GE FRAME 6B Cogeneration Unit

Page 2: GE Frame 6B_Dixie

CONTENTS

• EQUIPMENT OVERVIEW

• EQUIPMENT STATUS

• EQUIPMENT CONDITION AND COMPONENTS • TABLE 1 – EQUIPMENT CONDITION • TABLE 2 – EQUIPMENT SUMMARY

• PHOTOS

1 of 16

Page 3: GE Frame 6B_Dixie

1. EQUIPMENT OVERVIEW

The equipment being made available for purchase is a GE MS6001B Gas Turbine 33 MW Power Generation Package with Deltak heat recovery steam generator. Steam capacity is nominally 280Klbsm/hr @ 410psig/640F. For detailed equipment information reference Table 2.

2. EQUIPMENT STATUS

The cogeneration facility was operating satisfactorily when it was shutdown in February of 2004 by the equipment operator. The equipment was idled when a new power facility was brought on-line. Equipment preparations for a long-term outage were made by the cogeneration facility operator and the details of the equipment preparation are not known. It appears that minimal preparation was performed to preserve the equipment. Some equipment was removed and placed in climate controlled storage such as motors and switchgear. Prospective buyers should perform due diligence and/or assume some maintenance will be required prior to returning equipment to service.

3. EQUIPMENT CONDITION The following information is offered in good faith; however, OWNER DOES NOT MAKE ANY REPRESENTATION OR WARRANTY, EXPRESSED OR IMPLIED, AS TO THE CONDITION OF THE EQUIPMENT, AND SPECIFICALLY MAKES NO REPRESENTATION OR WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE. A prospective purchaser of the equipment must conduct its own due diligence as to the condition of the equipment. The equipment will only be made available for purchase on an “AS IS, WHERE IS” basis. Visual inspections and electrical / mechanical test were performed on the major components of the cogeneration facility in March 2009. The inspections and tests were performed to provide a reasonable assessment of the current condition of the equipment. The equipment assessment summary is provided in Table 1 and equipment details are provided in Table 2.

2 of 16

Page 4: GE Frame 6B_Dixie

Table 1: Summary of Equipment Conditions

Equipment

Condition 1. Salvage 2. Poor 3. Fair 4. Good 5. Excellent

Last Maintenance

Approx. Hours Since Last

Maintenance

Gas Turbine Fair Dec.

2001

Major Inspection: o Combustion hardware replaced o Turbine nozzles cleaned & inspected o VIGV’s; cleaned & inspected,

replaced inner bushings o Compressor stationary blades cleaned,

inspected and hand dressed o Case bolting replaced Refurbished Rotor: o Separated rotor o Compressor wheels un-stacked blades

removed cleaned, inspected and hand dressed

o Replaced turbine buckets o Balanced compressor o Balanced turbine o Replaced through bolts o Balanced rotor assembly

10,700

Generator Fair Nov.

1996

Major Inspection: o Removed field o Cleaned, baked & varnished field o Installed new 18Mn18Cr field

retaining rings o At speed balanced field o cleaned and painted stator o Partial re-wedge of stator o Installed flux probe o Testing and assembly performed under

directive of GE Generator Specialist

43,300

Load Gear Fair Nov. 2000

Major Inspection: o Disassembled NDT gears o Installed new quill shafts o Bearings replaced o Labyrinth oil seals replaced

14,000

Accessory Gear Fair Nov. 2000

Major Inspection: o Disassembled and changed gears o Bearings replaced o Labyrinth oil seals replaced

14,000

Generator Accessory Fair Nov.

1996

o Switch gear cleaned and tested per GE directive

o Wiring inspected & tested o Rat guard on GAC grouted

43,300

Diesel Starter Fair Nov. 2000

o Changed lube oil & filters o Changed fuel filters o Inspected torque converter

14,000

Boiler Fair Nov. 2000

o State Inspection o Repaired boiler liner, (new skin) 14,000

Filtration System

Poor Nov.

2000

o Repaired holes in filter housing roof o Cleaned & painted filter housing o Replaced filter elements (turbine &

generator)

14,000

3 of 16

Page 5: GE Frame 6B_Dixie

Equipment

Condition 6. Salvage 7. Poor 8. Fair 9. Good 10. Excellent

Last Maintenance

Approx. Hours Since Last

Maintenance

Lube Oil System Good Nov. 2000

o Replace main pump rotors and bearings

o Inspected and lubed auxiliary pump o Replaced lube oil filters

14,000

Hydraulic System Good Nov.

2000

o Replaced main pump o Inspected and lubed auxiliary pump o Replaced hydraulic oil filters o System check

14,000

Control System GE-Mark IV Poor Dec.

2001

o Tested and adjusted per directive of GE Control Specialist

o Control curve adjusted for changes associated with up-grade hardware and VIGV 86 degree opening

10,700

Table 1 LEGEND for Condition: 1. Salvage - parts and/or scrap. 2. Poor - significant repair and/or component replacement. 3. Fair - clean, inspect and perform normal maintenance. 4. Good - clean and inspect no repair. 5. Excellent - new or recently refurbished.

