DP300E rev 8.3 1 Show information... Show information... • Navigation links: Move the cursor across the links and wait for the “hand” symbol • - then click left mouse key. • Click the APC logo link to jump back to the previous showed slide. • Click the left margin area to jump to the index (“Contents of the presentation”) • From the index -links, you may jump to any other subjects. • - use the APC-return logo to return to the index slide again .
136
Embed
DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
DP300E rev 8.3
1
Show information...Show information...
•Navigation links: Move the cursor across the links and wait for the “hand” symbol
•- then click left mouse key.
•Click the APC logo link to jump back to the previous showed slide.
•Click the left margin area to jump to the index (“Contents of the presentation”)
•From the index -links, you may jump to any other subjects.
• - use the APC-return logo to return to the index slide again .
DP300E rev 8.3
2
Silcon DP300ESilcon DP300EOn-lineOn-line
power protectionpower protection
APC presentationAPC presentation
DurationDuration::
DP300E rev 8.3
3
It’s a world of It’s a world of riskyrisky
businessbusiness
DP300E rev 8.3
4
... 5 minutes... 5 minutes
power down time power down time
in your company !in your company !
Imagine...Imagine...
Sort
• Is your business depending
on IT infrastructure?
• What is the cost of IT
downtime?
• Do you have a strategy for
securing up-time?
• Do you have a strategy for
power availability?
5 minutes 5 minutes power down timepower down time
DP300E rev 8.3
7
Application
ServersNT, UNIX, Novell etc.
File server
DP300EMainframe
Print
Web
Mail
DP100E
Gateway
Mini Computers DP10E
Windows 95 Windows NT OS/ and others
Enterprise IT InfrastructureEnterprise IT Infrastructure
Policy...Policy...Protection
of the critical
infrastructure
to ensure:
Up-time
Data safety
Availability
Efficiency
Productivity
Is this the situation…?Is this the situation…?
DP300E rev 8.3
8
Silcon DP300E SeriesSilcon DP300E Series
ContentsContents
of the of the presentationpresentation
Headlines:
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
9
Cost of down time
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
10
Fortune 1000 companies average outage across Fortune 1000 companies average outage across industries that lasts four hours costs….industries that lasts four hours costs….
Source: Find/SVP. Outages includes other than power failures
Cost of IT Power Down timeCost of IT Power Down timeCost of down time
DP300E rev 8.3
11
A typical company experiences A typical company experiences 99 outages per year, outages per year, resulting in annual losses of almost resulting in annual losses of almost
(excluding the cost of lost employee productivity). (excluding the cost of lost employee productivity).
Source: Find/SVP. Outages includes other than power failures
Cost of IT Power Down timeCost of IT Power Down time
Cost of down time
DP300E rev 8.3
12
Financial Brokerage operations
Financial Credit card operations
Media Pay-per-view
Retail Home shopping (TV)
Retail Home catalog sales
Transportation Airline reservations
Media Tele ticket sales
Transportation Package shipping
Finance ATM fees
Source: Dataquest, Perspective, Sept. 30, 1996
Average industry cost of down timeAverage industry cost of down time
$ 6,45 million
$ 2,6 million
$ 150.000
$ 113.000
$ 90.000
$ 89.500
$ 69.000
$ 28.000
$ 14.500
Cost of down time
DP300E rev 8.3
13
...97%...97% of power supply problems are coursed by of power supply problems are coursed by
power disturbances and low supply voltage.power disturbances and low supply voltage.
Source: National Power Laboratories USA
IT Power problems...IT Power problems...Cost of down time
DP300E rev 8.3
14
Did You Know?Did You Know?
Power problemsPower problems are the largest single cause of data loss,
5 times more frequent than viruses.
Power problemsPower problems are the second largest (to theft) cause of hardware loss.
Causes of data loss...Causes of data loss...
Source: Contingency Planning
Power problems are preventable...Power problems are preventable...
Cost of down time
DP300E rev 8.3
15
Industry Trends Drive Demand for...Industry Trends Drive Demand for...
