Page 1
CONST
CONC
CONN
COMM
INCAND
IN WC
HORIZ
FLUOR
EQUIP
EXIST
CONTR
CONT
COMBINATION FIRE/SMOKE DAMPER
1 CAT-3 CABLE
SWITCH
MOTOR
DUPLEX RECEPTACLE MOUNTED 8" ABOVE COUNTERTOP U.N.O.
ISOLATED GROUND DUPLEX RECEPTACLE
OVERLOAD AND PILOT LIGHT
QUADRAPLEX RECEPTACLE (TWO DUPLEX UNDER COMMON
WALL MOUNTED OCCUPANCY WITH INTEGRAL MANUAL OVERRIDE
(SUBSCRIPT "3, 4, D OR P" DENOTES 3-WAY, 4-WAY,
MANUAL MOTOR STARTER SWITCH WITH THERMAL
COMBINATION MOTOR CONTROLLER/DISCONNECT
DIMMER OR PA SYSTEM CALL-IN, RESPECTIVELY)
DUPLEX RECEPTACLE
JUNCTION BOX
FIRE ALARM PULL STATION
WALL MOUNTED TV OUTLET
FIRE ALARM AUDIBLE/VISUAL DEVICE
WALL MOUNTED JUNCTION BOX
8" ABOVE COUNTERTOP U.N.O.) CAT-3 AND CAT-5E CABLES
CEILING MOUNTED OCCUPANCY SENSOR
AND TELEPHONE PROVISIONS/CONNECTIONS
DATA OUTLET (* INDICATES MOUNTED 8" ABOVE
COMBINATION TELEPHONE/DATA OUTLET (* INDICATES MOUNTED
FLOOR MOUNTED POKE-THRU DEVICE WITH POWER, DATA,
DUPLEX RECEPTACLE, GROUND FAULT INTERRUPTER TYPE
CONDUIT HOMERUN TO PANEL (2#12, 1#12G, 3/4"C UNO)
SPECIAL PURPOSE RECEPTACLE (COORDINATE EXACT TYPE WITH
COUNTERTOP U.N.O.) CAT - 5E CABLES
EQUIPMENT SUPPLIER)
TELEPHONE OUTLET (SUBSCRIPT "W" DENOTES WALL MOUNTED AT
48" A.F.F., * INDICATES MOUNTED 8" ABOVE COUNTERTOP U.N.O.)
BELL / BUZZER
PAGING SYSTEM SPEAKER
FIRE ALARM VISUAL DEVICE
SECONDARY CLOCK, DOUBLE FACE
SECURITY SYSTEM KEYPAD OUTLET
SECURITY SYSTEM MOTION SENSOR OUTLET, WALL MTD.
SECURITY SYSTEM MOTION SENSOR OUTLET, CLG. MTD.
FIRE ALARM SMOKE DETECTOR (SUBSCRIPT "S" DENOTES SUPPLY
DUCT DETECTOR, SUBSCRIPT "R" DENOTES RETURN DUCT DETECTOR)
ATOMIC WALL CLOCK
SMOKE DOOR HOLDER
SWITCH
SWITCH
COVER)
M
M
NOTES:
TEMPERATURE SENSOR
EMER
IN
KW
KA
KVA
HVAC
HWS
IG
HWC
HWR
HTG
HP
HD
FL
GPH
H
GPM
GFCI
GFI
GCR
GEN
GAL
GA
GALV
F/B
F/A
G
FS
FT
FN
FPVV
FPM
EXP
FD
FIXT
FF
FDR
FD
FCU
FA
FA
°F
EXH
EWT
ESP
EQ
EL
ELEV
ELEC
DIFF
EA
EER
EDH
EC
EAT
DS
DWG
DTL
DN
D
DFU
DIA
DC
DB
CWS
CWR
CW
CVO
COP
CR
CU
EXHAUST DUCT UP
CT
CT
M
MVD
48" A.F.F.
AS REQD.
SP
-
48" AFF
48" AFF
18" AFF
--
18" AFF
18" AFF
SUPPLY DUCT UP
STATIC PRESSURE SENSOR
RETURN DUCT UP
RETURN DUCT DOWN
EXHAUST DUCT DOWN
SUPPLY DUCT DOWN
MOTORIZED DAMPER
MANUAL VOLUME DAMPER
M
SD
M
--
18" AFF
AS REQ'D
18" AFF
AS REQ'D
AS REQ'D
18" AFF
18" AFF
18" AFF
96" AFF
80" AFF
48" AFF
THERMOSTAT
CHECK VALVE
BALL VALVE
SOLENOID VAVLE
GATE VALVE
DUCT MOUNTED SMOKE DETECTOR
STRAINER WITH BALL VALVE BLOW DOWN
THERMOMETER WITH BRASS WELL
CHILLED WATER SUPPLY
MOTORIZED 3-WAY VALVE
BUTTERFLY VALVE
MOTORIZED BUTTERFLY VALVE
POWER AND SYSTEMS
FIRE ALARM DEVICES
CEILING
80" AFF
96" AFF
96" AFF
48" AFF
96" AFF
FIRE LINE
CONDENSER WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE DRAIN
HEATING HOT WATER RETURN
HEATING HOT WATER SUPPLY
CONDENSER WATER RETURN
AIR LINE
GAS LINE
EMERGENCY LIGHT
SAFETY CIRCUIT
DOWN LIGHT FIXTURES ON EMERGENCY CIRCUIT
CEILING OR WALL MOUNTED.
EXIT LIGHT CEILING OR WALL MTD., SHADING
FLUORESCENT FIXTURE
DOWN LIGHT FIXTURES CLG. OR WALL MTD.
WALL WASHER LIGHT FIXTURE CEILING MTD.
FLUORESCENT FIXTURE ON EMERGENCY LIFE
NEMA SIZE
3-POLE, 30A. FUSE
MOTOR STARTER FVNR UNO; NUMBER INDICATES
CIRCUIT BREAKER DISCONNECT SWITCH - THERMAL
MAGNETIC CB IN NEMA 1 ENCLOSURE; AMPS/POLES
DISCONNECT SWITCH - 30/-/3 INDICATES 30A.,
3-POLE, NONFUSED: 30/30/3 INDICATES 30A.,
AS INDICATED
AS INDICATED
INDICATING SINGLE OR DOUBLE FACE, DIRECTION
SYMBOL
CFH
CKT
COL
CLG
CO
CI
CHS
CHR
CFM
ABV
AT
BTUH
CB
CD
CAT
C
BLDG
BTU
AUX
AV
AFF
AHU
AMB
AIC
AFG
AC
AF
ADJ
A/C
ABC
ABS
A
DESCRIPTIONSYMBOL
PIPE TURN DOWN
DOMESTIC HOT WATER (HW)
DOMESTIC COLD WATER (CW)
ROUND 90° ELBOW DOWN
SANITARY SEWER
DOMESTIC HOT WATER RECIRCULATION
CLEANOUT
PIPE TURN UP
GREASE WASTE
FCO
FD
FLOOR CLEANOUT
BALL VALVE
FLOOR DRAIN
WALL CLEANOUT
DESCRIPTIONSYMBOL
UNO
MTG. HEIGHT
SIZE TRANSITION
RECTANGULAR TO ROUND AND SIZE TRANSITION
RECTANGULAR ELBOW WITH TURNING VANES
90° RADIUS ELBOW, ROUND OR RECTANGULAR
45° ELBOW, ROUND OR RECTANGULAR
FLEXIBLE DUCT CONNECTION
ROUND 90° ELBOW DOWN
ROUND 90° ELBOW UP
DESCRIPTION
LIGHTING FIXTURES
C CFM
E CFM
AS REQD.
AS REQD.
AS REQD.
FIRE DAMPER
SMOKE DAMPER
DISCONNECTS AND MOTORS
9" BFC
ACFM
SUPPLY AIR DIFFUSER WITH FLEXIBLE DUCT CONNECTION. 4-WAY THROW
UNLESS NOTED OTHERWISE. TYPE AND CFM INDICATED ON PLANS.
CEILING RETURN AIR GRILLE. TYPE AND CFM INDICATED ON PLANS.
CEILING EXHAUST AIR GRILLE. TYPE AND CFM INDICATED ON PLANS.
