EC centrifugal module - RadiPac backward curved, single inlet in cube design K3G710-AS06-01 ebm-papst Mulfingen GmbH & Co. KG Bachmühle 2 · D-74673 Mulfingen Phone +49 7938 81-0 Fax +49 7938 81-110 [email protected]www.ebmpapst.com Limited partnership · Headquarters Mulfingen County court Stuttgart · HRA 590344 General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen County court Stuttgart · HRB 590142 Nominal data Type K3G710-AS06-01 Motor M3G200-QA Phase 3~ Nominal voltage VAC 400 Nominal voltage range VAC 380 .. 480 Type of data definition ml State prelim. Speed min -1 1550 Power input W 11800 Current draw A 18 Min. ambient temperature °C -40 Max. ambient temperature °C +40 ml = Max. load · me = Max. efficiency · fa = Running at free air · cs = Customer specs · cu = Customer unit Subject to alterations Data according to ErP directive Installation category A Efficiency category Static Variable speed drive Yes Specific ratio * 1.01 * Specific ratio = 1 + p fs / 100 000 Pa Actual Request 2013 Request 2015 Overall efficiency η es 64.1 58.1 62.1 Efficiency grade N 63.4 58 62 Power input P ed kW 11.76 Air flow q v m³/h 20235 Pressure increase p fs Pa 1291 Speed n min -1 1545 Data definition with optimum efficiency. Item no. 52067-5-9980 · Revision 79796 · Release 2013-03-27 · Page 1 / 5 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
EC centrifugal module - RadiPacbackward curved, single inlet
General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen
County court Stuttgart · HRB 590142
Nominal data
Type K3G710-AS06-01
Motor M3G200-QA
Phase 3~
Nominal voltage VAC 400
Nominal voltage range VAC 380 .. 480
Type of data definition ml
State prelim.
Speed min-1 1550
Power input W 11800
Current draw A 18
Min. ambient temperature °C -40
Max. ambient temperature °C +40ml = Max. load · me = Max. efficiency · fa = Running at free air · cs = Customer specs · cu = Customer unitSubject to alterations
Data according to ErP directive
Installation category A
Efficiency category Static
Variable speed drive Yes
Specific ratio* 1.01* Specific ratio = 1 + pfs / 100 000 Pa
Actual Request 2013 Request 2015
Overall efficiency ηes 64.1 58.1 62.1
Efficiency grade N 63.4 58 62
Power input Ped kW 11.76
Air flow qv m³/h 20235
Pressure increase pfs Pa 1291
Speed n min-1 1545Data definition with optimum efficiency.
KL 2 1 NO Status relay, floating status contact; normally open; make for failure
KL2 2 COM Status relay; floating status contact; changeover contact; common connection; contact rating 250 VAC / 2A (AC1)
KL2 3 NC Status relay, floating status contact; break for failure
KL 3 1 RSA Bus connection RS485; RSA; MODBUS RTU
KL 3 2 RSB Bus connection RS485; RSB; MODBUS RTU
KL 3 3 / 10 GND Reference ground for control interface
KL 3 4 Ain1 U Analogue input 1 (set value); 0-10 V; Ri= 100 kΩ; parametrisable curves; only usable as alternative toinput Ain1 I
KL 3 5 + 10 V Fixed voltage output 10 VDC; + 10 V +/-3%; max. 10 mA; short circuit proof; power supply for ext.devices (e.g. potentiometer)
KL 3 6 Ain1 I Analogue input 1 (set value); 4-20 mA; Ri= 100 Ω; parametrisable curves; only usable as alternative toinput Ain1 U
KL 3 7 Din1 Digital input 1: enabling of electronics; enabling: open pin or applied voltage 5 to 50 VDC; disabling: bridgeto GND or applied voltage < 1 VDC; reset function: triggers software reset after a level change to <1 V
KL 3 8 Din2 Digital input 2: parameter set switch 1/2; according to EEPROM setting, the valid/used parameter set isselectable per BUS or per digital input DIN2. Parameter set 1: open pin or applied voltage 5 to 50 VDC;parameter set 2: bridge to GND or applied voltage < 1 VDC
KL 3 9 Din3 Digital input 3: Control characteristic of the integrated controller; according to EEPROM setting, the controlcharacteristic of the integrated controller is normally/inversely selectable per BUS or per digital input;normal: open pin or applied voltage 5 to 50 VDC (control deviation = actual sensor value - set value)inverse: bridge to GND or applied voltage < 1 VDC (control deviation = set value - actual sensor value)
KL 3 11 Ain2 U Analogue input 2; actual sensor value 0-10 V; Ri= 100 kΩ; parametrisable curve; only usable asalternative to input Ain2 I
KL 3 12 + 20 V Fixed voltage output 20 VDC; + 20V +25/-10%; max. 50 mA; short circuit proof; supply voltage for ext.devices (e.g. sensors)
KL 3 13 Ain2 I Analogue input 2; actual sensor value 4-20 mA; Ri= 100 Ω; parametrisable curve; only usable asalternative to input Ain2 U
KL 3 14 Aout Analogue output 0-10 V; max. 5 mA; output of the actual motor control factor (output voltage of electronics)/of the actual motor speed. Parametrisable curve.
EC centrifugal module - RadiPacbackward curved, single inlet
in cube design
K3G710-AS06-01
Charts: Air flow 50 Hz
pfs @ rho=1,2 kg/m³
qv [m³/h]30.00025.00020.00015.00010.0005.0000
qv [CFM]20.00015.00010.0005.0000
pfs
[Pa]
1.800
1.700
1.600
1.500
1.400
1.300
1.200
1.100
1.000
900
800
700
600
500
400
300
200
100
0
pfs
[InH
2O]
7
6,5
6
5,5
5
4,5
4
3,5
3
2,5
2
1,5
1
0,5
01
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Measurement: LU-143979
Air performance measured as per ISO 5801Installation category A. For detailedinformation on the measuring set-up, pleasecontact ebm-papst. Suction-side noiselevels: LwA measured as per ISO 13347 /LpA measured with 1m distance to fan axis.The values given are valid under themeasuring conditions mentioned above andmay vary according to the actual installationsituation. With any deviation from thestandard set-up, the specific values have tobe checked and reviewed with the unitinstalled.
Measured values
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
U
V
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
f
Hz
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
n
min-1
1550
1550
1550
1550
1300
1300
1300
1300
1050
1050
1050
1050
800
800
800
800
Ped
W
7632
10356
11800
11144
4459
6174
6987
6518
2350
3253
3682
3434
1039
1439
1628
1519
I
A
11.88
16.00
18.00
17.09
6.94
9.54
10.69
9.99
3.66
5.03
5.63
5.27
1.62
2.22
2.49
2.33
LpAin
dB(A)
91
85
80
84
87
81
76
79
81
75
71
74
74
68
64
67
LwAin
dB(A)
101
94
88
91
96
89
84
86
91
84
78
81
84
77
72
74
LwAout
dB(A)
105
99
94
95
101
94
89
91
95
89
84
85
89
82
77
78
qv
m3/h
32655
27865
21025
15440
27300
23435
17670
12910
22050
18930
14275
10430
16800
14420
10875
7945
pfs
Pa
0
700
1300
1600
0
508
920
1119
0
331
600
730
0
192
349
424
U = Supply voltage · f = Frequency · n = Speed · Ped = Power input · I = Current draw · LpAin = Sound pressure level inlet side · LwAin = Sound power level inlet side · LwAout = Sound power level outlet side