APPROXIMATE LOCATION OF EXISTING ELECTRICAL CABINET DUFFERIN STREET DUPONT STREET HALLAM STREET GLADSTONE AVE. APPROXIMATE LOCATION OF NEW OUTDOOR NATURAL GAS GENERATOR APPROXIMATE LOCATION OF EXISTING BOILER ROOM E-1 SITE PLAN, DETAILS, SEQUENCE OF IMPLEMENTATION, DRAWING LIST AND SYMBOL LEGEND - ELECTRICAL FIRE STATION No.345 MMM Group Limited 100 Commerce Valley Drive West Thornhill, ON L3T 0A1 t. 905-882-1100 f. 905-882-0055 www.mmm.ca 1 2016/08/18 Issued For 75% Client Review 2 2016/09/21 Issued For Permit & Tender 3 2016/11/28 Issued For Tender - Rev.1 ELECTRICAL DRAWING LIST SITE PLAN, DETAILS, SEQUENCE OF IMPLEMENTATION, DRAWING LIST AND SYMBOL LEGEND - ELECTRICAL E-1 DRAWING No. E-3 EXISTING ELECTRICAL ROOM AND NEW WORK GENERATOR LAYOUT - POWER AND SIGNALS - ELECTRICAL DESCRIPTION AS NOTED SCALE N.T.S. ELECTRICAL SINGLE LINE DIAGRAM. E-2 AS NOTED SITE PLAN 1 E-1 SCALE: N.T.S. PLAN VIEW ELEVATION 50 DURO MASON SUPER W PAD 1/4" STEEL PLATES SCALE: N.T.S. SCALE: N.T.S. SCALE: N.T.S. OUTLINE OF GENERATOR BASE 61" 44" 35" "X" "X" 3/4" 2" 2" 4" 18" 3/4" 3/4" 18" 4" 2" 2" 3/4" GENERATOR BASE (ISOLATION LAYOUT) SUPER W PAD (ISOLATION DETAIL) SUPER W PAD W/ HOLE (ISOLATION DETAIL) PLAN VIEW ELEVATION REFER TO SHOP DRAWINGS 4"x18" 50 Duro Super W Pad Isolators ISOLATION DETAIL 2 E-1 SCALE: N.T.S. BE RESPONSIBLE TO LOCATE ALL UNDERGROUND UTILITIES, STRUCTURES AND ETC. PRIOR TO CONSTRUCTION AND ASSUME ALL LIABILITY FOR DAMAGE TO THEM DURING THE COURSE OF CONSTRUCTION. ANY DAMAGE TO THE EXISTING UTILITIES, STRUCTURES AND ETC. ARE TO BE DOCUMENTED AND WILL REQUIRE IMMEDIATE REPAIR. BE RESPONSIBLE FOR ALL COST OF THE REPAIR. NOTE: ELECTRICAL SYMBOL LIST DEMOLITION SYMBOLS SYMBOL DESCRIPTION EXISTING ITEM TO BE RELOCATED. EXTEND EXISTING WIRING IN CONDUIT TO NEW LOCATION AND CONNECT COMPLETE. EXISTING ITEM TO BE DELETED. REMOVE ALL EXISTING WIRING, CONDUIT, ETC. BACK TO ITS SOURCE. MAINTAIN CIRCUIT CONTINUITY DOWNSTREAM. EXISTING ITEM TO BE REPLACED BY A NEW FIXTURE OR DEVICE AND RECONNECTED TO EXISTING OR NEW CIRCUIT WHERE SHOWN. EXISTING ITEM TO BE DISCONNECTED, REMOVED, CLEANED, RE-INSTALLED IN SAME LOCATION AND RECONNECTED TO EXISTING CIRCUIT. EXISTING ITEM TO REMAIN AS INSTALLED. EXISTING ITEM IN RELOCATED POSITION. EXISTING ITEM IN ITS RE-INSTALLED POSITION. DESCRIPTION SYMBOL SYMBOL DESCRIPTION POWER SYMBOLS PP PP DUPLEX U-GROUND 15A, 125 VOLT, 2 POLE, 3 WIRE GROUNDING RECEPTACLE MOUNTED 12" (300 mm) ABOVE FINISHED LEVEL, UNLESS OTHERWISE NOTED. FLUSH-MOUNTED "EMERGENCY POWER OFF" PUSHBUTTON MOUNTED 3'-6" (1050mm) ABOVE FINISHED FLOOR LEVEL. "WP" DENOTES WEATHERPROOF. "CG" DENOTES C/W STI CLEAR GUARD C/W HORN. FLUSH-MOUNTED PUSHBUTTON MOUNTED 4'-0" (1.2 m) ABOVE FINISHED FLOOR LEVEL. "WP" DENOTES WEATHERPROOF. RECESSED OR SURFACE MOUNTED PANELBOARD, "PP" DENOTES POWER PANEL, "LP" DENOTES LIGHTING AND POWER PANEL, "DP" DENOTES DISTRIBUTION PANELBOARD. EPO WP DISCONNECT SWITCH (FUSED OR NOT FUSED) WHERE SHOWN ON DRAWINGS OR REQUIRED BY CODE. "WP" INDICATES WEATHERPROOF TYPE. WP CG SIMILAR TO ABOVE, BUT MOUNTED APPROXIMATELY 3'-6" (1050 mm) ABOVE FINISHED FLOOR LEVEL OR ABOVE COUNTER. EMERGENCY BATTERY UNIT COMPLETE WITH DUAL HEAD TYPE LIGHT. REFER TO SPECIFICATIONS FOR DETAILS. LIGHTING SYMBOLS E DESCRIPTION SYMBOL SINGLE LINE DIAGRAM SYMBOLS AUTOMATIC TRANSFER SWITCH (ATS) WITHOUT MANUAL BYPASS FIRE ALARM SYMBOLS DESCRIPTION SYMBOL 2 EX AUTOMATIC HEAT DETECTOR 15°F (8.3°C) RATE OF RISE AND FIXED TEMPERATURE TYPE 135°F (57°C) RATED AT 2500 FT (232m ) COVERAGE. "EX" WHERE SHOWN, DENOTES EXPLOSION PROOF. 2 FLAME DETECTOR CEILING MOUNTED TYPE. F D END OF LINE RESISTOR FOR FIRE ALARM SYSTEM. DRY TYPE STEP DOWN TRANSFORMER. MOLDED CASE CIRCUIT BREAKER. THE FOLLOWING IS A PROPOSED SEQUENCE IMPLEMENTATION, INTENDED TO GIVE A DIAGRAMMATIC OVERVIEW OF THE PROPOSED SEQUENCE OF INSTALLATION FOR THIS PROJECT. BE RESPONSIBLE TO CONFIRM THIS SEQUENCE, MAKE THE REQUIRED MODIFICATION TO SUIT THE ANOMALIES OF THIS BUILDING AND COORDINATE THIS WHEN PREPARING THE MASTER CONSTRUCTION SCHEDULE FOR THE IMPLEMENTATION OF ALL WORK ASSOCIATED WITH THIS PROJECT. PROPOSED SEQUENCE OF IMPLEMENTAION ELECTRICAL 1. 1.1 PREPARE SITE TO ACCOMMODATE THE NEW GENERATOR AND ANCILLARY EQUIPMENT/DEVICES. INSTALL NEW GENERATOR IN ITS PERMANENT LOCATION AND PROVIDE FEEDERS AS SHOWN ON THE DRAWINGS. CONFIRM SITE MEASUREMENTS AND ROUTINGS OF ALL FEEDERS AND PLACEMENT LOCATIONS OF ALL COMPONENTS PRIOR TO COMMENCEMENT OF WORK. 1.7 FIRE STOP ALL NEW WALL PENETRATIONS. WHEN ALL THE ELECTRICAL SERVICES HAVE BEEN INSTALLED, COMPLETED AND COMMISSIONED: 2. 2.2 COMPLETE AS-BUILTS, O&M MANUALS AND TURN OVER TO CONSULTANT. 2.3 COMPLETE ALL REMAINING REMEDIAL WORK, INCLUDING PATCHING WORK, FIRE STOPPING, CEILING INSTALLATIONS, PAINTING, ETC. UPON COMPLETION OF ELECTRICAL SERVICES. 1.3 1.4 1.5 1.6 PREPARE AND SUBMIT SHOP DRAWINGS FOR NEW GENERATOR AND TRANSFER SWITCH FOR REVIEW. ORDER EQUIPMENT AND COORDINATE DELIVERY AND INSTALLATION. 2.1 TEST OPERATION OF NEW GENERATOR AND TRANSFER SWITCH. REFER TO SPECIFICATION FOR DETAILS. 1.2 WATER SEAL ALL OPENINGS. PROJECT PROPOSED SEQUENCE OF IMPLEMENTATION FUSE DISCONNECT SWITCH. LINE OR LOW VOLTAGE CABLE IN CONDUIT. LINE OR LOW VOLTAGE CABLE IN CONDUIT. TEMPORARY GENERATOR NOT REQUIRED FOR POWER SHUTDOWN. CONTRACTOR IS TO NOTIFY THE CITY OF TORONTO PROJECT MANAGER 10 BUSINESS DAYS PRIOR TO WHEN THE POWER SHUTDOWN WILL BE REQUIRED. THE CONTRACTOR TO HAVE ALL NECESSARY WORK PREPARED TO ENSURE THE SHUTDOWN IS NO LONGER THAN 4 HOURS.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
APPROXIMATE LOCATION OF
EXISTING ELECTRICAL CABINET
DUFFERIN STREET
DU
PO
NT
S
TR
EE
T
HA
LLA
M S
TR
EE
T
GLADSTONE AVE.
APPROXIMATE LOCATION OF NEW
OUTDOOR NATURAL GAS GENERATOR
APPROXIMATE LOCATION OF
EXISTING BOILER ROOM
E-1
SITE PLAN, DETAILS, SEQUENCE
OF IMPLEMENTATION, DRAWING
LIST AND SYMBOL LEGEND -
ELECTRICAL
FIRE STATION No.345
MMM Group Limited100 Commerce Valley Drive West
Thornhill, ON L3T 0A1
t. 905-882-1100
f. 905-882-0055
www.mmm.ca
1 2016/08/18 Issued For 75% Client Review
2 2016/09/21 Issued For Permit & Tender
3 2016/11/28 Issued For Tender - Rev.1
ELECTRICAL DRAWING LIST
SITE PLAN, DETAILS, SEQUENCE OF IMPLEMENTATION,
DRAWING LIST AND SYMBOL LEGEND - ELECTRICAL
E-1
DRAWING No.
E-3
EXISTING ELECTRICAL ROOM AND NEW WORK GENERATOR
LAYOUT - POWER AND SIGNALS - ELECTRICAL
DESCRIPTION
AS NOTED
SCALE
N.T.S.ELECTRICAL SINGLE LINE DIAGRAM.
E-2 AS NOTED
SITE PLAN
1
E-1
SCALE: N.T.S.
PLAN VIEW
ELEVATION
50 DURO MASON SUPER W PAD
1/4" STEEL PLATES
SCALE: N.T.S.
SCALE: N.T.S.
SCALE: N.T.S.
OUTLINE OF GENERATOR BASE
61"
44"35"
"X
"
"X"
3/4"
2"
2"
4"
18"
3/4"
3/4"
18"
4"
2"
2"
3/4"
GENERATOR BASE (ISOLATION LAYOUT)
SUPER W PAD (ISOLATION DETAIL)
SUPER W PAD W/ HOLE (ISOLATION DETAIL)
PLAN VIEW
ELEVATION
REFER TO SHOP
DRAWINGS
4"x18" 50 Duro Super W Pad Isolators
ISOLATION DETAIL
2
E-1
SCALE: N.T.S.
BE RESPONSIBLE TO LOCATE ALL
UNDERGROUND UTILITIES, STRUCTURES
AND ETC. PRIOR TO CONSTRUCTION AND
ASSUME ALL LIABILITY FOR DAMAGE TO
THEM DURING THE COURSE OF
CONSTRUCTION. ANY DAMAGE TO THE
EXISTING UTILITIES, STRUCTURES AND
ETC. ARE TO BE DOCUMENTED AND WILL
REQUIRE IMMEDIATE REPAIR. BE
RESPONSIBLE FOR ALL COST OF THE
REPAIR.
NOTE:
ELECTRICAL SYMBOL LIST
DEMOLITION SYMBOLSSYMBOL DESCRIPTION
EXISTING ITEM TO BE RELOCATED. EXTEND EXISTING WIRING IN CONDUIT TO NEW
LOCATION AND CONNECT COMPLETE.
EXISTING ITEM TO BE DELETED. REMOVE ALL EXISTING WIRING, CONDUIT, ETC.
BACK TO ITS SOURCE. MAINTAIN CIRCUIT CONTINUITY DOWNSTREAM.
EXISTING ITEM TO BE REPLACED BY A NEW FIXTURE OR DEVICE AND
RECONNECTED TO EXISTING OR NEW CIRCUIT WHERE SHOWN.
EXISTING ITEM TO BE DISCONNECTED, REMOVED, CLEANED, RE-INSTALLED IN
SAME LOCATION AND RECONNECTED TO EXISTING CIRCUIT.
FLUSH-MOUNTED PUSHBUTTON MOUNTED 4'-0" (1.2 m) ABOVE FINISHED
FLOOR LEVEL. "WP" DENOTES WEATHERPROOF.
RECESSED OR SURFACE MOUNTED PANELBOARD, "PP" DENOTES POWER
PANEL, "LP" DENOTES LIGHTING AND POWER PANEL, "DP" DENOTES
DISTRIBUTION PANELBOARD.
EPO
WP
DISCONNECT SWITCH (FUSED OR NOT FUSED) WHERE SHOWN ON DRAWINGS
OR REQUIRED BY CODE. "WP" INDICATES WEATHERPROOF TYPE.
WP
CG
SIMILAR TO ABOVE, BUT MOUNTED APPROXIMATELY 3'-6" (1050 mm) ABOVE
FINISHED FLOOR LEVEL OR ABOVE COUNTER.
EMERGENCY BATTERY UNIT COMPLETE WITH DUAL HEAD TYPE LIGHT.
REFER TO SPECIFICATIONS FOR DETAILS.
LIGHTING SYMBOLS
E
DESCRIPTIONSYMBOL
SINGLE LINE DIAGRAM SYMBOLS
AUTOMATIC TRANSFER SWITCH (ATS) WITHOUT MANUAL BYPASS
FIRE ALARM SYMBOLSDESCRIPTIONSYMBOL
2
EX
AUTOMATIC HEAT DETECTOR 15°F (8.3°C) RATE OF RISE AND FIXED
TEMPERATURE TYPE 135°F (57°C) RATED AT 2500 FT (232m ) COVERAGE.
"EX" WHERE SHOWN, DENOTES EXPLOSION PROOF.
2
FLAME DETECTOR CEILING MOUNTED TYPE.
F
D
END OF LINE RESISTOR FOR FIRE ALARM SYSTEM.
DRY TYPE STEP DOWN TRANSFORMER.
MOLDED CASE CIRCUIT BREAKER.
THE FOLLOWING IS A PROPOSED SEQUENCE IMPLEMENTATION, INTENDED
TO GIVE A DIAGRAMMATIC OVERVIEW OF THE PROPOSED SEQUENCE OF
INSTALLATION FOR THIS PROJECT. BE RESPONSIBLE TO CONFIRM THIS
SEQUENCE, MAKE THE REQUIRED MODIFICATION TO SUIT THE ANOMALIES
OF THIS BUILDING AND COORDINATE THIS WHEN PREPARING THE MASTER
CONSTRUCTION SCHEDULE FOR THE IMPLEMENTATION OF ALL WORK
ASSOCIATED WITH THIS PROJECT.
PROPOSED SEQUENCE OF IMPLEMENTAION
ELECTRICAL1.
1.1
PREPARE SITE TO ACCOMMODATE THE NEW GENERATOR AND
ANCILLARY EQUIPMENT/DEVICES.
INSTALL NEW GENERATOR IN ITS PERMANENT LOCATION AND
PROVIDE FEEDERS AS SHOWN ON THE DRAWINGS.
CONFIRM SITE MEASUREMENTS AND ROUTINGS OF ALL FEEDERS
AND PLACEMENT LOCATIONS OF ALL COMPONENTS PRIOR TO
COMMENCEMENT OF WORK.
1.7
FIRE STOP ALL NEW WALL PENETRATIONS.
WHEN ALL THE ELECTRICAL SERVICES HAVE BEEN INSTALLED,
COMPLETED AND COMMISSIONED:
2.
2.2
COMPLETE AS-BUILTS, O&M MANUALS AND TURN OVER TO
CONSULTANT.
2.3
COMPLETE ALL REMAINING REMEDIAL WORK, INCLUDING PATCHING
WORK, FIRE STOPPING, CEILING INSTALLATIONS, PAINTING, ETC.
UPON COMPLETION OF ELECTRICAL SERVICES.
1.3
1.4
1.5
1.6
PREPARE AND SUBMIT SHOP DRAWINGS FOR NEW GENERATOR
AND TRANSFER SWITCH FOR REVIEW. ORDER EQUIPMENT AND
COORDINATE DELIVERY AND INSTALLATION.
2.1
TEST OPERATION OF NEW GENERATOR AND TRANSFER SWITCH.
REFER TO SPECIFICATION FOR DETAILS.
1.2
WATER SEAL ALL OPENINGS.
PROJECT PROPOSED SEQUENCE OF
IMPLEMENTATION
FUSE DISCONNECT SWITCH.
LINE OR LOW VOLTAGE CABLE IN CONDUIT.
LINE OR LOW VOLTAGE CABLE IN CONDUIT.
TEMPORARY GENERATOR NOT REQUIRED FOR POWER SHUTDOWN.
CONTRACTOR IS TO NOTIFY THE CITY OF TORONTO PROJECT MANAGER
10 BUSINESS DAYS PRIOR TO WHEN THE POWER SHUTDOWN WILL BE
REQUIRED. THE CONTRACTOR TO HAVE ALL NECESSARY WORK
PREPARED TO ENSURE THE SHUTDOWN IS NO LONGER THAN 4 HOURS.
AutoCAD SHX Text
DATE: 2016/07/20
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
PROJECT :
AutoCAD SHX Text
CLIENT : - CITY OF TORONTO
AutoCAD SHX Text
CONSULTANT
AutoCAD SHX Text
THIS DRAWING ARE NOT TO BE SCALED. REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL, ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFORE PROCEEDING WITH THE WORK. CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES AND REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST ASSUME FULL RESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS OR DAMAGES RESULTING FROM HIS WORK. THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BY AND IS THE PROPERTY OF THE ARCHITECT. THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITY FOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALL NOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROM THE SUPPLIED INFORMATION.
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
TRUE NORTH
AutoCAD SHX Text
CONSTRUCTON NORTH
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
REVIEWED BY:
AutoCAD SHX Text
1285 DUFFERIN STREET
AutoCAD SHX Text
TORONTO, ONTARIO, CANADA
AutoCAD SHX Text
- EMERGENCY SERVICES
AutoCAD SHX Text
Metro Hall City of Toronto
AutoCAD SHX Text
2nd floor, 55 John St.,
AutoCAD SHX Text
Toronto, Ontario M5V 3C6
AutoCAD SHX Text
CLIENT
AutoCAD SHX Text
ADDRESS :
AutoCAD SHX Text
MMM PROJECT No.: 1816292-001
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
I.Z.
AutoCAD SHX Text
D.L.
AutoCAD SHX Text
R
AutoCAD SHX Text
R
AutoCAD SHX Text
R
AutoCAD SHX Text
R
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
ER
AutoCAD SHX Text
ER
AutoCAD SHX Text
RR
AutoCAD SHX Text
EOL
AutoCAD SHX Text
RR
AutoCAD SHX Text
RR
AutoCAD SHX Text
RR
NEW NATURAL GAS GENERATOR IN AN
OUTDOOR SKIN-TIGHT ACOUSTICAL
ENCLOSURE, REFER TO SINGLE LINE
FOR GENERATOR DETAILS.
(IN
LE
T S
ID
E)
(D
IS
CH
AR
GE
S
ID
E)
37
00
1100
1500
EPO
WP/CG
GENERATOR SHORE
PANEL. PROVIDED WITH
GENERATOR ENCLOSURE.
EPO PROVIDED WITH
GENERATOR ENCLOSURE.
CONDUIT WITHIN BUILDING TO
ELECTRICAL EQUIPMENT
UNDERGROUND CONDUITS TO TRANSITION TO
SURFACE MOUNT ONTO BUILDING SURFACE, GOING
UP AND RUNNING TO ELECTRICAL EQUIPMENT.
EXISTING ELECTRICAL CABINET
EXISTING BOILER ROOM
EPO
NEW PANEL
GENERATOR
ANNUNCIATOR
CONDUITS FROM ELECTRICAL
CABINET TO ATS-1 AND
TRANSFORMER TX-1, REFER TO
SINGLE FOR DETAILS
CONDUIT TO
GENERATOR
SHORE PANEL
15
00
1 SPARE DUCT WITH PULL STRING
CAPPED AT BOTH END FOR FUTURE USE
CONDUITS SURFACE MOUNT ONTO
BUILDING SURFACE RUNNING TO
ELECTRICAL EQUIPMENT.
OUTLINE OF NEW CONCRETE PAD.
REFER TO STRUCTURE DRAWINGS.
PROTECTIVE BOLLARD WITH CONCRETE.
REFER TO STRUCTURAL DRAWINGS.
(TYPICAL), ENSURE BOLLARD NOT
BLOCKING GENSET DOOR SWING.
EX
IS
TIN
G F
EN
CE
EXISTING FENCE
7m
1389
88
9
50
0
1000
UNDERGROUND CONDUITS
APPROXIMATE LOCATION OF
CONDUITS ENTRANCE TO BUILDING,
PROVIDE ALL OPENINGS AS
REQUIRED FOR A COMPLETE
INSTALLATION.
18.5m
APPROXIMATE LOCATION OF
CONDUITS PENETRATION TO WALL,
PROVIDE ALL OPENINGS AS
REQUIRED FOR A COMPLETE
INSTALLATION.
REFER TO DETAIL 2 OF E-1
FOR ISOLATION DETAILS.
1
2
3
4
5
6 EXISTING SPLITTER IN RELOCATED LOCATION
EXISTING SWITCH IN RELOCATED LOCATION
R
3
2
1
6
4
5
RR
R
R
R
EXISTING SWITCH IN RELOCATED LOCATION
EXISTING SWITCH IN RELOCATED LOCATION
EXISTING SWITCH IN RELOCATED LOCATION
EXISTING SWITCH IN RELOCATED LOCATION
CONDUITS TO
ELECTRICAL
CABINET, REFER
TO SINGLE FOR
DETAILS
CONDUITS FROM
GENERATOR
CONDUIT WITHIN
BUILDING TO ELECTRICAL
EQUIPMENT
TO EPO
7
8 9
7 NEW ATS-1, REFER TO SINGLE FOR DETAILS
8
NEW U/F DISCONNECT FOR ATS-1, REFER TO
SINGLE FOR DETAILS
9
10
NEW REMOTE EMERGENCY BATTERY UNIT c/w HEADS.
PROVIDE NEW 15A-1P LOCK TYPE CIRCUIT BREAKER
FROM NEAREST AVAILABLE PANEL AND FEED WITH
2#12+G IN 16mmC.
CONDUIT TO
GENERATOR
SHORE PANEL
CONDUITS TO
GENERTOR
NEW DRY TYPE TRANSFORMER TX-1, MOUNTED UPHIGH
ON THE WALL TO FREE THE SPACE BELOW FOR OTHER
NEW EQUIPMENT, REFER TO SINGLE LINE FOR DETAIL
10
TO GENERATOR
ANNUNCIATOR
PANEL
E
E
5
4
3
E
M
2
1
NEW FUSED SWITCHBOARD, REFER TO SINGLE LINE FOR DETAILS
1
2
3
4
5
6
7
8
9
EXISTING ROOF TOP UNIT 'NORTH UNIT'
EXISTING EXHAUST FAN 'EF-1'
NEW THES METER, REFER TO SINGLE LINE FOR DETAILS.
NEW 600V SPLITTER, REFER TO SINGLE LINE FOR DETAILS.
ER
ER
ER
6
8
NEW 600V SERVICE ENTRANCE RATED DISCONNECT SWITCH ,REFER
TO SINGLE LINE FOR DETAILS.
EXISTING ROOF TOP UNIT 'SOUTH UNIT'
NEW FUSED DISCONNECT FOR CIRCUIT FEEDING NEW
TRANSFORMER "TX-1", REFER TO SINGLE LINE FOR DETAILS.
EXISTING DOOR OPENING
7
CONDUIT TO
GENERATOR
SHORE PANEL
EXISTING SERVICE ENTRANCE DUCTS
9
CONDUITS TO
ATS-1
CONDUIT FROM
TRANSFORMER
TX-1
CONDUIT TO
TRANSFORMER
TX-1
10
UNFUSED DISCONNECT SWITCH FOR NEW FUSED SWITCHBOARD,
REFER TO SINGLE LINE FOR DETAILS.