Increased IT usage:
Internet Internet extranetsextranets EDIEDI E-commerceE-commerce DatabasesDatabases
7 x 24 hours up-timenetwork availability
Utility deregulation
Constant-Constant-Clean-Clean-
PowerPower
Cost of down time
DP300E rev 8.3
16
Did you realize that....Did you realize that....
Investment
“nines”
99.9%99.9% uptime per year...
means 525 minutes down time (8½ hours)
99.99%99.99% uptime per year...
means 52 minutes down time
99.999%99.999% uptime per year...
means 5 minutes down time
Cost of down time
DP300E rev 8.3
17
Users Require 7 x 24 hours Availability...Users Require 7 x 24 hours Availability...
“As businesses becomes more internationalized,
7 x 24 hours access to computer systems is a
requirement.
E-mail, group-ware, and similar types of services are
becoming business critical,
- and as a result, highly available systems are now
needed by many more organizations.”
IDC, Highly Available Systems Study
Cost of down time
DP300E rev 8.3
18
Information availability...Information availability...throughout the enterprise networkthroughout the enterprise network
The UPS must always be power-sizedpower-sized to supply the sum of loads in
UPS Load power factor
LO
AD
Load power-factor
Type of load
kVAkVA
Power factor
DP300E rev 8.3
40
Power sizing the UPS...Power sizing the UPS...
kVA-loadPower factor on mixed loads
Power factor
60 kVA/ kWPF =1
60 kVA/48 kW
PF = 0.8
Legacy UPS
system
?
DP300E
? 60 kVA60 kVA
UPS size = kVA load
Load 1: (8 kW / 0.8) = …..…….. 10 kVA
Load 2: (18 kW / 0.9) = ………. 20 kVA
Load 3: (30 kW / 1) = ……..…... 30 kVA
Sum of loads…... 56 kW…….……..……. Sum of loads…... 56 kW…….……..……. 60 kVA60 kVA
??70 kVA/ 56 kW
PF = 0.8
Legacy UPS system
?70kVA
UPS size = kVA/ kW load
DP300E rev 8.3
41
Power sizing the UPS...Power sizing the UPS...
kW-load
Load 1: = …………..…..….. 10 kW
Load 2: =…………..………. 20 kW
Load 3: = ………..……..….. 30 kW
Sum of loads…………………………. 60 kWSum of loads…………………………. 60 kW
Power factor
60 kVA/ kWPF =1
75 kVA/ 60 kW
PF = 0.8
Legacy UPS system
?DP300E
?75kVA
60 kW
UPS load = Loads/ 0.8
UPS load = Loads/ 1
Power factor on loads = 1
DP300E rev 8.3
42
Silcon DP300E - Silcon DP300E - Power sizing the UPSPower sizing the UPS
Power sizing the DP300E UPSPower sizing the DP300E UPS Calculate the sum of the UPS-load in kVA
Define highest phase load
Choose the DP300E having its full load output power equal to - or bigger than the load
Additional considerations..
• Overload capacity• Redundancy• …….
- see the Power Binderfor further details
Additional considerations..
• Overload capacity• Redundancy• …….
- see the Power Binderfor further details
Power factor
DP300E rev 8.3
43
Headlines:
Cost of down time
Efficiency
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Fans
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
EconomyEconomy with with
Silcon DP300ESilcon DP300E
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
44
Purchase PricePurchase Price
Installation CostsInstallation Costs
Operating CostsOperating Costs
Maintenance & RepairMaintenance & Repair
:The total Economy... The total Economy...
Economy
- for a UPS system includes:
DP300E rev 8.3
45
Mains repercussion consists of a mains current out of phase Mains repercussion consists of a mains current out of phase with the mains voltage and a distorted mains current.with the mains voltage and a distorted mains current.
Utilities demand a min. PF or require payment for the kVAhUtilities demand a min. PF or require payment for the kVAhinstead of the kWh.instead of the kWh.
Utilities demand distortion filters installed if other powerUtilities demand distortion filters installed if other powerconsumers are disturbed.consumers are disturbed.
