Top Banner
EJECTOR EXPANSION REFRIGERATION SYSTEM SIJO K K S1 M-TECH M112 1
26

EJECTOR EXPANSION REFRIGERATION SYSTEM

Apr 15, 2017

Download

Engineering

sijo k k
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: EJECTOR EXPANSION REFRIGERATION SYSTEM

1

EJECTOR EXPANSION REFRIGERATION SYSTEM

S I J O K K

S1 M-TECH

M112

Page 2: EJECTOR EXPANSION REFRIGERATION SYSTEM

2

CONTENTS1. Introduction2. Ejector-expansion refrigeration cycle3. Working of EERS4. Constant area ejector5. working of constant area ejector6. System analysis7. Results and discussion8. Conclusion 9. References

Page 3: EJECTOR EXPANSION REFRIGERATION SYSTEM

3

INTRODUCTION•Refrigeration consumes major part of electricity

•70% systems using vapor compression

•Old and less efficient

•To overcome this difficulty high energy efficient technique should be selected

•Use of EERS improves system performance

•Decreases compressor power

•Increase COP

•Recover expansion process by isentropic expansion process

Page 4: EJECTOR EXPANSION REFRIGERATION SYSTEM

4

EJECTOR-EXPANSION REFRIGERATION CYCLE

Ejector-Expansion Refrigeration Cycle with its P-h diagram

Pc

Ps

PePb

Page 5: EJECTOR EXPANSION REFRIGERATION SYSTEM

5

EJECTOR-EXPANSION REFRIGERATION CYCLE(cond…)

•Main parts1) Compressor2) Condenser3) Two phase flow ejector4) Separator5) Expansion valve 6) Evaporator

•Modifications affects1. Expansion losses2. Suction pressure

Page 6: EJECTOR EXPANSION REFRIGERATION SYSTEM

6

WORKING OF EERC

•Compression

•Condensation

•Motive flow to ejector

•Liquid expansion in expansion device

•Evaporation (cooling)

•Secondary flow

•Mixing of flows

•Finally reaches the separator

Page 7: EJECTOR EXPANSION REFRIGERATION SYSTEM

7

CONSTANT AREA EJECTOR

Constant-area mixing ejector. a) Schematic diagram b) Pressure profile c) Velocity profile.

Page 8: EJECTOR EXPANSION REFRIGERATION SYSTEM

8

CONSTANT AREA EJECTOR

•Main parts are1. Motive nozzle

2. Suction chamber

3. Suction nozzle

4. Constant area mixing section

5. Diffuser

Page 9: EJECTOR EXPANSION REFRIGERATION SYSTEM

9

WORKING OF CONSTANT AREA EJECTOR

•Primary flow expansion in motive nozzle (P1b=Pb < Peva)

•Secondary flow expansion to pressure (P2b=Pb)

•Mixed together to a pressure (P3m > Pb)

•Choke wave take place

•Pressure increases and velocity reduces

•Further increase of pressure in diffuser (Psep )

•Intermediate pressure

Page 10: EJECTOR EXPANSION REFRIGERATION SYSTEM

10

WORKING OF CONSTANT AREA EJECTOR

Page 11: EJECTOR EXPANSION REFRIGERATION SYSTEM

11

SYSTEM ANALYSIS

•Based on conservation of mass, energy and momentum

•Major assumptions area) Neglect the pressure drops in tubes ,cooler and evaporator

b) Steady state 1D flow

c) No heat loss to environment

d) Zero velocities at the inlet of both nozzles

e) Friction losses in nozzle and diffuser defined in isentropic efficiencies

f) Liquid vapor separator is 100% efficient

Page 12: EJECTOR EXPANSION REFRIGERATION SYSTEM

12

Ejector analysis•Recovers expansion losses

•Increases compressor suction pressure

•Analysis based on conservation equations of fluid particles in following sections

a. Motive nozzle

b. Suction nozzle

c. Mixing section

d. diffuser

Page 13: EJECTOR EXPANSION REFRIGERATION SYSTEM

13

Motive nozzle•From P-h diagram isentropic efficiency of nozzle

•ηmn = (h1b – h1)/ (h1b, is − h1)