10
ER
E
E
5
4
3
E
M
M
8
2
1
7
EXISTING 120/240V FUSED SWITCHBOARD
1
2
3
4
5
6
7
8
9
EXISTING ROOF TOP UNIT 'NORTH UNIT'
EXISTING EXHAUST FAN 'EF-1'
EXISTING THES METER
EXISTING SPLITTER
D
D
ER
ER
ER
ER
6
9
EXISTING 600V SERVICE DISCONNECT SWITCH
EXISTING ROOF TOP UNIT 'SOUTH UNIT'
EXISTING 120/240V SERVICE DISCONNECT SWITCH
EXISTING THES METER
EXISTING DOOR OPENING
D
ER
D
EXISTING SERVICE ENTRANCE DUCTS
10
10
E
ER
R
3
2
1
6
4
5
1
2
3
4
5
6 EXISTING SPLITTER
EXISTING SWITCH
EXISTING SWITCH
EXISTING SWITCH
EXISTING SWITCH
EXISTING SWITCH
RR
R
R
R
E-2
EXISTING BOILER, ELECTRICAL
ROOMS AND NEW WORK
GENERATOR LAYOUT - POWER
AND SIGNALS - ELECTRICAL
1st FLOOR PART PLAN
1E-2
SCALE: N.T.S.
FIRE STATION No.345
MMM Group Limited100 Commerce Valley Drive West
Thornhill, ON L3T 0A1
t. 905-882-1100
f. 905-882-0055
www.mmm.ca
1 2016/08/18 Issued For 75% Client Review
2 2016/09/21 Issued For Permit & Tender
3 2016/11/28 Issued For Tender - Rev.1
1ALL EXISTING ELECTRICAL DEVICES ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
DEMOLITION NOTES:
2CAP OFF AND FIRE STOP ALL FLOOR/WALL CONDUIT STUB-UPS UPON REMOVAL OF FEEDERS.
EXISTING BOILER / ELECTRICAL - NEW WORK
4E-2
SCALE: N.T.S.
EXISTING ELECTRICAL CABINET - NEW WORK
5E-2
SCALE: N.T.S.
EXISTING ELECTRICAL CABINET -DEMOLITION
2E-2
SCALE: N.T.S.
EXISTING BOILER ROOM - DEMOLITION
3E-2
SCALE: N.T.S.
RED MARKING TAPE, THE FULL LENGTH
& WIDTH OF DUCT BANK, APPROXIMATE
HALF WAY BETWEEN THE INSTALLATION
AND GRADE LEVEL
DIRECT BURIED DETAIL
FINISHED GRADE
6
E-2
SCALE: N.T.S.
TRENCHING AND
BACKFILL AS REQUIRED.
TRENCH
MIN.
915
(36")
1. EXACT CONSTRUCTION DETAILS TO CONFORM TO OESC CODE REQUIREMENTS AND
DETAILS. AND PROVIDE PULL STRING AND CAP AT BOTH ENDS IF IT IS SPARE.
NOTES:
RIGID PVC CONDUITS FOR POWER AND
CONTROL WIRING, REFER TO SINGLE
LINE FOR DETAILS.
190
190 190
NEW WORK NOTES:
BE RESPONSIBLE FOR EXACT PLACEMENT, INSTALLATION AND COORDINATION OF
CONNECTING SERVICES OF PROPOSED GENERATOR AFTER REVIEW OF SHOP DRAWINGS.
BE RESPONSIBLE FOR THE SET-UP, INSTALLATION AND CONNECTION OF LOAD BANK FOR
ON-SITE TESTING. CABLING AND LOAD BANK WILL BE SUPPLIED BY GENERATOR
MANUFACTURER. UPON COMPLETION OF SITE TESTING, DISCONNECT LOAD BANK AND
CABLING AND PREPARE FOR PICK UP BY GENERATOR MANUFACTURER.
1.
ROUTING OF ALL SERVICES ARE DIAGRAMMATIC. BE RESPONSIBLE TO CONFIRM EXACT
ROUTING AND TERMINATIONS ON SITE PRIOR TO FABRICATION OR ROUGH-IN AND
INCLUDE FOR REQUIRED OFFSETS, TRANSITIONS ETC. AS REQUIRED FOR A COMPLETE
INSTALLATION. CONDUCTOR TO BE OVERSIZED TO SUIT VOLTAGE DROP AS PER OESC.
2.
ALL PENETRATIONS THROUGH WALLS AND CEILINGS SHALL BE FIRE STOPPED WITH
3m FIRE STOP MATERIAL. REFER TO SPECIFICATIONS FOR DETAILS.
3.
PROVISION OF ALL PENETRATIONS AND OPENINGS AS REQUIRED.4.
COORDINATE TRENCHING / EXCAVATION OF SURFACES TO SUIT NEW GENERATOR
SERVICES. REPLACE WITH NEW SURFACES AND MATCH BASE BUILDING MATERIALS.
CONFIRM AND MARK ON SITE ALL EXISTING SITE SERVICE LOCATIONS WITHIN AREA OF
INSTALLATION. REFER TO SPECIFICATION.
5.
AutoCAD SHX Text
DATE: 2016/07/20
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
PROJECT :
AutoCAD SHX Text
CLIENT : - CITY OF TORONTO
AutoCAD SHX Text
CONSULTANT
AutoCAD SHX Text
THIS DRAWING ARE NOT TO BE SCALED. REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL, ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFORE PROCEEDING WITH THE WORK. CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES AND REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST ASSUME FULL RESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS OR DAMAGES RESULTING FROM HIS WORK. THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BY AND IS THE PROPERTY OF THE ARCHITECT. THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITY FOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALL NOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROM THE SUPPLIED INFORMATION.
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
TRUE NORTH
AutoCAD SHX Text
CONSTRUCTON NORTH
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
REVIEWED BY:
AutoCAD SHX Text
1285 DUFFERIN STREET
AutoCAD SHX Text
TORONTO, ONTARIO, CANADA
AutoCAD SHX Text
- EMERGENCY SERVICES
AutoCAD SHX Text
Metro Hall City of Toronto
AutoCAD SHX Text
2nd floor, 55 John St.,
AutoCAD SHX Text
Toronto, Ontario M5V 3C6
AutoCAD SHX Text
CLIENT
AutoCAD SHX Text
ADDRESS :
AutoCAD SHX Text
MMM PROJECT No.: 1816292-001
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
I.Z.
AutoCAD SHX Text
D.L.
M
EXISTING INCOMING
ELECTRICAL SERVICE
600/347V, 3 PHASE,
CONTRACTOR TO
VERIFY.
ER
D
D
EXISTING TORONTO HYDRO METER CABINET TO BE
REPLACED TO SUIT NEW 3Ø, 4W 100A SERVICE
ENTRANCE, COORDINATE/COMFIRM WITH
TORONTO HYDRO FOR ASSOCIATED WORK AND
EXACT REQUIREMENT AND PROVIDE ALL
ASSOCIATED ACCESSORIES AS REQUIRED TO
FACILITATE THE NEW INSTALLATION COMPLETELY.
ER
EXISTING MAIN SERVICE DISCONNECT SWITCH TO BE
REPLACED WITH NEW 600V, 200A, 3Ø, 4W MAIN SERVICE
ENTRANCE RATED DISCONNECT SWITCH WITH NEW
100A FUSE INSTALLED TO ACCOMMODATE THE NEW
INCOMING TORONTO HYDRO SERVICE NEUTRAL AND
ENSURE EQUIPMENT IS GROUNDED AND BONDED
PROPERLY AS PER OESC REQUIREMENTS. THE NEW
DISCONNECT SWITCH WILL BE RELOCATED AS
REQUIRED TO SUIT NEW INSTALLATION.
M
EXISTING INCOMING
120/240V, 400A, 1PH, 3W
ELECTRICAL SERVICE TO BE
REMOVED, SEE NOTE 3.
D
D
D
EXISTING THES
METER
D
EXISTING MAIN
SERVICE ENTRANCE
DISCONNECT SWITCH
120/240V, 400A
D
EXISTING FUSED SWITCHBOARD TO BE REMOVED
250V
30A
E
EXISTING
ROOF TOP
UNIT 'SOUTH
UNIT'
EEE
EE
EXISTING SPLITTER TO BE REPLACED
EXISTING
EXHAUST FAN
'EF-1'
D
EXISTING LOAD
ER
SERVICE ENTRANCE GROUNDING GRID
PROVIDED BY ELECTRICAL CONTRACTOR.
TYPICAL GROUND RODS FOR MAIN SERVICE ENTRANCE.
100kW
100KW/125kVA, 600/347V, 3PH, 4W, NEW OUTDOOR NATURAL GAS
GENERATOR CONTAINERIZED IN SKIN-TIGHT ACOUSTICAL
ENCLOSURES . REFER TO SPECIFICATION FOR DETAILS.
1#3/0 GROUND, GROUND ALTERNATOR "WYE POINT (NEUTRAL)
OF GENERATOR IN ACCORDANCE WITH CODE REQUIREMENTS
AND MANUFACTURER RECOMMENDATIONS.
BONDING GENERATOR NEUTRAL TO THE FRAME AND GROUND OF
THE GENERATOR IN ACCORDANCE WITH CODE REQUIREMENTS.
EPO
WP
CG
150A-3P
NEW 100A, 120/208V, 3Ø, 4W SHORE PANEL INCLUDED IN
GENERATOR ENCLOSURE.
4#4+G, 53mmC
D 4#1/0+G, 53mmC
NEW AUTOMATIC TRANSFER SWITCH
'ATS-1', 600/347V, 200A, 3PH, 4W
(4 POLE, SWITCHED NEUTRAL)
AUTOMATIC "OPEN TRANSITION"
TRANSFER SWITCH. I.C.=30kA RATED
4#1/0+G, 53mmC
100A-3P
F@90A
75kVA,
600V-208/120V
DRY-TYPE
TRANSFORMER
"TX-1"
4#350+G, 78mmC
3#3+G, 35mmC
REPLACE EXISTING SPLITTER WITH NEW
600V, 225A, 3Ø, 4W SPLITTER AND
RECONNECT ALL EXISTING LOAD
FEEDERS AND ENSURE ALL LOADS ARE
CONNECTED AND EQUALLY BALANCED.
4#2/0+G, 103mmC.
CONTROL WIRING FOR ATS
START/STOP IN 53mmC"
CONDUIT, COORDINATE
WITH MANUFACTURER
RECOMMENDATION FOR
EXACT CABLING & CONDUIT
REQUIREMENTS.
EPOGENERATOR
ANNUNCIATOR
PANEL,
SUPPLIED BY
GENERATOR
MANUFACTURER.
REPLACE EXISTING 120/240V, 400A, FUSED SWITCHBOARD WITH NEW 120/208V, 400A, 3Ø, 4W
FUSED SWITCHBOARD WITH ALL REQUIRED BRANCH CIRCUIT FUSED DISCONNECTS (AND
FUSE) SIZED TO SUIT EACH EXISTING LOAD. RECONNECT ALL EXISTING LOAD FEEDERS AND
ENSURE ALL LOADS ARE CONNECTED AND EQUALLY BALANCED.
SEE NOTE 1
FUSED DISCONNECT
EXISTING OFFICE
GENERATOR BREAKER. COORDINATE WITH COORDINATION
STUDY AND MANUFACTURE RECOMMENDATION. UPDATE
DOWNSTREAM DISTRIBUTION SYSTEM AS REQUIRED TO SUIT
IN ACCORDANCE WITH CODE REQUIREMENTS.
600V
30A
EXISTING
ROOF TOP
UNIT 'NORTH
UNIT'
600V
30A
600V,30A
10A FUSE
MAX
250V
30A
250V
30A
250V
30A
250V
200A
250V
100A
250V
100A
250V
60A
250V
SPARE
200A-3P
F@100A
EXISTING FUSED SWITCHBOARD TO BE REPLACED
WITH NEW FUSED SWITCHBOARD. RECONNECT ALL
EXISTING LOAD FEEDERS COMPLETELY.
SEE NOTE 4
BE RESPONSIBLE TO CONFIRM AND VALIDATE
ELECTRICAL CHARACTERISTICS FOR ALL EXISTING
DOWNSTREAM LOADS AND REPORT BACK TO
CONSULTANT THAT ANY CONCERNS FOR 230/240V
LOADS RECONNECTIONS TO NEW 208V DISTRIBUTION.
200A-3P
U/F
GENERAL NOTES:
1
2ENSURE ELECTRICAL EQUIPMENT ARE BONDED TO GROUND PROPERLY AS PER OESC CODE.
3
COORDINATE/CONFIRM WITH TORONTO HYDRO FOR THE ASSOCIATED WORK OF REMOVING
THE EXISTING 120/240V HYDRO ELECTRICAL INCOMING SERVICES AND ITS ASSOCIATED
ACCESSORIES AND MAKE IT SAFE AS PER OESC.
4
6
EXISTING DISTRIBUTION SYSTEM SHOWN IS DIAGRAMMATIC TO SHOW THE DESIGN INTENT.
BE RESPONSIBLE TO CONFIRM/VERIFY IT PRIOR TO FABRICATION OR ROUGH-IN AND ENSURE
ALL EXISTING LOAD IS PICKED UP AND CONNECTED BALANCED BY THE NEW ELECTRICAL
DISTRIBUTION SYSTEM AND PROVIDE ALL ASSOCIATED ACCESSORIES AS REQUIRED TO
FACILITATE THE NEW INSTALLATION COMPLETELY.
D
5
CONTROL WIRING FOR GENERATOR
ANNUNCIATOR PANEL IN 53mmC CONDUIT,
COORDINATE WITH GENERATOR
MANUFACTURER RECOMMENDATION FOR
EXACT REQUIREMENTS.
CONTROL WIRING FOR EPO BUTTON IN 53mmC CONDUIT,
COORDINATE WITH MANUFACTURER RECOMMENDATION
FOR EXACT REQUIREMENTS.
EXISTING
EQUIPMENT
60A-3P
F@60A
EXISTING
EQUIPMENT
EXISTING
EQUIPMENT
EXISTING
TRANSFORMER
EXISTING
PANEL "A"
EXISTING WORK
BENCH
EXISTING
EQUIPMENT
400A-3P
U/F
D
D
D
D
D D
D
D
D
D
D
D
D
D
D
D
EE
EXISTING UPSTAIR
PANEL "C"
NEW FUSED SWITCHBOARD400A, 120/208V, 3Ø, 4W + G I.C.=25KA
COORDINATE WITH TORONTO HYDRO FOR THE ASSOCIATED WORK OF UPGRADING THE EXISTING
600/347V 3PHASE SERVICE ENTRANCE INCLUDING SERVICE ENTRANCE CABLE REPLACEMENT WITH
NEW CABLE C/W SERVICE NEUTRAL TO SUIT 100A 3PHASE 4 WIRE SERVICE ENTRANCE, ASSOCIATED
METERING UPGRADES AND ETC. ENSURE SERVICE NEUTRAL IS GROUNDED AND BONDED PROPERLY
AT NEW MAIN SERVICE ENTRANCE DISCONNECT SWITCH AS PER OESC. PROVIDE ALL ASSOCIATED
ACCESSORIES AS REQUIRED TO FACILITATE THE NEW INSTALLATION. ALL THIS WORK TO BE PAID
FOR FROM CASH ALLOWANCE.
250V
30A
EXISTING
EQUIPMENT
D
D
250V
30A
EXISTING
EQUIPMENT
D
D
D
SPACE
SPACE
VERIFY EXISTING ELECTRICAL EQUIPMENT INFORMATION SHOWN ON DRAWING WITH SITE
CONDITION PRIOR TO START OF WORK.
7
CONDUCTOR TO BE OVERSIZED TO SUIT VOLTAGE DROP AS PER OESC.
REGARDING TORONTO HYDRO ASSOCIATED WORK,
ALL CONTRACTOR COORDINATION WORK WITH
TORONTO HYDRO WILL BE PART OF BASE BID. ANY
DIRECT COSTS FROM TORONTO HYDRO TO BE PAID
BY THE CONTRACTOR THROUGH CASH ALLOWANCE
(NO MARK UP).
E-3
ELECTRICAL SINGLE LINE
DIAGRAM
FIRE STATION No.345
MMM Group Limited100 Commerce Valley Drive West
Thornhill, ON L3T 0A1
t. 905-882-1100
f. 905-882-0055
www.mmm.ca
1 2016/08/18 Issued For 75% Client Review
2 2016/09/21 Issued For Permit & Tender
3 2016/11/28 Issued For Tender - Rev.1
AutoCAD SHX Text
DATE: 2016/07/20
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
PROJECT :
AutoCAD SHX Text
CLIENT : - CITY OF TORONTO
AutoCAD SHX Text
CONSULTANT
AutoCAD SHX Text
THIS DRAWING ARE NOT TO BE SCALED. REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL, ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFORE PROCEEDING WITH THE WORK. CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES AND REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST ASSUME FULL RESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS OR DAMAGES RESULTING FROM HIS WORK. THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BY AND IS THE PROPERTY OF THE ARCHITECT. THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITY FOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALL NOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROM THE SUPPLIED INFORMATION.
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
TRUE NORTH
AutoCAD SHX Text
CONSTRUCTON NORTH
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
REVIEWED BY:
AutoCAD SHX Text
1285 DUFFERIN STREET
AutoCAD SHX Text
TORONTO, ONTARIO, CANADA
AutoCAD SHX Text
- EMERGENCY SERVICES
AutoCAD SHX Text
Metro Hall City of Toronto
AutoCAD SHX Text
2nd floor, 55 John St.,
AutoCAD SHX Text
Toronto, Ontario M5V 3C6
AutoCAD SHX Text
CLIENT
AutoCAD SHX Text
ADDRESS :
AutoCAD SHX Text
MMM PROJECT No.: 1816292-001
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
I.Z.
AutoCAD SHX Text
D.L.
DUFFERIN STREET
DU
PO
NT
S
TR
EE
T
HA
LLA
M S
TR
EE
T
GLADSTONE AVE.
EXISTING FIRE HALL #345
(1285 DUFFERIN ST.)
APPROXIMATE LOCATION OF EXISTING
GAS METER AND REGULATOR
ASSEMBLY TO BE REMOVED
NEW GAS METER AND
REGULATOR ASSEMBLY
APPROXIMATE LOCATION OF NEW
OUTDOOR NATURAL GAS GENERATOR.
REFER TO ELECTRICAL PLANS FOR
FINAL LOCATION.
G
ROUTE NEW GAS LINE ALONG BUILDING
WALL, CLEAR OF DOORS AND EQUIPMENT
TO GENERATOR
EXISTING GAS BBQ TO REMAIN
THE FOLLOWING IS A PROPOSED SEQUENCE IMPLEMENTATION, INTENDED TO
GIVE A DIAGRAMMATIC OVERVIEW OF THE PROPOSED SEQUENCE OF
INSTALLATION FOR THIS PROJECT. BE RESPONSIBLE TO CONFIRM THIS
SEQUENCE, MAKE THE REQUIRED MODIFICATION TO SUIT THE ANOMALIES OF
THIS BUILDING AND COORDINATE THIS WHEN PREPARING THE MASTER
CONSTRUCTION SCHEDULE FOR THE IMPLEMENTATION OF ALL WORK
ASSOCIATED WITH THIS PROJECT.
PROPOSED SEQUENCE OF IMPLEMENTATION
1. MECHANICAL:
1.1. PERFORM ALL DEMOLITION WORK ONCE NEW GENERATOR IS IN PLACE AS
EXISTING GENERATOR WILL BE USED TEMPORARILY UNTIL NEW
GENERATOR IS FULLY FUNCTIONAL.
1.2. PREPARE THE SHOP DRAWINGS FOR REQUIRED EQUIPMENT.
1.3. PROVIDE NEW GAS METER ASSEMBLY AND PIPING AS SHOWN.
2. WHEN ALL THE MECHANICAL SERVICES HAVE BEEN INSTALLED, COMPLETE
AND COMMISSIONED:
2.1. COMPLETE ALL REMAINING REMEDIAL WORK, INCLUDING PATCHING WORK,
FIRE STOPPING, CEILING INSTALLATIONS, PAINTING, ETC. UPON
COMPLETION OF MECHANICAL SERVICES.
2.2. COMPLETE AS-BUILTS, OPERATIONS & MAINTENANCE MANUALS AND TURN
OVER TO CONSULTANT.
GAS LINE
DEMOLISHED
PIPE RISER DOWN
EXISTING WORK TO BE RETAINED
EXISTING WORK TO BE REMOVED AND/OR
D
E
G
PIPE RISER UP
PIPE RISER UP
EXISTING WORK TO BE RELOCATED
R
FLEXIBLE CONNECTOR
DRAWING LIST
DRAWING No. DESCRIPTION SCALE
As NotedM-1
BRANCH OFF BOTTOM OF MAIN
BRANCH OFF TOP OF MAIN
CHECK VALVE
VALVE
UNION
SITE PLAN AND DETAILS - MECHANICAL
PROJECT PROPOSED SEQUENCE
OF IMPLEMENTATION
GENERAL NOTES:
1 THIS DRAWING IS ISSUED TO SHOW SCOPE OF WORK ONLY. THE CONTRACTOR MUST
PERFORM A SITE INSPECTION (INCLUDING CEILING SPACES) DURING THE TENDER
PERIOD & ENSURE THAT ALL WORK THAT IS VISIBLE IS INCLUDED IN THE DEMOLITION
CONTRACT. ANY OTHER EXISTING SERVICES THAT PASS THROUGH THE RENOVATION
AREA (UNLESS OBSOLETE) ARE TO BE MAINTAINED AND/OR RELOCATED TO SUIT THE
SCOPE OF WORK.
2ALL PENETRATIONS THROUGH WALLS AND CEILINGS MUST BE FIRE STOPPED WITH FIRE
STOP MATERIAL. REFER TO SPECIFICATIONS.
ROUTING OF SERVICES ARE DIAGRAMMATIC. BE RESPONSIBLE TO CONFIRM EXACT
ROUTING ON SITE PRIOR TO FABRICATION OR ROUGH-IN AND INCLUDE FOR ANY
OFFSETS, TRANSITIONS, ETC. AS REQUIRED FOR A COMPLETE INSTALLATION.
3
SUMMARY OF GAS ITEMS WITHIN BUILDING:
BOILERS - 2 @ 900 CFH
ROOF TOP UNIT - 2 @ 180 CFH
DOMESTIC HOT WATER HEATER - 1 @ 199 CFH
DOMESTIC 4 BURNER RANGE - 2 @ 60 CFH
BBQ - 1 @ 100 CFH
TOTAL EXISTING CONNECTED LOAD = 2740 CFH
NEW GENERATOR = 1090 CFH
NEW CONNECTED LOAD = 3830 CFH
2M-1
SCALE: N.T.S.
TO NEW GAS GENERATOR
ON GRADE (1090 CFH)
ROUTE PIPING ALONG
BUILDING EXTERIOR WALL
2#G
32ø
VALVE SHALL BE
COLORED "RED"
P.R.V.
G
~
EXISTING INCOMING GAS SERVICE
FOR A NEW CONNECTED LOAD OF
3830 CFH AT 2 PSI
EXISTING GAS PRV, METER
AND PIPING ASSEMBLY TO BE
REMOVED
CONNECT INTO
EXISTING SERVICE
~
GRADE
PROVIDE SIGNAGE STATING
"EMERGENCY GENERATOR
DO NOT SHUT OFF"
G
CONNECT TO THE
EXISTING GAS LINE
PROVIDE SIGNAGE STATING
"EMERGENCY GENERATOR
DO NOT SHUT OFF"
EMERGENCY
GENERATOR
NEW GAS METER ASSEMBLY
SECURED VALVE TYPICAL
ALONG PATH TO GENERATOR
EXISTING GAS LINE TO EXISTING
GAS FIRED EQUIPMENT WITH A
APPROXIMATE CONNECTED LOAD
OF 2740 CFH
32ø32ø
38ø
38ø
PRV TO REDUCE 2740 CFH
FROM 2 PSI TO 7" W.C.
PRV TO REDUCE 1090 CFH
FROM 2 PSI TO 11" W.C.
32ø
2#G
2#G
M-1
FIRE STATION
No.345
1 2016/08/18 Issued For 75% Client Review
2 2016/09/21 Issued For Permit & Tender
3 2016/11/28 Issued For Tender "Rev. 1"
1
M-1
SCALE: N.T.S.
GENERAL NOTES AND SPECIFICATIONS
A. GENERAL
1. CHECK DIMENSIONS ON STRUCTURAL DRAWINGS AGAINST ELECT DRAWINGS AND EXISTING SITECONDITIONS. REPORT ANY INCONSISTENCIES TO CONSULTANT BEFORE PROCEEDING WITH THE WORK.
2. REFER TO ELECTRICAL AND MECHANICAL DRAWINGS FOR LOCATION AND SIZE OF CONDUITS AND GASPIPING BURIED UNDERGROUND.
3. DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE. ELEVATIONS ARE IN METRES UNLESS NOTEDOTHERWISE.
4. PERFORM DESIGN, FABRICATION AND PLACEMENT AND/OR ERECTION IN ACCORDANCE WITHREQUIREMENTS OF REFERENCE STANDARDS, REGULATORY AUTHORITIES AND CONTRACT DOCUMENTS.BE AWARE THAT THE MORE SEVERE REQUIREMENTS OF CONTRACT DOCUMENTS TAKE PRECEDENCEOVER REQUIREMENTS OF REFERENCE STANDARDS AND REGULATORY AUTHORITIES.