Before comparing UPS prices it must be ensured theyBefore comparing UPS prices it must be ensured theyare equal with respect to mains repercussion:are equal with respect to mains repercussion:
Purchase PricePurchase Price
Economy
DP300E rev 8.3
46
Purchase PricePurchase Price
““To clean” the mains input current in a legacy UPSTo clean” the mains input current in a legacy UPS system with 6-pulse thyristor rectifier normally involves:system with 6-pulse thyristor rectifier normally involves:
Economy
A 12-pulse rectifier.A 12-pulse rectifier.
A harmonic filter.A harmonic filter.
A phase compensating unit.A phase compensating unit.
OPTION
OPTION
OPTION
Above might increase the Above might increase the purchase purchase
price for the UPS with up to 30%price for the UPS with up to 30%
UPS
Legacy UPSLegacy UPS
DP300E rev 8.3
47
The installation costs on the UPS mains input The installation costs on the UPS mains input side are determined by the prescribed input side are determined by the prescribed input fuse for the actual UPS.fuse for the actual UPS.
As a rule a DP300E requires an input fuse one As a rule a DP300E requires an input fuse one step smaller than a legacy UPS system without step smaller than a legacy UPS system without phase compensation. The installation costs are phase compensation. The installation costs are correspondingly lower.correspondingly lower.
High efficiency and unity power factor generally meanslower installation costs on the mains input side of the UPS:
Installation CostsInstallation Costs
Economy
DP300E rev 8.3
48
Annual cost savings with Annual cost savings with Silcon DP300ESilcon DP300E
Silcon DP300E compared to legacy UPS system…
– With harmonic filter
– Incl. cost of air conditioning
– Energy price: USD 0.18/kWh
Savings - pay back your UPS investment within 5 years
kVAkVA RatingRating
0
10000
20000
30000
40000
50000
60000
10 20 40 60 80 120 160 240 320 480
Savings USDSavings USD
USD 1472
USD 50 458
Economy
DP300E rev 8.3
49
Load power
UPS power losses
Air conditioning
Maintenance & repair
The operating costs come from:The operating costs come from:
Operating CostsOperating Costs
Economy
- Let´s focus the power loss and the savings...- Let´s focus the power loss and the savings...
DP300E rev 8.3
50
Power loss costs at 10 kVA...Power loss costs at 10 kVA...
Silcon DP310E
Period:
Efficiency:
Load:
8760 timer, 1 year
95%
100%
Air con. power 33%
Power price: USD 0.18/ kWh
UPS type: DP310E, 10kVA
Power losses = input - output power = (10/0.95)-10 = 0.53 kWCost of power loss: 0.53 x 8760 x 0,18 = USD 835
Cost of air con.: 835 x 0.33 = USD 275
Total to pay: 835 + 275 = USD 11101110
Economy
UPS power losses and air conditioning
have to be paid via the
electricity bill !
DP300E rev 8.3
51
Power loss costs at 10 kVA...Power loss costs at 10 kVA...
Legacy UPS
Period:
Efficiency:
Load:
8760 timer, 1 year
90%
100%
Air con. power 33%
Power price: USD 0.18/ kWh
UPS type: A legacy UPS, 10kVA
Power losses = input - output power = (10/0.9)-10 = 1.11 kW
Cost of power loss: 1.11 x 8760 x 0,18 = USD 1750
Cost of air con.: 1750 x 0.33 = USD 578
Total to pay: 1750 + 578 = USD 2328
A yearly saving of 2328 - 1110 = USD 1218
What about 3, 5 & 10 Years ????What about 3, 5 & 10 Years ????
