM
2015-02-06
13554
ISSUED FOR PERMIT
MERCEDES-BENZ OFDENVER
Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard
Glendale, CO 80246
P-001Author Checker
PLUMBING NOTES & LEGENDS
48552Larry P. McWilliams
EXTERIORDETAILBAYS
104
SERVICEDRIVE
103
CAFE130
BREAKROOM
117
WOMENS134
MENS132
CASHIER /LOANERRENTAL
131
KIDS128
WARRANTY124
SERVICEADMIN
126 MENS122
LOCKERROOM
123
WOMENS121
JANITOR133
P-6
P-4
P-1A P-2A P-3 P-3 P-3 P-3 P-1AP-1
3/4" HW
2" CW
3/4" HW2" CW
2" CW
1 1/2" CW
1 1/2" CW
1/2" CW
1" CW
1/2" HW
3/4"CW UPTO HB4
HB1HB1
2 1/2" CW
2 1/2"CW UP ALONGWALL TO 48"AFF.
PROVIDE RPZ BACKFLOWDEVICE EQUAL TO WILKINS375A. PROVIDE FUNNEL DRAINAND INDIRECT WASTE PIPINGTO SPILL @ 12"AFG
2 1/2"CW UPTO STRUCTURE
2"CW RISER
12
1" CW
2" CW
2" CW
2 1/2" CW
2 1/2" CW
2 1/2" CW
3/4" CW1/2" CW
2" CW
3/4" CW
EXTEND 2 1/2"CW TO 5'-0"OUTSIDE BUILDING. SEECIVIL UTILITY PLAN FORCONTINUATION.
P-2A
P-3A
P-1P-1A
P-10
EWH-1
STORAGE130A
2 1/2"GAS RISER
1 1/4"GAS DNTO BOILER(500 CFH)
G
GGGGGG
GG
GG
G
G
1 1/4" G
2" G
1 1/4" G
2" G
2" G
2" G
2 1/2" G
2 1/2" G
1 1/4" G
1 1/4" G
1 1/4" G
GAS MAIN TO METERBELOW GRADE BY GAS CO.
GAS METER (BY GAS CO)(3,014 CFH @ 2 PSIG)
2 1/2"GAS THROUGH WALL TOSTRUCTURE.
GAS SIZING BASED ON TABLE 402.4(3)(500 FEET) OF THE 2012 EDITION OFTHE IPC FUEL GAS CODE. TOTAL CFH 4014
3/4" CW3/4" CW
3/4"CW TO HOSE REEL(PROVIDED BY OTHERS)TYPICAL 13 LOCATIONS
HOSE REEL
3/4" CW
HOSE REEL
1/2" CW
1/2"CW DN IN WALL TOCOFFEE MACHINE. PROVIDEVACUUM BREAKER.
1/2"CW RISER
P-1A P-3A
P-111A2
INSTALL BACKFLOW DEVICE PERCITY OF GLENDALE STANDARDS.
LOCATION OF FIRE RISER
12
P-6
P-4
P-1A P-2A P-3 P-3
P-3 P-3 P-1AP-1
P-2AP-3A
P-1P-1A
P-10
EWH-1
P-1A P-3A
1/2" HW
1/2" CW3/4" CW
3/4" HW
3/4" HW
2" CW 1 1/2" CW 1 1/2" CW
1/2" HW
1/2" CW
1 1/4" CW
1 1/4" CW1" CW P-3A
2" CW
2" CW
1 1/2" CW
2" CW
1 1/4" CW
2" CW 2" CW 1" CW
1/2" CW
1 1/4" CW
1 1/2" CW
1/2" HW2" CW
1/2" HW 1/2" CW
3/4" HW
3/4" CW
3/4" CW
1/2" HW
1 1/4" CW
1/2" HW3/4" CW
2" CW
2" CW
1/2"CW DN IN WALL TOCOFFEE MACHINE. PROVIDEVACUUM BREAKER.
SA-A
SA-A
SA-A
SA-A
SA-A
1
A
B
C
D
E
3 4 5 62
DescriptionDateRev #
Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.