CONTINUOUSOC ON CENTER
RQMTEMERGENCY
REQUIREMENT
HEIGHT
VERT
XFMR
INCHES
INCHES WATER COLUMN
KILOWATT
KILOVOLT AMPERES
KILOAMPERES
INCANDESCENT
HOT WATER RECIRCULATION (DOMESTIC)
HOT WATER SUPPLY
ISOLATED GROUND
HOT WATER RETURN
HORSEPOWER
HORIZONTAL
HEATING
HEAD
HEATING, VENTILATION, & AIR CONDITIONING
WP
Y
WT
WPO
VV
WB
WH
W
W
VTR
VT
VPO
VARIABLE VOLUME TERMINAL UNIT
WEATHERPROOF
WASTE PLUGGED OPENING
TRANSFORMER
WYE
WEIGHT
VENT THRU THE ROOF
VENT PLUGGED OPENING
WATER HEATER
WET BULB
WATTS
WIDTH
VENT
VERTICAL
SENS
SEER
SPECS
SHT MTL
SQFT
SS, SAN
SPKR
SWGR
SWBD
SURF
T-STAT
VENTIL
EXPANSION
FIRE DAMPER
FINISH FLOOR
FLOOR DRAIN
FIXTURE
FEEDER
DEGREES FAHRENHEIT
FAN COIL UNIT
FREE AREA
FIRE ALARM
ENTERING WATER TEMPERATURE
EXTERNAL STATIC PRESSURE
EQUIPMENT
EXHAUST
EXISTING
EQUAL
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT INTERRUPTER
GALLONS PER MINUTE
GALLONS PER HOUR
GENERAL CONTRACTOR
GENERATOR
GALVANIZED
GALLONS
GAUGE
FROM BELOW
FROM ABOVE
FUSED SWITCH
GROUND
FEET
FEET PER MINUTE
FULL NEUTRAL
FLUORESCENT
FLOW LINE
FAN POWERED VARIABLE VOLUME TERMINAL UNIT
STD
VA
VAV
VA
V
UNO
V
UF
TTB
TYP
TELE
TC
TOT
SYM
SW
SFU
SSC
SQ
SP
SHT
RTU
SD
SA
RT
STANDARD
TELEPHONE TERMINAL BOARD
UNLESS NOTED OTHERWISE
TOTAL (BTU)
VARIABLE AIR VOLUME
VENTILATION
VOLT-AMPS
UNDERFLOOR
VOLT
VALVE
VACUUM
TYPICAL
TELEPHONE
TIMECLOCK
SYMMETRICAL
THERMOSTAT
SWITCHGEAR
SWITCHBOARD
SURFACE
SWITCH
SEASONAL ENERGY EFFICIENCY RATIO
SUPPLY FIXTURE UNITS
SHORT CIRCUIT CURRENT
SANITARY SEWER
SQUARE FEET
SPECIFICATIONS
STATIC PRESSURE
SHEET METAL
SPEAKER
SQUARE
SHEET
ROOF TOP UNIT
SUPPLY AIR
SENSIBLE (BTU)
STORM DRAIN
RAINTIGHT
PERF
PLBG
REQ'D
REFR
RM ELEVATION
ELEVATOR
ELECTRICAL
RPM
RMS
COEFFICIENT OF PERFORMANCE
CURRENT TRANSFORMER
COOLING TOWER
CARD READER
CONTRACTOR
DIFFUSER
ENTERING AIR TEMPERATURE
ENERGY EFFICIENCY RATIO
ELECTRICAL CONTRACTOR
EACH
ELECTRIC DUCT HEATER
DOWNSPOUT
DRAWING
DETAIL
DOWN
DRAINAGE FIXTURE UNITS
COLD WATER VALVED OPENING
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
DEPTH
DIRECT CURRENT
DRY BULB
DIAMETER
COLD WATER
CONDENSING UNIT
PWR
REC
RLA
REF
QTY
R/A
RCP
RCP
PNL
PVC
PSIG
PSIA
PSI
PH
PF
ODS
OZ
PD
PE
P
OD
ROOM
ROOT MEAN SQUARED
RPM
PRESSURE DROP
POUNDS PER SQUARE INCH-GAUGE
POUNDS PER SQUARE INCH-ABSOLUTE
REFORCED CONCRETE PIPE
POUNDS PER SQUARE INCH
POWER
RUNNING LOAD AMPS
REFLECTED CEILING PLAN
RECEPTACLE
REFRIGERATOR
REFERENCE
RETURN AIR
REQUIRED
QUANTITY
POLYVINYL CHLORIDE
PERFORATED
POWER FACTOR
PANEL
PLUMBING
PHASE
OVERFLOW DOWNSPOUT
PHOTO-ELECTRIC
OUTSIDE DIAMETER
POLES
OUNCE
LIN FT
MBTUH
MECH
MISC
MTRZD
NEMA
NFPA
CUBIC FEET PER HOUR
CONSTRUCTION
CONCRETE
CONNECT
CUBIC FEET PER MINUTE
COMMUNICATION
CLEAN OUT
CIRCUIT
COLUMN
CEILING
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CAST IRON
NO
OBD
OA
NEC
NO
NIC
NC
NA
N
MVD
ABOVE COUNTER
AMPS, AMPERE
ABS
AMP TRIP
BRITISH THERMAL UNIT PER HOUR
CIRCUIT BREAKER
CONDENSATE DRAIN
CATALOGUE
CONDUIT
BRITISH THERMAL UNIT
AUDIO VISUAL
AUXILIARY, AUXILIARIES
BUILDING
AMPERES INTERRUPTING CAPACITY
ABOVE FINISH FLOOR
AIR HANDLING UNIT
ABOVE FINISH GRADE
AMBIENT
AMP FRAME
ALTERNATING CURRENT
AIR CONDITIONER
ADJACENT
ABOVE LAT
MCF
MTL
MTR
MTG
MTD
MIN
MIC
MCM
MA
MCC
MCB
MAX
LWT
LTG
LB
LAT
KWH
L
MOTORIZED
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
OPPOSED BLADE DAMPER
NATIONAL ELECTRICAL CODE
MANUAL VOLUME DAMPER
NORMALLY OPEN
OUTSIDE AIR
NUMBER
NOT IN CONTRACT
NORMALLY CLOSED
NOT APPLICABLE
NEUTRAL
LATENT (BTU)
LEAVING WATER TEMPERATURE
THOUSAND CUBIC FEET
THOUSAND CIRCULAR MILS
MISCELLANEOUS
MICROPHONE
MECHANICAL
MOUNTING
MOUNTED
METAL
MOTOR
MINIMUM
MOTOR CONTROL CENTER
MAIN CIRCUIT BREAKER
MILI AMPS
LINEAR FOOT
POUNDS (WEIGHT)
MAXIMUM
LIGHTING
LEAVING AIR TEMPERATURE
KILOWATT - HOUR
LENGTH
9" BFC
ELECTRICAL SYMBOLS HVAC LEGEND PLUMBING LEGEND ABBREVIATIONS
1. PROVIDE 3/4"C FROM SECURITY, TELEPHONE AND DATA OUTLETS TO ABOVE NEAREST
ACCESSIBLE LAY-IN CEILING. REFER TO SPECIFICATIONS FOR WIRING
REQUIREMENTS.
2. MOUNT FIRE ALARM AUDIBLE/VISUAL AND VISUAL ONLY DEVICES AT 80"AFF UNLESS
OTHERWISE REQUIRED BY AMERICANS WITH DISABILITIES ACT REQUIREMENTS.
CO
WCO
S
K
C
S
F
F
F
MS
J
GFI
IG
A
GW
SS
TS
S
CHS
CHR
CWS
CWS
HWS
HWR
D
F
G
PROJECT NUMBER
DATE
SHEET TITLE
REV. # DESCRIPTION DATE 1
2
3
4
5
SHEET NUMBER
402 Parker Street M
cKinney, Texas
t 972.302.9747
conduitad.com
4144 N. Central Expressway, Suite 380
Dallas, Texas 75204
Ph: 214.428.7744
Fax: 214.428.7770
www.mezaengineeringinc.com
Project:
MEZA ENGINEERING, INC.Texas Registered Engineering Firm F-345
15006.000
Page 2
16. MAJOR CHANGES TO THE SYSTEMS ARRANGED AS SHOWN ON THE DRAWINGS, IF
DURING A 1-YEAR WRITTEN LABOR AND MATERIALS WARRANTY PERIOD TO BE
B. DUCTWORK, GRILLES AND ALL ACCESSORIES
A. ALL WARRANTY CERTIFICATES ISSUED SHALL BE TRANSMITTED IN WRITING TO
4. THE CONTRACTOR SHALL COORDINATE WITH AND NOTIFY THE OWNER'S
REPRESENTATIVE FOR APPROVAL AND SCHEDULING OF ANY BUILDING SYSTEM
INTERRUPTIONS OR WORK INVOLVING EXISTING AREAS. (INCLUDING NOISE, DUST,
ETC.). THE CONTRACTOR SHALL RECOGNIZE ANY EXISTING BUILDING EQUIPMENT
WARRANTIES PRIOR TO MODIFICATION OR CONNECTION TO SAME .
5. ALL EQUIPMENT SHALL BE NEW, UNLESS NOTED OTHERWISE, AND INSTALLED IN
ACCORDANCE WITH MANUFACTURER'S PUBLISHED RECOMMENDATIONS FOR THE
SERVICE INTENDED. PROVIDE ONLY PRODUCTS BEARING UNDERWRITERS
LABORATORIES (UL) LABEL AS APPLICABLE.
EQUIPMENT PRIOR TO PLACING ORDERS. SHOULD THE CONTRACTOR SUPPLY
EQUIPMENT DIFFERING FROM THE SCHEDULED OR SPECIFIED ITEMS IN THE CONTRACT
REMEDY ANY DEFICIENCIES ARISING FROM SAME.
7. PROVIDE FIVE COPIES OF CLEARLY MARKED SUBMITTAL DATA ON THE FOLLOWING
ITEMS AND AS REQUESTED BY THE ENGINEER:
C. PLUMBING EQUIPMENT, FIXTURES & TRIM
8. MATERIALS, WORKMANSHIP, AND INSTALLATION METHODS SHALL COMPLY WITH THE
CONTRACT DOCUMENTS AND ALL CURRENT APPLICABLE CODES AND STANDARDS.
SHOULD THE CONTRACTOR PROVIDE ANY ITEM OR PERFORM ANY WORK THAT DOES
NOT COMPLY WITH THE REQUIREMENTS OF CURRENT APPLICABLE CODES AND
STANDARDS, HE SHALL BEAR ALL COSTS ARISING IN CORRECTING ANY DEFICIENCIES.
UTILITY COMPANY REGULATIONS, FEDERAL REGULATIONS AND APPLICABLE
REQUIREMENTS OF CITY AND NATIONALLY ACCEPTED CODES AND STANDARDS.
A. HANDICAPPED PERSONS AND ADA REQUIREMENTS.
1. THE PLANS AND SPECIFICATIONS HAVE BEEN PREPARED IN
2. THE CONTRACTOR SHALL VERIFY AND COORDINATE THE TYPE OF
CURRENT APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL ORDINANCES,
DOCUMENTS WITHOUT NOTIFICATION TO THE ENGINEER, HE SHALL BEAR ALL COST TO
6. CONTRACTOR SHALL OBTAIN APPROVAL FROM THE ENGINEER OF ALL MAJOR ITEMS OF
THE OWNER.
A. HVAC EQUIPMENT
B. AIR DEVICES
D. HVAC CONTROLS
INCLUDED AS PART OF THIS WORK.
10. VERIFY ALL MEASUREMENTS. NO EXTRA COMPENSATION WILL BE ALLOWED BECAUSE
OF DIFFERENCES BETWEEN WORK SHOWN ON THE DRAWINGS AND ACTUAL
MEASUREMENTS AT THE SITE OF CONSTRUCTION. DO NOT SCALE THE DRAWINGS.
THE CONTRACTOR SHALL VISIT THE PREMISIS PRIOR TO BIDDING TO
THOROUGHLY FAMILIARIZE HIMSELF WITH ALL DETAILS AND
COORDINATE WITH ALL EXISTING CONDITIONS TO BE ENCOUNTERED BY
ALL TRADES. HE SHALL VERIFY ALL CONDITIONS IN THE FIELD, INCLUDE
ANY COSTS RELATED TO SAME IN HIS BID, AND SHALL NOTE IN WRITING,
ANY EXCEPTIONS TAKEN WHEN BIDDING THE WORK.
G. WIRING DEVICES & COVERPLATES
F. SWITCHGEAR
E. LIGHT FIXTURES
9.
ACCORDANCE WITH THE ENGINEERS INTERPRETATIONS OF THE
APPLICABLE PROVISIONS OF REGULATIONS, CODES AND ORDINANCES
REGARDING HANDICAPPED PERSONS. IT IS ASSUMED THAT THE
CONTRACTOR IS ALSO KNOWLEDGEABLE OF SAME AND THEIR
APPLICATION WITH REGARD TO HIS WORK.
EQUIPMENT BEING INSTALLED AND ITS LOCATION, MOUNTING HEIGHT
AND CLEARANCES AS PRESCRIBED BY ALL APPLICABLE HANDICAP
REGULATIONS, CODES AND ORDINANCES PRIOR TO PLACING EQUIPMENT
ORDERS AND PRIOR TO INSTALLATION OF ALL WORK.
GENERAL LISTING OF MOUNTING HEIGHTS
ITEM HEIGHT TO CENTER LINE
SENSORS, ETC. 48"
THERMOSTATS,
a.
3. THERMOSTATS
CONTROL SHALL BE ±1°F OF SETPOINT.
TEST AND BALANCE EACH TO ±10% OF FLOW VALUE SHOWN ON PLANS.
2. S/A & E/A GRILLES
a.
d. S/A DUCT STATIC PRESSURE AT 2/3 DISTANCE FROM UNIT.
c. R/A & S/A TEMPERATURES AT FULL COOLING AND FULL HEATING CONDITIONS.
b. VOLTS/AMPS ALL FANS.
a. VOLTS/AMPS EACH COMPRESSOR.
1. HVAC UNITS
REQUIRED TESTSB.
A.PROVIDE PERSONNEL AND EQUIPMENT, MAKE AND RECORD ALL DATA FOR
REQUIRED TESTS, AND SECURE REQUIRED APPROVALS FROM THE ENGINEER
AND GOVERNMENTAL AGENCIES HAVING JURISDICTION.
E. INSULATION
F. CONTROLS
DRAWINGS AS SPECIFIED.