Economy
The same calculation for a legacy UPS system having an efficiency of 90% results in a bill of
DP300E rev 8.3
52
Power loss costs at Power loss costs at 30 kVA30 kVA
Period:
Efficiency:
Load:
8760 timer, 1 year
96%
100%
Air con. power
33%
Power price: USD 0.18/ kWh
UPS type: DP300E, 30 kVA
8760 timer, 1 year
88%
100%
33%
USD 0.18/ kWh
A legacy UPS, 30 kVA
Legacy UPS power losses per year(30/0.88 - 30) kW x 8.760 hour x 0.18 USD x 1.33 air con = USD 8579
Silcon DP300E power losses per year(30/0.96 - 30) kW x 8.760 hour x 0.18 USD x 1.33 air con = USD 2621
Saving with DP300E = 8579 - 2621 = 5958 USD first year
Economy
DP300E rev 8.3
53
Power loss costs at Power loss costs at 160 kVA160 kVA
Period:
Efficiency:
Load:
8760 timer, 1 year
97%
100%
Air con. power 33%
Power price: USD 0.18/ kWh
UPS type: DP300E, 160 kVA
8760 timer, 1 year
91%
100%
33%
USD 0.18/ kWh
A legacy UPS, 160 kVA
Legacy UPS power losses per year(160/0.91 - 160) kW x 8.760 hour x 0.18 USD x 1.33 air con = USD 33186
Silcon DP300E power losses per year(160/0.97 - 160) kW x 8.760 hour x 0.18 USD x 1.33 air con = USD 10378
Saving with DP300E = 33186 - 10378 = 2280822808 USD first year
Economy
54
DP300E rev 8.3
Saving money with DP300ESaving money with DP300ECalculating actual costsCalculating actual costs
EconomyData:
Data: Units Enter value Comments
Energy cost USD/kWh 0,17
UPS data:
UPS power size kW 480
Competitor efficiency % 91 Nominal load operation
APC-Silcon efficiency % 97 Nominal load operation
Yearly energy cost to operate: UPS Aircon. Total
Competitor USD 70696 23330 94026
APC-Silcon DP300E USD 22108 7296 29403
Yearly energy cost savings USD 48588 16034 64623
All Warner model
Competitor system efficiency levels were obtained or calculated from commercially-available documentation. Competitor efficiency levels may be lower, i.e., if harmonic filter options are added.
55
DP300E rev 8.3
Saving money with DP300ESaving money with DP300ECalculate savings for a period of 10 years...Calculate savings for a period of 10 years...
Economy
DP300E rev 8.3
56
DP300EDP300E in parallel in parallel
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
57
DP300E series in parallel operation…DP300E series in parallel operation…
Parallel operationParallel operation
Parallel operation
1 2 3 4 5 6 7 8 9
- for expansion and redundancy or both.
DP300E rev 8.3
58
Expansion:Expansion:
- up to 9 units can be connected whenever you need more power.
Redundancy:Redundancy:
- to comply with strict requirements for uninterruptible operation
- oversized capacity
Expansion and RedundancyExpansion and Redundancy
Parallel operation
DP300E rev 8.3
59
Advanced Power ManagementAdvanced Power Management
Day 1
Day 2
Day 3
Parallel operation
Optimized redundancy Optimized redundancy operation by control operation by control system.system.
- only systems needed to supply the load are “active”.
- the load can be switched between the systems in a preprogrammed sequence.
Normal back-up time UPS: 5 to 10 minutes After 5 minutes - Diesel connects to DP300E Legacy UPS: 3-5 times over sizing Using DP300E series: no over sizing because:
– the sinusoidal input cause no distortion feed-back– no distortion of supply from tyristors– programmable soft start - step load from battery to
Benchmarking 10kVA systemsBenchmarking 10kVA systems
Product
Output power 10 kW / 10 kVA 8 kW / 12 kVA 8 kW / 12 kVA 8 kW / 12 kVA
Input voltage 208 208 208 208
Run Time (Full Load)
16 - 30 min. 7 - 18 min. 8 min. 8 - 10 min.
AC to AC efficiency 94.8% 89% 89% N/A
Power Factor 0.99 0.96 N/A 0.96
Acoustic noise 57dBA 57dBA 57dBA 57dBA
Dimensions (in)
High 55.12 28.10 36.00 62.00
Width 23.62 34.00 20.50 41.00
Depth 31.50 28.60 23.00 27.00
Weight 803 lbs. 920 lbs. 590 lbs. 702 lbs.