PROJECT NO:
Revision Schedule
DRAWN BY: CHECKED BY:
SONIC DEVELOPMENT, LLC
Charlotte, North Carolina
E N G I N E E R I N G I N C
Eng. of Record: License No.:
M VEIGH MANGUMC &1610 East Morehead Street, Suite 100
Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036
2/6/2015 11:56:22 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt
2/6/2015 11:56:22 AM
2015-02-06
13554
ISSUED FOR PERMIT
MERCEDES-BENZ OFDENVER
Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard
Glendale, CO 80246
P-111AAuthor Checker
DOMESTIC WATER PLAN - LOWERLEVEL - AREA A
48552Larry P. McWilliamsSCALE: 1/8" = 1'-0"P-111A
1
DOMESTIC WATER PLAN - LOWER LEVEL -AREA A
SCALE: 1/4" = 1'-0"P-111A
2 ENLARGED LOWER LEVEL PLUMBING PLAN
EXTERIORDETAILBAYS
104
SERVICEDRIVE
103
BREAKROOM
117
CAFE130
CASHIER /LOANERRENTAL
131
MENS132
WOMENS134
KIDS128
SERVICEADMIN
126 MENS122
LOCKERROOM
123
WARRANTY124
WOMENS121
JANITOR133
A
B
B.5
C
D
E
F
F.9G
5.1
5
4
3.23
21.1
1
INTERIORDETAIL BAY
105
JAN.118
ELEVATOR1
E101
LANE MGR102
SERVICEMGR
106QUICKLUBE
107
FUTUREALIGNMENT
BAY136
SERVICEWRITERS
101
SERVICEDRIVE
CANOPY100
FCO
FCO
FCO
3"V UP
YCO
12
FCO
FCO
FCO
YCO
4"SD UPTO AD1
4"SD UPTO AD1
4"SD UPTO AD1
4"SD UPTO AD1
4"SD UPTO AD1
6"SD RISER
6"SD DN
SDSDSD
SDSDSD
SDSD
SDSD
SD
SDSDSDSD
10"SD RISER
EXTEND 4"S TO 5'-0"OUTSIDE BUILDING. SEECIVIL UTILITY PLAN FORCONTINUATION.
EXTEND 4"S TO 5'-0"OUTSIDE BUILDING. SEECIVIL UTILITY PLAN FORCONTINUATION.
4"S STACK
4" S
4" S 4" S4" S3" S
4" S
4" S
4" S
3" S
4" S
3" S
3"FD2
3"FD2
3"FD23"FD2 3"FD2
2"V RISER
2" V
4" S
4" S
4" S 2" V
4" S
4" S
4" S
4" S
4" S
3" S
4" S
4" S
4" S 4" S
3" S
4" SD4" SD4" SD
2" V
2" V
1 1/2" V 4" S4" S4" S
4" S
4" SD
4" S
4" S3" V
4" S
3" V
4" S
3" V
4" S
4" S
4" S
4" S
3" V4" S
2" V 2" V4" S FCO4" S
1 1/2" V 2" S
2"FD1
SD
10" SD
4" S
PROVIDE 24"X24"X72"DEEPSUMP BASIN WITH 4"FD1 W/DOME STRAINER IN BOTTOMOF PIT. PROVIDE HEAVY DUTYGRATE OVER PIT.
4"S TO SPILL INDIRECTLYINTO SUMP PIT.
2"V UP
3"FD2 3"FD2
3" S 3" S 3" S
4" SD
4" SD
6" SD
6" SD 6" SD 6" SD
6" SD
6" SD
6" SD
6" SD
6" SD2" S
2"S UP
2"S DN IN WALL TO BELOWSLAB.
2"FD12" V
2"FD1
2" S 2" V
2"FD1
3"FD2
3" S
SEE CIVIL DRAWINGS FOR OIL WATER SEPARATOR.PC TO PROVIDE PROCEPTOR OMC-1500, REINFORCEDFIBERGLASS PLASTIC, 819 GALLONS OF OIL STORAGECAPACITY, MANHOLE EXTENSIONS, OR EQUAL.COORDINATE LOCATION WITH UTILITY CONTRACTOR.PROVIDE 2" CONNECTED TO BUILDING VENT SYSTEM.