5. DO NOT SCALE DRAWINGS.
B. DESIGN
1. STRUCTURAL DESIGN IS IN ACCORDANCE WITH PART 4 OBC 2012.2. DESIGN DATA (OBC 2012):
SEISMIC: Ie=1.5Sa(0.2)=0.22, Sa(0.5)=0.13, Sa(1.0)=0.067, Sa(2.0)=0.021PGA=0.12SITE CLASS = DFa=1.3, Fv=1.4
LIVE LOADS DUE TO SNOW AND RAIN: - GROUND SNOW LOAD: 0.90 kPa- 24 HOURS RAIN LOAD: 0.95 kPa
C. CONSTRUCTION PHASING
1. COORDINATE WITH ELECTRICAL, MECHANICAL AND GENERAL TRADES WORK TO DETERMINE REQUIREDSEQUENCE OF CONSTRUCTION FOR WORK SHOWN ON STRUCTURAL DRAWINGS.
D. REFERENCE STANDARDS & PUBLICATIONS
1. CAST-IN-PLACE CONCRETE, CONCRETE FORMWORK AND CONCRETE REINFORCEMENT:1) CSA STANDARD A23.1, CONCRETE MATERIALS AND METHODS OF CONCRETE CONSTRUCTION.2) CSA STANDARD A23.2, METHODS OF TEST AND STANDARD PRACTICES FOR CONCRETE.3) CSA STANDARD A23.3, DESIGN OF CONCRETE STRUCTURES FOR BUILDINGS.4) ADD CSA-S269.3 (R1998) CONCRETE FORMWORK.5) ACI 117 STANDARD SPECIFICATIONS FOR TOLERANCES FOR CONCRETE CONSTRUCTION AND MATERIALS.6) ACI 315, DETAILS AND DETAILING OF CONCRETE REINFORCEMENT.7) ACI 315R, MANUAL OF ENGINEERING AND PLACING DRAWINGS FOR REINFORCED CONCRETE STRUCTURES.8) RSIC-2004 REINFORCING STEEL MANUAL OF STANDARD PRACTICE.
2. STRUCTURAL STEEL:1) CAN/CSA STANDARD G-40.20/G-40.21, GENERAL REQUIREMENTS FOR ROLLED OR WELDED STRUCTURAL
QUALITY STEEL.2) CSA STANDARD S16.1-09, LIMIT STATES DESIGN OF STEEL STRUCTURES.3) CSA STANDARD W59-03, WELDED STEEL CONSTRUCTION (METAL ARC WELDING).4) CSA STANDARD W178.1 CERTIFICATION OF WELDING INSPECTION ORGANIZATIONS.5) CSA STANDARD W178.2 CERTIFICATION OF WELDING INSPECTORS.
E. SITE WORK
1. DEMOLITION:1) REMOVE CONCRETE PAVEMENT AS REQUIRED TO CONSTRUCT THE CONCRETE PAD AND BURY THE
CONDUITS. REINSTATE CONCRETE PAVEMENT AROUND NEW CONCRETE PAD AND PROVIDE 1% SLOPE TOLEAD THE WATER AWAY FROM CONCRETE PAD.
F. CONCRETE FORMWORK
1. FORMWORK CONSTRUCTION:1) FABRICATE AND ERECT FORMWORK IN ACCORDANCE WITH REQUIREMENTS OF REFERENCE STANDARDS.2) USE EARTH FORMS FOR FOOTINGS ONLY WITH GEOTECHNICAL ENGINEER'S WRITTEN APPROVAL.3) CLEAN FORMWORK IN ACCORDANCE WITH PROVISIONS OF CSA A23.1 PRIOR TO START OF CONCRETE
PLACEMENT.2. TOLERANCES:
1) CONSTRUCT CONCRETE FORMWORK IN ACCORDANCE WITH REVIEWED SHOP DRAWINGS, REQUIREMENTSOF CONTRACT DOCUMENTS AND REFERENCE STANDARDS TO PRODUCE FINISHED CONCRETECONFORMING TO SHAPE, DIMENSIONS, LOCATIONS AND LEVELS WITHIN TOLERANCES SPECIFIED IN CSAA23.1 AND ACI 117.
2) CONFORM TO CSA A23.1 FOR TOLERANCE.
G. CONCRETE REINFORCEMENT
1. REINFORCING STEEL: DEFORMED BARS TO CSA G30.18, GRADE 400R/W.2. FABRICATE REINFORCING STEEL ONLY IN A PERMANENT FABRICATING SHOP UNLESS OTHERWISE
APPROVED BY CONSULTANT.3. FABRICATE REINFORCING STEEL IN ACCORDANCE WITH REVIEWED BAR LISTS AND SHOP DRAWINGS.4. CLEARLY IDENTIFY REINFORCING BARS TO ALLOW CORRELATION WITH BAR LISTS AND PLACEMENT IN
ACCORDANCE WITH SHOP DRAWINGS.5. PROVIDE SPLICES ONLY WHERE SPECIFICALLY INDICATED ON DRAWINGS, UNLESS OTHERWISE APPROVED
IN WRITING BY THE CONSULTANT.6. BEFORE COMMENCING PLACEMENT OF REINFORCEMENT, CONFIRM THAT CONCRETE FORMWORK HAS
BEEN COMPLETED AND IS ADEQUATELY BRACED.7. PLACE REINFORCEMENT IN ACCORDANCE WITH REQUIREMENTS OF CSA STANDARDS A23.3 & SHOP
DRAWINGS.8. REMOVE CONTAMINANTS, INCLUDING CONCRETE RESIDUE FROM PREVIOUS POURS WHICH LESSEN BOND
BETWEEN CONCRETE AND REINFORCEMENT.9. REPLACE INCORRECTLY FABRICATED REINFORCEMENT, RELOCATE MISPLACED REINFORCEMENT AND
INSTALL OMITTED REINFORCEMENT BEFORE CONCRETE IS PLACED, AS DIRECTED BY CONSULTANT ORCONSULTANT'S REPRESENTATIVE.
H. MATERIALS
1. STRUCTURAL STEEL: TO CAN/CSA-G40.20/G40.21-041) W AND WWF SECTIONS, FABRICATED SECTIONS: GRADE 350W (50000 PSI)2) PLATES, ANGLES, CHANNELS: GRADE 300W (43500 PSI)3) HOLLOW STRUCTURAL SECTIONS TO GRADE 350W CLASS C, OR ASTM A500 GRADE C.
3. REINFORCING BAR AREAS ARE 100, 200, 300, 500, 700, 1000, 1500 AND 2500mm² FOR BAR DESIGNATIONS 10,15, 20, 25, 30, 35, 45 AND 55 RESPECTIVELY.
4. CONCRETE - REFER TO TABLE OF CONCRETE PROPERTIES.
I. SHOP DRAWINGS AND SUBMITTALS
1. CONCRETE REINFORCEMENT AND CONCRETE PLACEMENT:1) PREPARE SHOP DRAWINGS INCLUDING BAR PLACING DRAWINGS AND BAR LISTS IN ACCORDANCE WITH
THE REINFORCING STEEL INSTITUTE OF CANADA, REINFORCING STEEL MANUAL OF STANDARD PRACTICE,ACI 315, ACI 315R, AND THE TYPICAL DETAILS INCLUDED WITH THE CONTRACT DOCUMENTS.
2) SUBMIT SHOP DRAWINGS & BAR LISTS SUFFICIENTLY DETAILED & DIMENSIONED TO PERMIT CORRECTPLACEMENT OF REINFORCEMENT AND ACCESSORIES WITHOUT REFERENCE TO ARCHITECTURAL ANDSTRUCTURAL DRAWINGS.
3) SHOW CONCRETE COVER TO REINFORCEMENT AND LOCATION OF CONSTRUCTION JOINTS.2. STRUCTURAL STEEL:
1) SUBMIT SHOP DRAWINGS TO CONSULTANT FOR REVIEW BEFORE COMMENCING FABRICATION.2) PROFESSIONAL ENGINEER RESPONSIBLE FOR CONNECTION DESIGN MUST EITHER SEAL AND SIGN EACH
SHOP DRAWING SUBMITTED, OR SUBMIT A SEAL AND SIGNED LETTER AT COMMENCEMENT OF SHOPDRAWING PREPARATION CONFIRMING ASSUMPTION OF RESPONSIBILITY FOR COMPLIANCE OFCONNECTIONS WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.
3) SHOW SPLICE LOCATIONS AND DETAILS.3. REVIEW ALL SHOP DRAWINGS PRIOR TO SUBMISSION TO CONSULTANT. BY THIS REVIEW, CONTRACTOR
REPRESENTS TO HAVE DETERMINED AND VERIFIED ALL FIELD MEASUREMENTS, SITE CONDITIONS,MATERIALS, PRODUCT OR ACCESSORY, AND TO HAVE CHECKED AND COORDINATED EACH SHOP DRAWINGWITH THE REQUIREMENTS OF WORK AND OF CONTRACT DOCUMENTS.
4. CONFIRM CONTRACTOR'S REVIEW OF EACH SHOP DRAWING BY STAMP, DATE AND SIGNATURE OF ARESPONSIBLE PERSON. NOTIFY CONSULTANT IN WRITING AT TIME OF SUBMISSION OF ANY DEVIATIONS INSHOP DRAWINGS FROM REQUIREMENTS OF CONTRACT DOCUMENTS.
5. BE AWARE THAT CONSULTANT'S REVIEW OF SHOP DRAWINGS IS FOR CONFORMITY TO DESIGN CONCEPTAND FOR GENERAL ARRANGEMENT, AND THAT CONTRACTOR RETAINS RESPONSIBILITY FOR ERRORS ANDOMISSIONS IN SHOP DRAWINGS AND RESPONSIBILITY FOR MEETING ALL REQUIREMENTS OF CONTRACTDOCUMENTS.
6. MAKE CHANGES IN SHOP DRAWINGS WHICH CONSULTANT MAY REQUIRE CONSISTENT WITH CONTRACTDOCUMENTS AND RESUBMIT UNLESS OTHERWISE DIRECTED BY CONSULTANT. WHEN RESUBMITTINGNOTIFY CONSULTANT IN WRITING OF REVIEWS OTHER THAN THOSE REQUESTED BY CONSULTANT.
7. DO NOT COMMENCE FABRICATION OF STRUCTURAL STEEL AND CONCRETE REINFORCEMENT UNTIL SHOPDRAWINGS HAVE BEEN REVIEWED AND CONSULTANTS' COMMENTS ARE INCORPORATED ON SHOPDRAWINGS ISSUED TO FABRICATING SHOP.
8. ALLOW 7 DAYS FOR RETURN OF SHOP DRAWINGS FROM CONSULTANTS.
J. INSPECTION AND TESTING
1. PERFORM FIELD INSPECTIONS AND TESTING DESCRIBED BELOW BY AN INSPECTION AND TESTINGCOMPANY, APPOINTED AND PAID FOR BY THE GENERAL CONTRACTOR.
2. STRUCTURAL STEEL SHOP INSPECTION:1) MATERIALS AND PAINT CONFORM TO CONTRACT DRAWINGS. MILL TEST REPORTS, PROPERLY
CORRELATED TO THE MATERIALS, WILL BE ACCEPTED IN LIEU OF PHYSICAL TESTS OF STRUCTURALMATERIALS;
2) FABRICATION AND WELDING CONFORM TO CONTRACT DOCUMENTS AND DIMENSIONED SHOP DRAWINGS;3) SHOP SURFACE PREPARATION AND PAINTING CONFORM TO CONTRACT DRAWINGS;4) SURFACES INACCESSIBLE FOR SURFACE PREPARATION AND PAINTING AFTER ASSEMBLY ARE TREATED
BEFORE ASSEMBLY;5) INSPECTION AND TESTING COMPANY SHALL PERFORM NONDESTRUCTIVE TESTING OF WELDED
CONNECTIONS.3. FIELD INSPECTION AND TESTING OF CONCRETE:
1) STANDARD CONCRETE SLUMP TEST TO MEET CSA A23.2 REQUIREMENTS.2) CONCRETE CYLINDER COMPRESSION TESTS, 1 AT 7 DAYS AND 2 AT 28 DAYS TO MEET CSA A23.2
REQUIREMENTS.4. FIELD INSPECTION AND TESTING OF STRUCTURAL STEEL:
1) STRUCTURAL STEEL ERECTION AND FIT-UP.2) STRUCTURAL STEEL WELDED JOINTS, INCLUDING SLAG REMOVAL.3) STRUCTURAL STEEL BOLTED CONNECTIONS.4) GENERAL INSPECTION OF FIELD CUTTING AND ALTERATIONS OF STRUCTURAL STEEL.5) GENERAL INSPECTION OF SHOP COATING TOUCH-UP OF STRUCTURAL STEEL.6) INSPECTION OF SURFACE PREPARATION AND COATING THICKNESS FOR ZINC PRIMER AND ZINC-RICH
PAINT.5. REINFORCEMENT INSPECTION:
1) PROVIDE MINIMUM 48 HOURS NOTIFICATION TO CONSULTANT TO INSPECT THE INSTALLATION OFREINFORCEMENT PRIOR TO CONCRETE POUR.
K. GEOTECHNICAL DESIGN ASSUMPTIONS
1. STRUCTURAL DESIGN IS BASED ON A FROST DEPTH OF 1.2m (MIN) AND MODULUS OF SUBGRADE REACTIONOF 25 MPa/m.
THE CONTRACTOR SHALL RETAIN A GEOTECHNICAL ENGINEER TO PROVIDE INSTRUCTION FOR THESUBGRADE SOIL PREPARATION OF THE CONCRETE PAD TO SUIT THE DESIGN ASSUMPTIONS. THEGEOTECHNICAL ENGINEER SHALL REVIEW THE SUBGRADE PREPARATION PRIOR TO POURING THECONCRETE PAD. THE COST OF GEOTECHNICAL INVESTIGATION SHALL BE CARRIED BY GENERALCONTRACTOR.
AIRCONTENT
(%)
MAXW / C
RATIO
SLUMP(mm)
MINCOMPRESSIVESTRENGTH f'c
AT 28 DAYS(MPa)
LOCATION / MEMBER
TABLE OF CONCRETE PROPERTIES
EXPOSURECLASS
OT
HE
R 170 ± 20
80 ± 30
UNSHRINKABLE FILL
LEAN MIX CONCRETE 8
MAX 0.40
0.70
80 ± 30
CO
NC
RE
TE
NO
TE
XP
OS
ED
TO
DE
-IC
ING
CH
EM
ICA
LS
OR
FR
EE
ZIN
GA
ND
TH
AW
ING
U/N
SKIM SLABS 15 0.50
40 ± 20
40 ± 20CO
NC
RE
TE
EX
PO
SE
D T
OD
E-I
CIN
G C
HE
MIC
AL
SW
ITH
/WIT
HO
UT
FR
EE
ZIN
GA
ND
TH
AW
ING
NON STRUCTURAL TOPPINGS(EXPOSED TO FREEZINGAND THAWING)
32OT
HE
R
SIDEWALKS, CURBS,PAVING SLABS
30
0.45a
5-8 C-2
0.45a
5-8 C-2
80 ± 30CONCRETE PAD
FO
OT
ING
S 35 0.40 5-8b,d
C-1
NOTES:
a. SPECIAL CONCRETE HANDLING AND PLACING METHODS OR THE USE OF A SUPER PLASTICIZER WILL BE REQUIREDTO PLACE THIS CONCRETE.
b. PROVIDE CONCRETE WITH A MINIMUM CEMENTING MATERIALS CONTENT OF 325 kg/m³.c. MAXIMUM AGGREGATE SIZE IS 20mm.d. PROVIDE CORROSION INHIBITOR TO CONCRETE MIX WITH MINIMUM DOSAGE OF 10 L/m³ OF 30% SOLUTION OF
CALCIUM NITRITE.
CONCRETE FILL 30
FIRE STATION No.345
S0
PART PLAN1 : 50
NOTE:1. PROVIDE 60mm CONCRETE COVER FOR REINFORCEMENT.2. TRENCH EXCAVATION AND BACK FILL SHOULD BE UNDER
THE SUPERVISION OF GEOTECHNICAL ENGINEER.3. REMOVE EXISTING PAVEMENT AND EARTH FILL TO THE
REQUIRED DEPTH. THE SUBGRADE CONDITION SHOULD BEINSPECTED AND APPROVED BY GEOTECHNICAL ENGINEER.
4. COMPACT THE CRUSHER-RUN LIMESTONE OR EQUIVALENTTO 100% MAXIMUM STANDARD PROCTOR DRY DENSITY.
EXISTING BUILDING
1-
HSS 178Øx9.5 FILL WITHCONCRETE (TYPICAL)
NEW CONCRETE PAD
NEW GENERATORREFER TO ELECTRICALDRAWINGS
300 MIN
30
0 M
IN
1389 1500
15
00
88
9
70
00
MIN
CONCRETEPAD
30
0
EXISTINGBUILDING
PAINT STEEL PIPE ANDBASE PLATE WITH PRIMERAND TWO COATS ENAMELPAINT IN YELLOW
50mm STYROFOAM RIGIDINSULATION OR EQUIVALENT
200mm THICK 20mm CRUSHER-RUN LIMESTONE
600 MIN
EXIST CONCRETEPAVEMENT
NEW CONCRETEPAVEMENT
1%
15
0
11 : 20 -
SECTION
12
00
NEWGENERATOR
ROUND TOP OF CONCRETE
2-
15@200T&BEW
10@200 U-BARAROUND PERIMETER600
30
0
300
50
(T
YP
) 50 (TYP)
21 : 10 -
SECTION
BASE PLATE 300x300x16COMPLETED WITH 4-16ØHILTI 200 HIT-Z ANCHORWITH 115mm EMBEDMENT.PROVIDE NON-SHRINKGROUT UNDER BASEPLATE IF REQUIRED.
8
300 MIN
FIRE STATION No.345
S1
400 ESNA PARK DRIVE, UNIT 15, MARKHAM, ONTARIO L3R 3K2 P: 905 475 7755 F: 905 475 7718
WWW.FISHERENVIRONMENTAL.COM
August 10, 2016 Meaghan Aldcroft
Environmental Coordinator
City of Toronto, Corporate Services
Facilities Management
Metro Hall, 55 John Street
Toronto ON,
M5V 3C6
Re: Pre-reno Designated Substance Sampling at 1285 Dufferin Street, Toronto, ON.
Dear Ms. Aldcroft,
As requested, Fisher Environmental Ltd. (Fisher) has performed an assessment of the Toronto Fire
Station 345 building located at 1285 Dufferin Street, Toronto, Ontario (the “Site”). Fisher understands that
request to have the assessment performed is in anticipation of planned construction activities (backup
generator installation) at the Site. The purpose of the current survey was to identify Designated
Substances including sampling of materials suspected to contain asbestos and lead. The assessment
scope did not include the entirety of the subject building. Rather, the assessment was limited to locations
where construction activities are proposed (Electrical Room/ Utility Room and Building Exterior). The
fieldwork was conducted on June 10, 2016.
Asbestos-Containing Materials
A total of three (3) bulk samples of homogenous materials suspected to contain asbestos were collected
and submitted to Fisher Environmental Laboratories for Polarised Light Microscopy (PLM) analysis, as
outlined in NIOSH Method 9002. The results of PLM sample analysis are summarized in Table 1, below.
Fisher Environmental Laboratories (Lab ID #: 2745) is accredited by CALA (Canadian Association for Laboratory Accreditation Inc.) for asbestos analysis
by PLM.
Asbestos has been done in accordance with normal professional standard using the following Fisher Environmental Lab Method: Asbestos by PLM
(Polarized Light Microscope) F-26, Rev.2.2.
Not Detected
FISHER ENVIRONMENTAL LABORATORIES
FULL RANGE ANALYTICAL SERVICES SOIL /WATER / AIR TESTING ENVIRONMENTAL
FLUSH-MOUNTED PUSHBUTTON MOUNTED 4'-0" (1.2 m) ABOVE FINISHED
FLOOR LEVEL. "WP" DENOTES WEATHERPROOF.
RECESSED OR SURFACE MOUNTED PANELBOARD, "PP" DENOTES POWER
PANEL, "LP" DENOTES LIGHTING AND POWER PANEL, "DP" DENOTES
DISTRIBUTION PANELBOARD.
EPO
WP
DISCONNECT SWITCH (FUSED OR NOT FUSED) WHERE SHOWN ON DRAWINGS
OR REQUIRED BY CODE. "WP" INDICATES WEATHERPROOF TYPE.
WP
CG
SIMILAR TO ABOVE, BUT MOUNTED APPROXIMATELY 3'-6" (1050 mm) ABOVE
FINISHED FLOOR LEVEL OR ABOVE COUNTER.
EMERGENCY BATTERY UNIT COMPLETE WITH DUAL HEAD TYPE LIGHT.
REFER TO SPECIFICATIONS FOR DETAILS.
LIGHTING SYMBOLS
E
LINE OR LOW VOLTAGE CABLE IN CONDUIT.
DESCRIPTIONSYMBOL
SINGLE LINE DIAGRAM SYMBOLS
AUTOMATIC TRANSFER SWITCH (ATS) WITHOUT MANUAL BYPASS
FIRE ALARM SYMBOLSDESCRIPTIONSYMBOL
2
EX
AUTOMATIC HEAT DETECTOR 15°F (8.3°C) RATE OF RISE AND FIXED
TEMPERATURE TYPE 135°F (57°C) RATED AT 2500 FT (232m ) COVERAGE.
"EX" WHERE SHOWN, DENOTES EXPLOSION PROOF.
2
FLAME DETECTOR CEILING MOUNTED TYPE.
F
D
END OF LINE RESISTOR FOR FIRE ALARM SYSTEM.
DRY TYPE STEP DOWN TRANSFORMER.
MOLDED CASE CIRCUIT BREAKER.
THE FOLLOWING IS A PROPOSED SEQUENCE IMPLEMENTATION, INTENDED
TO GIVE A DIAGRAMMATIC OVERVIEW OF THE PROPOSED SEQUENCE OF
INSTALLATION FOR THIS PROJECT. BE RESPONSIBLE TO CONFIRM THIS
SEQUENCE, MAKE THE REQUIRED MODIFICATION TO SUIT THE ANOMALIES
OF THIS BUILDING AND COORDINATE THIS WHEN PREPARING THE MASTER
CONSTRUCTION SCHEDULE FOR THE IMPLEMENTATION OF ALL WORK
ASSOCIATED WITH THIS PROJECT.
PROPOSED SEQUENCE OF IMPLEMENTAION
ELECTRICAL1.
1.1
PREPARE SITE TO ACCOMMODATE THE NEW GENERATOR AND
ANCILLARY EQUIPMENT/DEVICES.
INSTALL NEW GENERATOR IN ITS PERMANENT LOCATION AND
PROVIDE FEEDERS AS SHOWN ON THE DRAWINGS.
CONFIRM SITE MEASUREMENTS AND ROUTINGS OF ALL FEEDERS
AND PLACEMENT LOCATIONS OF ALL COMPONENTS PRIOR TO
COMMENCEMENT OF WORK.
1.7
FIRE STOP ALL NEW WALL PENETRATIONS.
WHEN ALL THE ELECTRICAL SERVICES HAVE BEEN INSTALLED,
COMPLETED AND COMMISSIONED:
2.
2.2
COMPLETE AS-BUILTS, O&M MANUALS AND TURN OVER TO
CONSULTANT.
2.3
COMPLETE ALL REMAINING REMEDIAL WORK, INCLUDING PATCHING
WORK, FIRE STOPPING, CEILING INSTALLATIONS, PAINTING, ETC.
UPON COMPLETION OF ELECTRICAL SERVICES.
1.3
1.4
1.5
1.6
PREPARE AND SUBMIT SHOP DRAWINGS FOR NEW GENERATOR
AND TRANSFER SWITCH FOR REVIEW. ORDER EQUIPMENT AND
COORDINATE DELIVERY AND INSTALLATION.
2.1
TEST OPERATION OF NEW GENERATOR AND TRANSFER SWITCH.
REFER TO SPECIFICATION FOR DETAILS.
1.2
WATER SEAL ALL OPENINGS.
PROJECT PROPOSED SEQUENCE OF
IMPLEMENTATION
FUSE DISCONNECT SWITCH.
LINE OR LOW VOLTAGE CABLE IN CONDUIT.
TEMPORARY GENERATOR NOT REQUIRED FOR POWER SHUTDOWN.
CONTRACTOR IS TO NOTIFY THE CITY OF TORONTO PROJECT MANAGER
10 BUSINESS DAYS PRIOR TO WHEN THE POWER SHUTDOWN WILL BE
REQUIRED. THE CONTRACTOR TO HAVE ALL NECESSARY WORK
PREPARED TO ENSURE THE SHUTDOWN IS NO LONGER THAN 4 HOURS.
AutoCAD SHX Text
DATE: 2016/07/20
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
PROJECT :
AutoCAD SHX Text
CLIENT : - CITY OF TORONTO
AutoCAD SHX Text
CONSULTANT
AutoCAD SHX Text
THIS DRAWING ARE NOT TO BE SCALED. REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL, ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFORE PROCEEDING WITH THE WORK. CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES AND REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST ASSUME FULL RESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS OR DAMAGES RESULTING FROM HIS WORK. THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BY AND IS THE PROPERTY OF THE ARCHITECT. THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITY FOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALL NOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROM THE SUPPLIED INFORMATION.