17. TESTING AND INSPECTION:
ADVANCE OF EACH OF THESE:
2. AT COMPLETION OF THE WORK.
ACCEPTED, MUST BE APPROVED IN WRITING BY THE ENGINEER, PRIOR TO
PROCEEDING. ALL SUCH CHANGES SHALL BE INCORPORATED INTO THE "AS BUILT"
C. MAKE WRITTEN NOTICE TO THE ARCHITECT/ENGINEER ADEQUATELY IN
1. WHEN ROUGH-INS ARE COMPLETE, BUT NOT COVERED.
E. TEST ALL PARTS OF ALL SYSTEMS AND DEMONSTRATE THAT ALL SUCH
18. UPON COMPLETION OF THE WORK:
THE MANUFACTURER OF ANY ITEM BEING CLEANED.
FAMILIARIZE THEM WITH THE SYSTEM OPERATION AND REQUIRED PERIODIC MAINTENANCE.
COMMUNICATION WITH OWNER OR ENGINEER.
THE DIMENSIONED LOCATIONS OF SAME.
D. WHEN MATERIAL AND/OR WORKMANSHIP IS FOUND TO NOT COMPLY WITH THE
SPECIFIED REQUIREMENTS: WITHIN THREE DAYS AFTER RECEIPT OF NOTICE OF
SUCH NON-COMPLIANCE, REMOVE THE NON-COMPLYING ITEMS FROM THE JOB
SITE AND REPLACE THEM WITH ITEMS COMPLYING WITH THE SPECIFIED
REQUIREMENTS, ALL AT NO ADDITIONAL COST TO THE OWNER.
A. THOROUGHLY CLEAN ALL EXPOSED PORTIONS OF THE MECHANICAL AND
ELECTRICAL EQUIPMENT PROVIDED AND THE GENERAL AREA WHERE WORK
WAS PERFORMED. REMOVE ALL TRACES OF SOIL, LABELS, GREASE, OIL, AND
OTHER FOREIGN MATERIAL USING ONLY THE TYPE CLEANER RECOMMENDED BY
B. PROVIDE MANUFACTURERS' OPERATING AND MAINTENANCE INSTRUCTIONS TO
THE OWNER'S REPRESENTATIVE FOR ALL MAJOR MECHANICAL AND ELECTRICAL
EQUIPMENT PROVIDED. PROVIDE 4 HOURS OF FORMAL TRAINING (2 HOURS ON
TWO DIFFERENT DAYS) TO OWNER'S MAINTENANCE PERSONNEL IN ORDER TO
C. DOCUMENTATION OF ANY TEST AND THE "AS-BUILT" RECORD DRAWINGS SHALL
BE PROVIDED TO THE BUILDING OWNER UPON COMPLETION.
19. CONTRACTOR SHALL DESIGNATE ONE PERSON TO SERVE AS SOLE POINT OF
20. WORK AMONG ALL TRADES SHALL BE FULLY COORDINATED AS REQUIRED IN THE FIELD
TO AVOID SPACE CONFLICTS AND INTERRUPTION OF THE FLOW OF WORK.
21. IN THE EVENT THAT ANY ITEM PROVIDED UNDER THIS CONTRACT IS DAMAGED PRIOR
TO FINAL ACCEPTANCE THE CONTRACTOR SHALL REPLACE, NOT REPAIR, THE ITEM
WITH NEW. IF AN EXISTING ITEM IS DAMAGED DURING THE CONSTRUCTION, THE
CONTRACTOR SHALL RESTORE THE ITEM TO NEAR ORIGINAL CONDITION AND PRIOR
OPERATING CONDITION TO THE SATISFACTION OF THE OWNER'S REPRESENTATIVE.
22. CONTRACTOR SHALL PROVIDE ALL DIMENSIONS FOR BLOCK OUTS, SLEEVES, ETC., AND
23. UNLESS DETAILED OTHERWISE MAINTAIN A MINIMUM CLEARANCE FOR LIGHTS OF 7"
ABOVE FINISHED CEILING AND 1" MINIMUM BELOW ALL DUCTS, PIPES, CONDUIT OR ANY
OTHER EQUIPMENT IN THE CEILING SPACE. PROVIDE MANUFACTURER'S
RECOMMENDED SERVICE ACCESS CLEARANCE AT ALL EQUIPMENT.
ABOVE FINISHED FLOOR
D. PLUMBING FIXTURES, EQUIPMENT AND PIPING
C. PIPING SYSTEMS
PROVIDE WRITTEN REPORT: UPON COMPLETION, ALL INFORMATION SHALL BE
NEATLY TYPED AND FIVE (5) COPIES SUBMITTED TO THE OWNER WITH
ACCOMPANYING SCHEMATIC DIAGRAMS OF SYSTEMS TESTED. ALL TEST
REPORTS SHALL BE ASSEMBLED, INDEXED, AND SUBMITTED IN VINYL COVERED
LOOSE-LEAF NOTEBOOKS WITH PROJECT NAME AND BALANCING
CONTRACTOR'S NAME PERMANENTLY PRINTED THEREON, AND INCLUDED IN
PROJECT CLOSEOUT DOCUMENTS.
F.
SPECIFICATIONS
1. IT IS THE INTENT AND MEANING OF THE CONTRACT DOCUMENTS THAT THE
CONTRACTOR SHALL PROVIDE A MECHANICAL AND ELECTRICAL INSTALLATION THAT IS
COMPLETE WITH ALL ITEMS AND APPURTENANCES NECESSARY, REASONABLY
INCIDENTAL, OR CUSTOMARILY INCLUDED, EVEN THOUGH EACH AND EVERY ITEM IS
NOT DETAILED ON THE DRAWINGS OR SPECIFIED.
A. THE TERM "PROVIDE" IN THESE SPECIFICATIONS AND ON THE DRAWINGS
MEANS; FURNISH, TRANSPORT, INSTALL, CONNECT, WARRANT AND START-UP,
THE CONTRACTOR SHALL CONTACT OTHERS AS IS REQUIRED TO ESTABLISH A
MUTUAL UNDERSTANDING OF THE PROJECT REQUIREMENTS FOR AN ITEM AND
THE RESPECTIVE COSTS FOR EACH PARTY IN ORDER TO PROVIDE A COMPLETE
OPERATING PRODUCT OR LABOR FOR THIS PROJECT.
C. THE INSTALLATION OF ALL SYSTEMS SHALL BE MADE BY EXPERIENCED
CRAFTSMEN IN A NEAT WORKMANLIKE MANNER. ALL MATERIALS, TOOLS,
PERMITS AND INSPECTIONS AND ALL OTHER COSTS AND SERVICES NECESSARY
AND PAID FOR, IN FULL, BY THE CONTRACTOR.
2. THE CONTRACTOR SHALL TAKE PROPER PRECAUTIONS TO PROTECT ANY EXISTING
CONSTRUCTION AND ADJACENT PROPERTY, WITH WHICH WORK COMES IN CONTACT,
AND OVER WHICH HE MAY TRANSPORT, HOIST OR MOVE MATERIALS, EQUIPMENT,
DEBRIS, ETC., AND SHALL REPAIR SATISFACTORILY ALL DAMAGES CAUSED BY HIM
3. THE CONTRACTOR SHALL, AT NO COST TO THE OWNER, REPLACE WITH NEW
MATERIALS AND/OR EQUIPMENT, ANY ITEMS FAILING TO GIVE SATISFACTORY SERVICE
TO PROVIDE ALL MECHANICAL AND PLUMBING ITEMS SHALL BE FURNISHED
B. THE TERM "COORDINATE" IN THESE SPECIFICATIONS AND ON THE PLANS MEANS:
INCLUSIVELY.
DURING CONSTRUCTION.
GENERAL REQUIREMENTS FOR ALL MECHANICAL, PLUMBING AND ELECTRICAL WORK
26. PROPERLY SUPPORT ALL EQUIPMENT AND PIPING WITHIN THE BUILDING AND PROVIDE
ADEQUATE PROVISIONS FOR SLOPE AND ANCHORAGE. CONTRACTOR SHALL USE AND
STRUCTURE. ALL HANGERS SHALL HAVE A MINIMUM FACTOR OF SAFETY OF 5. ALL
PIPING SHALL BE SUPPORTED AT PROPER INTERVALS WITH ONE HANGER OR SUPPORT
A. HVAC EQUIPMENT
FUNCTIONING INSTALLATION.
GOOD PRACTICE AND OTHER CONSIDERATIONS.
13. IN THE CASE WHERE TWO OR MORE TRADES OR CONTRACTORS ARE INVOLVED IN THE
INSTALLATION OF ANY ITEM, ALL SUCH PERSONS SHALL BE RESPONSIBLE FOR
COORDINATING THEIR WORK AMONG THEMSELVES TO PROVIDE A FULLY COMPLETED,
14. WHETHER ITEMS SPECIFIED OR NOTED ARE DESCRIBED AS SINGULAR OR PLURAL
SHALL NOT ALTER THE REQUIREMENT THAT SUFFICIENT QUANTITIES OF THE ITEM ARE
TO BE PROVIDED IN ORDER TO RESULT IN A COMPLETE INSTALLATION AND PROJECT.
15. THE DRAWINGS ARE DIAGRAMMATIC, BUT ARE REQUIRED TO BE FOLLOWED AS
CLOSELY AS ACTUAL CONSTRUCTION AND WORK OF OTHER TRADES WILL PERMIT.
DATA INDICATED ON THE DRAWINGS AND IN THESE SPECIFICATIONS ARE AS EXACT AS
COULD BE SECURED, BUT THEIR ABSOLUTE ACCURACY IS NOT WARRANTED. BRANCH
CIRCUITS, PIPING ARRANGEMENTS, AND MECHANICAL AND ELECTRICAL COMPONENT
LOCATIONS AND THE LIKE HAVE BEEN DESIGNED FOR ECONOMY CONSISTENT WITH
PERFORATED STRAP AS HANGERS IS PROHIBITED.
VERTICALLY ALIGN HANGERS AND RODS. INSERTS ETC. SHALL BE LISTED BY
UNDERWRITERS' LABORATORIES FOR THE SERVICE INTENDED. THE USE OF
27. SECURELY SUPPORT ALL EQUIPMENT FROM STRUCTURAL MEMBERS PROVIDED AS
NEEDED, WHICH IN TURN ARE TO BE SUPPORTED DIRECTLY FROM THE BUILDING
WITHIN 12" OF EITHER SIDE OF EACH TURN.
28. IN THE EVENT OF A CONFLICT WITHIN THE DRAWINGS AND/OR SPECIFICATIONS,
PROVIDE THE GREATER QUANTITY OR HIGHER QUALITY.
1. WORK INCLUDES BUT IS NOT NECESSARILY LIMITED TO:
MECHANICAL SPECIFICATIONS
PROVIDE WRITTEN BALANCE REPORT SHOWING INDIVIDUAL GRILLE FLOWS AND SYSTEM FAN
PERFORMANCE FOR VOLTAGE, AMPERAGE DRAW AND EXTERNAL STATIC PRESSURE.
4. TESTING AND BALANCE SHALL BE BY AIR ENGINEERING AND TESTING UNDER
G.C. CONTRACT.
5.
CHANGE.
EQUALS OR EXCEEDS THAT OF THE NAMED ITEM.
11. EQUIPMENT SUBSTITUTIONS TO THE NAMED SPECIFIED PRODUCTS MAY BE PROPOSED
BY THE CONTRACTOR. HOWEVER, THE CONTRACTOR SHALL BASE HIS BID ON THE
NAMED ITEMS. THE CONTRACTOR SHALL DEMONSTRATE TO THE SATISFACTION OF
THE ENGINEER THAT THE QUALITY, CAPACITY AND SUITABILITY OF THE PROPOSED ITEM
12. COORDINATE EQUIPMENT SUBSTITUTIONS FOR THE SCHEDULED OR SPECIFIED ITEM
WITH ALL OTHER TRADES. COMPENSATION TO OTHER TRADES DUE TO CHANGES IN
RATED VOLTAGE, PHASE, PHYSICAL SIZE, ARRANGEMENTS, SHAPE, COLOR AND ALL
OTHER CHARACTERISTICS AND THEIR RELATED EFFECTS ARISING FROM EQUIPMENT
SUBSTITUTIONS IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR MAKING THE
BE VERTICAL AND PLUMB.
