Top Banner
Armien Edwards Chief Engineer Eskom - SO&P South Africa Eskom Wide Area Monitoring System
20

Eskom Wide Area Monitoring System

Dec 18, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Eskom Wide Area Monitoring System

Armien EdwardsChief EngineerEskom - SO&PSouth Africa

Eskom Wide Area Monitoring System

Page 2: Eskom Wide Area Monitoring System

2

Enabling Technologies

•GPS technology

•IP Based Telecommunications networks

•Highly accurate IEDs in substations–Phasor Measurement Units

-

ディジタルセンサ(CVT) CB,LS制御 機器監視センサーDigital Sensor(CVT ) CB,LScontrol

GISIntelligentSwitchgear

ITV(((( ))))

【【【【 】】】】

WAN

IED

Page 3: Eskom Wide Area Monitoring System

3

Synchronised Phasor Measurements

Page 4: Eskom Wide Area Monitoring System

4

PMU vs SCADA

ATTRIBUTE SCADA SYNCHONISED PHASOR

Resolution2-4 samples per sec

Up to 50/60 samples per sec

Observability Steady State Dynamic/Transient

Monitoring Local Wide-Area

Phase Angle Measurement

No Yes

Measured Quantity

Magnitude –

(RMS) – MW,

MVAR

Magnitude (RMS) and

phase offset from common

reference – MW, MVAR,and

Angle Difference

frequency

Page 5: Eskom Wide Area Monitoring System

5

PMU vs SCADA

Pegasus Busbar Voltage (PMU vs SCADA Data)

360000

370000

380000

390000

400000

410000

06:3

0:00

.000

06:3

0:07

.720

06:3

0:15

.440

06:3

0:23

.160

06:3

0:30

.880

06:3

0:38

.600

06:3

0:46

.320

06:3

0:54

.040

06:3

1:01

.760

06:3

1:09

.480

06:3

1:17

.200

06:3

1:24

.920

06:3

1:32

.640

06:3

1:40

.360

06:3

1:48

.080

06:3

1:55

.800

06:3

2:03

.520

06:3

2:11

.240

06:3

2:18

.960

06:3

2:26

.680

06:3

2:34

.400

06:3

2:42

.120

06:3

2:49

.840

06:3

2:57

.560

06:3

3:05

.280

06:3

3:13

.000

06:3

3:20

.720

06:3

3:28

.440

06:3

3:36

.160

06:3

3:43

.880

06:3

3:51

.600

06:3

3:59

.320

06:3

4:07

.040

06:3

4:14

.760

06:3

4:22

.480

06:3

4:30

.200

06:3

4:37

.920

06:3

4:45

.640

06:3

4:53

.360

Time

Vo

ltag

e (V

)

PMU Data

SCADA Data

Page 6: Eskom Wide Area Monitoring System

6

System Overview for WAMS

Wide Area Ethernet in the Substation

PMUData

Storage

EIA232 or 485

PMUEthernet

PC37.118

PhasorData Conc.

EthernetPC37.118

EthernetC37.118 Local

Operation

NationalOperations

Other Utilities

Substation IP Access

Security Issues

DedicatedIP Network

DedicatedIP Network

Internetor

VPN

Page 7: Eskom Wide Area Monitoring System

7

Wide Area Monitoring Applications for the Control Centre

Page 8: Eskom Wide Area Monitoring System

8

Situational Awareness

Global display-an alarm overview display

Page 9: Eskom Wide Area Monitoring System

9

Model Validation

Frequency

MW

MW

Page 10: Eskom Wide Area Monitoring System

10

Power system oscillations

Power swings of up to 100MW

Page 11: Eskom Wide Area Monitoring System

11

Dynamic Data Visualisation

Overview display for modal analysis

Page 12: Eskom Wide Area Monitoring System

12

Small Signal Stability Analysis

Page 13: Eskom Wide Area Monitoring System

13

Small Signal Stability Analysis

Poor damping of the 0.93Hz mode

Page 14: Eskom Wide Area Monitoring System

14

Offline model validation

2.0000-0.4000-2.8000-5.2000-7.6000-10.000 Neg. Damping [1/s]

7.6932

6.1546

4.6159

3.0773

1.5387

Damped Frequency [Hz]

Stable EigenvaluesUnstable Eigenvalues

DIg

SIL

EN

T

Page 15: Eskom Wide Area Monitoring System

15

Eskom WAMS Project

Page 16: Eskom Wide Area Monitoring System

16

User Requirements

Short Term (Phase 1)1-3 years

Medium Term3-5 years

Long Term> 5 years

Situational Awareness –Angle/Frequency Monitoring/Damping

Situational Awareness –Advanced Visualization Tools

State Measurement (Linear)

Post Event Analysis Model Benchmarking; Parameter Estimation

Real-Time Control

State Estimation (Improve) State Estimation (hybrid system)

Adaptive Protection

Model Benchmarking; Parameter Estimation

Advanced stability monitoring applications

WA Stabilization (WA-PSS)

Power System Restoration Planned Power-System Separation – Special Protection Systems

Small signal Stability monitoring applications

Page 17: Eskom Wide Area Monitoring System

17

PMU Locations• Feeders key to the interconnection between grid regions

• Nodes that exhibit large shifts in power anglebased on a loss of generation, load and change in topology

• Areas of interest from a load modellingperspective

• Areas of the grid with known dynamic stabilityissues

• Areas that can form frequency islands

• Areas of the grid prone to voltage collapse

• Nodes beneficial for the current state estimator improvement and a future linear state estimator

Page 18: Eskom Wide Area Monitoring System

18

PMU Locations

Page 19: Eskom Wide Area Monitoring System

19

System Architecture

Page 20: Eskom Wide Area Monitoring System

20

Conclusions• Synchronised phasor technology is an essential component of a ‘smart’ transmission grid

• Application benefits can be realised with immediate effect

• New visualisation and analysis tools provides the ability to operate the power system confidently under stressed conditions

• Although an independent system today, it will eventually migrate into the standard substation SCADA architecture