2" V
2"V TO OIL/WATERSEPARATOR
NOTE:PROVIDE CLEANOUT ATTHE BASE OF ALL RISERSAND STACKS.
P-6
P-4
P-1A P-2A P-3 P-3 P-3 P-3 P-1AP-1
P-2A
P-3A
P-1P-1A
P-10
2" S
2" S
2" V
2" V
6"SD TO SPILL @ 22"AFG.PROVIDE ZURN Z-199DCOR EQUAL
1
A
B
C
D
E
3 4 5 62
DescriptionDateRev #
Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.
PROJECT NO:
Revision Schedule
DRAWN BY: CHECKED BY:
SONIC DEVELOPMENT, LLC
Charlotte, North Carolina
E N G I N E E R I N G I N C
Eng. of Record: License No.:
M VEIGH MANGUMC &1610 East Morehead Street, Suite 100
Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036
2/6/2015 11:56:33 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt
2/6/2015 11:56:33 AM
2015-02-06
13554
ISSUED FOR PERMIT
MERCEDES-BENZ OFDENVER
Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard
Glendale, CO 80246
P-111BAuthor Checker
SANITARY & VENT PLAN - LOWERLEVEL - AREA A
48552Larry P. McWilliamsSCALE: 1/8" = 1'-0"P-111B
1
SANITARY & VENT PLAN - LOWER LEVEL -AREA A
SERVICEBAYS
116
UNITREPAIRS
TOOLEQUIPMENT
113STAIR 102
S102
3/4"CW UPTO HB2
12
1" CW1" CW
1" CW1" CW
3/4"CW RISER
1 1/4"GAS DNTO BOILER(500 CFH)
GG
GG
1 1/4" G
1 1/4" G1 1/4" G
3/4" CW
HOSE REEL
HOSE REEL HOSE REELHOSE REEL
HOSE REEL HOSE REEL
HOSE REEL
HOSE REEL
HOSE REEL
3/4" CW
3/4" CW
3/4" CW
3/4" CW3/4" CW
3/4" CW
3/4" CW
3/4" CW
3/4" CW
3/4" CW
1
A
B
C
D
E
3 4 5 62
DescriptionDateRev #
Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.
PROJECT NO:
Revision Schedule
DRAWN BY: CHECKED BY:
SONIC DEVELOPMENT, LLC
Charlotte, North Carolina
E N G I N E E R I N G I N C
Eng. of Record: License No.:
M VEIGH MANGUMC &1610 East Morehead Street, Suite 100
Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036
2/6/2015 11:56:40 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt
2/6/2015 11:56:40 AM
2015-02-06
13554
ISSUED FOR PERMIT
MERCEDES-BENZ OFDENVER
Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard
Glendale, CO 80246
P-111CAuthor Checker
DOMESTIC WATER PLAN - LOWERLEVEL - AREA B
48552Larry P. McWilliamsSCALE: 1/8" = 1'-0"P-111C
1
DOMESTIC WATER PLAN - LOWER LEVEL -AREA B
SERVICEBAYS
116
UNITREPAIRS
TOOLEQUIPMENT
113
STAIR 102S102
A
B
B.5
C
D
E
F
F.9G
11109
8
76.9
SPECIALTOOLS
109
EQUIPMENT112
SHOPFOREMEN
108
ALIGNMENTBAY115
PARTS LIFTE102
TECHPARTS
111
FASTMOVINGPARTS
110
ELECTRICAL114
12
FCO
FCO
6"SD RISER
4"SD UPTO AD1
8"SD RISER DN
EXTEND 8"SD TO 5'-0"OUTSIDE BUILDING. SEECIVIL UTILITY PLAN FORCONTINUATION.
SDSD
SDSD
SDSDSD
SDSD
EXTEND 10"SD TO 5'-0"OUTSIDE BUILDING. SEECIVIL UTILITY PLAN FORCONTINUATION.
