EC centrifugal module - RadiPac backward curved, single inlet in cube design K3G630-AS05-01 ebm-papst Mulfingen GmbH & Co. KG Bachmühle 2 · D-74673 Mulfingen Phone +49 7938 81-0 Fax +49 7938 81-110 [email protected]www.ebmpapst.com Limited partnership · Headquarters Mulfingen County court Stuttgart · HRA 590344 General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen County court Stuttgart · HRB 590142 Nominal data Type K3G630-AS05-01 Motor M3G200-QA Phase 3~ Nominal voltage VAC 400 Nominal voltage range VAC 380 .. 480 Frequency Hz 50/60 Type of data definition ml Speed min -1 1850 Power input W 11000 Current draw A 17 Min. ambient temperature °C -40 Max. ambient temperature °C +40 ml = Max. load · me = Max. efficiency · fa = Running at free air · cs = Customer specs · cu = Customer unit Subject to alterations Data according to ErP directive Installation category A Efficiency category Static Variable speed drive Yes Specific ratio * 1.02 * Specific ratio = 1 + p fs / 100 000 Pa Actual Request 2013 Request 2015 Overall efficiency η es 63.2 58 62 Efficiency grade N 62.7 58 62 Power input P ed kW 11.07 Air flow q v m³/h 16720 Pressure increase p fs Pa 1447 Speed n min -1 1840 Data definition with optimum efficiency. Item no. 51807-5-9980 · Revision 79127 · Release 2013-03-27 · Page 1 / 5 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
5
Embed
EC centrifugal module - RadiPac - ebmpapst Denmark€¦ · Actual Request 2013 Request 2015 ... EC centrifugal module - RadiPac backward curved, single inlet in cube design K3G630-AS05-01
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
EC centrifugal module - RadiPacbackward curved, single inlet
General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen
County court Stuttgart · HRB 590142
Nominal data
Type K3G630-AS05-01
Motor M3G200-QA
Phase 3~
Nominal voltage VAC 400
Nominal voltage range VAC 380 .. 480
Frequency Hz 50/60
Type of data definition ml
Speed min-1 1850
Power input W 11000
Current draw A 17
Min. ambient temperature °C -40
Max. ambient temperature °C +40ml = Max. load · me = Max. efficiency · fa = Running at free air · cs = Customer specs · cu = Customer unitSubject to alterations
Data according to ErP directive
Installation category A
Efficiency category Static
Variable speed drive Yes
Specific ratio* 1.02* Specific ratio = 1 + pfs / 100 000 Pa
Actual Request 2013 Request 2015
Overall efficiency ηes 63.2 58 62
Efficiency grade N 62.7 58 62
Power input Ped kW 11.07
Air flow qv m³/h 16720
Pressure increase pfs Pa 1447
Speed n min-1 1840Data definition with optimum efficiency.