24. PROVIDE ALL MATERIALS REQUIRED FOR THE SUPPORT OF SUCH ITEMS AS PIPING,
DUCTS, EQUIPMENT AND SIMILAR ITEMS. THIS SHALL INCLUDE RODS, ANGLES, ETC., TO
PROPERLY SUPPORT ALL ITEMS IN A PROPER AND SAFE MANNER. ALL HANGERS SHALL
BUILDING WALLS OR ROOF SHALL BE PROVIDED BY THE CONTRACTOR PROVIDING THE
INTEGRITY SHALL BE COORDINATED WITH THE GENERAL CONTRACTOR OR ENGINEER.
FLASHINGS FOR PENETRATIONS MAY ALSO BE PROVIDED ENTIRELY BY THE GENERAL
THE COMPLETENESS OF THIS ITEM.
25. SUITABLE FLASHINGS AND THEIR WATERTIGHT SEALING FOR OPENINGS IN THE
PENETRATING ITEM. THE INSTALLATION OF THE FLASHING AND ITS WATERTIGHT
CONTRACTOR. ALSO, REFER TO THE ARCHITECTS SPECIFICATIONS TO COORDINATE
ITEMS PROVIDED UNDER THIS SECTION FUNCTION IN THE REQUIRED
MANNER.
PROJECT NUMBER
DATE
SHEET TITLE
REV. # DESCRIPTION DATE 1
2
3
4
5
SHEET NUMBER
402 Parker Street M
cKinney, Texas
t 972.302.9747
conduitad.com
4144 N. Central Expressway, Suite 380
Dallas, Texas 75204
Ph: 214.428.7744
Fax: 214.428.7770
www.mezaengineeringinc.com
Project:
MEZA ENGINEERING, INC.Texas Registered Engineering Firm F-345
15006.000
Page 3
SPECIFICATIONS
ELECTRICAL SPECIFICATIONS
2. WORK INCLUDES BUT IS NOT NECESSARILY LIMITED TO:
A. PROVIDE ELECTRICAL EQUIPMENT AS MANUFACTURED BY:
3. CUTLER HAMMER
2. SIEMENS
1. SQUARE D
TO LOWEST EDGE OF DEVICE COVERPLATE.
18. DEVICES NOT DIMENSIONED SHALL BE LOCATED WITHIN 12" HORIZONTALLY OF THE
LOCATION SHOWN. WHERE NO MOUNTING HEIGHT IS GIVEN, INSTALL WALL RECEPTACLES
AT 15" A.F.F. INSTALL WALL SWITCHES AT 48" A.F.F. OBTAIN FINAL APPROVED LOCATION
FROM THE ARCHITECT IN THE FIELD WHERE DEVICES ARE LOCATED IN SPECIAL WALL
FINISHES. DEVICES THAT ARE DIMENSIONED SHALL BE INSTALLED MEASURING FROM AFF
A. ALL OUTLETS SHALL BE 20A RATED HUBBELL CR120 OR APPROVED EQUAL.
B. GFCI OUTLETS SHALL BE HUBBELL GF5352 OR APPROVED EQUAL.
C. SWITCHES SHALL BE 20A RATED HUBBELL CS120 / CS320 OR APPROVED EQUAL.
D. PROVIDE OTHER WIRING DEVICES AS SPECIFIED ON THE DRAWINGS.
MECHANICAL SPECIFICATIONS
FIRE ALARM SYSTEM
IF REQUIRED BY LOCAL CODES OR FIRE MARSHAL PROVIDE A FIRE ALARM SYSTEM.
COORDINATE ANY MONITORING REQUIREMENTS RELATED TO MODIFICATIONS OF THE
EXISTING FIRE SPRINKLER SYSTEM.
1.
ACTUAL FIRE ALARM DESIGN SHALL BE BY A COMPANY LICENSED TO
DESIGN/INSTALL FIRE ALARM SYSTEMS IN THE STATE OF TEXAS. FIRE ALARM
SUBMITTALS SHALL BE SUBMITTED TO AHJ FOR REVIEW AND APPROVAL.
2.
14. LIGHT FIXTURES SHALL BE INSTALLED IN LOCATIONS IN ACCORDANCE WITH THE FINAL
APPROVED ARCHITECTURAL PLANS.
13. PROVIDE EQUIPMENT GROUND WIRE AT EACH CONDUIT.
A. GROUND ALL ELECTRICAL APPARATUS IN ACCORDANCE WITH NATIONAL
ELECTRICAL CODE.
B. INSURE CONTINUOUS BOND WHERE FLEXIBLE CONDUIT IS USED.
C. PROVIDE SEPARATE GREEN GROUND WIRE FOR ALL BRANCH AND FEEDER
CIRCUITS.
D. WIRING METHODS SERVING ANY PATIENT CARE AREAS SHALL ADHERE TO NEC
517.13 AND 205.118.
12. PANELBOARDS AND/OR CIRCUIT BREAKERS SHALL BE PROVIDED AS INDICATED OR SHOWN,
EACH SHALL BE RATED FOR AT LEAST THE MINIMUM CURRENT INTERRUPTING CAPACITY
SHOWN. PANELBOARDS SHALL HAVE ALL COPPER BUSSING. PANELS SHOWN AS
ELECTRICAL SERVICES SHALL BE RATED FOR USE AS SERVICE EQUIPMENT.
15. PROVIDE ALL ELECTRICAL EQUIPMENT OF THE CAPACITY AND QUALITY AS INDICATED OR
SCHEDULED OR APPROVED EQUAL.
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE N.E.C., LATEST EDITION, AND ALL
APPLICABLE STATE AND LOCAL ORDINANCES. EACH PIECE OF ELECTRICAL EQUIPMENT
INSTALLED SHALL BE NEW UNLESS NOTED OTHERWISE AND ALL SHALL BEAR A U.L. LABEL.
GUARANTEE ENTIRE INSTALLATION (MATERIALS AND LABOR) TO BE IN GOOD REPAIR FOR A
PERIOD OF ONE YEAR FOLLOWING THE FINAL DATE OF ACCEPTANCE.
A. LIGHTING SYSTEMS.
B. ELECTRICAL DISTRIBUTION SYSTEMS, INCLUDING RECEPTACLES, AND ALL
OTHER WIRING DEVICES.
C. CONDUITS, WIRES, AND TERMINATIONS FOR LIGHTING, EQUIPMENT POWER,
GENERAL POWER.
D. POWER TO CONTROL CIRCUIT POWER SUPPLIES AND OTHER SYSTEMS AS
SHOWN OR INDICATED.
E. CONDUIT SYSTEMS FOR TELEPHONE AND OTHER CABLING.
3. IN THE DESCRIPTION OF WORK HEREIN OR ON THE DRAWINGS, THE WORD "CIRCUIT" SHALL
MEAN THE CONTRACTOR IS TO PROVIDE ALL COMPONENTS (WIRE, CONDUIT, FITTINGS,
HANGERS, CIRCUIT BREAKER, TERMINATIONS, ETC.) REQUIRED TO APPLY POWER TO AN
ITEM.
4. PROVIDE ALL BRANCH CIRCUITS AND SWITCHING AS INDICATED ON THE ELECTRICAL AND/OR
ARCHITECTURAL PLANS. SHARED NEUTRAL CONDUCTORS ARE NOT ALLOWED. PROVIDE
SEPARATE NEUTRAL FOR EACH BRANCH CIRCUIT. CIRCUITS SHALL BE #12 THWN/THHN
CONDUCTORS IN 3/4" C. METAL EMT OR RIGID METAL CONDUIT AS REQUIRED UNLESS
OTHERWISE NOTED; THESE ARE MINIMUM WIRE AND CONDUIT SIZES.
5. THE ELECTRICAL DESIGN IS BASED ON THE AMPACITY OF COPPER CONDUCTORS RATED AT
75°C FOR COMPATIBILITY WITH THE UL LISTING OF EQUIPMENT. CONDUCTORS RATED FOR
90°C SHALL BE ALLOWED, BUT AT THEIR 75°C RATING. ALUMINUM CABLE IS NOT ALLOWED.
6. FOR 120/208/240 VOLT CIRCUITS OF TOTAL PHYSICAL LENGTH OVER 150 FEET (ONE WAY),
PROVIDE #10 AWG CONDUCTORS. FOR 277/480V CIRCUITS OF TOTAL PHYSICAL LENGTH
OVER 250 FEET (ONE WAY), PROVIDE #10 AWG CONDUCTORS.
7. CONDUIT FITTINGS SHALL BE COMPRESSION TYPE OR SET SCREW TYPE, EXCEPT SET
SCREW TYPE ARE PROHIBITED FOR SUSPENDED CONDUIT. ALL CONDUCTORS SHALL BE
COPPER AND GROUND WIRES INDICATED SHALL BE INSULATED (GREEN COLOR) COPPER.
CONNECTIONS TO ALL EQUIPMENT AND LIGHTING FIXTURES SHALL BE BY A FLEXIBLE
TYPE CONDUIT ACCORDING TO THE NEC.
8. ALL LOADS SHALL BE PROPERLY BALANCED BETWEEN PHASES TO A MAXIMUM OF +/- 10% OF
AMPERAGE IMBALANCE.
9. ARRANGE FOR ALL ELECTRIC SERVICE REQUIRED BY ALL TRADES INVOLVED IN THE
CONSTRUCTION OF THIS PROJECT. RECEPTACLES, CORDS, LIGHTS, AND LEVELS OF
LIGHTING SHALL CONFORM TO O.S.H.A., NEC AND LOCAL ORDINANCES. PROVIDE
TEMPORARY POWER AT THE SITE WHEN REQUIRED.
10. PROVIDE ALL CIRCUITS IN ACCORDANCE WITH WIRING DIAGRAMS AND MANUFACTURER'S
WRITTEN INSTRUCTIONS FOR POWER AND FOR CONTROL OF HVAC EQUIPMENT.
COORDINATE ALL ELECTRICAL WORK WITH THE ELECTRICAL CHARACTERISTICS OF ALL
EQUIPMENT.
19. ALL WIRING DEVICES AND COVERPLATES SHALL BE WHITE COLOR AND ALL COVERPLATES
SHALL BE OF PLASTIC MATERIAL UNLESS NOTED OTHERWISE ON THE DRAWINGS. VERIFY
FINAL DEVICE AND COVER PLATE COLORS WITH ARCHITECT PRIOR TO PURCHASE OR
INSTALLATION OF ANY DEVICES.
90A AND 90B.
PLENUMS . . . . . . . . . . . .
RETURN AIR . . . . . . . . . .
SUPPLY AIR . . . . . . . . . .
12. INSULATE DUCTWORK AS FOLLOWS:
A. EXTERNAL DUCT WRAP SHALL BE 2" FOIL FACED EXTERNAL INSULATION
D. DUCT SIZES SHOWN ARE AIRSTREAM DIMENSIONS.
X
X
X
EXTERNAL WRAP LINER
C. DUCT SYSTEMS SHALL COMPLY WITH ALL APPLICABLE REQUIREMENTS OF NFPA
2. USE OF FLEXIBLE DUCT IS LIMITED TO THAT DETAILED ON THE
DRAWINGS, BUT ONLY IN AREAS WHERE DUCT IS NOT VISIBLE.