3"FD2 3"FD2
3"FD2 3"FD2
3"FD2 3"FD2
3"FD2
4" S 4" S
3" S
4" S
3" S
4" S
4" S
3" S 3" S 3" S
4" S
4" S
3" S3" S 3" S
3" S
8" SD
8" SD
8" SD
6" SD
6" SD
4" SD4" SD
FCO
3"S STACK
SD
3"FD2
3" S 3" S
NOTE:PROVIDE CLEANOUT ATTHE BASE OF ALL RISERSAND STACKS.
SEE DETAIL #10/P202FOR CONDENSATE DRAINBOX.
2" S
2" V
1
A
B
C
D
E
3 4 5 62
DescriptionDateRev #
Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.
PROJECT NO:
Revision Schedule
DRAWN BY: CHECKED BY:
SONIC DEVELOPMENT, LLC
Charlotte, North Carolina
E N G I N E E R I N G I N C
Eng. of Record: License No.:
M VEIGH MANGUMC &1610 East Morehead Street, Suite 100
Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036
2/6/2015 11:56:50 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt
2/6/2015 11:56:50 AM
2015-02-06
13554
ISSUED FOR PERMIT
MERCEDES-BENZ OFDENVER
Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard
Glendale, CO 80246
P-111DAuthor Checker
SANITARY & VENT PLAN - LOWERLEVEL - AREA B
48552Larry P. McWilliamsSCALE: 1/8" = 1'-0"P-111D
1
SANITARY & VENT PLAN - LOWER LEVEL -AREA B
BDC206
TELE /DATA
208
LOCKER207
TRAINING209
BREAKROOM
211
CORRIDOR210
OFFICE212
OFFICEMGR
214
OFFICE213
PARTS MGR234
STAIR 202S202
AIRCOMPRESSOR
/ OILSTORAGE
235
SHIPPINGAND
RECEIVING238
PARTSSTORAGE
233
SALESMGRS
227COPY / KEY
226
RETAILPARTS
225
SHOWROOM204
STAIR 201S201
GENERALMANAGER
228F&I229
F&I230
LOUNGE231
VEHICLEDISPLAY
205
MENS222
STORAGE216
COPY / FAX/ STORAGE
215CONFERENCE
217
SALES219
WOMENS220
JAN.221
3/4"CW RISER
HB2
3/4"CW RISER
HB2
3/4"CW UPTO HB4
12
PARTS LIFTE202
3/4" CW
3/4" CW
3/4" CW
3/4"CW UP TOMECHANICAL CONNECTIONON ROOF. COORDINATEWITH M.C.
3/4"CW UP TOMECHANICAL CONNECTIONON ROOF. COORDINATEWITH M.C.
3"GAS RISER
1/2"CW DN IN WALL TOCOFFEE MACHINE. PROVIDEVACUUM BREAKER.
P-112A2 3/4" CW
MENS222
SALES219
WOMENS220
JAN.221
2"CW RISER
3/4"CW UPTO HB3
P-1A
P-1
P-1
P-3
P-3
P-9
P-3
P-3
P-1
P-1A
P-2A
P-4
P-6
1 1/4" CW
1 1/2" CW
1 1/2" CW
2" CW1/2" HW
1/2" HW1/2" CW
1" CW
1/2" CW
1 1/2" CW
3/4" HW
1 1/2" CW
1 1/2" CW
3/4" CW
3/4" CW
1/2"CW DN IN WALL TOCOFFEE MACHINE. PROVIDEVACUUM BREAKER.
EWH-1
1/2" HW
1/2" HW
3/4" CW
1/2" CW
SA-B
SA-B
SA-A
1
A
B
C
D
E
3 4 5 62
DescriptionDateRev #
Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.
