DO’S AND DONT’S IN REINFORCEMENT DETAILING CHOICE OF MANDREL FOR BAR BENDING MIXED OF BARS 25 20 MANDREL 25 100 MANDREL d MANDREL DIA < 4d GENERAL d MANDREL DIA > 4d 4d DON’T DO DON’T DO DON’T DO TQR 40 (Fe 415) TQR 50 (Fe 500) COLUMN COLUMN COLUMN BARS (TQR 40) ELEVATION PLAN PLAN ELEVATION - TQR 40 (Fe 415) - TQR 40 (Fe 415) (ALTERNATIVELY ALL BARS TQ 60 (Fe 600) TO DESIGN) - TQR 50 (Fe 500) Acknowledgement: Sourced from ‘Reference Manual for Field Engineers on Building Construction’, Task Force for Quality Assurance in Public Constructions, Government of Karnataka
12

DO’S AND DONT’S IN REINFORCEMENT DETAILING

Oct 06, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: DO’S AND DONT’S IN REINFORCEMENT DETAILING

DO’S AND DONT’S IN REINFORCEMENT DETAILING

CHOICE OF MANDREL FOR BAR BENDING

MIXED OF BARS

25

20

MANDREL

25

100

MANDREL

d

MANDRELDIA < 4d

GENERAL

d

MANDRELDIA > 4d

4d

DON’T

DO

DON’T DODON’T DO

TQR 40 (Fe 415)

TQR 50 (Fe 500)

COLUMN COLUMN

COLUMN BARS (TQR 40)

ELEVATION

PLAN PLAN

ELEVATION

- TQR 40 (Fe 415) - TQR 40 (Fe 415) (ALTERNATIVELY ALL BARS TQ 60 (Fe 600) TO DESIGN)- TQR 50 (Fe 500)

Acknowledgement: Sourced from ‘Reference Manual for Field Engineers on Building Construction’,Task Force for Quality Assurance in Public Constructions, Government of Karnataka

Page 2: DO’S AND DONT’S IN REINFORCEMENT DETAILING

STAGGERING BARS FOR CONTINUITY IN COLUMNS

BAR LAPPING AT COLUMN - BEAM JUNCTION

Note: Alternatively, if staggering is not done, spacing of ties shall be reduced to half the normal spacing in the lapping region.

Acknowledgement: Sourced from ‘Reference Manual for Field Engineers on Building Construction’,Task Force for Quality Assurance in Public Constructions, Government of Karnataka

DEVELOPMENTLENGTH(MINIMUM)

COLUMNTIES

TIEPREFERABLE

COLUMNBARS

BEAM BARS

BEAM STIRRUPS

DON’T DO

DON’T DO

Page 3: DO’S AND DONT’S IN REINFORCEMENT DETAILING

ABRUPT KINKING OF BARS OUTSIDE THE COLUMNS

ABRUPT KINKING OF BARS IN COLUMNS

DON’T DO

TIEPREFERABLE

COLUMNTIES

BEAM

EXPOSED BAR

DON’T DO

Acknowledgement: Sourced from ‘Reference Manual for Field Engineers on Building Construction’,Task Force for Quality Assurance in Public Constructions, Government of Karnataka

Page 4: DO’S AND DONT’S IN REINFORCEMENT DETAILING

DISCONTINUITY OF BARS IN COLUMNS

DEFECTIVE PROVISION OF TIES IN COLUMN

THEPREFERABLE

(ALTERNATIVELYSTIRRUPS INBEAMS TO BECONTINUED)

TIE ATBEAM LEVEL

RECOMMENDEDWELD LENGTH

HOLE DRILLED ANDBAR ANCHOREDWITH BONDINGCHEMICAL

COLUMNBARSCOLUMN

DO

DO

DON’T

DON’T

160

MIN

Acknowledgement: Sourced from ‘Reference Manual for Field Engineers on Building Construction’,Task Force for Quality Assurance in Public Constructions, Government of Karnataka

Page 5: DO’S AND DONT’S IN REINFORCEMENT DETAILING

LAPPING OF BARS IN TENSION MEMBERS

LEAVING THE BARS FOR FUTURE EXPANSIONFU

TURE

EXP

AN

SIO

N

BARS STRAIGHTENEDAS AND WHENCONSTRUCTION IS TAKEN UP

DUMMYCOLUMN

BARS COATEDWITH ZINCRICH PRIMER

BENT AT TOP

STIRRUPS AT1/2 SPACING

WELDEDJOINT

DODON’T

DO DODON’T

1d 10d

21d

Acknowledgement: Sourced from ‘Reference Manual for Field Engineers on Building Construction’,Task Force for Quality Assurance in Public Constructions, Government of Karnataka