Table 2: Equipment Summary

Driver Comments

Description Frame 6B Gas Turbine Circa 1985 Manufacturer General Electric Manufactured Schenectady, NY Model MS-6001-B Serial Number 282522 Air Inlet Temperature 93F Altitude 16 feet Fuel Natural Gas Power 3330kw Turbine Exhaust 1028F RPM 5,100 Compressor Stages 17 Power Turbine Stages 3 NOx Emissions Control Steam Injection / 75ppm NP 169487 Fired Hours ~100,000 10,720 Since Major Total Fired Starts ~100

Reduction Gear Comments Description 5105/3600 RPM @ 49,700kw Manufacturer General Electric Manufactured Lynn, Mass. Model S-644A4 Serial Number 273824

4 of 16

Page 6: GE Frame 6B_Dixie

Driven Equipment Comments

Description Air cooled generator Manufacturer General Electric Manufactured Lynn, Mass. Model 6A2 Serial Number 335X441 NP 169377 Stator Max. Temp. 130C Field Max. Temp. 145C Performance Condition Rated Peak KVA 48,824 51,556 Stator Amps 2,043 2,157 Stator Volts 13,800 13,800 Field Amps 386 390 Excitation Volts 250 250 Power Factor 0.85 0.90 RPM 3,600 3,600

Starter/Helper Comments Description Diesel Engine Starter Manufacturer Detroit Diesel Allison Manufactured Detroit, Michigan Model V-71 / 7123-7300 Serial Number 12VA-077270 Description Hydraulic Torque Converter Manufacturer Twin Disc, Inc. Model 4-SGE-2015-1 Serial Number 282852

Auxiliary Equipment Comments Generator Isolation Open Air Generator Excitation Brushless Control Cabinet Mark IV Speedtronic Lube Oil System GE; moved filters external and added larger heat

exchanger to reduce oil temperature. See attached photo

Over-speed Protection Woodward Pro-Tech 203 Electronic Redundant System External Cooling Added external fin-fan exchanger and pumps Inlet Filtration Donaldson TTDOO-9027 Comp. Wash System RMC See attached photos GE Accessory Gearbox Type - ABJAS6A550

650HP/5100RPM/3583RPM/1415RPM S/N-273733 Lynn, Mass., see attached photos

HRSG Flame Detection System HRSG H2O Analyzer Conductivity & Sodium HRSG Exhaust Analyzer ABB; stack emissions, oxygen, NOX & CO

5 of 16

Page 7: GE Frame 6B_Dixie

Heat Recovery Steam Generator Comments

Description Steam Drum and Boiler Manufacturer Deltak Corporation Manufactured 1984 Surface Area 142,700 Sq. Ft. Serial Number 8318 MAWP 500psig Steam Temperature 640F Steam Capacity 325klbm/hr Description Economizer Replaced S/N 8318 in 1993 Manufacturer Deltak Corporation Manufactured 1993 Surface Area 75,995 Sq. Ft. Serial Number S93117-1669 MAWP 550psig Description Superheater Manufacturer Deltak Corporation Manufactured 1984 Surface Area 4,027 Sq. Ft. Serial Number 8318 MAWP 500psig Steam Capacity 325klbm/hr

6 of 16

Page 8: GE Frame 6B_Dixie

Heat Recovery Steam Generator

Generator and Generator Accessory Cab

7 of 16

Page 9: GE Frame 6B_Dixie

Donaldson Inlet Filter House

TCBOIReliability

urbine ompartment lower Moved utside for

mproved

Turbine Compartment Blower Moved Outside for Improved Reliability

External Turbine Compartment Blower

8 of 16

Page 10: GE Frame 6B_Dixie

Frame blower inlets moved to provide filtered air to turbine frame reducing potential of contaminates.

Turbine Frame Blower Inlet

Magnetic pick-ups for Woodward Pro-Tech electronic OST system

On-Line Wash Nozzles

RMC On-Line Compressor Wash Nozzles & Accessory Gearbox Coupling

9 of 16

Page 11: GE Frame 6B_Dixie

10 of 16

Page 12: GE Frame 6B_Dixie

Externally Located Lube Oil Filters

External Lube Oil Cooler / Heat Exchanger

11 of 16

Page 13: GE Frame 6B_Dixie

Cooling Water Pumps

Cooling Water Heat Exchangers

12 of 16

Page 14: GE Frame 6B_Dixie

Load Gear Mesh

Load Gear Right Flank LS Gear

13 of 16

Page 15: GE Frame 6B_Dixie

Accessory Gear Box

Accessory Gear Assemblies

14 of 16

Page 16: GE Frame 6B_Dixie

Accessory Gear # 2

Boiler Flame Detection System

15 of 16

Page 17: GE Frame 6B_Dixie

16 of 16

Boiler Exhaust Analyzer

Boiler H2O Analyzer