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
TRUE NORTH
AutoCAD SHX Text
CONSTRUCTON NORTH
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
REVIEWED BY:
AutoCAD SHX Text
33 CLAREMONT STREET
AutoCAD SHX Text
TORONTO, ONTARIO, CANADA
AutoCAD SHX Text
- EMERGENCY SERVICES
AutoCAD SHX Text
Metro Hall City of Toronto
AutoCAD SHX Text
2nd floor, 55 John St.,
AutoCAD SHX Text
Toronto, Ontario M5V 3C6
AutoCAD SHX Text
CLIENT
AutoCAD SHX Text
ADDRESS :
AutoCAD SHX Text
MMM PROJECT No.: 1816292-003
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
I.Z.
AutoCAD SHX Text
D.L.
AutoCAD SHX Text
R
AutoCAD SHX Text
R
AutoCAD SHX Text
R
AutoCAD SHX Text
R
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
ER
AutoCAD SHX Text
ER
AutoCAD SHX Text
RR
AutoCAD SHX Text
RR
AutoCAD SHX Text
RR
AutoCAD SHX Text
RR
AutoCAD SHX Text
EOL
(INLET SIDE)
(DISCHARGE SIDE)
3700
11
00
15
00
7m
EXISTING CATCHBASIN
EXISTING FENCE
EXISTING FENCE
PROTECTIVE BOLLARD WITH
CONCRETE. REFER TO STRUCTURAL
DRAWINGS. (TYPICAL), ENSURE
BOLLARD NOT BLOCKING GENSET
DOOR SWING.
EPO
EPO
WP/CG
EPO PROVIDED WITH
GENERATOR ENCLOSURE.
GENERATOR SHORE
PANEL. PROVIDED WITH
GENERATOR ENCLOSURE.
CONDUIT WITHIN BUILDING TO
ELECTRICAL EQUIPMENT, REFER TO
SINGLE LINE FOR DETAILS.
UNDERGROUND CONDUITS
TO TRANSITION TO
SURFACE MOUNT ONTO
BUILDING SURFACE, GOING
UP AND RUNNING TO
ELECTRICAL EQUIPMENT.
10
00
1 SPARE UNDERGROUND DUCT WITH PULL STRING
AND CAPPED AT BOTH END FOR FUTURE USE
NEW NATURAL GAS GENERATOR IN AN OUTDOOR
SKIN-TIGHT ACOUSTICAL ENCLOSURE, REFER TO
SINGLE LINE FOR GENERATOR DETAILS.
OUTLINE OF NEW CONCRETE PAD. REFER
TO STRUCTURE DRAWINGS.
GENERATOR
ANNUNCIATOR
PANEL
GROUND FAULT
ANNUNCIATOR
PANEL
TO GROUND
FAULT
INDICATOR,
REFER TO
SINGLE LINE
FOR DETAILS
13
89
EXISTING NATURAL GAS CONNECTION TO BBQ TO BE
RELOCATED, REFER TO MECHANICAL DRAWING FOR DETAILS.
UNDERGROUND CONDUITS
APPROXIMATE LOCATION OF
CONDUITS ENTRANCE TO BUILDING,
PROVIDE ALL OPENINGS AS
REQUIRED FOR A COMPLETE
INSTALLATION.
11
m
REFER TO DETAIL 2 OF E1 FOR
ISOLATION DETAILS.
E
E
E
E
E
E
E
E
13
14
15
16
17
18
19
12
11
E
M
M
E
E
5
4
1
E
3
20
21
22
7
26
25
8
EXISTING BOILER ROOM - DEMOLITION
EXISTING TORONTO HYDRO SERVICE ENTRANCE DUCT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
EXISTING PANEL
EXISTING DISCONNECT SWITCH FOR EXISTING FLOOR WATCH
EXISTING LIGHTING SWITCH
EXISTING SWITCH BOX
EXISTING DISCONNECT
EXISTING SPLITTER TO BE REPLACED
EXISTING 120/240V, 200A, MAIN SERVICE ENTRANCE DISCONNECT
SWITCH
EXISTING TORONTO HYDRO METER
EXISTING 600V, 225A SPLITTER
EXISTING DISCONNECT SWITCH FOR EXISTING ROOF TOP A/C UNIT
EXISTING DISCONNECT SWITCH FOR EXISTING SUPPLY FAN
(2NDFLOOR AIR UNIT)
18
19
20
21
22
EXISTING DISCONNECT SWITCH FOR EXISTING DOOR 1
EXISTING DISCONNECT SWITCH FOR EXISTING DOOR 2
EXISTING DISCONNECT SWITCH FOR EXISTING DOOR 3
EXISTING DISCONNECT SWITCH FOR EXISTING DOOR 4
EXISTING DISCONNECT SWITCH FOR EXISTING DOOR 5
EXISTING DISCONNECT SWITCH FOR EXISTING EVAC SYSTEM
EXISTING DISCONNECT SWITCH/STARTER FOR EXISTING
EXHAUST FAN EF-3
AREA FOR EXISTING MECHANICAL EQUIPMENT
EXISTING EF-1
EXISTING EF-2
23 EXISTING MECHANICAL PIPE
24 EXISTING SPLITTER
2
9
10
6
23
24
EEEEEEE
E
D
D
ER
E
E
E
E
ER
E
EXISTING DISCONNECT SWITCH TO BE REPLACED, REFER TO SINGLE
LINE FOR DETAILS.
25
26 EXISTING TORONTO HYDRO METER
D
ER
E
E
D
ER
E
E
EXISTING BOILER ROOM - DEMOLITION
E
E
E
E
E
E
E
E
13
14
15
16
17
18
19
12
11
E
M
E
E
5
4
1
E
3
20
21
22
26
25
2
9
10
6
23
24
EXISTING TORONTO HYDRO SERVICE ENTRANCE DUCT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
EXISTING PANEL,
EXISTING DISCONNECT SWITCH FOR EXISTING FLOOR WATCH
EXISTING LIGHTING SWITCH
EXISTING SWITCH BOX
EXISTING DISCONNECT
NEW 120/208V, 3 PHASE, 4 WIRE SPLITTER,
REFER TO SINGLE LINE FOR DETAILS
NEW TRANSFORMER TX-1 WALL MOUNTED UPHIGH TO FREE UP THE SPACE
UNDER FOR THE NEW EQUIPMENT. REFER TO SINGLE LINE FOR DETAIL
NEW FUSED DISCONNECT FEEDING CIRCUIT TO TRANSFORMER "TX-1",
REFER TO SINGLE LINE FOR DETAILS.
EXISTING SPLITTER
EXISTING DISCONNECT SWITCH FOR EXISTING ROOF TOP A/C UNIT
EXISTING DISCONNECT SWITCH FOR EXISTING SUPPLY FAN
(2NDFLOOR AIR UNIT)
18
19
20
21
22
EXISTING DISCONNECT SWITCH FOR EXISTING DOOR 1
EXISTING DISCONNECT SWITCH FOR EXISTING DOOR 2
EXISTING DISCONNECT SWITCH FOR EXISTING DOOR 3
EXISTING DISCONNECT SWITCH FOR EXISTING DOOR 4
EXISTING DISCONNECT SWITCH FOR EXISTING DOOR 5
EXISTING DISCONNECT SWITCH FOR EXISTING EVAC SYSTEM
EXISTING DISCONNECT SWITCH/STARTER FOR EXISTING
EXHAUST FAN EF-3
AREA FOR EXISTING MECHANICAL EQUIPMENT
EXISTING EF-1
EXISTING EF-2
23 EXISTING MECHANICAL PIPE
24 EXISTING SPLITTER
E
ER
ER
CONDUITS
TO ATS-1
CONDUITS TO
600V METER
AND SPLITTER
CONDUIT TO
GENERATOR
7
8
NEW 600V MAIN SERVICE ENTRANCE DISCONNECT SWITCH, REFER TO
SINGLE LINE FOR DETAIL
25
26NEW TORONTO HYDRO METER
CONDUIT TO
TRANSFORMER "TX-1"
CONDUIT TO NEW
120/208V SPLITTER
27
CONDUIT TO GENERATOR
SHORE PANEL
27NEW DISCONNECT FOR FEEDING
CIRCUIT TO GENERATOR SHORE PANEL
28
NEW REMOTE EMERGENCY BATTERY UNIT c/w HEADS. PROVIDE NEW
15A-1P LOCK TYPE CIRCUIT BREAKER FROM THE NEAREST AVAILABLE
PANEL AND FEED WITH 2#12+G IN 16mmC.
28
CONDUIT
WITHIN
BUILDING TO
ELECTRICAL
EQUIPMENT
CONDUITS TO
GENERATOR
NEW ATS-1, REFER TO SINGLE LINE FOR DETAILS.29
NEW UNFUSED DISCONNECT SWITCH FOR ATS-1,
WALL MOUNTED BELOW DISCONNECT FOR "EF-2",
REFER TO SINGLE LINE FOR DETAILS
30
29
30
E
CONDUIT TO
GENERATOR
E
E-2
EXISTING ELECTRICAL ROOM AND
NEW WORK GENERATOR LAYOUT -
POWER AND SIGNALS -
ELECTRICAL
1st FLOOR PART PLAN
1E-2
SCALE: N.T.S.
FIRE STATION No.331
MMM Group Limited100 Commerce Valley Drive West
Thornhill, ON L3T 0A1
t. 905-882-1100
f. 905-882-0055
www.mmm.ca
1 2016/08/18 Issued For 75% Client Review
2 2016/09/21 Issued For Permit & Tender
3 2016/11/28 Issued For Tender - Rev.1
1ALL EXISTING ELECTRICAL DEVICES ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
DEMOLITION NOTES:
2
CAP OFF AND FIRE STOP ALL FLOOR/WALL CONDUIT STUB-UPS/DOWNS UPON REMOVAL OF
FEEDERS.
EXISTING BOILER / ELECTRICAL -DEMOLITION
2E-2
SCALE: N.T.S.
EXISTING BOILER / ELECTRICAL - NEW WORK
3E-2
SCALE: N.T.S.
RED MARKING TAPE,
THE FULL LENGTH &
WIDTH OF DUCT
BANK, APPROXIMATE
HALF WAY BETWEEN
THE INSTALLATION
AND GRADE LEVEL
DIRECT BURIED DETAIL
FINISHED GRADE
4
E-2
SCALE: N.T.S.
TRENCHING AND
BACKFILL AS REQUIRED.
TRENCH
MIN.
915
(36")
1. EXACT CONSTRUCTION DETAILS TO CONFORM TO OESC CODE REQUIREMENTS AND
DETAILS. AND PROVIDE PULL STRING AND CAP AT BOTH ENDS IF IT IS SPARE.
NOTES:
RIGID PVC CONDUITS
FOR POWER AND
CONTROL WIRING,
REFER TO SINGLE
LINE FOR DETAILS.
190
190 190
NEW WORK NOTES:
BE RESPONSIBLE FOR EXACT PLACEMENT, INSTALLATION AND COORDINATION OF CONNECTING SERVICES OF PROPOSED GENERATOR AFTER REVIEW OF SHOP DRAWINGS. BE RESPONSIBLE FOR THE SET-UP, INSTALLATION AND CONNECTION OF LOAD BANK FOR ON-SITE TESTING. CABLING AND LOAD BANK WILL BE SUPPLIED BY GENERATOR MANUFACTURER. UPON COMPLETION OF SITE TESTING, DISCONNECT LOAD BANK AND CABLING AND PREPARE FOR PICK UP BY GENERATOR MANUFACTURER.1.
ROUTING OF ALL SERVICES ARE DIAGRAMMATIC. BE RESPONSIBLE TO CONFIRM EXACT ROUTING AND TERMINATIONS ON SITE PRIOR TO FABRICATION OR ROUGH-IN AND INCLUDE FOR REQUIRED OFFSETS, TRANSITIONS ETC. AS REQUIRED FOR A COMPLETE INSTALLATION. CONDUCTOR TO BE OVERSIZED TO SUIT VOLTAGE DROP AS PER OESC.
2.
ALL PENETRATIONS THROUGH WALLS AND CEILINGS SHALL BE FIRE STOPPED WITH 3m FIRE STOP MATERIAL. REFER TO SPECIFICATIONS FOR DETAILS.3.
PROVISION OF ALL PENETRATIONS AND OPENINGS AS REQUIRED.4.
COORDINATE TRENCHING / EXCAVATION OF SURFACES TO SUIT NEW GENERATOR SERVICES. REPLACE WITH NEW SURFACES AND MATCH BASE BUILDING MATERIALS. CONFIRM AND MARK ON SITE ALL EXISTING SITE SERVICE LOCATIONS WITHIN AREA OF INSTALLATION. REFER TO SPECIFICATION.5.
AutoCAD SHX Text
DATE: 2016/07/20
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
PROJECT :
AutoCAD SHX Text
CLIENT : - CITY OF TORONTO
AutoCAD SHX Text
CONSULTANT
AutoCAD SHX Text
THIS DRAWING ARE NOT TO BE SCALED. REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL, ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFORE PROCEEDING WITH THE WORK. CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES AND REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST ASSUME FULL RESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS OR DAMAGES RESULTING FROM HIS WORK. THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BY AND IS THE PROPERTY OF THE ARCHITECT. THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITY FOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALL NOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROM THE SUPPLIED INFORMATION.
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
TRUE NORTH
AutoCAD SHX Text
CONSTRUCTON NORTH
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
REVIEWED BY:
AutoCAD SHX Text
33 CLAREMONT STREET
AutoCAD SHX Text
TORONTO, ONTARIO, CANADA
AutoCAD SHX Text
- EMERGENCY SERVICES
AutoCAD SHX Text
Metro Hall City of Toronto
AutoCAD SHX Text
2nd floor, 55 John St.,
AutoCAD SHX Text
Toronto, Ontario M5V 3C6
AutoCAD SHX Text
CLIENT
AutoCAD SHX Text
ADDRESS :
AutoCAD SHX Text
MMM PROJECT No.: 1816292-003
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
I.Z.
AutoCAD SHX Text
D.L.
EXISTING SPLITTER 600V, 225A, 3 POLE
E
EXISTING SPLITTER TO BE REPLACED
E E
EXISTING
DISCONNECT
600V, 30A
EE
E
EXISTING
DISCONNECT
600V, 30A
E E
EXISTING
DISCONNECT
600V, 30A
E E E
E
EXISTING
DISCONNECT
/ STARTER
(10A MAX)
E
E
EXISTING
DISCONNECT
240V, 60A
E
EXISTING
DISCONNECT
240V, 30A
EE
EXISTING
PANEL
E
E
E E EE
EXISTING
DISCONNECT
600V, 30A
EXISTING
DISCONNECT
600V, 30A,
F@15A MAX
EXISTING
DISCONNECT
600V, 60A
EXISTING
DISCONNECT
600V, 30A
EXISTING
DISCONNECT
600V, 30A
EXISTING
ROOF TOP
A/C UNIT
EXISTING
SUPPLY FAN
(2ND FLOOR
AIR UNIT)
EXISTING
DOOR 1
EXISTING
DOOR 2
EXISTING
DOOR 3
EXISTING
DOOR 4
EXISTING
DOOR 5
EXISTING
EVAC
SYSTEM
EXISTING
EXHAUST
FAN EF-3
EXISTING
EF-1
EXISTING
EF-2
EXISTING
FLOOR WATCH
SPLIT UNIT
E
60A-3P
F@50A
45kVA,
600V-208/120V
DRY-TYPE
TRANSFORMER
"TX-1"
4#2/0+G, 53mmC
3#6+G, 27mmC
FUSED DISCONNECT
M
ER
D
D
SERVICE ENTRANCE GROUNDING GRID
PROVIDED BY ELECTRICAL CONTRACTOR.
TYPICAL GROUND RODS FOR MAIN SERVICE ENTRANCE.
100kW
100KW/125kVA, 600/347V, 3PH, 4W, NEW OUTDOOR NATURAL GAS
GENERATOR CONTAINERIZED IN SKIN-TIGHT ACOUSTICAL
ENCLOSURES . REFER TO SPECIFICATION FOR DETAILS.
1# 3/0 GROUND, REMOVE THE CONNECTION BETWEEN ALTERNATOR "WYE POINT
(NEUTRAL)" AND GENERATOR ENCLOSURE/FRAME/GROUND IN ACCORDANCE WITH
CODE REQUIREMENTS AND MANUFACTURER RECOMMENDATIONS.
NOT BONDING GENERATOR NEUTRAL TO THE FRAME AND GROUND
OF THE GENERATOR IN ACCORDANCE WITH CODE REQUIREMENTS.
EPO
WP
CG
150A-3P
NEW 100A, 120/208V, 3Ø, 4W SHORE PANEL INCLUDED IN
GENERATOR ENCLOSURE.
4#4+G, 53mmC
D
NEW AUTOMATIC TRANSFER SWITCH
'ATS-1', 600V, 200A, 3PH, 3W
(UNSWITCHED NEUTRAL)
AUTOMATIC "OPEN TRANSITION"
TRANSFER SWITCH. I.C.=30kA RATED
3#2/0+G, 103mmC.
CONTROL WIRING FOR ATS START/STOP IN 53mmC" CONDUIT,
COORDINATE WITH MANUFACTURER RECOMMENDATION FOR
EXACT REQUIREMENTS.
EPO
FUSED DISCONNECT
60A-3P
F@60A
GENERATOR BREAKER. COORDINATE WITH COORDINATION
STUDY AND MANUFACTURE RECOMMENDATION. UPDATE
DOWNSTREAM DISTRIBUTION SYSTEM AS REQUIRED TO SUIT
IN ACCORDANCE WITH CODE REQUIREMENTS.
GENERAL NOTES:
3#1/0+G, 53mmC.
3#1/0+G, 53mmC.
ER
E
EXISTING LOAD
SEE NOTE 4
M
D
D
D
D
ER
200A-3P
U/F
BE RESPONSIBLE TO CONFIRM AND VALIDATE
ELECTRICAL CHARACTERISTICS FOR ALL EXISTING
DOWNSTREAM LOADS AND REPORT BACK TO
CONSULTANT ANY CONCERNS FOR 230/240V LOADS
RECONNECTIONS TO NEW 208V DISTRIBUTION.
EXISTING THES
METER
EXISTING MAIN
SERVICE ENTRANCE
DISCONNECT SWITCH
120/240V, 200A
EXISTING INCOMING
120/240V, 200A, 1PH, 3W
ELECTRICAL SERVICE TO BE
REMOVED, SEE NOTE 3
EXISTING TORONTO HYDRO METER CABINET TO BE
UPDATED AS PER TORONTO HYDRO REQUIREMENT.
COORDINATE/COMFIRM WITH TORONTO HYDRO FOR
ASSOCIATED WORK OF UPDATING THE METER AND
INSTALLING ONTO STANDARD METERBASE TO SUIT
NEW 100A SERVICE ENTRANCE AND PROVIDE ALL
ASSOCIATED ACCESSORIES AS REQUIRED TO
FACILITATE THE NEW INSTALLATION COMPLETELY.
EXISTING INCOMING
ELECTRICAL SERVICE
600V, 3 PHASE - DELTA
CONTRACTOR TO
VERIFY.
EXISTING MAIN SERVICE ENTRANCE DISCONNECT
SWITCH TO BE REPLACED WITH NEW 600V, 3Ø, 200A
MAIN SERVICE ENTRANCE RATED DISCONNECT
SWITCH WITH NEW 100A FUSE INSTALLED
SEE NOTE 1
GENERATOR ANNUNCIATOR PANEL,
SUPPLIED BY GENERATOR
MANUFACTURER.
EXISTING OFFICE
GROUND FAULT REMOTE ANNUNCIATOR
PANEL, SUPPLIED BY GROUND FAULT
INDICATOR MANUFACTURE, COORDINATE
WITH MANUFACTURER FOR EXACT
REQUIREMENT OF CABLING & CONDUIT,
MOUNTING/CONNECTION DETAILS, AND
ETC. PROVIDE BOTH VISUAL & SOUND
ALARMS FOR GROUND FAULT AND ALL
ASSOCIATED ACCESSORIES AS
REQUIRED TO FACILITATE THE NEW
INSTALLATION COMPLETELY.CONTROL WIRING FOR GROUND FAULT
REMOTE ANNUNCIATOR PANEL IN 53mmC
CONDUIT, COORDINATE WITH GROUND
FAULT INDICATOR MANUFACTURER
RECOMMENDATION FOR EXACT
REQUIREMENTS.
GROUND FAULT INDICATOR, REFER TO
SPECIFICATION FOR DETAILS. COORDINATE
WITH MANUFACTURER RECOMMENDATION
FOR EXACT REQUIREMENT OF CABLING &
CONDUIT, MOUNTING/CONNECTION DETAILS,
AND ETC. PROVIDE ALL ASSOCIATED
ACCESSORIES AS REQUIRED TO FACILITATE
THE NEW INSTALLATION COMPLETELY.
EXISTING LOAD
D
D
D D
D D
EXISTING CONTROL
PANEL FOR FUEL PUMP
GENERATOR BACK-UP
SYSTEM TO BE REMOVED
EXISTING OUTLET
CONNECTION TO BE
REMOVED
EXISTING SWITCH
(HYDRO/GENERATOR) TO
BE REMOVED
1
2ENSURE ELECTRICAL EQUIPMENT ARE BONDED TO GROUND PROPERLY AS PER OESC CODE.
3
COORDINATE/CONFIRM WITH TORONTO HYDRO FOR THE ASSOCIATED WORK OF REMOVING
THE EXISTING 120/240V HYDRO ELECTRICAL INCOMING SERVICES AND ITS ASSOCIATED
ACCESSORIES AND MAKE IT SAFE AS PER OESC.
4REPLACE EXISTING SPLITTER WITH NEW 120/208V, 225A, 3Ø, 4W SPLITTER. RECONNECT ALL
EXISTING LOAD FEEDERS AND ENSURE ALL LOADS ARE CONNECTED AND EQUALLY
BALANCED.
5
6
EXISTING DISTRIBUTION SYSTEM SHOWN IS DIAGRAMMATIC TO SHOW THE DESIGN INTENT.
BE RESPONSIBLE TO CONFIRM/VERIFY IT PRIOR TO FABRICATION OR ROUGH-IN AND ENSURE
ALL EXISTING LOAD IS PICKED UP AND CONNECTED BALANCED BY THE NEW ELECTRICAL
DISTRIBUTION SYSTEM AND PROVIDE ALL ASSOCIATED ACCESSORIES AS REQUIRED TO
FACILITATE THE NEW INSTALLATION COMPLETELY.
D
E
EXISTING PANEL
ON SECOND
FLOOR
E
E
E
COORDINATE WITH TORONTO HYDRO FOR THE ASSOCIATED WORK OF UPGRADING THE EXISTING
600V 3PHASE DELTA SERVICE INCLUDING SERVICE ENTRANCE CABLE REPLACEMENT TO SUIT NEW
100A SERVICE ENTRANCE, ASSOCIATED METERING UPGRADES, AND ETC. ENSURE DISCONNECT
SWITCH IS BONDED TO GROUND PROPERLY AS PER OESC. PROVIDE ALL ASSOCIATED ACCESSORIES
AS REQUIRED TO FACILITATE THE NEW INSTALLATION. ALL THIS WORK TO BE PAID FOR FROM CASH
ALLOWANCE.
CONTROL WIRING FOR GENERATOR
ANNUNCIATOR PANEL IN 53mmC CONDUIT,
COORDINATE WITH GENERATOR
MANUFACTURER RECOMMENDATION FOR
EXACT REQUIREMENTS.
CONTROL WIRING FOR EPO BUTTON IN 53mmC CONDUIT,
COORDINATE WITH MANUFACTURER RECOMMENDATION
FOR EXACT REQUIREMENTS.
200A-3P
F@100A
VERIFY EXISTING ELECTRICAL EQUIPMENT INFORMATION SHOWN ON DRAWING WITH SITE
CONDITION PRIOR TO START OF WORK.
7
CONDUCTOR TO BE OVERSIZED TO SUIT VOLTAGE DROP AS PER OESC.
REGARDING TORONTO HYDRO ASSOCIATED WORK,
ALL CONTRACTOR COORDINATION WORK WITH
TORONTO HYDRO WILL BE PART OF BASE BID. ANY
DIRECT COSTS FROM TORONTO HYDRO TO BE PAID
BY THE CONTRACTOR THROUGH CASH ALLOWANCE
(NO MARK UP).
E-3
ELECTRICAL SINGLE LINE
DIAGRAM
FIRE STATION No.331
MMM Group Limited100 Commerce Valley Drive West
Thornhill, ON L3T 0A1
t. 905-882-1100
f. 905-882-0055
www.mmm.ca
1 2016/08/18 Issued For 75% Client Review
2 2016/09/21 Issued For Permit & Tender
3 2016/11/28 Issued For Tender - Rev.1
AutoCAD SHX Text
DATE: 2016/07/20
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
PROJECT :
AutoCAD SHX Text
CLIENT : - CITY OF TORONTO
AutoCAD SHX Text
CONSULTANT
AutoCAD SHX Text
THIS DRAWING ARE NOT TO BE SCALED. REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL, ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFORE PROCEEDING WITH THE WORK. CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES AND REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST ASSUME FULL RESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS OR DAMAGES RESULTING FROM HIS WORK. THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BY AND IS THE PROPERTY OF THE ARCHITECT. THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITY FOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALL NOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROM THE SUPPLIED INFORMATION.
