Content1 Definition of Zone, Temperature Class and Protection Type .........................................................42 Smoke Detection Panels SDS-4, SDS-8, SDS-16 and Extension Units SDS-E8, SDS-E12, SDS-E16, SDS-EC16 ...................................................................................................................................4
2.1 System Description....................................................................................................................42.2 System Analysis........................................................................................................................5
3 Fan Unit SDS-M0440 / SDS-M0441 ..............................................................................................74 Attached Documents ......................................................................................................................8
4.1 Drawings...................................................................................................................................84.2 Certificates of Conformity.........................................................................................................8
1 Definition of Zone, Temperature Class and Protection TypeHazardous atmosphere in detection unit: Zone 1Equipment Protection Level: EPL GbTemperature Class: T5Environment Temperature: -20°C … +45°CProtection Type: Gas - Intrinsic Safety “ia” acc. IEC 60079-11Ex Group: IIC
2 Smoke Detection Panels SDS-4, SDS-8, SDS-16 and Extension Units SDS-E8, SDS-E12, SDS-E16, SDS-EC16
2.1 System DescriptionA block diagram of the SDS-48 including earting points will be shown in drawing SDS-48-Ex-1.tcd (see appendix).
The smoke detection panels exist of 2 self-contained functional areas, the detection unit and the evaluation unit. The detection unit will be penetrated by hazardous atmosphere. The evaluation unit is separated from the detection unit and will not be penetrated by hazardous atmosphere.
The extension panels are compound only of detection units.
Every detection unit contains one intrinsically safe circuit with max. 8 smoke detectors type XP95 I.S. 55000-640, the same number of airflow indicators type 605 and one Detector Connection Module with max. 8 resistors 1KOhm 3 Watt.
The evaluation unit and the detection units contain the following components:
safetec 2.2.2 Max. Temperature Rise in Resistors under Fault Conditions
The resistors, which are integrated into the circuit, are simple apparatus according IEC 60079-11 clause 5.7. They do not add any capacitors or inductances. The resistors are small parts with a surface area smaller than 1000 mm², which allows a maximum temperature of 150°C for T5 (IEC 60079-0:2007 clause 5.6.2).
R1: Resistor 1K Ω
surface area: ~ 275 mm² (< 1000 mm²)rated power dissipation: 3 Wmax. power supply from isolator: 0,653 Wtemperature rise at 1W power dissipation: 120 K (see datasheet)temperature rise at 0,653 W: 78,4 Kmax. environment temperature: 45°Cmax. temperature rise at 0,653 W: 123,4 °C (< 150°C)
R2: Resistor 22K Ω
surface area: < 1000 mm²rated power dissipation: 1 Wmax. power dissipation: 28V*28V/22KΩ= 0,036 Wthermal resistance 108 K/Wtemperature rise at 0,036 W: ~4 K
3 Fan Unit SDS-M0440 / SDS-M0441
The fan unit SDS-M0440/SDS-M0441 is protected by method “c” (constructional safety). See separate documentation „Technical Documentation“ DOK02.056.
Block Diagram Smoke Detection System SDS-48 with Earth Connections Seite / Page:
1
Zeichnung / Drawing:
SDS48-Ex-1.tcd
Application: System:
SDS-48Smoke Det.
2
3
1
to Cargo Holds
1 3-Way-Valve, Connection to CO2-manifold 2 Hose, 13/20mm 3 Smoke Detection Oanel, compound of: 1 or 2 Detection Units (upper) and 1 Evaluation Unit 4 Extension Panel, compound of: 1 or 2 Detection Units 5 Repeater Panel (not exposed to hazardous area) 6 Steel Pipe 7 Fan Unit SDS-M0440 or SDS-M0441 Earth connection
4
6
5
7
safetecRev.Gepr.Bearb. 28.03.11
20.05.11 kbkb20.05.11
kb
0
1 2 3 4 5 6 7 820.05.2011Ausgabe:
and Extension Unit(s) (E-4, E-8, E-12, E-16, EC-16)Connection Diagram SDS-48 Smoke Detection Panel (SDS-0, SDS-4, SDS-8, SDS-12) Seite / Page:
15 Description of the variation to the Equipment or Protective System
Variation 4.1
i) To permit minor drawing changes, minor PCB layout changes and the addition of the certification code [Ex iaD].
ii) Addition of two new models:
KFD0-CS-Ex1.54 with part number Y207411 KFD0-CS-Ex2.54 with part number Y207412
iii) To confirm that the current designs meet the requirements of EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2004 and EN 61241-11:2005
16 Report Number
GB/BAS/ExTR08.0169/00
17 Special Conditions for Safe Use
None
18 Essential Health and Safety Requirements
Compliance with the Essential Health and Safety Requirements is not affected by this variation.
19 Drawings and Documents
Number Sheet Issue Date Description
*251-0412C 1 of 1 C 14.11.01 Circuit Diagram (ref) for Smart Fire Detector Isolator Type K*D0-CS-Ex1.54 & 2.54(-Y72221&2)
*252-1070H 1 – 7 H 04.10.04 Parts List for Smart Fire Detector Isolator Type KHD0-CS-Ex2.54 and KFD0-CS-Ex2.54(-Y72222)
*252-1130B 1 of 1 B 09.02.00 Parts List for T1/. Transformer Mounting Board for K*D0-CS-Ex1.54(-Y72221) and K*D0-CS-Ex2.54(Y-72222)
*252-1131H 1 – 5 H 04.10.04 Parts List for Smart Fire Detector Isolator Type KHD0-CS-Ex1.54 and KFD0-CS-Ex1.54(-Y72221)
*253-0236A 1 of 1 A 31.01.00 Component Overlay (ref) for Smart Fire Detector Isolator Type K*D0-CS-Ex1.54 & 2.54(-Y72221&2)
*254-0263A 1 of 1 A 16.06.98 Plastic Moulding Details for Toroidal Transformers for Galvanic Isolators
254-0284G 1 & 2 G 10.02.03 G.A. for 20mm Non-Power Rail FIM Housing *255-0698B 1 of 1 B 11.06.99 Cutting/Drilling Details for Barrier Zener Mounting Board *255-0751C 1 & 2 C 14.01.99 P.C.B. Master for (Mk.5) Transformer Mounting Board [K… and E…
System] *255-1036F 1 – 3 F 31.01.00 P.C.B. Master for Smart Fire Detector Isolator K*D0-CS-Ex1.54 &
2.54(-Y72221&2)
Certificate Number BAS00ATEX7087/4
Issued 10 September 2008 Page 3 of 3
Number Sheet Issue Date Description
*256-0065C 1 of 1 C 11.02.00 Connection Details for Transformer T1/. For K*D0-CS-Ex1.54(-Y72221) and K*D0-CS-Ex2.54(-Y72222)
*256-0120A 1 of 1 A 11.02.00 Winding Details for Transformer. 50 Turns Bifilar P1 & P2. 50 Turns Bifilar S1 & S2.
*257-0208C 1 & 2 C 21.03.06 PCB Lacquering Details for Smart Fire Detector Isolator Type K*D0-CS-Ex2.54(-Y72222)
*257-0212D 1 & 2 D 21.03.06 PCB Lacquering Details for Smart Fire Detector Isolator Type K*D0-CS-Ex1.54(-Y72221)
266-0041BS-10 1 & 2 - 29.04.08 Type Label – ATEX. KFD0-CS-Exx.54… *These drawings are common to, and held with, IECEx BAS 08.0079.