KL 2 1 NO Status relay, floating status contact; normally open; make for failure
KL2 2 COM Status relay; floating status contact; changeover contact; common connection; contact rating 250 VAC / 2A (AC1)
KL2 3 NC Status relay, floating status contact; break for failure
KL 3 1 RSA Bus connection RS485; RSA; MODBUS RTU
KL 3 2 RSB Bus connection RS485; RSB; MODBUS RTU
KL 3 3 / 10 GND Reference ground for control interface
KL 3 4 Ain1 U Analogue input 1 (set value); 0-10 V; Ri= 100 kΩ; parametrisable curves; only usable as alternative toinput Ain1 I
KL 3 5 + 10 V Fixed voltage output 10 VDC; + 10 V +/-3%; max. 10 mA; short circuit proof; power supply for ext.devices (e.g. potentiometer)
KL 3 6 Ain1 I Analogue input 1 (set value); 4-20 mA; Ri= 100 Ω; parametrisable curves; only usable as alternative toinput Ain1 U
KL 3 7 Din1 Digital input 1: enabling of electronics; enabling: open pin or applied voltage 5 to 50 VDC; disabling: bridgeto GND or applied voltage < 1 VDC; reset function: triggers software reset after a level change to <1 V
KL 3 8 Din2 Digital input 2: parameter set switch 1/2; according to EEPROM setting, the valid/used parameter set isselectable per BUS or per digital input DIN2. Parameter set 1: open pin or applied voltage 5 to 50 VDC;parameter set 2: bridge to GND or applied voltage < 1 VDC
KL 3 9 Din3 Digital input 3: Control characteristic of the integrated controller; according to EEPROM setting, the controlcharacteristic of the integrated controller is normally/inversely selectable per BUS or per digital input;normal: open pin or applied voltage 5 to 50 VDC (control deviation = actual sensor value - set value)inverse: bridge to GND or applied voltage < 1 VDC (control deviation = set value - actual sensor value)
KL 3 11 Ain2 U Analogue input 2; actual sensor value 0-10 V; Ri= 100 kΩ; parametrisable curve; only usable asalternative to input Ain2 I
KL 3 12 + 20 V Fixed voltage output 20 VDC; + 20V +25/-10%; max. 50 mA; short circuit proof; supply voltage for ext.devices (e.g. sensors)
KL 3 13 Ain2 I Analogue input 2; actual sensor value 4-20 mA; Ri= 100 Ω; parametrisable curve; only usable asalternative to input Ain2 U
KL 3 14 Aout Analogue output 0-10 V; max. 5 mA; output of the actual motor control factor (output voltage of electronics)/of the actual motor speed. Parametrisable curve.
EC centrifugal module - RadiPacbackward curved, single inlet
in cube design
K3G630-AS05-01
Charts: Air flow 50 Hz
pfs @ rho=1,2 kg/m³
qv [m³/h]25.00020.00015.00010.0005.0000
qv [CFM]14.00012.00010.0008.0006.0004.0002.0000
pfs
[Pa]
2.100
2.000
1.900
1.800
1.700
1.600
1.500
1.400
1.300
1.200
1.100
1.000
900
800
700
600
500
400
300
200
100
0
pfs
[InH
2O]
8
7,5
7
6,5
6
5,5
5
4,5
4
3,5
3
2,5
2
1,5
1
0,5
01
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Measurement: LU-142781
Air performance measured as per ISO 5801Installation category A. For detailedinformation on the measuring set-up, pleasecontact ebm-papst. Suction-side noiselevels: LwA measured as per ISO 13347 /LpA measured with 1m distance to fan axis.The values given are valid under themeasuring conditions mentioned above andmay vary according to the actual installationsituation. With any deviation from thestandard set-up, the specific values have tobe checked and reviewed with the unitinstalled.
Measured values
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
U
V
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
f
Hz
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
n
min-1
1850
1850
1850
1850
1600
1600
1600
1600
1300
1300
1300
1300
1000
1000
1000
1000
Ped
W
7459
10040
11000
9894
4888
6537
7253
6418
2622
3506
3890
3442
1193
1596
1771
1567
I
A
11.55
15.39
17.00
15.15
7.57
10.02
11.11
9.83
4.06
5.37
5.96
5.27
1.85
2.45
2.71
2.40
LpAin
dB(A)
93
88
83
85
90
85
80
81
84
79
75
76
78
73
68
69
LwAin
dB(A)
101
96
91
92
98
93
88
88
93
87
82
83
86
81
76
77
LwAout
dB(A)
107
100
96
98
103
97
93
94
98
92
88
89
91
85
81
82
qv
m3/h
25660
22170
16700
11130
22290
19235
14495
9635
18110
15625
11780
7830
13930
12020
9060
6020
pfs
Pa
0
800
1500
1800
0
616
1138
1352
0
406
752
893
0
240
445
528
U = Supply voltage · f = Frequency · n = Speed · Ped = Power input · I = Current draw · LpAin = Sound pressure level inlet side · LwAin = Sound power level inlet side · LwAout = Sound power level outlet side