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
TRUE NORTH
AutoCAD SHX Text
CONSTRUCTON NORTH
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
REVIEWED BY:
AutoCAD SHX Text
33 CLAREMONT STREET
AutoCAD SHX Text
TORONTO, ONTARIO, CANADA
AutoCAD SHX Text
- EMERGENCY SERVICES
AutoCAD SHX Text
Metro Hall City of Toronto
AutoCAD SHX Text
2nd floor, 55 John St.,
AutoCAD SHX Text
Toronto, Ontario M5V 3C6
AutoCAD SHX Text
CLIENT
AutoCAD SHX Text
ADDRESS :
AutoCAD SHX Text
MMM PROJECT No.: 1816292-003
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
I.Z.
AutoCAD SHX Text
D.L.
M
A
N
N
IN
G
A
V
E
.
C
L
A
R
E
M
O
N
T
S
T
R
E
E
T
C
R
O
C
K
E
R
A
V
E
.
APPROXIMATE LOCATION OF EXISTING GAS METER
AND REGULATOR ASSEMBLY TO BE REMOVED
APPROXIMATE LOCATION OF NEW OUTDOOR
NATURAL GAS GENERATOR.
REFER TO ELECTRICAL PLANS FOR FINAL LOCATION.
NEW GAS METER AND REGULATOR
ASSEMBLY
EXISTING FIRE
HALL #331
(33 CLAREMONT ST.)
NEW GAS LINE TO BE ROUTED ALONG
WALL, CLEAR OF DOORS AND OPENINGS
TO NEW GENERATOR
REMOVE THE EXISTING GAS CONNECTION FOR BBQ
NEW GAS CONNECTION C/W ISOLATION VALVE &
QUICK CONNECT FOR BBQ, FINAL LOCATION TO
BE DETERMINED ON SITE. PIPE TO BE ROUTED
ALONG WALL, CLEAR OF DOORS AND OPENINGS
X
THE FOLLOWING IS A PROPOSED SEQUENCE IMPLEMENTATION, INTENDED TO
GIVE A DIAGRAMMATIC OVERVIEW OF THE PROPOSED SEQUENCE OF
INSTALLATION FOR THIS PROJECT. BE RESPONSIBLE TO CONFIRM THIS
SEQUENCE, MAKE THE REQUIRED MODIFICATION TO SUIT THE ANOMALIES OF
THIS BUILDING AND COORDINATE THIS WHEN PREPARING THE MASTER
CONSTRUCTION SCHEDULE FOR THE IMPLEMENTATION OF ALL WORK
ASSOCIATED WITH THIS PROJECT.
PROPOSED SEQUENCE OF IMPLEMENTATION
1. MECHANICAL:
1.1. PERFORM ALL DEMOLITION WORK ONCE NEW GENERATOR IS IN PLACE AS
EXISTING GENERATOR WILL BE USED TEMPORARILY UNTIL NEW
GENERATOR IS FULLY FUNCTIONAL.
1.2. PREPARE THE SHOP DRAWINGS FOR REQUIRED EQUIPMENT.
1.3. PROVIDE NEW GAS METER ASSEMBLY AND PIPING AS SHOWN.
2. WHEN ALL THE MECHANICAL SERVICES HAVE BEEN INSTALLED, COMPLETE
AND COMMISSIONED:
2.1. COMPLETE ALL REMAINING REMEDIAL WORK, INCLUDING PATCHING WORK,
FIRE STOPPING, CEILING INSTALLATIONS, PAINTING, ETC. UPON
COMPLETION OF MECHANICAL SERVICES.
2.2. COMPLETE AS-BUILTS, OPERATIONS & MAINTENANCE MANUALS AND TURN
OVER TO CONSULTANT.
GAS LINE
DEMOLISHED
PIPE RISER DOWN
EXISTING WORK TO BE RETAINED
EXISTING WORK TO BE REMOVED AND/OR
D
E
G
PIPE RISER UP
PIPE RISER UP
EXISTING WORK TO BE RELOCATED
R
FLEXIBLE CONNECTOR
DRAWING LIST
DRAWING No. DESCRIPTION SCALE
As NotedM-1
BRANCH OFF BOTTOM OF MAIN
BRANCH OFF TOP OF MAIN
CHECK VALVE
VALVE
UNION
SITE PLAN AND DETAILS - MECHANICAL
PROJECT PROPOSED SEQUENCE
OF IMPLEMENTATION
GENERAL NOTES:
1 THIS DRAWING IS ISSUED TO SHOW SCOPE OF WORK ONLY. THE CONTRACTOR MUST
PERFORM A SITE INSPECTION (INCLUDING CEILING SPACES) DURING THE TENDER
PERIOD & ENSURE THAT ALL WORK THAT IS VISIBLE IS INCLUDED IN THE DEMOLITION
CONTRACT. ANY OTHER EXISTING SERVICES THAT PASS THROUGH THE RENOVATION
AREA (UNLESS OBSOLETE) ARE TO BE MAINTAINED AND/OR RELOCATED TO SUIT THE
SCOPE OF WORK.
2 ALL PENETRATIONS THROUGH WALLS AND CEILINGS MUST BE FIRE STOPPED WITH FIRE STOP
MATERIAL. REFER TO SPECIFICATIONS.
ROUTING OF SERVICES ARE DIAGRAMMATIC. BE RESPONSIBLE TO CONFIRM EXACT ROUTING
ON SITE PRIOR TO FABRICATION OR ROUGH-IN AND INCLUDE FOR ANY OFFSETS, TRANSITIONS,
ETC. AS REQUIRED FOR A COMPLETE INSTALLATION.
3
SUMMARY OF GAS ITEMS WITHIN BUILDING:
BOILERS - 2 @ 750 CFH
ROOF TOP UNIT - 0
DOMESTIC HOT WATER HEATERS - 1 @ 156 CFH
DOMESTIC 4 BURNER RANGE - 2 @ 60 CFH
BBQ - 1 @ 100 CFH
TOTAL EXISTING CONNECTED LOAD = 1876 CFH
NEW GENERATOR = 1090 CFH
NEW CONNECTED LOAD = 2966 CFH @ 2 PSI
2M-1
SCALE: N.T.S.
TO NEW GAS GENERATOR
ON GRADE (1090 CFH)
2#G
25ø
VALVE SHALL BE
COLORED "RED"
P.R.V.
G
~
EXISTING INCOMING GAS SERVICE
FOR A NEW CONNECTED LOAD OF
2966 CFH AT 2 PSI
EXISTING GAS PRV, METER
AND PIPING ASSEMBLY TO BE
REMOVED
CONNECT INTO
EXISTING SERVICE
~
GRADE
PROVIDE SIGNAGE STATING
"EMERGENCY GENERATOR
DO NOT SHUT OFF"
G
CONNECT TO THE
EXISTING GAS LINE
PROVIDE SIGNAGE STATING
"EMERGENCY GENERATOR
DO NOT SHUT OFF"
EMERGENCY
GENERATOR
NEW GAS METER ASSEMBLY
SECURED VALVE TYPICAL
ALONG PATH TO GENERATOR
EXISTING GAS LINE TO EXISTING
GAS FIRED EQUIPMENT WITH A
APPROXIMATE CONNECTED LOAD
OF 1876 CFH
25ø25ø
32ø
32ø
25ø
PRV TO REDUCE 1876 CFH
FROM 2 PSI TO 7" W.C.
PRV TO REDUCE 1090 CFH
FROM 2 PSI TO 11" W.C.
32ø
2#G
2#G
G
EXISTING BBQ
CONNECTION
TO BE REMOVED
NEW BBQ CONNECTION
TO BE INSTALLED C/W
VALVE & QUICK CONNECT
CONNECT TO THE
EXISTING GAS LINE
20ø
ROUTE PIPING ALONG
BUILDING WALL TO
GENERATOR
M-1
1
M-1
SCALE: N.T.S.
FIRE STATION
No.331
1 2016/08/18 Issued For 75% Client Review
2 2016/09/21 Issued For Permit & Tender
3 2016/11/28 Issued For Tender "Rev. 1"
GENERAL NOTES AND SPECIFICATIONS
A. GENERAL
1. CHECK DIMENSIONS ON STRUCTURAL DRAWINGS AGAINST ELECT DRAWINGS AND EXISTING SITECONDITIONS. REPORT ANY INCONSISTENCIES TO CONSULTANT BEFORE PROCEEDING WITH THE WORK.
2. REFER TO ELECTRICAL AND MECHANICAL DRAWINGS FOR LOCATION AND SIZE OF CONDUITS AND GASPIPING BURIED UNDERGROUND.
3. DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE. ELEVATIONS ARE IN METRES UNLESS NOTEDOTHERWISE.
4. PERFORM DESIGN, FABRICATION AND PLACEMENT AND/OR ERECTION IN ACCORDANCE WITHREQUIREMENTS OF REFERENCE STANDARDS, REGULATORY AUTHORITIES AND CONTRACT DOCUMENTS.BE AWARE THAT THE MORE SEVERE REQUIREMENTS OF CONTRACT DOCUMENTS TAKE PRECEDENCEOVER REQUIREMENTS OF REFERENCE STANDARDS AND REGULATORY AUTHORITIES.
5. DO NOT SCALE DRAWINGS.
B. DESIGN
1. STRUCTURAL DESIGN IS IN ACCORDANCE WITH PART 4 OBC 2012.2. DESIGN DATA (OBC 2012):
SEISMIC: Ie=1.5Sa(0.2)=0.22, Sa(0.5)=0.13, Sa(1.0)=0.067, Sa(2.0)=0.021PGA=0.12SITE CLASS = DFa=1.3, Fv=1.4
LIVE LOADS DUE TO SNOW AND RAIN: - GROUND SNOW LOAD: 0.90 kPa- 24 HOURS RAIN LOAD: 0.95 kPa
C. CONSTRUCTION PHASING
1. COORDINATE WITH ELECTRICAL, MECHANICAL AND GENERAL TRADES WORK TO DETERMINE REQUIREDSEQUENCE OF CONSTRUCTION FOR WORK SHOWN ON STRUCTURAL DRAWINGS.
D. REFERENCE STANDARDS & PUBLICATIONS
1. CAST-IN-PLACE CONCRETE, CONCRETE FORMWORK AND CONCRETE REINFORCEMENT:1) CSA STANDARD A23.1, CONCRETE MATERIALS AND METHODS OF CONCRETE CONSTRUCTION.2) CSA STANDARD A23.2, METHODS OF TEST AND STANDARD PRACTICES FOR CONCRETE.3) CSA STANDARD A23.3, DESIGN OF CONCRETE STRUCTURES FOR BUILDINGS.4) ADD CSA-S269.3 (R1998) CONCRETE FORMWORK.5) ACI 117 STANDARD SPECIFICATIONS FOR TOLERANCES FOR CONCRETE CONSTRUCTION AND MATERIALS.6) ACI 315, DETAILS AND DETAILING OF CONCRETE REINFORCEMENT.7) ACI 315R, MANUAL OF ENGINEERING AND PLACING DRAWINGS FOR REINFORCED CONCRETE STRUCTURES.8) RSIC-2004 REINFORCING STEEL MANUAL OF STANDARD PRACTICE.
2. STRUCTURAL STEEL:1) CAN/CSA STANDARD G-40.20/G-40.21, GENERAL REQUIREMENTS FOR ROLLED OR WELDED STRUCTURAL
QUALITY STEEL.2) CSA STANDARD S16.1-09, LIMIT STATES DESIGN OF STEEL STRUCTURES.3) CSA STANDARD W59-03, WELDED STEEL CONSTRUCTION (METAL ARC WELDING).4) CSA STANDARD W178.1 CERTIFICATION OF WELDING INSPECTION ORGANIZATIONS.5) CSA STANDARD W178.2 CERTIFICATION OF WELDING INSPECTORS.
E. SITE WORK
1. DEMOLITION:1) REMOVE CONCRETE PAVEMENT AS REQUIRED TO CONSTRUCT THE CONCRETE PAD AND BURY THE
CONDUITS. REINSTATE CONCRETE PAVEMENT AROUND NEW CONCRETE PAD AND PROVIDE 1% SLOPE TOLEAD THE WATER AWAY FROM CONCRETE PAD.
F. CONCRETE FORMWORK
1. FORMWORK CONSTRUCTION:1) FABRICATE AND ERECT FORMWORK IN ACCORDANCE WITH REQUIREMENTS OF REFERENCE STANDARDS.2) USE EARTH FORMS FOR FOOTINGS ONLY WITH GEOTECHNICAL ENGINEER'S WRITTEN APPROVAL.3) CLEAN FORMWORK IN ACCORDANCE WITH PROVISIONS OF CSA A23.1 PRIOR TO START OF CONCRETE
PLACEMENT.2. TOLERANCES:
1) CONSTRUCT CONCRETE FORMWORK IN ACCORDANCE WITH REVIEWED SHOP DRAWINGS, REQUIREMENTSOF CONTRACT DOCUMENTS AND REFERENCE STANDARDS TO PRODUCE FINISHED CONCRETECONFORMING TO SHAPE, DIMENSIONS, LOCATIONS AND LEVELS WITHIN TOLERANCES SPECIFIED IN CSAA23.1 AND ACI 117.
2) CONFORM TO CSA A23.1 FOR TOLERANCE.
G. CONCRETE REINFORCEMENT
1. REINFORCING STEEL: DEFORMED BARS TO CSA G30.18, GRADE 400R/W.2. FABRICATE REINFORCING STEEL ONLY IN A PERMANENT FABRICATING SHOP UNLESS OTHERWISE
APPROVED BY CONSULTANT.3. FABRICATE REINFORCING STEEL IN ACCORDANCE WITH REVIEWED BAR LISTS AND SHOP DRAWINGS.4. CLEARLY IDENTIFY REINFORCING BARS TO ALLOW CORRELATION WITH BAR LISTS AND PLACEMENT IN
ACCORDANCE WITH SHOP DRAWINGS.5. PROVIDE SPLICES ONLY WHERE SPECIFICALLY INDICATED ON DRAWINGS, UNLESS OTHERWISE APPROVED
IN WRITING BY THE CONSULTANT.6. BEFORE COMMENCING PLACEMENT OF REINFORCEMENT, CONFIRM THAT CONCRETE FORMWORK HAS
BEEN COMPLETED AND IS ADEQUATELY BRACED.7. PLACE REINFORCEMENT IN ACCORDANCE WITH REQUIREMENTS OF CSA STANDARDS A23.3 & SHOP
DRAWINGS.8. REMOVE CONTAMINANTS, INCLUDING CONCRETE RESIDUE FROM PREVIOUS POURS WHICH LESSEN BOND
BETWEEN CONCRETE AND REINFORCEMENT.9. REPLACE INCORRECTLY FABRICATED REINFORCEMENT, RELOCATE MISPLACED REINFORCEMENT AND
INSTALL OMITTED REINFORCEMENT BEFORE CONCRETE IS PLACED, AS DIRECTED BY CONSULTANT ORCONSULTANT'S REPRESENTATIVE.
H. MATERIALS
1. STRUCTURAL STEEL: TO CAN/CSA-G40.20/G40.21-041) W AND WWF SECTIONS, FABRICATED SECTIONS: GRADE 350W (50000 PSI)2) PLATES, ANGLES, CHANNELS: GRADE 300W (43500 PSI)3) HOLLOW STRUCTURAL SECTIONS TO GRADE 350W CLASS C, OR ASTM A500 GRADE C.
3. REINFORCING BAR AREAS ARE 100, 200, 300, 500, 700, 1000, 1500 AND 2500mm² FOR BAR DESIGNATIONS 10,15, 20, 25, 30, 35, 45 AND 55 RESPECTIVELY.
4. CONCRETE - REFER TO TABLE OF CONCRETE PROPERTIES.
I. SHOP DRAWINGS AND SUBMITTALS
1. CONCRETE REINFORCEMENT AND CONCRETE PLACEMENT:1) PREPARE SHOP DRAWINGS INCLUDING BAR PLACING DRAWINGS AND BAR LISTS IN ACCORDANCE WITH
THE REINFORCING STEEL INSTITUTE OF CANADA, REINFORCING STEEL MANUAL OF STANDARD PRACTICE,ACI 315, ACI 315R, AND THE TYPICAL DETAILS INCLUDED WITH THE CONTRACT DOCUMENTS.
2) SUBMIT SHOP DRAWINGS & BAR LISTS SUFFICIENTLY DETAILED & DIMENSIONED TO PERMIT CORRECTPLACEMENT OF REINFORCEMENT AND ACCESSORIES WITHOUT REFERENCE TO ARCHITECTURAL ANDSTRUCTURAL DRAWINGS.
3) SHOW CONCRETE COVER TO REINFORCEMENT AND LOCATION OF CONSTRUCTION JOINTS.2. STRUCTURAL STEEL:
1) SUBMIT SHOP DRAWINGS TO CONSULTANT FOR REVIEW BEFORE COMMENCING FABRICATION.2) PROFESSIONAL ENGINEER RESPONSIBLE FOR CONNECTION DESIGN MUST EITHER SEAL AND SIGN EACH
SHOP DRAWING SUBMITTED, OR SUBMIT A SEAL AND SIGNED LETTER AT COMMENCEMENT OF SHOPDRAWING PREPARATION CONFIRMING ASSUMPTION OF RESPONSIBILITY FOR COMPLIANCE OFCONNECTIONS WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.
3) SHOW SPLICE LOCATIONS AND DETAILS.3. REVIEW ALL SHOP DRAWINGS PRIOR TO SUBMISSION TO CONSULTANT. BY THIS REVIEW, CONTRACTOR
REPRESENTS TO HAVE DETERMINED AND VERIFIED ALL FIELD MEASUREMENTS, SITE CONDITIONS,MATERIALS, PRODUCT OR ACCESSORY, AND TO HAVE CHECKED AND COORDINATED EACH SHOP DRAWINGWITH THE REQUIREMENTS OF WORK AND OF CONTRACT DOCUMENTS.
4. CONFIRM CONTRACTOR'S REVIEW OF EACH SHOP DRAWING BY STAMP, DATE AND SIGNATURE OF ARESPONSIBLE PERSON. NOTIFY CONSULTANT IN WRITING AT TIME OF SUBMISSION OF ANY DEVIATIONS INSHOP DRAWINGS FROM REQUIREMENTS OF CONTRACT DOCUMENTS.
5. BE AWARE THAT CONSULTANT'S REVIEW OF SHOP DRAWINGS IS FOR CONFORMITY TO DESIGN CONCEPTAND FOR GENERAL ARRANGEMENT, AND THAT CONTRACTOR RETAINS RESPONSIBILITY FOR ERRORS ANDOMISSIONS IN SHOP DRAWINGS AND RESPONSIBILITY FOR MEETING ALL REQUIREMENTS OF CONTRACTDOCUMENTS.
6. MAKE CHANGES IN SHOP DRAWINGS WHICH CONSULTANT MAY REQUIRE CONSISTENT WITH CONTRACTDOCUMENTS AND RESUBMIT UNLESS OTHERWISE DIRECTED BY CONSULTANT. WHEN RESUBMITTINGNOTIFY CONSULTANT IN WRITING OF REVIEWS OTHER THAN THOSE REQUESTED BY CONSULTANT.
7. DO NOT COMMENCE FABRICATION OF STRUCTURAL STEEL AND CONCRETE REINFORCEMENT UNTIL SHOPDRAWINGS HAVE BEEN REVIEWED AND CONSULTANTS' COMMENTS ARE INCORPORATED ON SHOPDRAWINGS ISSUED TO FABRICATING SHOP.
8. ALLOW 7 DAYS FOR RETURN OF SHOP DRAWINGS FROM CONSULTANTS.
J. INSPECTION AND TESTING
1. PERFORM FIELD INSPECTIONS AND TESTING DESCRIBED BELOW BY AN INSPECTION AND TESTINGCOMPANY, APPOINTED AND PAID FOR BY THE GENERAL CONTRACTOR.
2. STRUCTURAL STEEL SHOP INSPECTION:1) MATERIALS AND PAINT CONFORM TO CONTRACT DRAWINGS. MILL TEST REPORTS, PROPERLY
CORRELATED TO THE MATERIALS, WILL BE ACCEPTED IN LIEU OF PHYSICAL TESTS OF STRUCTURALMATERIALS;
2) FABRICATION AND WELDING CONFORM TO CONTRACT DOCUMENTS AND DIMENSIONED SHOP DRAWINGS;3) SHOP SURFACE PREPARATION AND PAINTING CONFORM TO CONTRACT DRAWINGS;4) SURFACES INACCESSIBLE FOR SURFACE PREPARATION AND PAINTING AFTER ASSEMBLY ARE TREATED
BEFORE ASSEMBLY;5) INSPECTION AND TESTING COMPANY SHALL PERFORM NONDESTRUCTIVE TESTING OF WELDED
CONNECTIONS.3. FIELD INSPECTION AND TESTING OF CONCRETE:
1) STANDARD CONCRETE SLUMP TEST TO MEET CSA A23.2 REQUIREMENTS.2) CONCRETE CYLINDER COMPRESSION TESTS, 1 AT 7 DAYS AND 2 AT 28 DAYS TO MEET CSA A23.2
REQUIREMENTS.4. FIELD INSPECTION AND TESTING OF STRUCTURAL STEEL:
1) STRUCTURAL STEEL ERECTION AND FIT-UP.2) STRUCTURAL STEEL WELDED JOINTS, INCLUDING SLAG REMOVAL.3) STRUCTURAL STEEL BOLTED CONNECTIONS.4) GENERAL INSPECTION OF FIELD CUTTING AND ALTERATIONS OF STRUCTURAL STEEL.5) GENERAL INSPECTION OF SHOP COATING TOUCH-UP OF STRUCTURAL STEEL.6) INSPECTION OF SURFACE PREPARATION AND COATING THICKNESS FOR ZINC PRIMER AND ZINC-RICH
PAINT.5. REINFORCEMENT INSPECTION:
1) PROVIDE MINIMUM 48 HOURS NOTIFICATION TO CONSULTANT TO INSPECT THE INSTALLATION OFREINFORCEMENT PRIOR TO CONCRETE POUR.
K. GEOTECHNICAL DESIGN ASSUMPTIONS
1. STRUCTURAL DESIGN IS BASED ON A FROST DEPTH OF 1.2m (MIN) AND MODULUS OF SUBGRADE REACTIONOF 25 MPa/m.
THE CONTRACTOR SHALL RETAIN A GEOTECHNICAL ENGINEER TO PROVIDE INSTRUCTION FOR THESUBGRADE SOIL PREPARATION OF THE CONCRETE PAD TO SUIT THE DESIGN ASSUMPTIONS. THEGEOTECHNICAL ENGINEER SHALL REVIEW THE SUBGRADE PREPARATION PRIOR TO POURING THECONCRETE PAD. THE COST OF GEOTECHNICAL INVESTIGATION SHALL BE CARRIED BY GENERALCONTRACTOR.
AIRCONTENT
(%)
MAXW / C
RATIO
SLUMP(mm)
MINCOMPRESSIVESTRENGTH f'c
AT 28 DAYS(MPa)
LOCATION / MEMBER
TABLE OF CONCRETE PROPERTIES
EXPOSURECLASS
OT
HE
R 170 ± 20
80 ± 30
UNSHRINKABLE FILL
LEAN MIX CONCRETE 8
MAX 0.40
0.70
80 ± 30
CO
NC
RE
TE
NO
TE
XP
OS
ED
TO
DE
-IC
ING
CH
EM
ICA
LS
OR
FR
EE
ZIN
GA
ND
TH
AW
ING
U/N
SKIM SLABS 15 0.50
40 ± 20
40 ± 20CO
NC
RE
TE
EX
PO
SE
D T
OD
E-I
CIN
G C
HE
MIC
AL
SW
ITH
/WIT
HO
UT
FR
EE
ZIN
GA
ND
TH
AW
ING
NON STRUCTURAL TOPPINGS(EXPOSED TO FREEZINGAND THAWING)
32OT
HE
R
SIDEWALKS, CURBS,PAVING SLABS
30
0.45a
5-8 C-2
0.45a
5-8 C-2
80 ± 30CONCRETE PAD
FO
OT
ING
S 35 0.40 5-8b,d
C-1
NOTES:
a. SPECIAL CONCRETE HANDLING AND PLACING METHODS OR THE USE OF A SUPER PLASTICIZER WILL BE REQUIREDTO PLACE THIS CONCRETE.
b. PROVIDE CONCRETE WITH A MINIMUM CEMENTING MATERIALS CONTENT OF 325 kg/m³.c. MAXIMUM AGGREGATE SIZE IS 20mm.d. PROVIDE CORROSION INHIBITOR TO CONCRETE MIX WITH MINIMUM DOSAGE OF 10 L/m³ OF 30% SOLUTION OF
CALCIUM NITRITE.