PROJECT NO:
Revision Schedule
DRAWN BY: CHECKED BY:
SONIC DEVELOPMENT, LLC
Charlotte, North Carolina
E N G I N E E R I N G I N C
Eng. of Record: License No.:
M VEIGH MANGUMC &1610 East Morehead Street, Suite 100
Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036
2/6/2015 11:57:02 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt
2/6/2015 11:57:02 AM
2015-02-06
13554
ISSUED FOR PERMIT
MERCEDES-BENZ OFDENVER
Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard
Glendale, CO 80246
P-112AAuthor Checker
DOMESTIC WATER PLAN - UPPERLEVEL
48552Larry P. McWilliams
SCALE: 1/8" = 1'-0"P-112A
1 DOMESTIC WATER PLAN - UPPER LEVEL
SCALE: 1/4" = 1'-0"P-112A
2 ENLARGED UPPER LEVEL PLUMBING PLAN
BDC206
VEHICLEDISPLAY
205
TELE /DATA
208
LOCKER207
TRAINING209
BREAKROOM
211
CORRIDOR210
OFFICE212
OFFICE213
OFFICEMGR
214
COPY / FAX/ STORAGE
215
CONFERENCE217
SALES219
STORAGE216
WOMENS220
JAN.221
MENS222
STAIR 201S201
RETAILPARTS
225
COPY / KEY226
SALESMGRS
227
PARTSSTORAGE
233
GENERALMANAGER
228F&I229
F&I230
LOUNGE231
SHIPPINGAND
RECEIVING238
AIRCOMPRESSOR
/ OILSTORAGE
235STAIR 202S202
PARTS MGR234
SHOWROOM204
A
B
B.5
C
D
E
F
F.9G
9
8
76.9
5.1
5
4
3.23
21.1
1
2"V UPTO 2"VTR
PARTS LIFTE202
PARTSVESTIBULE
236
PARTSCLERKS
237
KIDS239
DOCUMENTCONTROL
ROOM218
LOUNGE223
DISPLAY224
OUTDOORSHOWROOM
200
NEW CARDELIVERY
232
SHOWROOM204
3"V UPTO 3"VTR
12
SDSDSDSDSDSDSDSDSD SD
2"V RISER
6"SD UPTO 6"SD1
6"SD UPTO 6"SD1
6"SD UPTO 6"SD1
6"SD UPTO 6"SD1
6"SD UPTO 6"SD1
10"SD RISERDOWN
6" SD8" SD10" SD8" SD8" SD6" SD
6" SD
SD SD
SD
4" SD 4" SD
4" SD
4" SD6"SD RISERDOWN
AD1 AD1 AD1
AD1 AD1 AD1
AD1
SD SD SD6" SD 6" SD
6"SD RISERDOWN
WCO
2" V
2" V
2" V
2" V
2" V 1 1/2" V
1 1/2" V
FCOP-1A
P-1
P-1
P-3
P-3
P-9
P-3
P-3
P-1
P-1A
P-2A
P-4
4"S DOWN
4" S
4" S
4" S
4" S
4" S
4" S
2" S
P-6
2"V RISER
3" S 3"FD1
2"V UPTO 2"VTR SEE DETAIL #10/P202
FOR CONDENSATE DRAINBOX.
2"FD1
2"FD1
2" V
2" S
2"FD1
1
A
B
C
D
E
3 4 5 62
DescriptionDateRev #
Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.
PROJECT NO:
Revision Schedule
DRAWN BY: CHECKED BY:
SONIC DEVELOPMENT, LLC
Charlotte, North Carolina
E N G I N E E R I N G I N C
Eng. of Record: License No.:
M VEIGH MANGUMC &1610 East Morehead Street, Suite 100
Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036
PROVIDE 6"SD1 WITHINTERNAL 3"WATER DAMPIPE TO UNDERSIDE OFCANOPY. TERMINATE WITHPERFORATED STAINLESSSTEEL COVER TO MATCHCANOPY FINISH.
6"SD1(1427 SQFT)
PROVIDE 6"SD1 WITHINTERNAL 3"WATER DAMPIPE TO UNDERSIDE OFCANOPY. TERMINATE WITHPERFORATED STAINLESSSTEEL COVER TO MATCHCANOPY FINISH.
6"SD1(2534 SQFT)
1
A
B
C
D
E
3 4 5 62
DescriptionDateRev #
Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.
PROJECT NO:
Revision Schedule
DRAWN BY: CHECKED BY:
SONIC DEVELOPMENT, LLC
Charlotte, North Carolina
E N G I N E E R I N G I N C
Eng. of Record: License No.:
M VEIGH MANGUMC &1610 East Morehead Street, Suite 100
Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036
PROVIDE ONLY PRODUCTS MADE BY THECLOSELY MATCHES THE SPECIFIED PRODUCT.PROVIDING THE MODEL WHICH MOSTTHE CONTRACTOR IS RESPONSIBLE FOR
MANUFACTURER'S LISTED.
