EasyIO FC20 User Reference v1.6 EasyIO FC 20 Series User Reference
EasyIO FC20 User Reference v1.6
EasyIO FC 20 Series User Reference
EasyIO FC20 User Reference v1.6
Document Change Log
1st April 2013 Document created. 13th July 2013 Software configurations added. 27th Sept 2014 FC now support pulse input. 6th June 2015 Serial address image. Serial Port settings explanations.
17th
Jan 2018 Updated disclaimer and support channel emails addresses Removed Sedona Workbench installation.
EasyIO FC20 User Reference v1.6
Disclaimer Confidentiality Notice
The information contained in this document is confidential information of EasyIO Holdings Pte Ltd. Such information and the software described herein, is furnished under a license agreement and may be used only in accordance with that agreement. The information contained in this document is provided solely for use by EasyIO Holdings Pte Ltd employees, licensees, and system owners; and, except as permitted under the below copyright notice, is not to be released to, or reproduced for, anyone else. While every effort has been made to assure the accuracy of this document, EasyIO Holdings Pte Ltd is not responsible for damages of any kind, including without limitation consequential damages, arising from the application of the information contained herein. Information and specifications published here are current as of the date of this publication and are subject to change without notice. The latest product specifications can be found by contacting our corporate headquarters or support channel. Trademark Notice EasyIO logo are registered trademarks of EasyIO Holdings Pte Ltd. CPT Tool is by Online Tools Inc. BACnet and ASHRAE are registered trademarks of American Society of Heating, Refrigerating and Air- Conditioning Engineers. All other product names and services, mentioned in this publication, that are known to be trademarks, registered trademarks, or service marks are the property of their respective owners. Copyright and Patent Notice This document may not, in whole or in part, be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form without prior written consent from EasyIO Holdings Pte Ltd Copyright © 2017 EasyIO Holdings Pte Ltd. All rights reserved
Disclaimer
The material in this manual is for information purposes only. The contents and the product it describes are subject to change without notice. EasyIO Holdings Pte Ltd makes no representations or warranties with respect to this manual. In no event shall EasyIO Holdings Pte Ltd be liable for any damages, direct or incidental, arising out of or related to the use of this manual. EasyIO Holdings Pte Ltd 101, Cecil Street #09-07 Tong Eng Building Singapore 069533 Worldwide and Asia Pacific Support : [email protected] Americas Support : [email protected] Europe Support : [email protected]
EasyIO FC20 User Reference v1.6
Federal Communication Commission Interference Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant
to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may cause harmful interference
to radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which can
be determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
• Consult the dealer or an experienced radio/TV technician for help.
Caution: Any changes or modifications not expressly approved by the party responsible for compliance
could void the user's authority to operate this equipment.
FCC Caution
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
FCC Radiation Exposure Statement
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment.
This equipment should be installed and operated with minimum distance 20cm between the radiator &
your body.
RF Exposure: A distance of 20 cm shall be maintained between the antenna and users, and the
transmitter module may not be co-located with any other transmitter or antenna.
EasyIO FC20 User Reference v1.6
Contents Introduction .................................................................................................................................................... 6
Hardware Configurations ................................................................................................................................ 7
Power supply Connection ........................................................................................................................... 7
RS485 Connection ....................................................................................................................................... 8
Jumpers Setting ........................................................................................................................................ 10
Digital Output Wiring Connection ............................................................................................................ 12
Universal Input Connection ...................................................................................................................... 13
Analog Output Connection ....................................................................................................................... 14
Buttons and Indications ................................................................................................................................ 15
Technical Support ......................................................................................................................................... 15
EasyIO FC20 User Reference v1.6
Introduction
The EasyIO FC Series is aimed at affordable ‘canned’ solutions for standalone applications, such as Roof Top Units, Fan Coils, AHU’s, package units etc. EasyIO FC20 Series controller comes with built in bootloader program. Built in bootloader program will enable user to upgrade firmware without sending back to factory. EasyIO FC20 do not have an Ethernet port. It only has RS 485 serial port. Firmware Upgrade is perform via direct serial connection to the controller.
EasyIO FC20 User Reference v1.6
Hardware Configurations
Power supply Connection Both AC and DC can be used for EasyIO FC-20 controller. Refer to electrical specification for the working
range. In order to avoid damage on the controller input/output devices and RS485 connection, use
individual power supply for each controller. If a single power supply is used, make sure controller power
supplies are connected with the same polarity.
Power Supply Connection
Multiple controllers share single transformer connection
EasyIO FC20 User Reference v1.6
RS485 Connection RS485 connection must be terminated at both ends with termination resistor, typically 120Ohms. It is
recommended to use shielded twisted pair wire (STP) for the wiring. Lightning protection circuit is
recommended to be installed at one end of the wiring. The controller should be wired in daisy chain
network topology as shown as image below. If wire branch can be avoided, keep it as short as possible,
and never connect more than one device to the wire branch.
Be careful if single power supply is used for all connected RS485 device, make sure all devices are
having the same ground connection. Make sure you are connecting the same wire for the same
terminal position, all “H” terminals connected to the same wire.
Daisy Chain Network Topology
RS485 Connection
EasyIO FC20 User Reference v1.6
RS 485 Serial port settings.
Every EasyIO FC controller comes with 2 RS -485 ports respectively D1 and D2. Below is a table explaining the details for each serial port configurations.