•Velocity at nozzle exit

•Mass flux at exit

Page 14: EJECTOR EXPANSION REFRIGERATION SYSTEM

14

Motive nozzle•From conservation of mass area of motive stream at 1b

•Primary mass flow

•ω=ṁs / ṁp

Page 15: EJECTOR EXPANSION REFRIGERATION SYSTEM

15

Suction nozzle•The equations are

Page 16: EJECTOR EXPANSION REFRIGERATION SYSTEM

16

Constant area mixing section•From conservation of momentum Velocity after mixing calculated as

•Mass flux

•Applying conservation of energy, specific enthalpy given by

Page 17: EJECTOR EXPANSION REFRIGERATION SYSTEM

17

Diffuser •Specific enthalpy at diffuser exit

•Exit isentropic specific enthalpy

ηd is the isentropic efficiency of the diffuser

Page 18: EJECTOR EXPANSION REFRIGERATION SYSTEM

18

Performance characteristics of EERS•The cooling capacity is calculated as

•Compressor power

η com = (h 5is − h4 )/ (h5 – h4 )

•COP

Page 19: EJECTOR EXPANSION REFRIGERATION SYSTEM

19

Performance characteristics of EERS•Pressure lift

•Ejector efficiency

hch2hb ha

Page 20: EJECTOR EXPANSION REFRIGERATION SYSTEM

20

RESULTS AND DISCUSSION

•Effect of evaporation temperature ṁp ṁs Plift MF ω COP

Page 21: EJECTOR EXPANSION REFRIGERATION SYSTEM

21

Effect of evaporation temperature

Page 22: EJECTOR EXPANSION REFRIGERATION SYSTEM

22

Effect of condensation temperature

ṁp ṁs MF Plift ω COP

Page 23: EJECTOR EXPANSION REFRIGERATION SYSTEM

23

Effect of condensation temperature

Page 24: EJECTOR EXPANSION REFRIGERATION SYSTEM

24

CONCLUSION•Performance of EERS is evaluated by theoretical analysis

•COP increases with increase of evaporation temp

•Compressor work decreases with increase of evaporation temp

•COP decreases with increase of condensing temp

•Compressor increases with increase of condensing temp

Page 25: EJECTOR EXPANSION REFRIGERATION SYSTEM

25

REFERENCES1. Hassanain, M., Elgendy, E., Fatouh, M., Ejector expansion refrigeration system:

ejector design and performance evaluation, International Journal of Refrigeration (2015) .

2. Li Zhao , Xingyang Yang , Shuai Deng , Hailong Li, Zhixin Yu. Performance analysis of the ejector-expansion refrigeration cycle using zeotropic mixtures International journal of refrigeration(2015)

3. Rounak Sahni ., Ejector Expansion Refrigeration Systems . International Journal of Refrigeration (2015)

4. Ersoy, H. K., Sag, N. B., 2014. Preliminary experimental results on the R134a refrigeration system using a two-phase ejector as an expander. International Journal of Refrigeration. 43, 97-110.

Page 26: EJECTOR EXPANSION REFRIGERATION SYSTEM

26

REFERENCES

5. Hu, J., Shi, J., Liang, Y., Yang, Z., Chen, J., 2014. Numerical and experimental investigation on nozzle parameters for R410A ejector air conditioning system. International Journal of Refrigeration 40, 338-346.

6. Chaiwongsa, P., Wongwises, S., 2007. Effect of throat diameters of the ejector on the performance of the refrigeration cycle using a two- phase ejector as an expansion device. International Journal of Refrigeration 30, 601- 608.

7. Bilir, N., Ersoy, H., 2009. Performance improvement of the vapor compression refrigeration cycle by a two-phase constant area ejector. International Journal of Energy Research 33, 469–480.

8. Nehdi, E., Kairouani, L., Bouzaina, M., 2007. Performance analysis of the vapor compression cycle using ejector as an expander. International Journal of Energy Research 31, 364–375.