AND PIPE CONTENT. ADHESIVE TYPE MARKERS ARE PROHIBITED.
VAPOR TIGHT WITH FOIL TAPE OR MASTIC.
18. CONTROL ACCURACY SHALL BE +/- 1 DEGREE F.
17. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL CONTROLS THAT WILL
COMPLETELY ACCOMPLISH THE IMPLIED OR INTENDED FUNCTIONS OF THE CONTROL
OUTDOORS.
SYSTEM AS SHOWN OR SPECIFIED.
GROWTH AND NFPA-90A AND 90B.
AMERICAN STANDARD
KOHLER
ELJER
JOSAM
WADE
ELKAY
SHALL BE CERTIFIED FOR FUNGI RESISTANCE WHICH SHALL BE 100% NO-
REQUIREMENTS OF ASTM C1071 FOR PHYSICAL PROPERTIES EXCEPT LINER
PLUMBING FIXTURES AND EQUIPMENT SHALL BE FURNISHED AS SCHEDULED OR
INDICATED AND INSTALLED COMPLETE WITH STOP KITS, ESCUTCHEONS, TRIM,
CARRIERS, BLOCKING AND ALL OTHER APPURTENANCES REQUIED TO CNNECT
FIXTURES AND EQUIPMENT TO ROUGH-IN PIPING AT FLOORS AND WALS UNLESS
SPECIFIED OTHERWISE.
PROVIDE PLUMBING EQUIPMENT AS OF THE TYPE AND QUALITY AS SCHEDULED
OR INDICATED ON THE DRAWINGS AS MANUFACTURED BY:
PROVIDE EACH FLOOR DRAIN OR HUB DRAIN WITH A TRAP PRIMER AS SHOWN OR
ACCORDING TO THE LOCAL CODE AUTHORITY HAVING JURISDICTION.
PROVIDE ENGRAVED NAMEPLATE ATTACHED WITH SCREWS FOR ALL MAJOR
EQUIPMENT PROVIDED. USE NOMENCLATURE FROM EQUPMENT SCHEDULES.
13.
A.
1.
2.
3.
4.
5.
6.
B.
14.
A. PROVIDE SAFETY DISCONNECT SWITCH WHEN AVAILABLE AS A FACTORY
ELECTRICAL DRAWINGS ONLY. PROVIDE AS REQUIRED AND SPECIFIED BELOW.
PROVIDING THE EQUIPMENT THAT REQUIRES SAME. THESE ITEMS ARE SHOWN ON THE
CONTACTORS FOR EQUIPMENT. THESE SHALL BE FURNISHED BY THE CONTRACTOR
15. PROVIDE MANUAL STARTERS, MAGNETIC STARTERS, COMBINATION STARTERS AND
B. DUCT LINER SHALL BE 1" LINER, 3 PCF DENSITY COMPLYING WITH THE
19. 24 VOLT CONTROL WIRING SHALL BE IN 1/2" EMT CONDUIT WITH COMPRESSION FITTINGS
16. PROVIDE SNAP-ON TYPE PIPE MARKERS EACH 10' THAT INDICATE BOTH FLOW DIRECTION
(INSTALLED R VALUE = 5.0) SEAL ALL EXTERNAL WRAP INSULATION SEAMS
1. NAILOR
4. TITUS
A. PROVIDE AIR DEVICES AS MANUFACTURED BY:
2. KRUEGER
3. METALAIRE
10. INSULATE PIPING AS FOLLOWS:
9. ALL FANS SHALL CARRY THE CERTIFIED RATING SEAL AUTHORIZED BY AMCA.
CONDENSATE PIPING . . . . . . . . . . . . . . . . . 1/2"
PIPING THICKNESS
WITH THE PIPING.
D. SUPPORTS FOR ANY INSULATED PIPING SHALL NOT BE IN DIRECT CONTACT
25/50 FOR AIR PLENUM USE OR WHERE EXPOSED TO HVAC SYSTEM AIR.
C. PROVIDE ALL INSULATION AND JACKET MATERIALS SPECIFICALLY APPROVED IS
INSULATION AT HANGERS AND OTHER SUPPORTS.
AND SHEET METAL INSULATION SHIELDS TO PREVENT CRUSHING OF
CEILINGS AND AT HANGERS. PROVIDE REDWOOD OR CALCIUM SILICATE BLOCKS
SEALED TO PREVENT SWEATING AND CONTINUOUS THROUGH WALLS, FLOORS,
B. PROVIDE OWENS CORNING FIBERGLASS ASJ SSL-II OR APPROVED EQUAL,
2. DOMESTIC HOT AND COLD WATER AND RELIEF VALVE PIPING SHALL BE TYPE "L" COPPER
WITH WROUGHT COPPER FITTINGS. NO JOINTS SHALL BE CONCEALED IN SLABS. JOIN
ALL WATER PIPING WITH LEAD FREE SOLDER. SANITIZE POTABLE WATER SYSTEMS PER
LOCAL HEALTH DEPARTMENT REQUIREMENTS.
3. CONDENSATE DRAINAGE PIPING SHALL BE TYPE 'M' WITH WROUGHT FITTINGS JOINED
WITH SOLDER. PVC MAY BE USED (EXCEPT IN RETURN AIR PLENUMS) WHERE LOCAL
CODES PERMIT.
4. SANITARY SEWER DRAIN WASTE AND VENT PIPING SHALL BE SERVICE WEIGHT CAST IRON
WITH PROPER CAST IRON FITTINGS. PROVIDE A HUB DRAIN AND PIPING FOR ANY DRAIN
OR RELIEF VALVE.
5. ALL OTHER PIPING SHALL BE TYPE L COPPER WITH 50/50 SOLDER JOINTS. FITTINGS
SHALL BE WROUGHT COPPER, FACTORY FABRICATED, HAVING INDUSTRY STANDARD
FLOW PATTERNS.
6. PROVIDE A DIELECTRIC FITTING WHEREVER DISSIMILAR METALS ARE JOINED, EXCEPT
AT VALVE BODIES.
7. BALL VALVES SHALL BE TWO PIECE, BRASS BODY, THREAD CONNECTION TEFLON SEAT,
STOCKHAM FIGURE #S214-BR-TT OR EQUAL.
8. DIFFUSERS, REGISTERS AND GRILLES SHALL BE AS SCHEDULED OR NOTED AND ALL
SHALL BE PROVIDED WITH FRAMES COMPATIBLE WITH EACH CEILING TYPE.
CONTRACTOR SHALL COORDINATE ALL DIFFUSER LOCATIONS AND FRAME TYPES
WITH FINAL APPROVED REFLECTED CEILING PLAN FOR LIGHT FIXTURE AND ALL
OTHER CEILING MOUNTED DEVICE LOCATIONS.
11. DUCTWORK SHALL BE SHEET METAL CONSTRUCTED AND SEALED ACCORDING TO
SMACNA STANDARDS FOR 1" W.C. POSITIVE AND NEGATIVE PRESSURE. FLEXIBLE
DUCT MAY BE USED ONLY AS DETAILED ON THE DRAWINGS. REFER TO DUCTWORK
LEGEND AND DUCT DETAILS ON DRAWINGS FOR DUCTWORK, FITTINGS, VANES,
DAMPERS, ETC.
A. PROVIDE VIBRATION ISOLATION FOR MOTOR-DRIVEN MECHANICAL EQUIPMENT
PER MANUFACTURER'S RECOMMENDATIONS AND AS SHOWN.
B. PROVIDE FLEXIBLE DUCTWORK CONNECTIONS AT INLET AND OUTLET OF
EQUIPMENT.
1. FLEXIBLE DUCT SHALL HAVE 1" THICK INSULATION WITH FOIL JACKET AND
VAPOR BARRIER LINER. DUCT SHALL MEET CLASS I, UL-181, AND 25/50 FIRE
RATING REQUIREMENTS.
11. LABEL PANELBOARDS THAT ARE PROVIDED WITH ENGRAVED NAMEPLATE,
FASTENED WITH SCREWS. USE NOMENCLATURE FROM PANELBOARD SCHEDULE
AND AS NOTED ON THE DRAWINGS. PANELBOARD DIRECTORIES SHALL BE
ACCURATE AND TYPEWRITTEN.
16. PROVIDE (1) EMPTY 3/4" CONDUIT WITH PULL STRING FROM EACH DATA AND EACH
TELEPHONE OUTLET INDICATED OR SHOWN STORAGE ROOM. DATA AND
TELEPHONE CABLE TO BE PROVIDED BY OTHERS. ALL CABLE TO BE INSTALLED BY
OTHERS IS ASSUMED TO BE PLENUM RATED.
17. ALL TELEPHONE, DATA, AND ELECTRICAL OUTLETS SHALL BE MOUNTED
VERTICALLY, UNLESS NOTED OTHERWISE. REFER TO DRAWINGS FOR
MOUNTING HEIGHTS.
HOT WATER . . . . . . . . . . . . . . . . . . . . . . . . . NOTE A
COLD WATER . . . . . . . . . . . . . . . . . . . . . . . . 1/2"
TO 1". PIPE INSULATION WILL HAVE A CONDUCTIVITY OF LESS THAN
IF PIPE LESS THAN 1.5" NOMINAL DIAMETER. LARGER PIPE MUST BE INSULATED
A. SERVICE HOT WATER PIPING WHERE REQUIRED, MUST BE INSULATED TO 1/2"
0.28 BTU.IN/(H-FT2-°F).
PROJECT NUMBER
DATE
SHEET TITLE
REV. # DESCRIPTION DATE 1
2
3
4
5
SHEET NUMBER
402 Parker Street M
cKinney, Texas
t 972.302.9747
conduitad.com
4144 N. Central Expressway, Suite 380
Dallas, Texas 75204
Ph: 214.428.7744
Fax: 214.428.7770
www.mezaengineeringinc.com
Project:
MEZA ENGINEERING, INC.Texas Registered Engineering Firm F-345
15006.000
Page 4
EXISTING
HVAC
EXISTING
ELEC
STORAGE
COMMUNITY ROOM
FIRE RISER
1
2
3
4
5
6
6
9
7
7
8
7
GENERAL NOTES
NOTES BY SYMBOL
1
THESE PLANS ARE DIAGRAMMATIC IN NATURE, INCLUDE APPROPRIATE
ALLOWANCES FOR OFFSETS AS REQUIRED TO ACCOMMODATE VERTICAL AND
HORIZONTAL VARIATIONS IN THE LOCATIONS AND ELEVATIONS OF DUCTWORK,
PIPING, ETC. DUE TO EXISTING CONDITIONS.
REMOVE EXISTING SINK, FAUCET, AND CAP ALL PLUMBING SERVICES.
REMOVE EXISTING WATER CLOSET, AND CAP ALL PLUMBING SERVICES.
REMOVE EXISTING OUTSIDE AIR INTAKE LOUVER; CAP OPENING PER
ARCHITECTURAL REQUIREMENTS. OUTSIDE AIR DUCT TO BE REROUTED TO ROOF.
EXISTING FURNACE, COOLING COILS, AND RETURN AIR GRILLE TO REMAIN. CLEAN
GRILLE, CLEAN DRAIN PAN, CLEAN COILS, REPLACE FILTERS,AND RECHARGE
REFRIGERANT. EXISTING FLUE THRU ROOF TO REMAIN.
EXISTING CONDENSING UNIT TO REMAIN. CLEAN COILS AND RECHARGE AS
REQUIRED. PROVIDE A WRITTEN INSPECTION REPORT ON ENTIRE SPLIT SYSTEM
PRIOR TO STARTING WORK.