Port Number Protocol Communications supported Default Serial port settings Remarks
Port 1 ( D1+ , D1- )
Modbus OR BACnet Protocol selection is done via DIP switch 1. DIP 1 = OFF = Modbus RTU DIP 1 = ON = BACnet MSTP
Modbus Baud Rate : 19.2K Parity : even Data Bit : 8 (Not editable) Stop Bit : 1 BACnet Baud Rate : 19.2K
Port 1 is used to perform; - Firmware flashing. (FwTool.exe) - Virtual Device for program downloads. (FcVirtualDevice.exe) - Terminal mode for serial configurations editing. (FwTool.exe)
Port 2 ( D2+ , D2- )
Only supports Modbus RTU Protocol (Default). It supports Modbus Master as well if configure via FC Virtual Tool.
Modbus Baud Rate : 19.2K Parity : even Data Bit : 8 (Not editable) Stop Bit : 1
If port 2 is configured Modbus Master RTU (Default) Port 2 is used to perform;
- Virtual Device for program downloads. (FcVirtualDevice.exe)
EasyIO FC20 User Reference v1.6
Jumpers Setting
Below image shows the jumper setting for Universal Input, Analog Output, BACnet/Modbus Selection,
and the BACnet MSTP ID (1~127) or Modbus Serial ID (1~127).
The controller comes with BACnet and Modbus protocols selection. By default, Modbus protocol is
selected. To switch to BACnet protocol, toggle the ‘1’ of the dip switch to ON.
The remaining DIP switch ‘2’ ~ ‘8’ are for BACnet MSTP ID or Modbus Serial ID (address 0 is not available;
it will be set to 1) depending on DIP switch 1 selection.
Any changes to the DIP switch, a power cycle is needed.
EasyIO FC-20 Jumpers Setting
Image below show the DIP switch settings details.
For serial addressing it uses binary bit. The Least Significant Bit (LSB) in DIP 8. The Most Significant Bit
(MSB) is DIP 2.
The white the spot/white square represent the DIP switch in ON position.
EasyIO FC20 User Reference v1.6
EasyIO FC-20 enlarged DIP switch Setting
DIP switch number
Functions Remarks
1 Protocol Setting On = Bacnet MSTP Off = Modus RTU
2 Serial Address (Address 64) MSB 3 Serial Address (Address 32) 4 Serial Address (Address 16) 5 Serial Address (Address 8) 6 Serial Address (Address 4) 7 Serial Address (Address 2) 8 Serial Address (Address 1) LSB
117
EasyIO FC20 User Reference v1.6
Digital Output Wiring Connection
EasyIO FC-20 has four general purpose isolated digital output connections (relay output). Each relay
output able to drive up to 1A 30VDC/ 48VAC load.
It does not output voltage or current. It is a dry relay contact.
Digital Output Connection
EasyIO FC20 User Reference v1.6
Universal Input Connection
EasyIO FC-20 has twelve non-isolated universal inputs. The universal input supports three type of analog
signal i.e. resistance, voltage and current transmitter via hardware jumper and internal register settings:
a) Resistance – The working range of resistance is 0 – 300K Ohms. If the input is configured as
Thermistor type, the system provides 8 customizable temperature lookup tables for resistance to
temperature translation. The commonly used Thermistor like 10K, 10K with Shunt, 1K Balco and 1K
Platinum are all supported
b) Voltage – Two selection of working range 0 – 5V and 0 – 10V. The minimum input impedance of
voltage input is 1 Mega Ohm.
c) Current – Two selection of working ranges 0 – 20mA and 4 – 20mA. The current input impedance is
less than 25 Ohm.
d) Pulse Input – Only UI1, UI2, UI3 and UI4 are capable of receiving high speed pulse. Minimum on time
pulse is 25ms and minimum off time is 25ms. Refer to image below.
Universal Input Connection
EasyIO FC20 User Reference v1.6
Universal Input as Pulse Input specifications, Max 20Hz
Analog Output Connection
EasyIO FC-20 has four Analog Output connections. Each Analog Output can be configured to drive voltage
or current output via hardware jumper setting and internal register settings.
The working range for voltage is 0 – 10V and for current either 0 – 20mA or 4 – 20mA.
**We DO NOT recommend you to drive a relay directly from UO 0-10V mode as it is not design for it
and will damaged the AO. **
For voltage mode, the circuit able to drive load with a minimum impendence of 8,000 ohms. For current transmitter, the circuit able to drive load impedance up to 800 ohm which is ideal for long wire connection (up to 500 meter wire length).
Analog Output Connection
EasyIO FC20 User Reference v1.6
Buttons and Indications The controller will perform a hardware reset when the Reset Button is toggle. The Service button is used to activate the built-in bootloader program for software upgrade. Each digital output has a correspondence LED to indicate its current state.
Button and LED indications
LED Conditions Description
1 PWR PWR is used to indicate the presence of
24VAC power source, and internal power
2 ERR ERR is to indicate whenever there is
communication errors.
3
STS
STS is used to indicate the heartbeat of the
Microcontroller. The STS LED will blink at
1-second interval in normal operation
condition.
4 TXRX TXRX is used to indicate when there are
communication activities (Transmitting or
Receiving) on the communication port.
Technical Support For technical issue, please contact Worldwide and Asia Pacific Support : [email protected] Americas Support : [email protected] Europe Support : [email protected]