T&S BRASS, DELTA, AMERICAN STANDARD
BRASSCRAFT, E.B.C.
CENTOCO, BENEKE, BEMIS
BRADFORD-WHITE, STATE, RHEEM
KOHLER, SLOAN
OASIS, HAWS, MURDOCHELKAY (WATER COOLERS)AO SMITH (WATER HEATERS)
MCGUIRE (SUPPLY STOPS)
CHURCH (TOILET SEATS)AMERICAN STANDARD (A.S.)
SLOAN COMMERCIAL (FAUCETS)ELKAY (S.S. SINKS) JUST
ZURN (FLOOR DRAINS, CLEANOUTS) JR SMITH, WADE, JOSAMSCHIER, ROCKFORD
ZURN, JR SMITH, MIFABACORN, WILLOUGHBYBRADLEY (MULTI STATION WASH SINKS)
WOODFORD (HYDRANTS)
PROCEPTOR (OIL/WATER SEPARATOR)
FLORESTONEFIAT (MOP SINK)
1
A
B
C
D
E
3 4 5 62
DescriptionDateRev #
Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.
PROJECT NO:
Revision Schedule
DRAWN BY: CHECKED BY:
SONIC DEVELOPMENT, LLC
Charlotte, North Carolina
E N G I N E E R I N G I N C
Eng. of Record: License No.:
M VEIGH MANGUMC &1610 East Morehead Street, Suite 100
Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036
2/6/2015 11:57:37 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt
2/6/2015 11:57:37 AM
2015-02-06
13554
ISSUED FOR PERMIT
MERCEDES-BENZ OFDENVER
Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard
Glendale, CO 80246
P-201Author Checker
PLUMBING SCHEDULES
48552Larry P. McWilliams
GAS PIPING
ROOF
DIELECTRICUNION
DIRTLEG
GAS COCKPITCH BACK TO SOURCE
ROOFTOPUNIT
GAS PRESSUREREGULATOR(2 PSI TO 7" W.G.)
DIELECTRICUNION
10 PIPE DIAMETERS (MIN.)
DIELECTRICUNION
CAPPEDPRESSURETEST PORT
ROOFTOP PIPING SUPPORTSEE DETAIL #11/P0.3
BY M.C.BY P.C.
NOTE:GAS PIPING AND SHUT-OFF VALVE SHALL BE BY PLBG. CONTR., DIRT LEG, REGULATOR,AND FINAL CONNECTION TO UNIT SHALL BE BY MECH. CONTR.
ADDITIONAL LAYEROF ROOF MEMBRANEAS CUSHION
GAS PIPING
MIRO PIPESTAND
UNION
3-R
3-R
2" 3-R 10'
15'2 1/2"
4" 4-R, 4-RAH 9'
13'3"
1 1/4" 1.5 8'
10'1.51 1/2"
1" 1.5 7'
6'1.53/4"
MAX. SPACINGMODEL NO.PIPE SIZE
3. DO NOT ATTACH PIPE STANDS TO ROOF.
2. PIPE STAND SHALL BE MIRO, IND. OREQUAL "PILLOWBLOCK" MODEL 1.5 (UPTO 1 1/2"), 3-R (UP TO 3"), AND 4-R &4-RAH FOR 4", 6-RAH (5 TO 6").
1. PIPING SHALL BE SUPPORTED AT ALLELBOWS AND TEES AND AT SPACINGSPECIFIED IN THE TABLE BELOW.
GG
(TYPICAL)
BY GAS CO. BY CONTRACTOR
4" CONCRETE PAD
FINISH GRADE
PRESSURE REGULATOR
SHUT-OFF VALVE(TYPICAL)
1 1/2" (1,254 CFH @ 2 PSI)
DIGITAL PLUSE OUTPUTGAS METER, SHUT-OFF VALVE ANDREGULATOR. CONTRACTOR SHALLCOORDINATE WITH LOCAL GAS UTILITY(PRIOR TO UTILITY WORK) FOR TOENSURE THE PROVISION OF A GAS METERWITH DIGITAL PULSE OUTPUT REQUIREDBUILDING AUTOMATION SYSTEM'SMEASUREMENT AND VERIFICATION.