EXISTING DUCT TO BE REMOVED AND CAPPED AT TAP. PROVIDE DUCT INSULATION
EQUAL TO EXISTING.
EXISTING CEILING AIR DEVICE TO BE RELOCATED.
EXISTING CEILING AIR DEVICE TO REMAIN. (TYPICAL)
EXISTING FLUE.
2
PENETRATIONS OF WALLS OR FLOORS FOR THE PASSAGE OF PIPING, DUCTWORK,
OR OTHER EQUIPMENT SHALL BE PROPERLY SEALED AFTER INSTALLATION OF
ITEMS AND EQUIPMENT. FIELD VERIFY EXISTING WALL PENETRATIONS AND
PROPERLY SEAL AS REQUIRED TO MAINTAIN WALL OR FLOOR RATING.
PROVIDE ACCESS TO ALL CONCEALED EQUIPMENT. COORDINATE LOCATIONS OF
ACCESS PANELS WITH ARCHITECT.
ALL CONSTRUCTION DEBRIS SHALL BE DISPOSED OF BY CONTRACTOR UNLESS
NOTED OTHERWISE.
CONTRACTOR TO VERIFY LOCATION AND SIZE OF EXISTING WATER, SEWER, AND
VENT PIPES PRIOR TO THE COMMENCING OF WORK.
ALL WORK TO CONFORM TO ALL APPLICABLE FEDERAL, STATE, AND LOCAL
BUILDING CODES INCLUDING CURRENT INTERNATIONAL ENERGY CONSERVATION
CODE.
3
4
5
6
7
8
9
PROJECT NUMBER
DATE
SHEET TITLE
REV. # DESCRIPTION DATE 1
2
3
4
5
SHEET NUMBER
402 Parker Street M
cKinney, Texas
t 972.302.9747
conduitad.com
4144 N. Central Expressway, Suite 380
Dallas, Texas 75204
Ph: 214.428.7744
Fax: 214.428.7770
www.mezaengineeringinc.com
Project:
MEZA ENGINEERING, INC.Texas Registered Engineering Firm F-345
15006.000
1 DEMO FLOOR PLAN - HVAC & PLUMBING
3/8" = 1'-0"
DEMO FLOOR PLAN
- HVAC & PLUMBING
Page 5
WH
3
4
R300
5
R300
7
E 300
14"Ø
E300
E300
E300
8"Ø
S-1
6
MS-1
WH-1
FD-1
A50
WC-1
EF-2
L-1
L-1
EF-1
WC-1
EF-3
R100
9
9
9
10"Ø
6
9
8
FD-1FD-1
A50
1 1
2 2
GENERAL NOTES
NOTES BY SYMBOL
1. THESE PLANS ARE DIAGRAMMATIC IN NATURE, INCLUDE APPROPRIATE
ALLOWANCES FOR OFFSETS AS REQUIRED TO ACCOMMODATE VERTICAL AND
HORIZONTAL VARIATIONS IN THE LOCATIONS AND ELEVATIONS OF DUCTWORK,
PIPING, ETC. DUE TO EXISTING CONDITIONS.
2. PENETRATIONS OF WALLS OR FLOORS FOR THE PASSAGE OF PIPING, DUCTWORK,
OR OTHER EQUIPMENT SHALL BE PROPERLY SEALED AFTER INSTALLATION OF
ITEMS AND EQUIPMENT. FIELD VERIFY EXISTING WALL PENETRATIONS AND
PROPERLY SEAL AS REQUIRED TO MAINTAIN WALL OR FLOOR RATING.
3. PROVIDE ACCESS TO ALL CONCEALED EQUIPMENT. COORDINATE LOCATIONS OF
ACCESS PANELS WITH ARCHITECT.
4. ALL CONSTRUCTION DEBRIS SHALL BE DISPOSED OF BY CONTRACTOR UNLESS
NOTED OTHERWISE.
5. CONTRACTOR TO VERIFY LOCATION AND SIZE OF EXISTING WATER, SEWER, AND
VENT PIPES PRIOR TO THE COMMENCING OF WORK.
6. ALL WORK TO CONFORM TO ALL APPLICABLE FEDERAL, STATE, AND LOCAL
BUILDING CODES INCLUDING CURRENT INTERNATIONAL ENERGY CONSERVATION
CODE.
1INSTALL NEW LAV AND FAUCET AT THIS LOCATION; EXTEND PLUMBING SERVICES
TO THIS LOCATION AND MAKE CONNECTIONS ACCORDINGLY.
INSTALL NEW ADA WATER CLOSET AT THIS LOCATION; EXTEND PLUMBING
SERVICES TO THIS LOCATION AND MAKE CONNECTIONS ACCORDINGLY.
INSTALL NEW SINK AND FAUCET AT THIS LOCATION; EXTEND PLUMBING SERVICES
TO THIS LOCATION AND MAKE CONNECTIONS ACCORDINGLY.
LOCATE WH-1 ON SHELF ABOVE MOP SINK.
EXISTING CONDENSING UNIT TO REMAIN. CLEAN COILS AND RECHARGE AS
REQUIRED. PROVIDE A WRITTEN INSPECTION REPORT ON ENTIRE SPLIT SYSTEM
PRIOR TO STARTING WORK.
EXTEND EXISTING FURNACE OUTSIDE AIR DUCT (VENTILATION) UP THRU ROOF.
MAINTAIN A MINIMUM OF 15'-0" FROM AIR VENTS, FLUE'S, AND EXHAUST OUTLETS.
PROVIDE ROOF CAP. PROVIDE NEW INLINE FAN (SF-1) WITH MOTORIZED DAMPER IN
OUTSIDE AIR DUCT. LOCATE FAN IN MECH ROOM. FAN (SF-1) AND MOTORIZED
DAMPER SHALL BE INTERLOCKED WITH FURNACE (FAN/DAMPER OFF/CLOSED WHEN
FURNACE IS OFF; FAN/DAMPER ON/OPEN WHEN FURNACE IS ON). INCLUDE ALL
NECESSARY DUCTWORK, CONTROLS, POWER, ETC. AS REQUIRED.
CLEAN AND PAINT ALL EXISTING CEILING AIR DEVICES TO REMAIN. AIR DEVICES TO
BE PAINTED SAME COLOR AS NEW DEVICES. (TYPICAL OF 7)
REBALANCE ALL AIR DEVICES TO NOTED AIR QUANTITIES.
DUCT UP THRU ROOF. TERMINATE WITH ROOF CAP.
2
3
7. MODIFY THE EXISTING SPRINKLER SYSTEM TO PROVIDE COVERAGE FOR THE
RENOVATED AND EXPANDED FLOOR PLAN LAYOUT; COMPLY WITH NFPA-13 AND
LOCAL AND STATE FIRE PROTECTION CODES.
8. ALLOW FOR SAWCUTTING RELATED TO NEW UNDERFLOOR PLUMBING
REQUIREMENTS, ALONG WITH COLD WATER, HOT WATER, VENTING, ETC. FOR ALL
NEW PLUMBING REQUIREMENTS FROM A COST BUDGETARY STANDPOINT. FUTURE
PHASE WILL SHOW ANTICIPATED PIPING REQUIREMENTS.
4
5
6
7
8
9
PROJECT NUMBER
DATE
SHEET TITLE
REV. # DESCRIPTION DATE 1
2
3
4
5
SHEET NUMBER
402 Parker Street M
cKinney, Texas
t 972.302.9747
conduitad.com
4144 N. Central Expressway, Suite 380
Dallas, Texas 75204
Ph: 214.428.7744
Fax: 214.428.7770
www.mezaengineeringinc.com
Project:
MEZA ENGINEERING, INC.Texas Registered Engineering Firm F-345
15006.000
1 FLOOR PLAN - HVAC & PLUMBING
3/8" = 1'-0"
FLOOR PLAN - HVAC
& PLUMBING
Page 6
CEILING
PERFORATED METAL GRILLE
FURNISHED WITH FAN
CEILING EXHAUST FAN
MOUNTING BRACKETS SHALL
HANGER RODS SUPPORTED
FROM STRUCTURE ABOVE
BE ADJUSTABLE TO ALLOW
FLUSH MOUNTING IN CEILING.
ROOF
SHEETMETAL DUCT
4 CEILING EXHAUST FAN DETAIL
NO SCALE
FAN TO BE
FURNISHED WITH
BACKDRAFT
DAMPER
UNION CONNECTION
DISTRIBUTION UNIT
(4-WAY MAX.) WALL MTD.
FLOOR DRAIN WITH
DEEP SEAL TRAP
FINISHED FLOOR
BALL VALVE (ISOLATION VALVE)
1/2" TRAP PRIMER SUPPLY
1/2" TRAP PRIMER LINE
DOMESTIC WATER LINE
SLEEVE THRU
SLAB
TPV
"PPPI" PRIME RITE TRAP
PRIMER VALVE WITH
INTEGRAL VACUUM
BREAKER
1/2" MIN. COLD WATER SUPPLY
(AVOID DIRECT CONNECTIONS
TO PREVENT FOREIGN
MATERIAL FROM ENTERING
PRIMER VALVE)
TRAP PRIMER ASSEMBLY AND
ISOLATION VALVE TO BE ABOVE
ACCESSIBLE CEILING OR IF IN WALL
PROVIDE STAINLESS STEEL ACCESS
PANEL FOR PROPER MAINTENANCE
TAILPIECE
DEEPSEAL P-TRAP
FLOOR
WASTE LINE
FLOOR DRAIN
REF: PLANS FOR LOCATION
1/2" TRAP
PRIMER LINE
INSULATION EXTEND DAMPER OPERATOR
THROUGH INSULATION
CEILING
SPIN-IN FITTING
WITH DAMPER
SUPPLY DUCT
INSULATE TOP
OF DIFFUSER
SECURE FLEXIBLE DUCT TO
DUCT COLLAR AND DIFFUSER
NECK WITH S.S. SCREW CLAMP
INSULATED FLEXIBLE DUCT
MAXIMUM 5 FOOT LENGTH
CEILING DIFFUSER
DUCT SIZE SAME SIZE AS
SCHEDULED NECK
CONNECTION OF
DIFFUSER
D
R
R > 1.5D MINIMUM
RADIUS
5 DIFFUSER CONNECTION DETAIL
NO SCALE
22 GA. GALV. STEEL WATERTIGHT
DRAIN PAN (2" LARGER THAN WATER
HEATER ON ALL SIDES) WITH
INDIRECT DRAIN TO MOP SINK
3/8" HANGER RODS SUPPORTED
FROM STRUCTURE (4 TOTAL)
T&P RELIEF VALVE WITH
FULL SIZE DISCHARGE
TO MOP SINK
1-1/2"x1-1/2"x3/16"
STEEL ANGLES OR
EQUIV. UNISTRUT
EXPANSION TANK
VACUUM RELIEF VALVE
CHECK VALVE (TYP.)
BALL VALVE (TYP.)
COLD WATER
SUPPLY
THERMOMETER (TYP.)
DIELECTRIC UNION (TYP.)