Page 6: DO’S AND DONT’S IN REINFORCEMENT DETAILING

LAPPING / PLACEMENT OF BARS IN BEAMS

CURTAILMENT OF BARS IN BEAMS

KINK 1 IN 10PREFERABLE

ABOUT12 DIA

CURTAILED BARS(>50%)

ABOUT12 DIAAst

DON’T

DO

DON’T

DO 0.1L

>0.2L

0.1L

A

A

B

B

>0.2L

Acknowledgement: Sourced from ‘Reference Manual for Field Engineers on Building Construction’,Task Force for Quality Assurance in Public Constructions, Government of Karnataka

Page 7: DO’S AND DONT’S IN REINFORCEMENT DETAILING

DEFECTIVE POSITION OF BARS IN BEAMS

LAPPING OF BARS IN CANTILEVER BEAMS

MAIN REINFORCEMENT

MAIN REINFORCEMENT

CANTILEVER BEAM

1.2 TIMES DESIGN

EFFE

CTI

VE

DEP

TH

EFFE

CTI

VE

DEP

TH

CLEAR COVER

LAP LENGTH

R.C.BEAM

R.C.BEAM

DON’T

DON’T

DO

DO

DO

Acknowledgement: Sourced from ‘Reference Manual for Field Engineers on Building Construction’,Task Force for Quality Assurance in Public Constructions, Government of Karnataka

Page 8: DO’S AND DONT’S IN REINFORCEMENT DETAILING

PLACEMENT OF BARS AT SLAB SUPPORT

UNEQUAL COVERS IN BEAMS

UNEQUALCOVER

EQUAL & ADEQUATECOVER

EQUAL & ADEQUATECOVERUNEQUAL

COVER

DON’T

DON’T

DO

DO

L0.2L

0.3L0.3L

Acknowledgement: Sourced from ‘Reference Manual for Field Engineers on Building Construction’,Task Force for Quality Assurance in Public Constructions, Government of Karnataka

Page 9: DO’S AND DONT’S IN REINFORCEMENT DETAILING

MIXING UP OF BARS IN TWO-WAY SLABS

BAR PLACEMENT IN CANTILEVERED SLAB

TOR 50 ORTORKARI

TOR 40

CANTILEVERSLAB

DON’T

DON’T

DO

DO

L

0.3L

0.2L

TOR 40

TOR 40

Acknowledgement: Sourced from ‘Reference Manual for Field Engineers on Building Construction’,Task Force for Quality Assurance in Public Constructions, Government of Karnataka

Page 10: DO’S AND DONT’S IN REINFORCEMENT DETAILING

REINFORCEMENT DETAILING IN GABLES

ARRANGEMENT OF BARS IN ONE-WAY SLAB

MAINBARS

MAINBARS

MAINBARS

DISTRIBUTIONBARS

DISTRIBUTIONBARS

DISTRIBUTIONBARS

SECTION A-APLAN - ONE - WAY SLAB

DO

DON’T

DO

DON’T

1d

A A

SECTION A-A

Acknowledgement: Sourced from ‘Reference Manual for Field Engineers on Building Construction’,Task Force for Quality Assurance in Public Constructions, Government of Karnataka

Page 11: DO’S AND DONT’S IN REINFORCEMENT DETAILING

REINFORCEMENT DETAILING IN LARGE DOMES

REINFORCEMENT IN FOLDED STAIRCASE

DOME

DODON’T

1d

Acknowledgement: Sourced from ‘Reference Manual for Field Engineers on Building Construction’,Task Force for Quality Assurance in Public Constructions, Government of Karnataka

Page 12: DO’S AND DONT’S IN REINFORCEMENT DETAILING

PLACEMENT OF BARS IN WAIST SLAB

REINFORCEMENT AT WALL INTERSECTIONS

WAIST SLAB

PLAN

ANCHORAGELENGTH

ANCHORAGELENGTH

WALL REINFORCEMENT

WALL REINFORCEMENT WALL REINFORCEMENT

WALL REINFORCEMENT

R.C. WALL

R.C. WALL R.C. WALL

R.C. WALL

WAIST SLAB

DON’T

DON’T

DO

DO

PLAN PLAN

PLAN

Acknowledgement: Sourced from ‘Reference Manual for Field Engineers on Building Construction’,Task Force for Quality Assurance in Public Constructions, Government of Karnataka