Direct Load Analysis and Modeling System Azlan Abdul Rahim Utility Automation Unit, TNB Research, Malaysia IERE 2017 Putrajaya 22.11.2017
Direct Load Analysis and
Modeling System
Azlan Abdul Rahim Utility Automation Unit, TNB Research, Malaysia
IERE 2017 Putrajaya 22.11.2017
2 Copyright © 2017 TNB Research
1
Direct Load Analysis & Modeling System 2
Introduction- Load Modeling in General
Data requirement for Load Analysis & Modeling 3
Load Model Parameters Derivation 4
5 Load Model & Demand Reduction
6 Conclusion
Presentation Outlines
3 Copyright © 2017 TNB Research
Load Modeling in General (1) Load model is the mathematical description of the relationship between the voltage, real power and reactive power of the bus. Power system planning and operation decisions require system studies which involve modeling of the entire system including the loads.
Representation of load in power system study (example)
where
ZIP
4 Copyright © 2017 TNB Research
Load Modeling in General (2) Grid of the future; advancement of power system with increasing amount of non-linear load type and DER, ES, EV etc. will bring changes on the demand-side. Reasonable models needed to understand the system impacts of these changes.
Advancement of power system • Electric vehicle (EV) chargers • Energy storage (ES) • Power electronic loads, VFD,
Inverter AC compressor, LED lights
• Distributed Energy Resources (DER) e.g. PV
• Microgrid
• Resistive-type loads e.g. incandescent lights are phasing out (energy inefficient but exhibit ‘grid-friendly’ behavior)
5 Copyright © 2017 TNB Research
Load Modeling in General (3) Advancement in technology would change the load behavior.
P&Q vs V response of similar equipment over time
BOKHARI et al.: EXPERIMENTAL DETERMINATION OF THE ZIP COEFFICIENTS
6 Copyright © 2017 TNB Research
Direct Load Analysis & Modeling System (1)
Direct & automatic system will be installed within substation for generating load model parameters for the distribution substations.
• Automatic acquisition of disturbance data file, leveraging on IEC61850 based Substation Automation System
• Automatic load analysis and modeling application utilizing the system disturbance data
• Communication interface to distributed energy resources (DER), Energy Storage for measurement
• Communication interface to metering device for load profiling
7 Copyright © 2017 TNB Research
Direct Load Analysis & Modeling System (2)
Load model parameters derivation application based on the system disturbance data. P&Q waveform, curve fitting to find model parameters for ZIP load model structure and motor model. The system continuously capture new event and derive the load models (load is changing and one model can’t be used for all cases).
Math Algorithm
Logic
IEC 61850 MMS Server
IEC 61850 File Transfer
Historian
Control Center
IEC 101 M/SIEC 104 M/SModbus TCPTASEIEC 61850-90-2
IEEE C37.118IEC 61850-90-5Web Server
File Database(FIFO)
Disturbance Recorder
Time Synchronization
SNTPIRIG-BIEEE 1588
IEC 61850 SMV
IETF File Transfer
DLANS Application Platform
IEC 61850 MMS Client
IEC 61850 GOOSE
Virtual Machine
Artificial Intelligent
Load Modeling
Grid analysis applications
Network optimization applications
Load model report
p
q
Disturbance Record
DER Load profile Weather monitoring
8 Copyright © 2017 TNB Research
Data requirement for Load Analysis & Modeling
The system disturbance data will be captured by DFR – function in protection IEDs or a dedicated DFR IEDs. Digital fault recorder (DFR), PQ recorder will record V & I waveform whenever there is disturbance occur, depending on the setting.
System disturbances i.e. voltage dip events or any voltage events
• External fault in upstream e.g. trees, lightning • Transformer tap changes • Record the V & I (then convert to r.m.s V, P & Q)
Capture multiple events for the same feeders
• Time of the day, seasonal, weekly pattern
Data resolution • 32 samples / cycle for 5 sec is sufficient
9 Copyright © 2017 TNB Research
Load Model Parameters Derivation Curve fitting with constrained least square error (LSE). An optimization routine implemented to deliver the best fit with the constraint that the sum of the three ZIP coefficients has to add to 1. The optimization problem is formulated as follows:
Subject to
10 Copyright © 2017 TNB Research
Load model for demand reduction application(1) Conservation Voltage Reduction(CVR); reduce supply voltage within the regulatory standard (+10% & -6% of 230Vac) to reduce energy consumption and peak demand.
230V
216V
253V +10%
0% -6%
National std Typical Rural
Real and reactive power consumption clearly drop off when voltage is reduced and return to normal values when full voltage is restored
Pee Dee Electric Cooperative in Darlington, South Carolina, U.S
Malaysia standard – steady state supply voltage level
11 Copyright © 2017 TNB Research
Load model for demand reduction application(2) Residential ZIP Load model example with >50% is air conditional load. CVR factor is about 1.0 (10% reduction of voltage will save 10% of energy).
BOKHARI et al.: EXPERIMENTAL DETERMINATION OF THE ZIP COEFFICIENTS
New York City -summer
12 Copyright © 2017 TNB Research
Conclusion
1. Direct load analysis and modeling system is a new innovative method for load modeling
2. Automatic system will reduce dependencies to people 3. The system will continuously update the load model as part of
substation automation system 4. Produce multiple models for the same load feeders which
may suitable for various application such as CVR
[Azlan Abdul Rahim] Head of Unit, Utility Automation, TNB Research Sdn. Bhd. [email protected]