CONCRETE FILL 30
FIRE STATION No.331
S0
PART PLAN1 : 50
NOTE:1. PROVIDE 60mm CONCRETE COVER FOR REINFORCEMENT.2. TRENCH EXCAVATION AND BACK FILL SHOULD BE UNDER
THE SUPERVISION OF GEOTECHNICAL ENGINEER.3. REMOVE EXISTING PAVEMENT AND EARTH FILL TO THE
REQUIRED DEPTH. THE SUBGRADE CONDITION SHOULD BEINSPECTED AND APPROVED BY GEOTECHNICAL ENGINEER.
4. COMPACT THE CRUSHER-RUN LIMESTONE OR EQUIVALENTTO 100% MAXIMUM STANDARD PROCTOR DRY DENSITY.
1-
HSS 178Øx9.5 FILL WITHCONCRETE. (TYPICAL)
NEW CONCRETE PAD
NEW GENERATORREFER TO ELECTRICALDRAWINGS
30
0 M
IN
300 MIN
EXISTING BUILDING
7000 MIN
13
89
15
00
ADD 2-15M BARSx1200 LONGTOP AND BOTTOM
CONCRETEPAD
30
0
EXISTINGBUILDING
PAINT STEEL PIPE ANDBASE PLATE WITH PRIMERAND TWO COATS ENAMELPAINT IN YELLOW
50mm STYROFOAM RIGIDINSULATION OR EQUIVALENT
200mm THICK 20mm CRUSHER-RUN LIMESTONE
600 MIN
EXIST CONCRETEPAVEMENT
NEW CONCRETEPAVEMENT
1%
15
0
11 : 20 -
SECTION
12
00
NEWGENERATOR
ROUND TOP OF CONCRETE
2-
15@200T&BEW
10@200 U-BARAROUND PERIMETER600
30
0
300
50
(T
YP
) 50 (TYP)
21 : 10 -
SECTION
BASE PLATE 300x300x16COMPLETED WITH 4-16ØHILTI 200 HIT-Z ANCHORWITH 115mm EMBEDMENT.PROVIDE NON-SHRINKGROUT UNDER BASEPLATE IF REQUIRED.
8
300 MIN
FIRE STATION No.331
S1
400 ESNA PARK DRIVE, UNIT 15, MARKHAM, ONTARIO L3R 3K2 P: 905 475 7755 F: 905 475 7718
WWW.FISHERENVIRONMENTAL.COM
April 28, 2016 Meaghan Aldcroft
Environmental Coordinator
City of Toronto, Corporate Services
Facilities Management
Metro Hall, 55 John Street
Toronto ON,
M5V 3C6
Re: Pre-reno Designated Substance Sampling, 33 Claremont Street, Toronto, ON.
Dear Ms. Aldcroft,
As requested, Fisher Environmental Ltd. (Fisher) has performed an assessment of the Toronto Fire
Station 331 building located at 33 Claremont Street, Toronto, Ontario (the “Site”). Fisher understands that
the request to have the assessment performed is in anticipation of planned construction activities (backup
generator installation). The purpose of the current survey was to identify Designated Substances
including sampling of materials suspected to contain asbestos and lead. The assessment scope did not
include the entirety of the subject building. Rather, the assessment was limited to locations where
construction activities are proposed (Electrical Room/ Utility Room, Mechanical Room and Building
Exterior). The fieldwork was conducted on April 8, 2016.
Asbestos-Containing Materials
A total of six (6) bulk samples suspected to contain asbestos were collected and submitted to Fisher
Environmental Laboratories for Polarised Light Microscopy (PLM) analysis, as outlined in NIOSH Method
9002. The results of PLM sample analysis are summarized in Table 1, below.
Dormitory (2-11), Office (2-13), and in the Corridor Pole Hole (2-14).
Based on the observations and findings outlined above, Fisher recommends that if the identified
asbestos-containing materials are to be disturbed as part of the planned construction activities then it
should be removed using removal operation procedures as outlined in Ontario Regulation 278/05.
Removal of asbestos-containing parging cement on pipe fittings will require Removal Operational
Procedures as detailed in Ontario Regulation 278/05 (Type 2 Glove Bag);
Removal of asbestos-containing pipe insulation will require Removal Operational Procedures as
detailed in Ontario Regulation 278/05 (Type 2 Operation); and
Removal of asbestos-containing vinyl floor tiles will require Removal Operational Procedures as
detailed in Ontario Regulation 278/05 (Type 1 Operation).
The presence of ACM should be presumed in locations not accessed during the assessment. It is
possible that ACM is present at the Site that is not identified in this report. Should additional suspected
ACM not outlined in this report be discovered, it should be presumed as ACM until sample analysis
determines asbestos content. Due to the limited scope of work and the presence of solid building finishes
(i.e. plaster or drywall walls and ceilings etc.) in many locations throughout the Site, the full extent of
potential ACM may not be confirmed. Precautions should be taken when dismantling solid wall or ceiling
finishes, or any other building surfaces which may conceal potential ACM. Such precautions include, but
are not limited to, isolation measures and appropriate personal protective equipment.
Lead-Containing Paint
Materials expected to be impacted by planned construction activities and suspected to contain lead
included one visually distinct paint finish at the Site. One (1) bulk sample was collected and submitted to
Fisher Environmental Laboratories for inductively coupled plasma (ICP) analysis, as outlined in NIOSH
Fisher Environmental Ltd.
April 28, 2016
Fisher Project No.16-7706 Page 3
33 Claremont Road, Toronto, ON
The City of Toronto, Facilities Management
7300. The laboratory analysis report for lead paint sample results is included as Attachment A. The
results of sample analysis by ICP method are summarized in Table 2, below.
Table 2 - Summary of Lead Paint Sample Analysis
Sample No. Sample Location Sample Description Lead Content (ppm and % by Weight)
16-3727-07 2-11 Mechanical Room Green Paint 208 ppm (0.02%)
The Ontario Ministry of Labour (MOL) has not prescribed criteria defining an analyzed sample of bulk
material as “lead-containing”. Further, the MOL has not established a lower limit for concentrations of
lead in paint, below which precautions do not need to be considered during construction projects.
However, except for aggressive disturbance of painted finishes, (e.g., abrasive blasting, torch cutting, or
grinding), Fisher believes that a lead content below 0.1% by weight (1,000 ug/g or 1000 ppm) represents
a concentration in which the lead content is not the limiting hazard for construction hygiene purposes.
Based on the laboratory findings, the lead concentration of the green paint was found to be 208 ppm
which is below 0.1% by weight (1,000 ug/g or 1000 ppm).
A review of most recent annual reassessment survey for the Site indicated that light blue paint in the
mechanical room (1-01) found to contain 10,110 ppm (1% by weight). Based on the review, elevated
concentrations of lead (greater than 0.1% lead) were detected in light blue paint observed in the
Mechanical Room (1-01).
If the work activities affecting the lead containing light blue paint observed in the mechanical room (1-01)
then it should be removed using appropriate lead abatement procedures following MOL Guideline: Lead
on Construction Projects, 2011.
Also, bell & spigot pipe joint connections associated with drainage piping were noted to be present in the
project scope area. This type of piping connection is historically known to have commonly been packed
with a gasket consisting of lead. While no sampling of this material was performed, Fisher noted the
presence of a metallic bluish-grey gasket within the collar of the bell & spigot pipe joints (good condition
throughout). This material is presumed to be lead-containing.
Where any lead-containing materials may be disturbed or removed, Fisher recommends that appropriate
lead abatement procedures be used. The lead abatement procedures to be used are determined by the
method(s) of disturbance employed. Regular construction dust suppression techniques and worker
hygiene practices are sufficient for disturbance of paint finishes determined to contain less than 0.1% lead
by weight, provided that work is limited to non-aggressive operations. Refer to MOL Guideline: Lead on
Construction Projects, 2011, for details of the Ministry’s health and safety guidelines regarding lead.
Table 3, below, identifies these potential methods and the associated respirator required, as outlined in
Ontario Ministry of Labour guidelines.
Fisher Environmental Ltd.
April 28, 2016
Fisher Project No.16-7706 Page 4
33 Claremont Road, Toronto, ON
The City of Toronto, Facilities Management
Table 3 - Classifications of Lead-Containing Operations and Required Respirator
Type 1 Operations (where concentrations of airborne lead would be expected to be < 0.05 mg/m3)
Activities that include;
Removal of lead containing coatings with chemical gel or paste and fibrous laminated cloth wrap
Removal of lead containing coatings / materials using power tool that has an effective dust collection system equipped with HEPA filter
Removal of lead containing coatings / materials using non-powered hand tools other than manual scraping or sanding
Respirators should not be necessary if general procedures are followed and level of air is less than 0.05 mg/m3. However, if worker wishes to use a respirator, a half-mask particulate respirator with N-, R- or P- series filter, and 95, 99 or 100% efficiency should be provided.
Type 2a Operations (where concentrations of airborne lead would be expected to be > 0.05 to 0.50 mg/m3)
Activities that include;
Removal of lead containing coatings / materials by scraping or sanding using non-powered hand tools
Manual demolition of lead painted plaster walls / building components by striking with a sledgehammer or similar tool
NIOSH APF = 10 Half-mask particulate respirator with N- , R- or P- series filter, and 95, 99 or 100% efficiency.
Type 2b Operations (where concentrations of airborne lead would be expected to be > 0.50 to 1.25 mg/m3)
Not applicable to potential renovation activities.
Type 3a Operations (where concentrations of airborne lead would be expected to be > 1.25 to 2.50 mg/m3)
Activities that include;
• Welding or high temperature cutting of lead-containing coatings or
materials indoors or in a confined space.
Dry removal of lead-containing mortar using an electronic or pneumatic cutting device.
Burning of a surface containing lead
Removal of lead containing coatings / materials using power tools without an effective dust collection system equipped with HEPA filter
NIOSH APF = 50
Full-face piece air-purifying respirator with N- , R- or P- series filter and 100% efficiency.
Tight-fitting powered air-purifying respirator with high efficiency filter.
Full-face piece supplied-air respirator operated in demand mode.
Half-mask or full-face piece supplied air respirator operated in continuous-flow mode.
Type 3b Operations (where concentrations of airborne lead would be expected to be > 2.50 mg/m3)
Abrasive blasting of lead-containing coatings or materials.
NIOSH APF >=1000
Type CE abrasive-blast supplied respirator operated in a positive pressure mode with a tight-fitting half-mask face piece.
Where any lead-containing materials may be disturbed or removed, Fisher recommends that appropriate
lead abatement procedures be used. The lead abatement procedures to be used are determined by the
method(s) of disturbance employed. Regular construction dust suppression techniques and worker
hygiene practices are sufficient for disturbance of paint finishes determined to contain less than 0.1% lead
by weight, provided that work is limited to non-aggressive operations. Refer to MOL Guideline: Lead on
Construction Projects, 2011, for details of the Ministry’s health and safety guidelines regarding lead.
Other Designated Substances
During the current survey, no sampling for mercury was conducted. However, fluorescent light tubes
(known to contain mercury) were observed throughout the Site. Thermostatic controls, where observed,
were noted to be electric or “dry type”. No other building materials or components suspected to contain
mercury were noted during the building survey.
Fisher Environmental Ltd.
April 28, 2016
Fisher Project No.16-7706 Page 5
33 Claremont Road, Toronto, ON
The City of Toronto, Facilities Management
No immediate recommendations are warranted with regard to mercury. However, if disturbance of the
identified fluorescent light tubes presumed to contain mercury is planned as part of the anticipated
construction activities, Fisher recommends that these items be removed and disposed of in accordance
with all regulations. The disposal of mercury-containing items is regulated under Ministry of Environment
(MOE) O. Reg. 347 – General Waste Management. Specifically, the fluorescent light tubes should be
disposed of at an MOE licensed receiver.
Crystalline silica is a constituent of all concrete and masonry products present at the Site. While the
cutting, grinding, or demolition of materials containing silica is not anticipated at the Site, these activities
should be completed in accordance with Ontario Ministry of Labour Guidelines for Silica on Construction
projects. Specifically, the Guideline prescribes respiratory protection, site isolation, and the use of wetting
to control dust emissions during the cutting, grinding, drilling, or demolition of silica-containing materials.
Please refer to the Guideline for details concerning Silica on Construction Projects.
No other Designated Substances or other potentially hazardous building materials were identified in the
proposed project scope areas. If additional suspected Designated Substances or other potentially
hazardous building materials not identified in this or previous reports pertaining to the Site are discovered,
work should be stopped and the material(s) in question should be sampled for determination of content.
We trust you find the enclosed in order, however should you have any questions or concerns please do
not hesitate to contact us.
Respectfully submitted,
Muhammad Junayed, B.Sc., EPt. David Fisher, P. Eng., C. Chem.
Project Manager Principal
Attachment: Attachment A - Laboratory Analysis Report
Attachment A - Laboratory Analysis Report
Client: City of Toronto F.E. Job #: 16-3727
Facilities Management Project Name: Pre-Reno DSS
Address: 2nd Floor, Metro Hall Project ID: FE-16-7706
55 John Street, Toronto, ON Date Sampled: 7-Apr-16
Asbestos has been done in accordance with normal professional standard using the following Fisher Environmental Lab Method: Asbestos by PLM
(Polarized Light Microscope) F-26, Rev.2.2.
02B, Plaster, Loc:1-01, Mechanical
RoomNot Detected
02A, Plaster, Loc:1-01, Mechanical
Room
Fisher Environmental Laboratories (Lab ID #: 2745) is accredited by CALA (Canadian Association for Laboratory Accreditation Inc.) for asbestos analysis
by PLM.
01A, Plaster, Loc:2-11, Mechanical
RoomNot Detected
01B, Plaster, Loc:2-11, Mechanical
RoomNot Detected
01C, Plaster, Loc:2-11, Mechanical
Room
Certificate of Analysis
Client Sample ID Asbestos Content
Analysis Requested:
Sample Description:
FISHER ENVIRONMENTAL LABORATORIES
FULL RANGE ANALYTICAL SERVICES SOIL /WATER / AIR TESTING ENVIRONMENTAL
FLUSH-MOUNTED PUSHBUTTON MOUNTED 4'-0" (1.2 m) ABOVE FINISHED
FLOOR LEVEL. "WP" DENOTES WEATHERPROOF.
RECESSED OR SURFACE MOUNTED PANELBOARD, "PP" DENOTES POWER
PANEL, "LP" DENOTES LIGHTING AND POWER PANEL, "DP" DENOTES
DISTRIBUTION PANELBOARD.
EPO
WP
DISCONNECT SWITCH (FUSED OR NOT FUSED) WHERE SHOWN ON DRAWINGS
OR REQUIRED BY CODE. "WP" INDICATES WEATHERPROOF TYPE.
WP
CG
SIMILAR TO ABOVE, BUT MOUNTED APPROXIMATELY 3'-6" (1050 mm) ABOVE
FINISHED FLOOR LEVEL OR ABOVE COUNTER.
EMERGENCY BATTERY UNIT COMPLETE WITH DUAL HEAD TYPE LIGHT.
REFER TO SPECIFICATIONS FOR DETAILS.
LIGHTING SYMBOLS
E
DESCRIPTIONSYMBOL
SINGLE LINE DIAGRAM SYMBOLS
AUTOMATIC TRANSFER SWITCH (ATS) WITHOUT MANUAL BYPASS
FIRE ALARM SYMBOLSDESCRIPTIONSYMBOL
2
EX
AUTOMATIC HEAT DETECTOR 15°F (8.3°C) RATE OF RISE AND FIXED
TEMPERATURE TYPE 135°F (57°C) RATED AT 2500 FT (232m ) COVERAGE.
"EX" WHERE SHOWN, DENOTES EXPLOSION PROOF.
2
FLAME DETECTOR CEILING MOUNTED TYPE.
F
D
END OF LINE RESISTOR FOR FIRE ALARM SYSTEM.
DRY TYPE STEP DOWN TRANSFORMER.
MOLDED CASE CIRCUIT BREAKER.
THE FOLLOWING IS A PROPOSED SEQUENCE IMPLEMENTATION, INTENDED
TO GIVE A DIAGRAMMATIC OVERVIEW OF THE PROPOSED SEQUENCE OF
INSTALLATION FOR THIS PROJECT. BE RESPONSIBLE TO CONFIRM THIS
SEQUENCE, MAKE THE REQUIRED MODIFICATION TO SUIT THE ANOMALIES
OF THIS BUILDING AND COORDINATE THIS WHEN PREPARING THE MASTER
CONSTRUCTION SCHEDULE FOR THE IMPLEMENTATION OF ALL WORK
ASSOCIATED WITH THIS PROJECT.
PROPOSED SEQUENCE OF IMPLEMENTAION
ELECTRICAL1.
1.1
PREPARE SITE TO ACCOMMODATE THE NEW GENERATOR AND
ANCILLARY EQUIPMENT/DEVICES.
INSTALL NEW GENERATOR IN ITS PERMANENT LOCATION AND
PROVIDE FEEDERS AS SHOWN ON THE DRAWINGS.
CONFIRM SITE MEASUREMENTS AND ROUTINGS OF ALL FEEDERS
AND PLACEMENT LOCATIONS OF ALL COMPONENTS PRIOR TO
COMMENCEMENT OF WORK.
1.7
FIRE STOP ALL NEW WALL PENETRATIONS.
WHEN ALL THE ELECTRICAL SERVICES HAVE BEEN INSTALLED,
COMPLETED AND COMMISSIONED:
2.
2.2
COMPLETE AS-BUILTS, O&M MANUALS AND TURN OVER TO
CONSULTANT.
2.3
COMPLETE ALL REMAINING REMEDIAL WORK, INCLUDING PATCHING
WORK, FIRE STOPPING, CEILING INSTALLATIONS, PAINTING, ETC.
UPON COMPLETION OF ELECTRICAL SERVICES.
1.3
1.4
1.5
1.6
PREPARE AND SUBMIT SHOP DRAWINGS FOR NEW GENERATOR
AND TRANSFER SWITCH FOR REVIEW. ORDER EQUIPMENT AND
COORDINATE DELIVERY AND INSTALLATION.
2.1
TEST OPERATION OF NEW GENERATOR AND TRANSFER SWITCH.
REFER TO SPECIFICATION FOR DETAILS.
1.2
WATER SEAL ALL OPENINGS.
PROJECT PROPOSED SEQUENCE OF
IMPLEMENTATION
FUSE DISCONNECT SWITCH.
LINE OR LOW VOLTAGE CABLE IN CONDUIT.
LINE OR LOW VOLTAGE CABLE IN CONDUIT.
TEMPORARY GENERATOR NOT REQUIRED FOR POWER SHUTDOWN.
CONTRACTOR IS TO NOTIFY THE CITY OF TORONTO PROJECT MANAGER
10 BUSINESS DAYS PRIOR TO WHEN THE POWER SHUTDOWN WILL BE
REQUIRED. THE CONTRACTOR TO HAVE ALL NECESSARY WORK
PREPARED TO ENSURE THE SHUTDOWN IS NO LONGER THAN 4 HOURS.
AutoCAD SHX Text
DATE: 2016/07/20
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
PROJECT :
AutoCAD SHX Text
CLIENT : - CITY OF TORONTO
AutoCAD SHX Text
CONSULTANT
AutoCAD SHX Text
THIS DRAWING ARE NOT TO BE SCALED. REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL, ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFORE PROCEEDING WITH THE WORK. CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES AND REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST ASSUME FULL RESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS OR DAMAGES RESULTING FROM HIS WORK. THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BY AND IS THE PROPERTY OF THE ARCHITECT. THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITY FOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALL NOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROM THE SUPPLIED INFORMATION.
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
TRUE NORTH
AutoCAD SHX Text
CONSTRUCTON NORTH
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
REVIEWED BY:
AutoCAD SHX Text
140 LANDSDOWNE AVE.
AutoCAD SHX Text
TORONTO, ONTARIO, CANADA
AutoCAD SHX Text
- EMERGENCY SERVICES
AutoCAD SHX Text
Metro Hall City of Toronto
AutoCAD SHX Text
2nd floor, 55 John St.,
AutoCAD SHX Text
Toronto, Ontario M5V 3C6
AutoCAD SHX Text
CLIENT
AutoCAD SHX Text
ADDRESS :
AutoCAD SHX Text
1.
AutoCAD SHX Text
2016/07/28
AutoCAD SHX Text
Issued For 75%%%
AutoCAD SHX Text
MMM PROJECT No.: 1816292-002
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
Client Review
AutoCAD SHX Text
I.Z.
AutoCAD SHX Text
D.L.
AutoCAD SHX Text
R
AutoCAD SHX Text
R
AutoCAD SHX Text
R
AutoCAD SHX Text
R
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
ER
AutoCAD SHX Text
ER
AutoCAD SHX Text
RR
AutoCAD SHX Text
EOL
AutoCAD SHX Text
RR
AutoCAD SHX Text
RR
AutoCAD SHX Text
RR
(INLET SIDE)
(DISCHARGE SIDE)
3700
APPROXIMATE LOCATION OF ROOF TOP NATURAL GAS GENERATOR,
REFER TO SINGLE LINE FOR DETAILS. COORDINATE/VERIFY WITH SITE
CONDITION, EXISTING EQUIPMENT ON ROOF, AND
MECHANICAL/STRUCTURE DRAWING FOR EXACT GENERATOR LOCATION
AND INSTALLATION DETAILS PRIOR TO START OF WORK. PROVIDE ALL
ASSOCIATED ACCESSORIES TO FACILITATE THE NEW INSTALLATION
COMPLETELY. NOT BLOCKING DOOR SWING ON EACH SIDE.
GENERATOR
SHORE PANEL.
PROVIDED WITH
GENERATOR
ENCLOSURE.
EPO(WP/CG) PROVIDED WITH GENERATOR ENCLOSURE
CONDUITS SURFACE MOUNT TO BUILDING
EXTERIOR WALL GOING DOWN TO
ELECTRICAL EQUIPMENT OR CAPPED AS
SPARE.
CONDUIT TO GENERATOR
ANNUNCIATOR PANEL AND EPO
BUTTON
CONDUITS ON THE ROOF, REFER
TO SINGLE LINE FOR DETAILS
EXISTING MECHANICAL PIPE
TO BE RELOCATED TO FREE
UP THE SPACE FOR
GENERATOR INSTALLATION,
REFER TO MECHANICAL
DRAWING FOR DETAILS.
EXISTING GAS
PIPE
EXISTING GAS PIPE GO DOWN TO GAS METER
1100
1-100mmC RIGID PVC SPARE CONDUIT WITH PULL
STRING AND CAPPED AT BOTH END AND STOP
BEFORE ENTERING BUILDING FOR FUTURE USE
EXISTING SOLAR
PANEL
EXISTING
MECHANICAL
EQUIPMENT
1.2m CLEARANCE TO
STRUCTURE HANDRAIL
FOR MAINTENANCE AND
NOT BLOCKING DOOR
SWING
CONDUITS TO EQUIPMENT, REFER
TO SINGLE LINE FOR DETAILS.
REFER TO
DETAIL 2 OF
E1 FOR
ISOLATION
DETAILS.
APPROXIMATE LOCATION OF CONDUIT ENTRANCE TO EXISTING
BUILDING. PROVIDE ALL ASSOCIATED ACCESSORIES AS REQUIRED
FOR A COMPLETE INSTALLATION. CONTRACTOR TO COORDINATE
EXACT LOCATION AS PER SITE CONDITION.
SPARE CONDUIT SURFACE MOUNT TO
BUILDING EXTERIOR WALL GOING UP TO
ROOF TOP GENERATOR.
EPO
CONDUITS SURFACE MOUNT TO BUILDING
EXTERIOR WALL TO GENERATOR
ANNUNCIATOR PANEL AND EPO. REFER TO
SINGLE LINE FOR DETAIL.