APCDP300E
Exide Powerware
Plus 18
MGEEPS 3000
LiebertUPStation S3
Technical data
- bypass 208/480V technical data
DP300E rev 8.3
116
Customer Customer references references
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
117
Insurance's - CodanInsurance's - Codan
Statement…
"As an Insurance company, we always rate security highly and therefore the security of the data in our computers must also be at the highest level”
Phrases from the statement:
– We protect all our business data with UPS equipment from Silcon.
– Before choosing Silcon we analysed 2 different suppliers.
– Several power-down situations has been
handled by the Silcon equipment in battery back-up mode or by controlled shut-down.
– In the end - it is a matter of finance
Codan Network - Mr. Lars M. Anker Section Leader, Denmark
Codan is one of Denmark’s biggest and best consolidated insurance companies.Codan has branches throughout the country and the concern has about 2000 employees. The Codan concern comprises banking as well as the insurance business.
Mr. Julian Baarwell, Lloyds Bank Engineering Manager
Lloyds Bank - London
Installation: 2.7 megawatt of Silcon UPS supplies
“Our original calculations showed
that we would save USD 70,000 in electricity
bills every year. That wasn’t right
DP300E rev 8.3
119
HitachiSemiconductor GmbH
One of the biggest supplier of electronic components in the world.
• 330.000 employees
• 6 billion USD in turn over
Peter NikonowitchHitachi, Tyskland
Semiconductors - Semiconductors - HITACHIHITACHI
Peter Nikonowitch says…
“Quality and safety comes first”
“10 milliseconds of power down is fatal for a whole production batch.
Beside the power security we have achieved essential savings in power consumption.
The technology and the environmental aspects we have achieved with the Silcon DP300E product has also been decisive”.
Customer references
DP300E rev 8.3
120
IT ServicesIT ServicesIBM Megacentre in Portsmouth UKIBM Megacentre in Portsmouth UK
IBM chose Silcon DP300E systems
IBM´s European and Middle East/African organizationhave put their trust in the safetyof their business data in the handsof APC/Silcon-UPS.
“If you have 6 Mega watt to back-upthe efficiency of the UPS system is essential.”
Chris Hayes, UPS ConsultantIT Infrastructure Services
Installation:
6 x DP3440 in parallelCapacity: 2 x 2.64 MWAdditional: 540 kW on vital systems12 minutes back-up at a load of 6 MW2.5 MW generator back-up
“We can’t afford any drops at all”
Customer references
SHELL, Danmark
“We power ensure the whole control center with the Silcon UPS systems.Most essential for us was the low heat emission - meaning lower installation and operation costs”.
SHELL refinery in Fredericia
ChemicalsChemicalsShellShell
Shell in Frederica has the most advanced control system in the world !
Customer references
DP300E rev 8.3
122
Air transportationAir transportationRDM LufthansaRDM Lufthansa
Statement…
“For RDM Lufthansa security and reliability are very important. With round-the-clock working and on-line access to RDM Lufthansa's host system in Germany, a power failure would have very serious financial consequences for the airline company”.
RDM Lufthansa, India
Customer references
“We simply can't afford to go down because of a
power cut.APC´s Silcon UPS systems gives us reliability and we
Statement…“We have always maintained the policy that one power cut per year is acceptable only. But since we have recently suffered three successive power cuts, we took the decision to install our own emergency power supply”.
The project:396 batteries - 11 tons - 10 minutes back-up time4 Silcon DP300E UPS systems1 Diesel generator - takes over after 30 seconds
Ove Vestergaard, Bankdata, Managing Director, …
”We have estimated that in 1996 alone, the Silcon installation has saved us some USD 4 million worth of losses by protecting critical infrastructure against power failures”
Erik Nielsen, Bankdata’s Installation Manager says...With the Silcon equipment we have installed some of the best electrical energy transformer systems with full back-up service.Bankdata can now be added to an already impressive client list.Bankdata is a data centre for 18 banks - employing 225 people - supporting banks with modern EDP systems.