10 PIPE DIAMETERS (MIN.)
CAPPED PRESSURETEST PORT
TO EQUIPMENTGAS TRAIN
GAS PIPING
DIELECTRICUNION (TYP)
GAS COCK GWH
FLOOR
GAS PRESSUREREGULATOR.(2 PSI TO .5 PSI)
DRIP LEG
GRID DRAINCONNECTOR.
36"
48"
18"
WALL
MOP (BY OTHERS)
HOSE BRACKET
FINISHED FLOOR.
MOP BASIN
APPLY SILICONESEALANT AROUNDTOP AND SIDES OFSINK AT ALL WALLS.
MOP HANGER (BY G.C.)
SERVICE FAUCETWITH VACUUMBREAKER.
30" HOSE
SADDLE
FOAM GLASS(AT SADDLE ONLY)
CLEVIS HANGER
INSULATION
PIPE
RUN RESTRAINING CABLES INFOUR DIRECTIONS AND SECURETO STRUCTURE TO PREVENTLATERAL MOVEMENT OF PIPES.(SEE SEISMIC RESTRAINT CODEFOR REQUIREMENT CRITERIA.)
GALVANIZED THREADED ROD,SECURE TO STRUCTURE.
LOCKING NUT
3"=1'-0"TYPICAL VENT THRU ROOF
VENT PIPE THRUROOF BY P.C.
SEALANT BY G.C.
ADHESIVE BY G.C.
ROOF INSUL.BY G.C.
FORMED PIPE FLASHINGBY G.C.
BALLASTED SINGLE PLYMEMBRANE ROOFING
ROOF DECK - SEE PLUMB.& MECH. DWGS. FORLOCATION AND NO. OFPENETRATIONS
4"
8"
FLOW
GRADE
VARI
ES
UNDERGROUND PIPING
CAST IRON PIPING1/8 BEND
CONCRETE
CLEANOUT BOX
CLEANOUT PLUG
COVER
STEEL CHANNEL SUPPORTBASE. SHALL MATCH SIZEOF WTR. HTR. DRAIN PAN
CORRUGATED STEELDECKING OR PLATETO MATCH THE SIZEOF DRAIN PAN
EWH-1
D
MECH EQUIPMENT
VENT PIPING(BY PLBG. CONTR.)
FULL SIZECONDENSATEDRAIN DOWN INWALL TO WASHERBOX CONNECTIONBY M.C.
REFRIGERANT PIPINGBY M.C.
FLOORWASTE PIPING(BY PLBG. CONTR.)
MOUNT UNIT @4'-0" A.F.F.
PROVIDE SOUIX CHIEF "OX BOX"696-3 W/696-CF DRAINAGEFUNNEL AND COVER MOUNTEDAT 48"AFF. GUY GREY ANDPLASTIC ODDITIES ARE EQUALS
1
A
B
C
D
E
3 4 5 62
DescriptionDateRev #
Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.