GENERATOR
ANNUNCIATOR
PANEL
EXISTING DISCONNECT SWITCH FOR EXISTING ROOF TOP AIR
CONDITION UNIT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
EXISTING DISCONNECT SWITCH FOR EXISTING
CIRCULATION PUMPS
EXISTING DISCONNECT SWITCH FOR EXISTING SUPPLY
AIR UNIT S-2
EXISTING DISCONNECT SWITCH FOR EXISTING EXHAUST
FAN EF-7
EXISTING DISCONNECT SWITCH FOR TRUCK EXHAUST
EXISTING DISCONNECT SWITCH FOR EXISTING MAKE-UP
AIR UNIT
EXISTING DISCONNECT SWITCH FOR EXISTING DOORS 1 & 2
EXISTING DISCONNECT SWITCH FOR EXISTING EF-1
EXISTING DISCONNECT SWITCH FOR EXISTING SUPPLY AIR
EXISTING TORONTO HYDRO METER CABINET
EXISTING 600V,3Ø MAIN SERVICE ENTRANCE DISCONNECT
SWITCH
EXISTING TORONTO HYDRO SERVICE ENTRANCE DUCT
18
19
20
21
22
EXISTING 120/240V, 1Ø MAIN SERVICE ENTRANCE DISCONNECT SWITCH
EXISTING TORONTO HYDRO METER CABINET
EXISTING PANEL
EXISTING DISCONNECT SWITCH FOR EXISTING
LIGHTING PANEL "B"
EXISTING DISCONNECT SWITCH FOR EXISTING
LIGHTING PANEL "C"
EXISTING DISCONNECT
EXISTING LIGHTING PANEL "A"
EXISTING DISCONNECT SWITCH FOR EXISTING BR-1
EXISTING DISCONNECT SWITCH FOR EXISTING MAIN
FLOOR NEW DRYER
EXISTING LIGHTING SWITCH
23 EQUIPMENTS FOR IT & TELECOM
24 EXISTING LIGHTING
E
E
E
E
E
E
E
E
E
M
E
E
E
E
M
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
23
24
E
ER
R
D
D
ER
E
E
D
D
D
ER
25 EXISTING 600V SPLITTER
26 EXISTING SPLITTER
25
26
E
D
E
E
E
E
E
E
E
E
E
E
E
E
E
EXISTING DISCONNECT SWITCH FOR EXISTING ROOF TOP AIR
CONDITION UNIT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
1
2
3
4
5
6
7
8
EXISTING DISCONNECT SWITCH FOR EXISTING
CIRCULATION PUMPS
EXISTING DISCONNECT SWITCH FOR EXISTING SUPPLY
AIR UNIT S-2
EXISTING DISCONNECT SWITCH FOR EXISTING EXHAUST
FAN EF-7
EXISTING DISCONNECT SWITCH FOR TRUCK EXHAUST
EXISTING DISCONNECT SWITCH FOR EXISTING MAKE-UP
AIR UNIT
EXISTING DISCONNECT SWITCH FOR EXISTING DOORS 1 & 2
EXISTING DISCONNECT SWITCH FOR EXISTING EF-1
EXISTING DISCONNECT SWITCH FOR EXISTING SUPPLY AIR
10
11
12
TORONTO HYDRO METER AT NEW LOCATION TO FREE UP THE
SPACE FOR THE OTHER NEW EQUIPMENT, REFER TO SINGLE
LINE FOR DETAIL
NEW 600/347V,3Ø, 4W MAIN SERVICE ENTRANCE RATED FUSED
DISCONNECT SWITCH AT NEW LOCATION, REFER TO SINGLE LINE
FOR DETAIL
EXISTING TORONTO HYDRO SERVICE ENTRANCE DUCT
15
16
17
18
20
21
22
23
23
18
19
20
21
22
NEW AUTOMATIC TRANSFER SWITCH 'ATS-1', REFER TO SINGLE
FOR DETAILS.
NEW DRY TYPE TRANSFORMER TX-1, FLOOR
MOUNTED ON CONCRETE PAD UNDER NEW 600V
SPLITTER, COORDINATE SPACE REQUIREMENT WITH
SITE CONDITION. REFER TO SINGLE LINE FOR
DETAILS.
EXISTING PANEL
EXISTING DISCONNECT SWITCH FOR EXISTING
LIGHTING PANEL "B"
EXISTING DISCONNECT SWITCH FOR EXISTING
LIGHTING PANEL "C"
EXISTING DISCONNECT
EXISTING LIGHTING PANEL "A"
EXISTING DISCONNECT SWITCH FOR EXISTING BR-1
EXISTING DISCONNECT SWITCH FOR EXISTING MAIN
FLOOR NEW DRYER
EXISTING LIGHTING SWITCH
23 EQUIPMENTS FOR IT & TELECOM
24 EXISTING LIGHTING
24
E
R
E
M
CONDUITS WITHIN BUILDING TO
ELECTRICAL EQUIPMENTS FROM
GENERATOR
E
9
NEW SPLITTER, REFER TO SINGLE LINE
FOR DETAILS.
26
26
100mm
CONCRETE
PAD
ER
CONDUITS TO ROOF
TOP GENERATOR,
REFER TO SINGLE
LINE FOR DETAIL
ER
NEW SPLITTER, REFER TO SINGLE LINE
FOR DETAILS.
25
25
13
14
ENCLOSED BREAKER FOR CIRCUIT TO GENERATOR
SHORE PANEL, REFER TO SINGLE LINE FOR DETAILS.
27
27
CONDUITS FROM ROOF TOP
GENERATOR
NEW REMOTE EMERGENCY BATTERY UNIT
c/w HEADS. PROVIDE NEW 15A-1P LOCK
TYPE CIRCUIT BREAKER FROM THE
NEAREST AVAILABLE PANEL AND FEED
WITH 2#12+G IN 16mmC.
28
28
ATS-1
TX-1
29
ENCLOSED BREAKER FOR TRANSFORMER
"TX-1", REFER TO SINGLE LINE FOR
DETAILS.
29
NEW UNFUSED DISCONNECT SWITCH FOR
ATS-1, REFER TO SINGLE LINE FOR DETAILS
30
30
ER
E-2
EXISTING ELECTRICAL ROOM AND
NEW WORK GENERATOR LAYOUT -
POWER AND SIGNALS -
ELECTRICAL
1st FLOOR PART PLAN
1E-2
SCALE: N.T.S.
FIRE STATION No.426
MMM Group Limited100 Commerce Valley Drive West
Thornhill, ON L3T 0A1
t. 905-882-1100
f. 905-882-0055
www.mmm.ca
1 2016/08/18 Issued For 75% Client Review
2 2016/10/05 Issued For Permit & Tender
3 2016/11/28 Issued For Tender - Rev.1
1
NEW WORK NOTES:
2
3
ROUTING OF ALL SERVICES CONDUIT/DUCT ARE DIAGRAMMATIC. BE RESPONSIBLE TO CONFIRM EXACT
ROUTING AND TERMINATIONS ON SITE PRIOR TO FABRICATION OR ROUGH-IN AND INCLUDE FOR
REQUIRED OFFSETS, TRANSITIONS ETC. AS REQUIRED FOR A COMPLETE INSTALLATION.
ALL PENETRATIONS THROUGH WALLS AND CEILINGS SHALL BE FIRE SMOKE STOPPED WITH 3m FIRE STOP
MATERIAL. REFER TO SPECIFICATIONS FOR DETAILS.
PROVISION OF ALL PENETRATIONS AND OPENINGS 50mm (2") AND LESS IN SIZE SHALL BE THE RESPONSIBILITY OF
THE ELECTRICAL TRADE. REFER TO SPECIFICATIONS FOR DETAILS.
EXISTING ELECTRICAL ROOM -DEMOLITION3E-2
SCALE: N.T.S.
EXISTING ELECTRICAL ROOM - NEW WORK4E-2 SCALE: N.T.S.
ROOF PART PLAN
2E-2
SCALE: N.T.S.
1ALL EXISTING ELECTRICAL DEVICES ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
DEMOLITION NOTES:
2CAP OFF AND FIRE STOP ALL FLOOR/WALL CONDUIT STUB-UPS UPON REMOVAL OF FEEDERS.
NEW WORK NOTES:
BE RESPONSIBLE FOR EXACT PLACEMENT, INSTALLATION AND COORDINATION OF
CONNECTING SERVICES OF PROPOSED GENERATOR AFTER REVIEW OF SHOP DRAWINGS.
BE RESPONSIBLE FOR THE SET-UP, INSTALLATION AND CONNECTION OF LOAD BANK FOR
ON-SITE TESTING. CABLING AND LOAD BANK WILL BE SUPPLIED BY GENERATOR
MANUFACTURER. UPON COMPLETION OF SITE TESTING, DISCONNECT LOAD BANK AND
CABLING AND PREPARE FOR PICK UP BY GENERATOR MANUFACTURER.
1.
ROUTING OF ALL SERVICES ARE DIAGRAMMATIC. BE RESPONSIBLE TO CONFIRM EXACT
ROUTING AND TERMINATIONS ON SITE PRIOR TO FABRICATION OR ROUGH-IN AND
INCLUDE FOR REQUIRED OFFSETS, TRANSITIONS ETC. AS REQUIRED FOR A COMPLETE
INSTALLATION. CONDUCTOR TO BE OVERSIZED TO SUIT VOLTAGE DROP AS PER OESC.
2.
ALL PENETRATIONS THROUGH WALLS AND CEILINGS SHALL BE FIRE STOPPED WITH
3m FIRE STOP MATERIAL. REFER TO SPECIFICATIONS FOR DETAILS.
3.
PROVISION OF ALL PENETRATIONS AND OPENINGS AS REQUIRED.4.
COORDINATE TRENCHING / EXCAVATION OF SURFACES TO SUIT NEW GENERATOR
SERVICES AND INSTALLATION. REPLACE WITH NEW SURFACES AND MATCH BASE
BUILDING MATERIALS. CONFIRM AND MARK ON SITE ALL EXISTING SITE SERVICE
LOCATIONS WITHIN AREA OF INSTALLATION. REFER TO SPECIFICATION.
5.
AutoCAD SHX Text
DATE: 2016/07/20
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
PROJECT :
AutoCAD SHX Text
CLIENT : - CITY OF TORONTO
AutoCAD SHX Text
CONSULTANT
AutoCAD SHX Text
THIS DRAWING ARE NOT TO BE SCALED. REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL, ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFORE PROCEEDING WITH THE WORK. CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES AND REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST ASSUME FULL RESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS OR DAMAGES RESULTING FROM HIS WORK. THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BY AND IS THE PROPERTY OF THE ARCHITECT. THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITY FOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALL NOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROM THE SUPPLIED INFORMATION.
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
TRUE NORTH
AutoCAD SHX Text
CONSTRUCTON NORTH
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
REVIEWED BY:
AutoCAD SHX Text
140 LANDSDOWNE AVE.
AutoCAD SHX Text
TORONTO, ONTARIO, CANADA
AutoCAD SHX Text
- EMERGENCY SERVICES
AutoCAD SHX Text
Metro Hall City of Toronto
AutoCAD SHX Text
2nd floor, 55 John St.,
AutoCAD SHX Text
Toronto, Ontario M5V 3C6
AutoCAD SHX Text
CLIENT
AutoCAD SHX Text
ADDRESS :
AutoCAD SHX Text
1.
AutoCAD SHX Text
2016/07/28
AutoCAD SHX Text
Issued For 75%%%
AutoCAD SHX Text
MMM PROJECT No.: 1816292-002
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
Client Review
AutoCAD SHX Text
I.Z.
AutoCAD SHX Text
D.L.
50A-3P
45kVA,
600V-208/120V
DRY-TYPE
TRANSFORMER
"TX-1"
4#2/0+G, 53mmC
3#6+G, 27mmC
ENCLOSED BREAKER
EXISTING SPLITTER TO BE REPLACED
E
EXISTING
DISCONNECT
MAX FUSE
15A
E
EXISTING
DISCONNECT
/ STARTER
E
EXISTING
DISCONNECT
600V, 30A
EE
E
EXISTING
DISCONNECT
600V, 30A
E
E
E
E
EXISTING
DISCONNECT
600V, 30A
E
E
E
E
E
E
EXISTING
DISCONNECT
600V, 60A
E
EXISTING
DISCONNECT
/ STARTER
EXISTING
DISCONNECT
/ STARTER
EXISTING
DISCONNECT
/ STARTER
E
TRUCK
EXHAUST
EXISTING
EXHAUST
FAN
EF-7
EXISTING
CIRCULATION
PUMPS
EXISTING
MAKE-UP
AIR
UNIT
EXISTING
SUPPLY
AIR
UNIT
S-2
EXISTING
DOORS
1 & 2
EXISTING
SUPPLY
AIR
EXISTING
EF-1
EXISTING
ROOF TOP AIR
CONDITION
UNIT
EXISTING SPLITTER TO BE REPLACED
E
E
E
EXISTING
DISCONNECT
125/250V,
100A
E
EE
E
E
E
E
E
E
EXISTING
PANEL
EXISTING
DISCONNECT
240V, 100A
EXISTING
DISCONNECT
240V, 100A,
MAX FUSE
70A
E
EXISTING
LIGHTING
PANEL "B"
EXISTING
LIGHTING
PANEL "C"
EXISTING
LIGHTING
PANEL "A"
EXISTING
BR-1
EXISTING
MAIN FLOOR
NEW DRYER
EXISTING INCOMING
ELECTRICAL SERVICE
120/240V, 200A, 1Ø, 3W.
SEE NOTE 3.
M
EXISTING INCOMING
ELECTRICAL SERVICE
600/347V, 3 PHASE.
CONTRACTOR TO VERIFY.
R
D
E
EXISTING TORONTO HYDRO METER CABINET TO BE
RELOCATED TO SUIT NEW INSTALLATION.
COORDINATE/COMFIRM WITH TORONTO HYDRO FOR
ASSOCIATED WORK AND EXACT REQUIREMENT AND
PROVIDE ALL ASSOCIATED ACCESSORIES AS REQUIRED
TO FACILITATE THE NEW INSTALLATION COMPLETELY.
SERVICE ENTRANCE GROUNDING GRID
PROVIDED BY ELECTRICAL CONTRACTOR.
TYPICAL GROUND RODS FOR MAIN SERVICE ENTRANCE.
100kW
100KW/125kVA, 600/347V, 3PH, 4W, NEW OUTDOOR NATURAL GAS GENERATOR CONTAINERIZED IN
SKIN-TIGHT ACOUSTICAL ENCLOSURES . REFER TO SPECIFICATION FOR DETAILS.
1# 3/0 GROUND, GROUND ALTERNATOR "WYE POINT (NEUTRAL) OF GENERATOR IN
ACCORDANCE WITH CODE REQUIREMENTS AND MANUFACTURER RECOMMENDATIONS.
BONDING GENERATOR NEUTRAL TO THE FRAME AND GROUND OF THE GENERATOR IN
ACCORDANCE WITH CODE REQUIREMENTS.EPO
WP
CG
150A-3P
NEW 100A, 120/208V, 3Ø, 4W SHORE PANEL INCLUDED IN
GENERATOR ENCLOSURE.
4#4+G, 53mmC
D
NEW AUTOMATIC TRANSFER SWITCH
'ATS-1', 600/347V, 200A, 3PH, 4W
(4 POLE, SWITCHED NEUTRAL)
AUTOMATIC "OPEN TRANSITION"
TRANSFER SWITCH. I.C.=30kA RATED
4#2/0+G, 103mmC.
CONTROL WIRING FOR ATS START/STOP IN 53mmC" CONDUIT,
COORDINATE WITH MANUFACTURER RECOMMENDATION FOR
EXACT CABLING & CONDUIT REQUIREMENTS.
EPOGENERATOR
ANNUNCIATOR
PANEL,
SUPPLIED BY
GENERATOR
MANUFACTURER.
ENCLOSED BREAKER
60A-3P
ER
4#1/0+G, 53mmC.
4#1/0+G, 53mmC.
M
D
D
D
EXISTING THES
METER
D
EXISTING MAIN
SERVICE ENTRANCE
DISCONNECT SWITCH
120/240V, 200A
200A-3P
F@100A
SEE NOTE 4
ER
REPLACE EXISTING SPLITTER
WITH NEW 600V, 225A, 3Ø, 4W
SPLITTER AND RECONNECT
EXISTING LOAD TO NEW
SPLITTER BALANCED AND
EVENLY AMONG PHASES.
200A-3P
U/F
BE RESPONSIBLE TO CONFIRM AND VALIDATE
ELECTRICAL CHARACTERISTICS FOR ALL EXISTING
DOWNSTREAM LOADS AND REPORT BACK TO
CONSULTANT ANY CONCERNS FOR 230/240V LOADS
RECONNECTIONS TO NEW 208V DISTRIBUTION.
GENERAL NOTES:
1
2ENSURE ELECTRICAL EQUIPMENT ARE BONDED TO GROUND PROPERLY AS PER OESC CODE.
3
COORDINATE/CONFIRM WITH TORONTO HYDRO FOR THE ASSOCIATED WORK OF REMOVING
THE EXISTING 120/240V HYDRO ELECTRICAL INCOMING SERVICES AND ITS ASSOCIATED
ACCESSORIES AND MAKE IT SAFE AS PER OESC.
4
6
EXISTING DISTRIBUTION SYSTEM SHOWN IS DIAGRAMMATIC TO SHOW THE DESIGN INTENT.
BE RESPONSIBLE TO CONFIRM/VERIFY IT PRIOR TO FABRICATION OR ROUGH-IN AND ENSURE
ALL EXISTING LOAD IS PICKED UP AND CONNECTED BALANCED BY THE NEW ELECTRICAL
DISTRIBUTION SYSTEM AND PROVIDE ALL ASSOCIATED ACCESSORIES AS REQUIRED TO
FACILITATE THE NEW INSTALLATION COMPLETELY.
5
COORDINATE WITH TORONTO HYDRO FOR THE ASSOCIATED WORK OF RELOCATING AND
RECONNECTING EXISTING 600/347V, 3 PHASE SERVICE ENTRANCE EQUIPMENT. ENSURE SERVICE
NEUTRAL IS GROUNDED AND BONDED PROPERLY AT NEW MAIN SERVICE ENTRANCE DISCONNECT
SWITCH AS PER OESC. PROVIDE ALL ASSOCIATED ACCESSORIES AS REQUIRED TO FACILITATE THE
NEW INSTALLATION. ALL THIS WORK TO BE PAID FOR FROM CASH ALLOWANCE.
VERIFY EXISTING ELECTRICAL EQUIPMENT INFORMATION SHOWN ON DRAWING WITH SITE
CONDITION PRIOR TO START OF WORK.
7
CONDUCTOR TO BE OVERSIZED TO SUIT VOLTAGE DROP AS PER OESC.
RECONNECT EXISTING TORONTO HYDRO SERVICE
ENTRANCE CABLE TO THE NEW SERVICE ENTRANCE
DISCONNECT SWITCH AT NEW LOCATION.
EXISTING MAIN SERVICE DISCONNECT SWITCH TO BE
REPLACED WITH NEW 600V, 200A, 3Ø, 4W MAIN SERVICE
ENTRANCE RATED DISCONNECT SWITCH WITH NEW
100A FUSE INSTALLED TO ACCOMMODATE THE
INCOMING TORONTO HYDRO SERVICE NEUTRAL AND
ENSURE EQUIPMENT IS GROUNDED AND BONDED
PROPERLY AS PER OESC CODE REQUIREMENTS. THE
NEW DISCONNECT SWITCH WILL BE RELOCATED TO
SUIT NEW INSTALLATION.
ER
REPLACE EXISTING SPLITTER WITH NEW 120/208V, 225A, 3Ø, 4W SPLITTER. RECONNECT ALL
EXISTING LOAD FEEDERS AND ENSURE ALL LOADS ARE CONNECTED AND EQUALLY BALANCED.
CONTROL WIRING FOR GENERATOR
ANNUNCIATOR PANEL IN 53mmC CONDUIT,
COORDINATE WITH GENERATOR
MANUFACTURER RECOMMENDATION FOR
EXACT REQUIREMENTS.
CONTROL WIRING FOR EPO BUTTON IN 53mmC
CONDUIT, COORDINATE WITH MANUFACTURER
RECOMMENDATION FOR EXACT REQUIREMENTS.
EXISTING OFFICE
GENERATOR BREAKER. COORDINATE WITH COORDINATION
STUDY AND MANUFACTURE RECOMMENDATION. UPDATE
DOWNSTREAM DISTRIBUTION SYSTEM AS REQUIRED TO SUIT
IN ACCORDANCE WITH CODE REQUIREMENTS.
EXISTING LOAD
EXISTING
DISCONNECT
125/250V,
100A
EXISTING
DISCONNECT
125/250V,
100A
SEE NOTE 1.
REGARDING TORONTO HYDRO ASSOCIATED WORK,
ALL CONTRACTOR COORDINATION WORK WITH
TORONTO HYDRO WILL BE PART OF BASE BID. ANY
DIRECT COSTS FROM TORONTO HYDRO TO BE PAID
BY THE CONTRACTOR THROUGH CASH ALLOWANCE
(NO MARK UP).
PROVIDE LOAD BANK BREAKER, REFER TO SPECIFICATION FOR DETAILS.
E-3
ELECTRICAL SINGLE LINE
DIAGRAM
FIRE STATION No.426
MMM Group Limited100 Commerce Valley Drive West
Thornhill, ON L3T 0A1
t. 905-882-1100
f. 905-882-0055
www.mmm.ca
1 2016/08/18 Issued For 75% Client Review
2 2016/10/05 Issued For Permit & Tender
3 2016/11/28 Issued For Tender - Rev.1
AutoCAD SHX Text
DATE: 2016/07/20
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
PROJECT :
AutoCAD SHX Text
CLIENT : - CITY OF TORONTO
AutoCAD SHX Text
CONSULTANT
AutoCAD SHX Text
THIS DRAWING ARE NOT TO BE SCALED. REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL, ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFORE PROCEEDING WITH THE WORK. CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES AND REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST ASSUME FULL RESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS OR DAMAGES RESULTING FROM HIS WORK. THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BY AND IS THE PROPERTY OF THE ARCHITECT. THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITY FOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALL NOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROM THE SUPPLIED INFORMATION.
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
TRUE NORTH
AutoCAD SHX Text
CONSTRUCTON NORTH
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
REVIEWED BY:
AutoCAD SHX Text
140 LANDSDOWNE AVE.
AutoCAD SHX Text
TORONTO, ONTARIO, CANADA
AutoCAD SHX Text
- EMERGENCY SERVICES
AutoCAD SHX Text
Metro Hall City of Toronto
AutoCAD SHX Text
2nd floor, 55 John St.,
AutoCAD SHX Text
Toronto, Ontario M5V 3C6
AutoCAD SHX Text
CLIENT
AutoCAD SHX Text
ADDRESS :
AutoCAD SHX Text
1.
AutoCAD SHX Text
2016/07/28
AutoCAD SHX Text
Issued For 75%%%
AutoCAD SHX Text
MMM PROJECT No.: 1816292-002
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
No.
AutoCAD SHX Text
Date
AutoCAD SHX Text
Description
AutoCAD SHX Text
Client Review
AutoCAD SHX Text
I.Z.
AutoCAD SHX Text
D.L.
LANDSDOWNE AVE.
EXISTING FIRE HALL #426
(140 LANDSDOWNE AVE.)
EXISTING SOLAR
PANEL
EXISTING
MECHANICAL
EQUIPMENT
EXISTING GAS PIPE
ON ROOF
APPROXIMATE LOCATION OF EXISTING
GAS METER AND REGULATOR
ASSEMBLY TO BE REMOVED
NEW GAS METER AND REGULATOR
ASSEMBLY
APPROXIMATE LOCATION OF NEW
OUTDOOR NATURAL GAS GENERATOR
ON ROOF OF BUILDING.
REFER TO ELECTRICAL & STRUCTURAL
PLANS FOR FINAL LOCATION.
EXISTING GAS LINE UP TO
ROOF MOUTED MUA UNIT
RECONNECT TO EXISTING
ABOVE ROOF
RELOCATED POSITION FOR
PIPING TO SOLAR PANEL
RECONNECT TO THE EXISTING
RETAINED PIPES AT SOLAR PANEL
REMOVE EXISTING PIPING AND
SUPPORTS.
* RETAIN PIPING AND
SUPPORTS FOR RELOCATION
* PROVIDE ADDITIONAL PIPING
AND SUPPORTS AS REQUIRED
TO SUIT NEW ROUTING
* REINSULATE AS REQUIRED
EQUAL TO EXISTING
32mm NEW GAS LINE UP TO
ROOF MOUNTED GENERATOR
THE FOLLOWING IS A PROPOSED SEQUENCE IMPLEMENTATION, INTENDED TO
GIVE A DIAGRAMMATIC OVERVIEW OF THE PROPOSED SEQUENCE OF
INSTALLATION FOR THIS PROJECT. BE RESPONSIBLE TO CONFIRM THIS
SEQUENCE, MAKE THE REQUIRED MODIFICATION TO SUIT THE ANOMALIES OF
THIS BUILDING AND COORDINATE THIS WHEN PREPARING THE MASTER
CONSTRUCTION SCHEDULE FOR THE IMPLEMENTATION OF ALL WORK
ASSOCIATED WITH THIS PROJECT.
PROPOSED SEQUENCE OF IMPLEMENTATION
1. MECHANICAL:
1.1. PERFORM ALL DEMOLITION WORK ONCE NEW GENERATOR IS IN PLACE AS
EXISTING GENERATOR WILL BE USED TEMPORARILY UNTIL NEW
GENERATOR IS FULLY FUNCTIONAL.
1.2. PREPARE THE SHOP DRAWINGS FOR REQUIRED EQUIPMENT.
1.3. PROVIDE NEW GAS METER ASSEMBLY AND PIPING AS SHOWN.
2. WHEN ALL THE MECHANICAL SERVICES HAVE BEEN INSTALLED, COMPLETE
AND COMMISSIONED:
2.1. COMPLETE ALL REMAINING REMEDIAL WORK, INCLUDING PATCHING WORK,
FIRE STOPPING, CEILING INSTALLATIONS, PAINTING, ETC. UPON
COMPLETION OF MECHANICAL SERVICES.
2.2. COMPLETE AS-BUILTS, OPERATIONS & MAINTENANCE MANUALS AND TURN
OVER TO CONSULTANT.