Bankdata, Denmark
Silcon Technology
Customer references
DP300E rev 8.3
125
American ExpressLloyds Bank, UKBGZ PolandQingdao City Bank, ChinaCzech National BankPekao, PolandOrel Bank, RussiaCrediplus, PortugalUBS, SwitzerlandInter-Europa Bank, HungarySlovak Stock ExchangeRaiffeisenbank, GermanyGenerali, IrelandCitibank, DenmarkChase Manhattan Bank, USADen Danske Bank, DenmarkBank of New ZealandBloomberg, JapanBCA, IndonesiaDresdner Bank, Germany
National Bank of SlovakiaBank OTP, HungaryXiosbank, GreecePacific Finance,ThailandUlster Bank, IrelandMBNA Bank, UKSBG, SwitzerlandAlliance & Leicester, UKFINIbanco, PortugalJordan Gulf BankAllied Irish Bank, IrelandParibasSydbank, DenmarkDeutsche Bank, Germany
BankingBanking
Customer references
DP300E rev 8.3
126
Tele communicationTele communicationTelia - UKTelia - UK
””APC´s Silcon products are probably going APC´s Silcon products are probably going to the front in UPS support for to the front in UPS support for telecommunications”telecommunications”
“The Silcon UPS is like having a gentle giant
hidden in your cupboard that you can pull out when ever you fancy. So we are very happy with the Silcon
product".
Mr. Paul MulvenneFacilities Manager
"The main reason for choosing Silcon UPS systems over the
competitors considered, was the electronics.
The electronics gives advantages and behaves in a much more
structured way. This meets the needs of the
Telecoms.
Customer references
DP300E rev 8.3
127
Portugal PTTNokiaFinland PTTEricsson LMTelecom EireannMotorolaMCI USATeleDanmarkSonofonFrance TelecomTelecom New ZealandT.T. Mobiles IndiaAT&TPolish TelecomSwiss PTTGlobal OneAlcatelSwissphoneTeleDanmark MobilVEW Telnet D
FujitsuBritish TelecomPolish Mobile PhoneTeletas TurkeyTelex-Exchange IndonesiaCity Telephone ChinaTaiyan PTT ChinaPTT ChinaGEC AlsthomBosch TelecomTelesystem MobilfunkTMI Telecom ItaliaTeliaDutch PTTOrange TelecomVODAphoneDeutsche TelecomPost UngarnTele NordiaTelecom Malaysia
Size Is there enough space on the installation site? Will it go through the door? Is there free space for servicing and
operation?
Weight Will the floor carry the load? Can the lift carry the load? How can it be lifted off the pallet?
Fuses Which fuses to use in installation?
Cables What cable size to use in the installation? And where to connect to the DP300E (cable entry)?
Where to find information:
Spec SheetInstallation GuideQuick Reference
Data SheetInstallation GuideQuick Reference
Installation GuideQuick Reference
Installation GuideQuick Reference
Installation of DP300EInstallation of DP300E
Installation
DP300E rev 8.3
130
Where to find information:Where to find information:
Installation Guide Quick Reference
Please note on ordering sheet
Consider:Consider:
Heat dissipation:• Ensure correct dimensioning of the air
conditioning system
Diesel generators:• Due to the sinusoidal input current a diesel
generator of only 1.3 times the size of the DP300E can be used. (A diesel for a traditional UPS must be 3-5 times the size of the UPS)
• For very sensitive diesels the DP300E series can be programmed for soft start (diesel
modification).
Installation of DP300EInstallation of DP300E
Installation
DP300E rev 8.3
131
Consider:Parallel operation:
Parallel to increase output power. Redundancy to increase safety. Up to four standard systems can be paralleled (only parallel boards needed). With external static switch up to nine systems
can be paralleled (parallel boards and external static switch needed.
Parallel systems can have common or separate batteries.
Batteries: Configuration sheet for Johnson control
batteries are available. Battery dimensioning for special applications
has to be handled from case to case.
Where to find Where to find informationinformation::