FINISHED
FLOOR
3/4"
MOP SINK
PROVIDE EXTERNAL HEAT
TRAPS TO COLD AND HOT
WATER PIPING
HOT WATER
SUPPLY
MIXING VALVE
TO MOP SINK
MECHANICAL AND
PLUMBING DETAILS
PROJECT NUMBER
DATE
SHEET TITLE
REV. # DESCRIPTION DATE 1
2
3
4
5
SHEET NUMBER
402 Parker Street M
cKinney, Texas
t 972.302.9747
conduitad.com
4144 N. Central Expressway, Suite 380
Dallas, Texas 75204
Ph: 214.428.7744
Fax: 214.428.7770
www.mezaengineeringinc.com
Project:
MEZA ENGINEERING, INC.Texas Registered Engineering Firm F-345
15006.000
Page 7
PLUMBING FIXTURE CONNECTION SCHEDULE
TYPE OF FIXTURE WASTE VENT CW HW NOTES
WATER CLOSET - TANK TYPE 4" 2"
3
4
" -
LAVATORY 2" 1
1
2
"
1
2
"
1
2
"
SINK 2" 1
1
2
"
1
2
"
1
2
"
FLOOR DRAIN 3" 2" - - PROVIDE ALL FLOOR DRAIN WITH TRAP PRIMER
MOP SINK 3" 2"
3
4
"
3
4
"
WATER HEATER SCHEDULE
DESIGNATION SERVES LOCATION
ELECT
CHARACTRISTICS
MANUFACTURER MODEL NO.
RECOVERY
PER HOUR @
100° RISE
TANK
GALLONS
NOTES
WH-1SUITE
JANITOR
CLOSET
208V/60Hz/1Ph AO SMITH DEL-15 17 15 ALL
NOTE:
1. FACTORY ASSEMBLED UNIT. INLET AND OUTLET THERMOMETERS, TANK TEMPERATURE THERMOMETER, RELIEF VALVE AND TANK TEMPERATURE CONTROL.
2. REFERENCE DETAILS.
3. PROVIDE TEMPERATURE MIXING VALVE.
EXPANSION TANK SCHEDULE
MARK SERVES LOCATION TANK CAPACITY
INSTALLATION
CONFIGURATION
TANK
PRESSURE
RATING (PSI)
MANUFACTURERMODEL
NOTES
ET-1WH-1
JANITOR
CLOSET
2.1 SUSPENDED 150 AMTROL ST-5-C
ASME CERTIFIED AND SHALL
COMPLY WITH NSF 61
PLUMBING FIXTURE SCHEDULE
MARK FIXTURE DESCRIPTION
L-1LAVATORY
TOTO SUPREME LHT241.8G COTTON COLOR #01 WALL-HUNG LAVATORY, DELTA LAHARA 3538 MPU-DST, CHROME, 0.5
GPM TWO-HANDLE FAUCET 8" SPREAD. LEONARD MODEL 170-BP ADJUSTABLE THERMOSTATIC MIXING VALVE WITH
RECESSED CABINET ASSEMBLY. McGUIRE # 155-WC OFFSET GRID STRAINER DRAIN. McGUIRE # 2167-LK SUPPLIES,
LOOSE KEY STOP, JOSAM # 17100 SERIES WALL CARRIER.
S-1SINK
ELKAY MODEL NO. ELUHAD1916-5.5" "LUSTERTONE" 18 GA. TYPE 304 STAINLESS STEEL, SINGLE COMPARTMENT 5
1
2
"
DEEP UNDERMOUNT SINK. DELTA LINDEN 1353-DS, CHROME, AND 2 GPM LAMINAR FLOW SPOUT. McGUIRE #152 GRID
DRAIN. McGUIRE # 8903 P-TRAP, 1-1/2" TAILPIECE. McGUIRE # 171LK SUPPLIES WITH WHEEL HANDLE STOPS.
WC-1
WATER CLOSET
(ADA)
AMERICAN STANDARD "COLONY" 221AA.105. 1.28 GPF. TANK TYPE VITREOUS CHINA ELONGATED BOWL HIGH
EFFICIENCY TOILET, 16
1
2
" RIM HEIGHT. CHURCH MODEL 9500C
ELONGATED SEAT, OPEN FRONT LESS COVER, WHITE
SOLID PLASTIC, CONCEALED CHECK STAINLESS STEEL HINGES.
MS-1MOP SINK
FIAT #MSB 24"x24" MOLDED STONE SERVICE BASIN, 10" HIGH WITH 1" WIDE PLAIN SHOULDERS, STAINLESS STEEL
INTEGRAL DRAIN BODY AND STRAINER. FIAT #830-AA SERVICE FAUCET WITH VACUUM BREAKER, INTEGRAL STOPS,
ADJUSTABLE WALL BRACE, PAIL HOOK AND 3/4" HOSE THREAD ON SPOUT, #832-AA HOSE AND HOSE BRACKET AND 3
EACH #889-CC MOP HANGERS.
FD-1FLOOR DRAIN
J.R. SMITH # 2005Y-B-CP SQUARE FLOOR DRAIN WITH NO HUB NICKEL BRONZE HEEL PROOF STRAINER AND TRAP
PRIMER CONNECTION.
TPV
TRAP PRIMER
VALVE
PRECISION PLUMBING PRODUCTS TRAP PRIMER VALVE # P2-500 WITH DISTRIBUTION SYSTEM.
GENERAL NOTES:
1. FIXTURE MANUFACTURER SHALL BE AS LISTED.
2. PROVIDE ALL CARRIERS AND SUPPORT MATERIALS REQUIRED FOR A SOLID, SECURE INSTALLATION.
3. PROVIDE ALL DRAIN COVERS, ESCUTCHEONS,AND MISCELLANEOUS TRIM ITEMS FOR A NEAT APPEARANCE.
4. ALL MOUNTED HEIGHTS SHALL BE VERIFIED WITH THE ELEVATIONS SHOWN ON THE ARCHITECTURAL DRAWINGS.
5. ALL PUMPING FIXTURES MUST CONFORM TO CURRENT WATER CONSERVATION REGULATIONS.
6. ALL HANDICAPPED ACCESSIBLE PLUMBING FIXTURES MUST CONFORM TO CURRENT TEXAS ACCESSIBILITY STANDARDS.
AIR DEVICE SCHEDULE
MARK SERVICE TYPE MOUNTING VOLUME CONTROL
SIZE
MANUFACTURER MODEL NO. MATERIAL NOTES
FACE NECK
A SUPPLY PERFORATED CEILING NO 12"X12" NOTE 1 TITUS PAS STEEL1,2,3,5
E EXISTING - - - - - - - - 4
R
EXISTING
RELOCATED
- - - - - - - - 4
NOTES:
1. 6"Ø(25-100 CFM); 8"Ø(101-200 CFM); 10"Ø(201-400 CFM); 12"Ø(401-600 CFM).
2. REFERENCE AIR DEVICE CONNECTION DETAIL FOR VOLUME CONTROL REQUIREMENTS.
3. COORDINATE CEILING FRAME REQUIREMENT WITH ARCHITECTURAL REFLECTED CEILING PLANS.
4. EXISTING AIR DEVICE TO BE REUSED, CLEAN AND BALANCE AS INDICATED.
5. PROVIDE WITH OPTIONAL FOIL BACKED INSULATION BLANKET.
FAN SCHEDULE
MARK SERVES TYPE CFM EXT. SP. DRIVE
MOTOR
MANUFACTURER MODEL NO. NOTES
WATTS RPM VOLTS/HZ/Ø
EF-1,2
MEN/WOMEN
RESTROOM
CEILING 70 0.375 DIRECT 85 950 115/60/1 GREENHECK SP-B1101, 2, 3, 4, 6, 7
EF-3 JANITOR CEILING 50 0.375 DIRECT 55 900 115/60/1 GREENHECK SP-B802, 3, 4, 6, 7, 8
SF-1
FURNACE
OUTSIDE AIR
IN LINE DUCT 300 0.5 DIRECT 220 1070 115/60/1 GREENHECK CSP-A503, 4, 5, 7
NOTES:
1. EXHAUST FAN TO BE CONTROLLED WITH LIGHT SWITCH.
2. PROVIDE BACKDRAFT DAMPER.
3. PROVIDE ROOF CAP.
4. PROVIDE SPEED CONTROLLER AND INTEGRAL DISCONNECT. LOCATE CONTROLLER IN ACCESSIBLE LOCATION.
5. PROVIDE FAN WITH MOTORIZED DUCT DAMPER - INTERLOCKED WITH FAN.
6. PROVIDE STANDARD FAN GRILLE
7. PROVIDE HANGING VIBRATION ISOLATOR KIT.
8. PROVIDE WALL SWITCH. FAN TO RUN CONTINUOUSLY.
1/2"
1 1/2"
S-1
2"
FLOOR
CEILING
ROOF
1/2"
1 1/2"
L-1
2"
MS-1
WH-1
3/4"
2"
2"
3"
FD-1
2"
3/4"
WC-1
4"
GENERAL NOTES
1. RISER DIAGRAMS ARE SCHEMATIC IN NATURE AND DO NOT REFLECT EVERY
OFFSET, BRANCH, RISER OR UNION.
2. CONTRACTOR SHALL REFER TO PLUMBING FLOOR PLANS FOR FIXTURE
DESIGNATIONS.
3. CONTRACTOR SHALL REVIEW PLUMBING, AND ARCHITECTURAL DRAWINGS AND
PROVIDE ALL PLUMBING FIXTURES SHOWN ON EACH DRAWING.
4. CONTRACTOR SHALL VERIFY LOCATIONS OF ADA/TAS APPROVED PLUMBING
FIXTURES WITH ARCHITECTURAL DRAWINGS.
5. CONTRACTOR SHALL INSTALL SHOCK ABSORBERS ON ALL PLUMBING FIXTURE
BATTERIES AND QUICK CLOSING EQUIPMENT AND FIXTURES.
6. CONTRACTOR SHALL INSTALL TRAP PRIMERS ON ALL FLOOR DRAINS, FLOOR
SINKS, HUB DRAINS, AND INDIRECT DRAINS UNLESS OTHERWISE NOTED.
7. CONTRACTOR SHALL INSTALL 12"x12" ACCESS PANELS DIRECTLY IN FRONT OF
SHOCK ABSORBERS AND TRAP PRIMERS.
8. CONTRACTOR SHALL PROVIDE AN ISOLATION BALL VALVE ON ALL TRAP PRIMERS
AND SHOCK ABSORBERS FOR MAINTENANCE.
9. ACCESS PANEL SIZES AND EXACT LOCATIONS SHALL BE COORDINATED WITH
ARCHITECT BEFORE INSTALLATION.
10. ARCHITECT RESERVES THE RIGHT TO RELOCATE ACCESS PANELS PRIOR TO
INSTALLATION WITHOUT ADDITIONAL COST.
NOT TO SCALE
1
PLUMBING RISERS
2"
FD-1
SCHEDULES AND
RISERS
PROJECT NUMBER
DATE
SHEET TITLE
REV. # DESCRIPTION DATE 1
2
3
4
5
SHEET NUMBER
402 Parker Street M
cKinney, Texas
t 972.302.9747
conduitad.com
4144 N. Central Expressway, Suite 380
Dallas, Texas 75204
Ph: 214.428.7744
Fax: 214.428.7770
www.mezaengineeringinc.com
Project:
MEZA ENGINEERING, INC.Texas Registered Engineering Firm F-345
15006.000
Page 8
EXISTING
HVAC
EXISTING
ELEC
STORAGE
COMMUNITY ROOM
FIRE RISER
D
D
SC
SC
D
WP
GFI/WP
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
GENERAL NOTES
NOTES BY SYMBOL
REFER TO MEP1.01 FOR SYMBOLS AND ABBREVIATIONS.
EXISTING 120/208V, 200AMP PANEL 'L' TO REMAIN.