PROJECT NO:
Revision Schedule
DRAWN BY: CHECKED BY:
SONIC DEVELOPMENT, LLC
Charlotte, North Carolina
E N G I N E E R I N G I N C
Eng. of Record: License No.:
M VEIGH MANGUMC &1610 East Morehead Street, Suite 100
Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036
2/6/2015 11:57:49 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt
2/6/2015 11:57:49 AM
2015-02-06
13554
ISSUED FOR PERMIT
MERCEDES-BENZ OFDENVER
Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard
Glendale, CO 80246
P-202Author Checker
PLUMBING DETAILS
48552Larry P. McWilliams
SCALE: 1/8" = 1'-0"P-202
1 GAS CONNECTION SCHEMATIC
SCALE: 1/8" = 1'-0"P-202
2 GAS PIPING SUPPORT SCHEMATIC
SCALE: 1/8" = 1'-0"P-202
3 GAS SERVICE ENTRANCE
SCALE: 1/8" = 1'-0"P-202
4 GAS SERVICE PRV PIPING SCHEMATIC
SCALE: 1/8" = 1'-0"P-202
5 MOP BASIN AND ACCESSORIES
SCALE: 1/8" = 1'-0"P-202
6 PIPING HANGER SCHEMATIC
SCALE: 1/8" = 1'-0"P-202
7 VENT THRU ROOF DETAIL
SCALE: 1/8" = 1'-0"P-202
8 YARD CLEANOUT DETAIL
SCALE: 1/8" = 1'-0"P-202
9 WATER HEATER DETAIL EWH-1
SCALE: 1/8" = 1'-0"P-202
10 WALL MTD A/C UNIT CONDENSATE DRAIN
6"SD1
6"SD1
6"SD1
6"SD1
6"SD1
5"SD2
5"SD2
4"SD2
5"SD2
AD1
AD1
AD1
AD1
AD1
AD1
3"FD2
3"FD2
3"FD2
3"FD2
3"FD2
3"FD2
3"FD2
3"FD2
3"FD2
3"FD2
3"FD2
3"FD2
FCO
FCO FCO
FCO
FCO
FCO
FCO
FCO
FCO
FCO
WCO 3"FD2
FCO
3"VTR
2"VTR6" SD
8" SD
10" SD
8" SD
6" SD
10" SD
10" SD
4" S
2" V
4" S
4" S
4" S
4" S
2" V
4" S
4" S
3" S
4" S
4" S
4" S
4" S 3" S4" S
3" S
3" S4" S
8" SD
6" SD6" SD
4" S
3" S
3" S
3" S8" SD
4" S
4" S
4" S
4" SD
4" S
2" V
4" S
4" S
1 1/2" V2" V
2" V
2" V3" V3" V
3" V
4" S
6" SD
6" SD
3" S
4" S4" S
6" SD
4" SD
4" SD
4" SD
6" SD
6" SD
6" SD
6" SD
3" V
2" V2" V
2" V 2" V1 1/2" V
2" V
2" S4" S4" S
2" S
4" S
4" S
3" S
4" SD
3" S
4" S4" S
4" S
4" S
4" S
1 1/2" V
2" V
3"FD1
HB2
P-6
P-3A
P-2A
P-1
P-1A
P-4
P-6P-1A
P-10
P-3A
P-1A
P-9
P-1A
P-1
P-3P-9
P-3
P-1AP-1P-1P-3P-3
P-3P-3
P-9
P-2A
P-1P-1A
P-4
2"VTR
2" V
2" S
2" S
3"FD2
3"FD23" S
4" S
3" S
1" CW
1" CW2" CW
2 1/2" CW
2 1/2" CW
2 1/2" CW
2" CW
3/4" CW
2" CW3/4" CW
2" CW
1 1/2" CW
2" CW 1 1/2" CW
3/4" HW
1 1/4" CW3/4" CW
2" CW
2" CW
1 1/2" CW
1 1/2" CW 1/2" CW
3/4" CW
1" CWHB2
HB2
HB4
HB3
2 1/2"RPZ
P-6
P-3A
P-2A
P-1
P-1AP-4
P-6
P-1A
P-10
P-3AP-1A
P-9
P-1A
P-1P-3
P-9
P-3
P-1
P-1A
P-1P-1
P-3P-3
P-3 P-3
P-9
P-2AP-1P-1A
HB1
HB1
1/2" CW1/2" HW1 1/2" CW
1" CW1/2" CW1/2" CW
1 1/4" CW1 1/2" CW
1 1/2" CW
3/4" CWP-4
3/4"CW TOMECHANICALUNITS
3/4"CW TOMECHANICALUNITS
3/4" CW
3/4" CW
1
A
B
C
D
E
3 4 5 62
DescriptionDateRev #
Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.
PROJECT NO:
Revision Schedule
DRAWN BY: CHECKED BY:
SONIC DEVELOPMENT, LLC
Charlotte, North Carolina
E N G I N E E R I N G I N C
Eng. of Record: License No.:
M VEIGH MANGUMC &1610 East Morehead Street, Suite 100
Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036