GAS LINE
DEMOLISHED
PIPE RISER DOWN
EXISTING WORK TO BE RETAINED
EXISTING WORK TO BE REMOVED AND/OR
D
E
G
PIPE RISER UP
PIPE RISER UP
EXISTING WORK TO BE RELOCATED
R
FLEXIBLE CONNECTOR
DRAWING LIST
DRAWING No. DESCRIPTION SCALE
As NotedM-1
BRANCH OFF BOTTOM OF MAIN
BRANCH OFF TOP OF MAIN
CHECK VALVE
VALVE
UNION
SITE PLAN AND DETAILS - MECHANICAL
PROJECT PROPOSED SEQUENCE
OF IMPLEMENTATION
GENERAL NOTES:
1 THIS DRAWING IS ISSUED TO SHOW SCOPE OF WORK ONLY. THE CONTRACTOR MUST
PERFORM A SITE INSPECTION (INCLUDING CEILING SPACES) DURING THE TENDER
PERIOD & ENSURE THAT ALL WORK THAT IS VISIBLE IS INCLUDED IN THE DEMOLITION
CONTRACT. ANY OTHER EXISTING SERVICES THAT PASS THROUGH THE RENOVATION
AREA (UNLESS OBSOLETE) ARE TO BE MAINTAINED AND/OR RELOCATED TO SUIT THE
SCOPE OF WORK.
2 ALL PENETRATIONS THROUGH WALLS AND CEILINGS MUST BE FIRE STOPPED WITH FIRE STOP
MATERIAL. REFER TO SPECIFICATIONS.
ROUTING OF SERVICES ARE DIAGRAMMATIC. BE RESPONSIBLE TO CONFIRM EXACT ROUTING
ON SITE PRIOR TO FABRICATION OR ROUGH-IN AND INCLUDE FOR ANY OFFSETS, TRANSITIONS,
ETC. AS REQUIRED FOR A COMPLETE INSTALLATION.
3
SUMMARY OF GAS ITEMS WITHIN BUILDING:
BOILERS - 2 @ 700 CFH
ROOF TOP UNIT - 1 @ 351 CFH
DOMESTIC HOT WATER HEATERS - 0
DOMESTIC 4 BURNER RANGE - 2 @ 60 CFH
BBQ - 1 @ 100 CFH
TOTAL EXISTING CONNECTED LOAD = 1971 CFH
NEW GENERATOR = 1090 CFH
NEW CONNECTED LOAD = 3061 CFH @ 2 PSI
2M-1
SCALE: N.T.S.
TO NEW GAS GENERATOR
ON ROOF(1090 CFH)
2#G
32ø
VALVE SHALL BE
COLORED "RED"
P.R.V.
G
~
EXISTING INCOMING GAS SERVICE
FOR A NEW CONNECTED LOAD OF
3061 CFH AT 2 PSI
EXISTING GAS PRV, METER
AND PIPING ASSEMBLY TO BE
REMOVED
CONNECT INTO
EXISTING SERVICE
~
GRADE
PROVIDE SIGNAGE STATING
"EMERGENCY GENERATOR
DO NOT SHUT OFF"
G
CONNECT TO THE
EXISTING GAS LINE
PROVIDE SIGNAGE STATING
"EMERGENCY GENERATOR
DO NOT SHUT OFF"
EMERGENCY
GENERATOR
NEW GAS METER ASSEMBLY
SECURED VALVE TYPICAL
ALONG PATH TO GENERATOR
EXISTING GAS LINE TO EXISTING
GAS FIRED EQUIPMENT WITH A
APPROXIMATE CONNECTED LOAD
OF 1971 CFH
32ø32ø
38ø
38ø
32ø
PRV TO REDUCE 1971 CFH
FROM 2 PSI TO 7" W.C.
PRV TO REDUCE 1090 CFH
FROM 2 PSI TO 11" W.C.
32ø
2#G
2#G
PIPING TO BE ROUTED UP THE
EXTERIOR WALL. LOCATE GAS
LINE BESIDE THE EXISTING GAS
LINE.
M-1
FIRE STATION
No.426
1 2016/08/18 Issued For 75% Client Review
2 2016/09/21 Issued For Permit & Tender
3 2016/11/28 Issued For Tender "Rev. 1"
1
M-1
SCALE: N.T.S.
GENERAL NOTES AND SPECIFICATIONS
A. GENERAL1. CHECK DIMENSIONS ON STRUCTURAL DRAWINGS AGAINST ELECTRICAL / MECHNICAL DRAWINGS AND
EXISTING SITE CONDITIONS. REPORT ANY INCONSISTENCIES TO CONSULTANT BEFORE PROCEEDING WITHTHE WORK.
2. REFER TO ELECTRICAL AND MECHANICAL DRAWINGS FOR LOCATION AND SIZE OF CONDUITS AND GASPIPING.
3. DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE. ELEVATIONS ARE IN METRES UNLESS NOTEDOTHERWISE.
4. PERFORM DESIGN, FABRICATION AND PLACEMENT AND/OR ERECTION IN ACCORDANCE WITHREQUIREMENTS OF REFERENCE STANDARDS, REGULATORY AUTHORITIES AND CONTRACT DOCUMENTS.BE AWARE THAT THE MORE SEVERE REQUIREMENTS OF CONTRACT DOCUMENTS TAKE PRECEDENCEOVER REQUIREMENTS OF REFERENCE STANDARDS AND REGULATORY AUTHORITIES.
5. DO NOT SCALE DRAWINGS.
B. DESIGN1. STRUCTURAL DESIGN IS IN ACCORDANCE WITH PART 4 OBC 2012.2. DESIGN DATA (OBC 2012):
SEISMIC: Ie=1.5Sa(0.2)=0.22, Sa(0.5)=0.13, Sa(1.0)=0.067, Sa(2.0)=0.021PGA=0.12SITE CLASS = DFa=1.3, Fv=1.4
LIVE LOADS DUE TO SNOW AND RAIN: - GROUND SNOW LOAD: 0.90 kPa- 24 HOURS RAIN LOAD: 0.95 kPa
C. CONSTRUCTION PHASING1. COORDINATE WITH ELECTRICAL, MECHANICAL AND GENERAL TRADES WORK TO DETERMINE REQUIRED
SEQUENCE OF CONSTRUCTION FOR WORK SHOWN ON STRUCTURAL DRAWINGS.
D. REFERENCE STANDARDS & PUBLICATIONS1. CAST-IN-PLACE CONCRETE, CONCRETE FORMWORK AND CONCRETE REINFORCEMENT:
1) CSA STANDARD A23.1, CONCRETE MATERIALS AND METHODS OF CONCRETE CONSTRUCTION.2) CSA STANDARD A23.2, METHODS OF TEST AND STANDARD PRACTICES FOR CONCRETE.3) CSA STANDARD A23.3, DESIGN OF CONCRETE STRUCTURES FOR BUILDINGS.4) ADD CSA-S269.3 (R1998) CONCRETE FORMWORK.5) ACI 117 STANDARD SPECIFICATIONS FOR TOLERANCES FOR CONCRETE CONSTRUCTION AND MATERIALS.6) ACI 315, DETAILS AND DETAILING OF CONCRETE REINFORCEMENT.7) ACI 315R, MANUAL OF ENGINEERING AND PLACING DRAWINGS FOR REINFORCED CONCRETE STRUCTURES.8) RSIC-2004 REINFORCING STEEL MANUAL OF STANDARD PRACTICE.
2. STRUCTURAL STEEL:1) CAN/CSA STANDARD G-40.20/G-40.21, GENERAL REQUIREMENTS FOR ROLLED OR WELDED STRUCTURAL
QUALITY STEEL.2) CSA STANDARD S16.1-09, LIMIT STATES DESIGN OF STEEL STRUCTURES.3) CSA STANDARD W59-03, WELDED STEEL CONSTRUCTION (METAL ARC WELDING).4) CSA STANDARD W178.1 CERTIFICATION OF WELDING INSPECTION ORGANIZATIONS.5) CSA STANDARD W178.2 CERTIFICATION OF WELDING INSPECTORS.
E. SITE WORK1. DEMOLITION:
1) REMOVE EXISTING ROOFING, WATERPROOFING, STEEL DECK AS REQUIRED TO EXTEND EXISTING STEELCOLUMNS INDICATED ON DRAWINGS.
F. SHOP DRAWINGS AND SUBMITTALS1. STRUCTURAL STEEL:
1) SUBMIT SHOP DRAWINGS TO CONSULTANT FOR REVIEW BEFORE COMMENCING FABRICATION.2) PROFESSIONAL ENGINEER RESPONSIBLE FOR CONNECTION DESIGN MUST EITHER SEAL AND SIGN EACH
SHOP DRAWING SUBMITTED, OR SUBMIT A SEAL AND SIGNED LETTER AT COMMENCEMENT OF SHOPDRAWING PREPARATION CONFIRMING ASSUMPTION OF RESPONSIBILITY FOR COMPLIANCE OFCONNECTIONS WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.
3) SHOW SPLICE LOCATIONS AND DETAILS.2. REVIEW ALL SHOP DRAWINGS PRIOR TO SUBMISSION TO CONSULTANT. BY THIS REVIEW, CONTRACTOR
REPRESENTS TO HAVE DETERMINED AND VERIFIED ALL FIELD MEASUREMENTS, SITE CONDITIONS,MATERIALS, PRODUCT OR ACCESSORY, AND TO HAVE CHECKED AND COORDINATED EACH SHOP DRAWINGWITH THE REQUIREMENTS OF WORK AND OF CONTRACT DOCUMENTS.
3. CONFIRM CONTRACTOR'S REVIEW OF EACH SHOP DRAWING BY STAMP, DATE AND SIGNATURE OF ARESPONSIBLE PERSON. NOTIFY CONSULTANT IN WRITING AT TIME OF SUBMISSION OF ANY DEVIATIONS INSHOP DRAWINGS FROM REQUIREMENTS OF CONTRACT DOCUMENTS.
4. BE AWARE THAT CONSULTANT'S REVIEW OF SHOP DRAWINGS IS FOR CONFORMITY TO DESIGN CONCEPTAND FOR GENERAL ARRANGEMENT, AND THAT CONTRACTOR RETAINS RESPONSIBILITY FOR ERRORS ANDOMISSIONS IN SHOP DRAWINGS AND RESPONSIBILITY FOR MEETING ALL REQUIREMENTS OF CONTRACTDOCUMENTS.
5. MAKE CHANGES IN SHOP DRAWINGS WHICH CONSULTANT MAY REQUIRE CONSISTENT WITH CONTRACTDOCUMENTS AND RESUBMIT UNLESS OTHERWISE DIRECTED BY CONSULTANT. WHEN RESUBMITTINGNOTIFY CONSULTANT IN WRITING OF REVIEWS OTHER THAN THOSE REQUESTED BY CONSULTANT.
6. DO NOT COMMENCE FABRICATION OF STRUCTURAL STEEL AND CONCRETE REINFORCEMENT UNTIL SHOPDRAWINGS HAVE BEEN REVIEWED AND CONSULTANTS' COMMENTS ARE INCORPORATED ON SHOPDRAWINGS ISSUED TO FABRICATING SHOP.
7. ALLOW 7 DAYS FOR RETURN OF SHOP DRAWINGS FROM CONSULTANTS.
G. INSPECTION AND TESTING1. PERFORM FIELD INSPECTIONS AND TESTING DESCRIBED BELOW BY AN INSPECTION AND TESTING
COMPANY, APPOINTED AND PAID FOR BY THE GENERAL CONTRACTOR.2. STRUCTURAL STEEL SHOP INSPECTION:
1) MATERIALS AND PAINT CONFORM TO CONTRACT DRAWINGS. MILL TEST REPORTS, PROPERLYCORRELATED TO THE MATERIALS, WILL BE ACCEPTED IN LIEU OF PHYSICAL TESTS OF STRUCTURALMATERIALS;
2) FABRICATION AND WELDING CONFORM TO CONTRACT DOCUMENTS AND DIMENSIONED SHOP DRAWINGS;3) SHOP SURFACE PREPARATION AND PAINTING CONFORM TO CONTRACT DRAWINGS;4) SURFACES INACCESSIBLE FOR SURFACE PREPARATION AND PAINTING AFTER ASSEMBLY ARE TREATED
BEFORE ASSEMBLY;5) INSPECTION AND TESTING COMPANY SHALL PERFORM NONDESTRUCTIVE TESTING OF WELDED
CONNECTIONS.3. FIELD INSPECTION AND TESTING OF STRUCTURAL STEEL:
1) STRUCTURAL STEEL ERECTION AND FIT-UP.2) STRUCTURAL STEEL WELDED JOINTS, INCLUDING SLAG REMOVAL.3) STRUCTURAL STEEL BOLTED CONNECTIONS.4) GENERAL INSPECTION OF FIELD CUTTING AND ALTERATIONS OF STRUCTURAL STEEL.5) GENERAL INSPECTION OF SHOP COATING TOUCH-UP OF STRUCTURAL STEEL.6) INSPECTION OF SURFACE PREPARATION AND COATING THICKNESS FOR ZINC PRIMER AND ZINC-RICH
PAINT.7) INSPECTION OF WELD AS PER NOTES I. 29 & 30.
H. CHEMICAL/ADHESIVE AND MECHANICAL ANCHORS1. CHEMICAL/ADHESIVE ANCHORS SHALL BE HILTI HY-200 MAX ADHESIVE SYSTEM, UNLESS NOTED
OTHERWISE.2. MECHANICAL ANCHORS SHALL BE HILTI KWIK-BOLT TZ, UNLESS NOTED OTHERWISE.3. WHERE DETAILS NOTE EPOXY GROUT, USE HILTI HY-200 MAX ADHESIVE SYSTEM.4. ALTERNATIVE ENGINEER APPROVED ANCHOR TYPES ARE PERMITTED. SUBMIT PROPOSED ANCHOR TYPE
AND MANUFACTURE'S PUBLISHED DATA INCLUDING LOAD CAPACITY, EDGE DISTANCE REQUIREMENTS ANDSPACING REQUIREMENTS FOR APPROVAL PRIOR TO USING ALTERNATIVE ANCHOR.
5. INSTALL ANCHORS IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS.
6. THE MANUFACTURER'S REPRESENTATIVE SHALL TRAIN INSTALLERS.
I. STRUCTURAL STEEL1. STRUCTURAL WIDE FLANGE SHAPES (W) shall CONFORM TO CAN/CSA-G40.20/G40.21 GRADE 350W OR ASTM
A992/A992M GRADE 50 (345 MPa).2. ANGLES, PLATES AND CHANNELS (L, C) shall CONFORM TO CAN/CSA-G40.20/G40.21 GRADE 300W.3. HOLLOW STRUCTURAL SECTIONS (HSS) shall CONFORM TO ASTM A500 GRADE C.4. ANCHOR RODS SHALL CONFORM TO ASTM F1554 GRADE 55 WELDABLE STEEL OR 300W THREADED ROD
CONFORMING TO CSA G40.21-M, UNLESS OTHERWISE NOTED OR SHOWN.5. STRUCTURAL BOLTS SHALL CONFORM TO ASTM A325M, NUTS shall CONFORM TO ASTM A563M. WASHERS
CONFORM TO ASTM F436M.6. NON-SHRINK GROUT SHALL HAVE A 35 MPa (5000 PSI) MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS.7. PROVIDE MINIMUM LENGTH OF BEARING OF 200 mm (8") FOR ALL STEEL BEAMS BEARING ON MASONRY AND
CONCRETE AND A MINIMUM OF 100 mm (4") ON STRUCTURAL STEEL, UNLESS OTHERWISE NOTED ORSHOWN.
8. CENTRE BEARING PLATES UNDER BEAMS UNLESS OTHERWISE NOTED OR SHOWN.9. BEARING PLATE DIMENSION GIVEN FIRST INDICATES SIDE PARALLEL TO BEAM WEB.10. NO STRUCTURAL STEEL SHALL BE CUT IN THE FIELD UNLESS REVIEWED AND APPROVED BY THE
CONSULTANT.11. ALL WELDS EXPOSED TO VIEW SHALL BE GROUND SMOOTH.12. IT IS THE INTENTION OF THESE DESIGN DOCUMENTS TO DELEGATE THE DESIGN OF ALL STRUCTURAL
STEEL CONNECTIONS TO A PROFESSIONAL ENGINEER, LICENSED IN THE PROVINCE OF ONTARIO. THISREQUIREMENT EXTENDS TO ALL CONNECTIONS, WITH THE EXCEPTION OF THOSE SPECIFICALLY FULLYDESIGNED IN THE DESIGN DOCUMENTS. IT IS ANTICIPATED THAT PROSPECTIVE STRUCTURAL STEELFABRICATORS WILL PERFORM NECESSARY INVESTIGATION TO DETERMINE THE FULL IMPACT OFCONNECTION CLEARANCE REQUIREMENTS, AS WELL AS THE POTENTIAL NECESSARY INTRODUCTION OFDOUBLER PLATES, CONTINUITY PLATES, AND/OR WEB FLANGE OR OTHER STIFFENERS PRIOR TOSUBMITTING ANY BID FOR THIS WORK.
13. PROVIDE SIGNED AND SEALED CALCULATIONS FOR ALL STRUCTURAL STEEL CONNECTION DESIGN.CALCULATIONS ARE TO BE SUBMITTED SIMULTANEOUSLY WITH CORRESPONDING SUBMITTAL.
14. FORCES INDICATED ARE FACTORED LOADS UNLESS OTHERWISE NOTED OR SHOWN. SUBSCRIPTS D, L. WAND Q REFER TO DEAD, LIVE, WIND AND EARTHQUAKE LOADS, RESPECTIVELY.
15. WHERE MOMENT CONNECTIONS ARE CALLED FOR BUT VALUES ARE NOT INDICATED, DESIGNCONNECTIONS FOR FULL MOMENT CAPACITY OF THE SMALLER MEMBER JOINED.
16. SPLICES SHALL BE DESIGNED TO DEVELOP THE FULL CAPACITY OF THE MEMBER AT THE POINT OF THESPLICE. MEMBERS SHALL NOT BE SPLICED AT POINTS OF MAXIMUM STRESS. NO SPLICES SHALL BE MADEUNLESS SHOWN ON THE DRAWINGS OR REVIEWED AND APPROVED BY THE CONSULTANT.
17. PROVIDE WELDED STIFFENER PLATES ON BOTH SIDES OF THE WEB OF BEAMS AT POINTS OFCONCENTRATED LOAD INCLUDING BEAMS SUPPORTING COLUMNS OR RUNNING OVER TOPS OF COLUMNS,UNLESS SHOWN BY DESIGN, THAT STIFFENERS ARE NOT REQUIRED.
18. CONNECT ALL COLUMNS TO THE BASE PLATES FOR THE LARGER OF THE FOLLOWING FORCES IN ADDITIONTO OTHER FORCES SHOWN:
1) AT BRACING FOR THE FACTORED HORIZONTAL COMPONENTS FROM THE BRACING.2) FOR 3% OF THE FACTORED VERTICAL COLUMN LOAD APPLIED HORIZONTALLY.
20. SHAPE AND SIZE GUSSET PLATES TO CLEAR ARCHITECTURAL FINISHES, MECHANICAL DUCTS, PIPES,ELEVATOR SHAFTS AND THE LIKE.
21. PROVIDE ALL ANCHOR RODS, CAST IN PLATES WITH ANCHORS, AND ANCHORS REQUIRED TO CONNECTSTRUCTURAL STEEL TO CAST-IN-PLACE CONCRETE.
22. LENGTH FOR ANCHOR RODS, STRAP ANCHORS AND SIMILAR DEVICES IS GIVEN FOR THE STRAIGHT LENGTHWITHOUT HOOK. PROVIDE A 75 mm (3") HOOK FOR ALL ANCHOR RODS AND A 50 mm (2") HOOK FOR ALLSTRAP ANCHORS, TYPICAL UNLESS NOTED OTHERWISE.
23. PROVIDE CAMBER TO BEAMS, GIRDERS AND TRUSSES AS SHOWN ON THE PLANS. CAMBERS SHOWN AREFOR ERECTED IN-PLACE CONDITION OF MEMBERS BEFORE INSTALLATION OF STEEL DECK. WHERECONCRETE ON STEEL DECK IS CALLED FOR, SCREED SLAB TO SUIT BEAM CAMBERS.
24. UNLESS OTHERWISE SHOWN ON THE DRAWINGS, TYPICAL SHEAR CONNECTIONS ARE TO BE DESIGNED ASFOLLOWS:
1) TYPICAL BEAM TO BEAM (NON-SPANDREL CONDITION) CONNECTIONS - ONE SIDED, TWO SIDED OR ENDPLATE CONNECTIONS.
2) TYPICAL BEAM TO SPANDREL BEAM CONNECTIONS - TWO SIDED OR END PLATE CONNECTIONS.3) TYPICAL BEAM TO COLUMN CONNECTIONS - TWO SIDED OR END PLATE CONNECTIONS.4) TYPICAL SPANDREL BEAM TO COLUMN CONNECTIONS - TWO SIDED CONNECTIONS.5) ALL OTHER CONDITIONS - TWO SIDED OR END PLATE CONNECTIONS.
NOTE: THE ADDITION OF OTHER CONNECTION FORCES (I.E. AXIAL FORCES) MAY RESULT IN DIFFERENTCONNECTIONS TO THOSE NOTED ABOVE.
25. ALL STRUCTURAL STEEL OUTSIDE OF THE BUILDING ENVELOPE SHALL BE HOT DIPPED GALVANIZED PERASTM A123 AND ALL FASTENERS AND HARDWARE SHALL BE HOT DIPPED GALVANIZED PER ASTM A153.
26. THE CAMBER OF STEEL MEMBERS SHALL BE VERIFIED IN THE SHOP AND THE FIELD. WHEN NO CAMBER ISINDICATED, TURN THE MEMBER NATURAL CAMBER UP.
27. HIGH STRENGTH BOLTS IN BEARING CONDITION SUPPORTING SIMPLE SPAN BEANS NOT SUBJECT TO AXIALLOADS MAY BE INSTALLED TO “SNUG TIGHT” CONDITION IF NORMAL, SHORT SLOTTED OR OVERSIZEDHOLES ARE USED. THE ENGINEER OF RECORD WILL BE THE ULTIMATE AUTHORITY IN THE USE OF “SNUGTIGHT” BOLTS.
28. WELDS SHOWN ON STRUCTURAL DRAWINGS ARE MINIMUM DESIGN REQUIREMENTS. THE FABRICATOR'SSHOP DRAWINGS SHALL REFLECT WELDS IN ACCORDANCE WITH CWS REQUIREMENTS.
29. FULL PENETRATION GROOVE WELDS SHALL BE INSPECTED BY ULTRASONIC TESTING.30. TWENTY- FIVE PERCENT OF THE WELDS SHALL BE INSPECTED AT RANDOM UNLESS NOTED OTHERWISE.31. UNLESS NOTED OTHERWISE ON THE DRAWINGS, GROOVE WELDS SHALL BE FULL PENETRATION.32. CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE SITE DURING THE TENDER TO IDENTIFY ANY
INTERFERENCE THAT WOULD PREVENT INSTALLATION OF STRUCTURAL STEEL. ANY INTERFERENCE SHALLTO BE RELOCATED AS REQUIRED SO AS TO PERMIT INSTALLATION OF THE STRUCTURAL STEEL.CONTRACTOR SHALL CONSULT MECHANICAL AND ELECTRICAL DRAWINGS AND SPECIFICATIONS TODETERMINE REQUIREMENTS PRIOR TO RELOCATING ANY INTERFERENCES.
J. RAILINGS1. ENGINEERED RAILING SYSTEM AND CONNECTION TO THE STRUCTURE SHALL BE DESIGNED BY AN
ENGINEER LICENSED IN THE PROVINCE OF ONTARIO.2. RAILING SYSTEM AND CONNECTIONS SHALL BE DESIGNED FOR LOADS INDICATED IN THE APPLICABLE
CODES.3. SUBMIT SIGNED AND SEALED SHOP DRAWINGS, INDICATING THE LOADING UTILIZED, PRIOR TO
FABRICATION.
K. STEEL STAIRS / LADDERS1. ENGINEERED STEEL STAIR / LADDER SYSTEM AND CONNECTIONS OF SAME TO THIS STRUCTURE SHALL BE
DESIGNED BY AN ENGINEER LICENSED IN THE PROVINCE OF ONTARIO.2. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY AN ENGINEER LICENSED IN THE PROVINCE OF
ONTARIO.3. STEEL STAIR SYSTEM AND CONNECTIONS SHALL BE DESIGNED FOR APPLICABLE LOADS AS INDICATED IN
THE BUILDING CODE.4. THE LOADS SHALL BE CLEARLY INDICATED ON SHOP DRAWINGS.5. SHOP DRAWINGS SHALL SHOW AND SPECIFY CONNECTIONS UTILIZED WITHIN THE STEEL STAIR SYSTEM AS
WELL AS CONNECTIONS TO AND LOADS IMPOSED UPON THE STRUCTURAL SYSTEM SHOWN ON THESEDRAWINGS.
6. SUBMIT SHOP DRAWINGS AND CALCULATIONS FOR REVIEW PRIOR TO FABRICATION.
Asbestos has been done in accordance with normal professional standard using the following Fisher Environmental Lab Method: Asbestos by PLM
(Polarized Light Microscope) F-26, Rev.2.2.
Fisher Environmental Laboratories (Lab ID #: 2745) is accredited by CALA (Canadian Association for Laboratory Accreditation Inc.) for asbestos analysis
by PLM.