ITEMS SHOWN DASHED OR ITEMS ON WALLS OR CEILINGS THAT ARE TO BE
DEMOLISHED ARE TO BE REMOVED. RETAIN EXISTING BRANCH CIRCUITS FOR
POTENTIAL REUSE DURING RENOVATION WORK. AS-BUILT DOCUMENTS WERE NOT
AVAILABLE FOR USE DURING CONSTRUCTION DOCUMENT PREPARATION; TRACE
OUT ALL EXISTING BRANCH CIRCUITS WITHIN PROJECT SCOPE AREA AND PROVIDE
LIST OF AVAILABLE BRANCH CIRCUITS TO ARCHITECT/ENGINEER PRIOR TO START
OF DEMOLITION OR RENOVATION WORK.
PROVIDE TYPEWRITTEN UPDATE FOR PANELBOARD CIRCUIT DIRECTORIES TO
REFLECT ALL CHANGES ASSOCIATED WITH THIS PROJECT.
WHERE DEVICES HAVE BEEN REMOVED AND EXISTING BRANCH CIRCUITS WILL NOT
BE REUSED, REMOVE BRANCH CIRCUIT FROM DEVICE TO SOURCE.
REFER TO MECHANICAL PLANS FOR OVERALL EQUIPMENT DEMOLITION
REQUIREMENTS AND ACCOUNT FOR SUCH WITHIN BID.
EXISTING WALL MOUNTED WET LOCATION RATED SPEAKERS TO BE REMOVED;
COORDINATE WITH OWNER'S REPRESENTATIVE FOR DISPOSAL REQUIREMENTS.
REMOVE EXISTING WIRING DEVICE.
REMOVE EXISTING LIGHT.
REMOVE EXISTING CEILING FAN AND RETAIN FOR RELOCATION; REFER TO
RENOVATION PLAN FOR NEW LOCATIONS.
WHERE EXISTING DEVICES HAVE BEEN REMOVED, COORDINATE WITH OWNER'S
REPRESENTATIVE FOR DISPOSAL REQUIREMENTS AND ACCOUNT FOR
ACCORDINGLY WITHIN BID.
WHERE EXISTING DEVICES HAVE BEEN REMOVED, PATCH AND PAINT OPENINGS
PER ARCHITECTURAL DOCUMENT REQUIREMENTS.
EXISTING TO BE REMOVED.
TYPE DESCRIPTION
EXISTING TO REMAIN.
PROJECT NUMBER
DATE
SHEET TITLE
REV. # DESCRIPTION DATE 1
2
3
4
5
SHEET NUMBER
402 Parker Street M
cKinney, Texas
t 972.302.9747
conduitad.com
4144 N. Central Expressway, Suite 380
Dallas, Texas 75204
Ph: 214.428.7744
Fax: 214.428.7770
www.mezaengineeringinc.com
Project:
MEZA ENGINEERING, INC.Texas Registered Engineering Firm F-345
15006.000
1 DEMO FLOOR PLAN - POWER & LIGHTING
3/8" = 1'-0"
DEMO FLOOR PLAN -
POWER & LIGHTING
Page 9
WH
GFI
GFI
GFIGFI
A A A
AAA
A A A
AAA
A A A
AAA
A A A
AA
A
A
B B
C C
D
D
CF(b)
CF(a)
CF(c)
EM
EM
X
X
GFI
WP
D
D
SC
SC
SC
EF-2 EF-1
EM
EM
L-32
L-34
L-36
L-38
L-40
A
L-42
L-31/33
30/2
WH-1
GFI
(a)
(b)
(c)
SF-1
L-35
D
D
X
EF-3
E
EXISTING
PANEL 'L'
GENERAL NOTES
NOTES BY SYMBOL
REFER TO MEP1.01 FOR SYMBOLS AND ABBREVIATIONS.
LOCATE DEVICES TO SERVE OWNER PROVIDED PROJECTOR (INSTALL AT
APPROXIMATELY 9'-6"AFF) CONFIRM FINAL LOCATION REQUIREMENTS WITH
OWNER'S REPRESENTATIVE PRIOR TO INSTALLATION AND ACCOMMODATE
ACCORDINGLY. PROVIDE EMPTY 1 1/2"C CONCEALED TO EQUIPMENT SOURCE
LOCATION FOR PROJECTOR INPUT CABLING REQUIREMENTS.
MATCH COLOR OF EXISTING WIRING DEVICES AND COVERPLATES FOR NEW
DEVICES; COORDINATE FINAL COLOR OF ALL NEW DEVICES WITH ARCHITECT.
ALL ELECTRICAL OUTLETS IN WET LOCATIONS TO BE GFCI TYPE.
PROVIDE DEDICATED NEUTRAL CONDUCTOR FOR EACH NEW BRANCH CIRCUIT; DO
NOT SHARE NEUTRAL CONDUCTORS BETWEEN CIRCUITS.
WHERE NEW CIRCUIT BREAKERS ARE INSTALLED IN EXISTING PANELS, MATCH AIC
RATING AND MANUFACTURER OF EXISTING EQUIPMENT.
TYPE DESCRIPTION
NEW UNLESS OTHERWISE NOTED.
EXISTING TO REMAIN.
POWER SUPPLY TO OWNER PROVIDED OVERHEAD MOTORIZED PROJECTOR
SCREEN; CONFIRM FINAL LOCATION REQUIREMENTS WITH OWNER'S
REPRESENTATIVE PRIOR TO INSTALLATION AND ACCOMMODATE ACCORDINGLY.
LOCATE DEVICES IN MILLWORK; COORDINATE FINAL LOCATIONS WITH OWNER'S
REPRESENTATIVE PRIOR TO INSTALLATION AND ACCOMMODATE ACCORDINGLY.
INSTALL 1P20AMP CIRCUIT BREAKER IN AVAILABLE SPACE OF EXISTING 120/208V
PANEL 'L'; MAKE CONNECTION WITH 2#12, #12G, 3/4"C.
CONNECT NEW LIGHTS, CEILING FANS, AND EXHAUST FANS TO 120V, 20AMP
BRANCH CIRCUITS RETAINED FROM DEMOLITION. BALANCE LOAD ON AVAILABLE
CIRCUITS, AND SWITCH / CONTROL AS INDICATED.
CONNECT NEW EXIT LIGHTS AND NEW EGRESS LIGHTS TO SAME LIGHTING BRANCH
CIRCUITS SERVING OTHER SWITCHED LIGHTING FIXTURES FOR AREA LOCATED IN
AHEAD OF ANY SWITCHING (CONNECT UNSWITCHED).
INTERLOCK INLINE FAN IF-1 WITH HVAC UNIT SUCH THAT WHEN THE HVAC UNIT IS
ENERGIZED SF-1 IS ALSO ENERGIZED.
PROVIDE SEPARATE 3-SPEED SWITCH FOR CONTROL FOR EACH CEILING FAN PER
MANUFACTURER'S REQUIREMENTS; LOCATE AT WALL NEAR LIGHT SWITCHES.
CONNECT EXTERIOR LIGHT FIXTURES TO BRANCH CIRCUIT PREVIOUSLY SERVING
REMOVED EXTERIOR LIGHT FIXTURES. CONTROL BRANCH CIRCUIT SERVING
EXTERIOR LIGHT FIXTURES VIA PHOTOCELL AND/OR TIMECLOCK. CONNECT
EGRESS PORTION OF ANY EXTERIOR LIGHT FIXTURES AHEAD OF ANY SWITCHING
(SEE GENERAL NOTE 7 ABOVE).
PROJECT NUMBER
DATE
SHEET TITLE
REV. # DESCRIPTION DATE 1
2
3
4
5
SHEET NUMBER
402 Parker Street M
cKinney, Texas
t 972.302.9747
conduitad.com
4144 N. Central Expressway, Suite 380
Dallas, Texas 75204
Ph: 214.428.7744
Fax: 214.428.7770
www.mezaengineeringinc.com
Project:
MEZA ENGINEERING, INC.Texas Registered Engineering Firm F-345
15006.000
1 FLOOR PLAN - POWER & LIGHTING
3/8" = 1'-0"
FLOOR PLAN -
POWER & LIGHTING
Page 10
LIGHTING FIXTURE SCHEDULE
MARK MANUFACTURER CATALOG NUMBER LAMP VOLTAGE MOUNTING DESCRIPTION
A DMF LIGHTING
DRDHNIC6-DRD2M10935-
DRD2TR6SWH
LED, 14.7W120V RECESSED
RECESSED LED DOWNLIGHT; SUITABLE FOR
RECESSED MOUNTING IN INSULATED ATTIC AREA.
WHERE FIXTURE IS INSTALLED AT SLOPED CEILING
AREA PROVIDE WITH SLOPED FRAME AND TRIM KIT.
B DMF LIGHTING
DRDHNIC6-DRD2M7935-
DRD2TR6SWH
LED, 11.8W120V RECESSED
RECESSED LED DOWNLIGHT; SUITABLE FOR
RECESSED MOUNTING IN INSULATED ATTIC AREA.
C TBD TBD 60W MAXIMUM 120V SURFACE
WALL MOUNTED DECORATIVE LIGHT FIXTURE,
BRONZE FINISH; CHOSEN BY ARCHITECT AND
OWNER'S VENDOR.
CF EXISTING EXISTING EXISTING 120V PENDANT
EXISTING CEILING FAN TO BE RELOCATED;
COORDINATE FINAL LOCATIONS WITH ARCHITECT.
D ASL LIGHTING
BSV-LED-12.5-
DV-3500-FBZ-EMG
LED 12.5W 120V SURFACE
WALL MOUNTED, WET LOCATION RATED LIGHT
FIXTURE, WITH INTEGRAL BATTERY PACK AND
CHARGER. COORDINATE FINAL MOUNTING LOCATION
WITH ARCHITECT.
E LITHONIA OLWX1-LED-20W-4000KLED, 22W
120V SURFACE
WALL MOUNTED, WET LOCATION RATED LIGHT
FIXTURE, WITH INTEGRAL BATTERY PACK AND
CHARGER. COORDINATE FINAL MOUNTING LOCATION
WITH ARCHITECT.
EM LITHONIA AFN DB FWDLED, 10.8W
120V SURFACE
SURFACE MOUNTED EMERGENCY EGRESS LIGHT
FIXTURE WITH INTEGRAL BATTERY PACK AND
CHARGER, DARK BRONZE FINISH.
UC LITHONIA 2UC-117-MVOLT-LP- GEB10IS
1-LAMP, 17W (24")
120V SURFACE
UNDER COUNTER FLUORESCENT LIGHT FIXTURE;
COORDINATE FINAL MOUNTING LOCATION WITH
ARCHITECT PRIOR TO INSTALLATION.
X LITHONIA LQM S W 3 R 120/ 277 ELN SDLED, 1W
120V UNIVERSAL
LED UNIVERSAL MOUNT EXIT SIGN WITH NICKEL
CADMIUM BATTERY AND INTEGRAL CHARGER, SELF
DIAGNOSTIC TEST.
NOTE:
1. WHERE RECESSED LIGHT FIXTURES ARE INSTALLED IN GYPBOARD CEILING AREAS PROVIDE LIGHT FIXTURES WITH FLANGE KIT PER MANUFACTURER'S REQUIREMENT.
E3.00
PROJECT NUMBER
DATE
SHEET TITLE
REV. # DESCRIPTION DATE 1
2
3
4
5
SHEET NUMBER
402 Parker Street M
cKinney, Texas
t 972.302.9747
conduitad.com
4144 N. Central Expressway, Suite 380
Dallas, Texas 75204
Ph: 214.428.7744
Fax: 214.428.7770
www.mezaengineeringinc.com
Project:
MEZA ENGINEERING, INC.Texas Registered Engineering Firm F-345
15006.000