Design Criteria for LP BYPASS SYSTEM
25

Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

Dec 23, 2015

Download

Documents

Emory Norman
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

Design Criteria for

LP BYPASS SYSTEM

Page 2: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

LP Bypass system provide a very effective means of controlling reheat –steam flow during

Startup Low-load / part load operationSudden load rejection

Page 3: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

It enhances fast starting capability of turbines from all initial conditions e.g.

Cold condition Warm condition Hot Condition

Page 4: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

LP steam-bypass system operate in parallel with the turbine

Protect Condenser from excessive temperature and pressure that

could result from sudden injection of superheated steam

Page 5: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

Ensure coordinated control between HP and IP turbine control valves and the steam bypass systems to operate at any remaining load

Subsequently reloaded in a controlled manner

Page 6: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

Schematic Diagram of Bypass System

Page 7: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

• The controls for LP Bypass system are combination of electrical and well proven hydraulic system

• Electro-hydraulic converter provides the necessary link between hydraulic actuator and electrical system

Page 8: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

• The LPBypass Controller acts as a maximum pressure Controller

• It regulates the reheater pressure either to the fixed set value or suitably derived variable set value

• If the reheater pressure exceeds this set value, the Controller causes the electro-hydraulic converter to operate and initiate bypass operation

Page 9: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

Set Value formation

The Two set values – fixed and variable are formed for the LPBypass control systemset value to be used is determined by a maximum value selectorFor the formation of variable set point, a pressure transducer is used to measure the steam pressure in HP turbine

Page 10: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

SEQUENCE OF EVENTS RESULTING FROM LOAD REJECTION

Upon receiving load rejection signal from electrical system:

Turbine Speed Controller assumes control of the TG set

It initiates fast closure of HP & IP turbine control valves through position controller

Fast closure of turbine control valves cause an immediate decrease in HP 1st. Stage pressure

Page 11: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

SEQUENCE OF EVENTS RESULTING FROM LOAD REJECTION

Pressure increases in main and reheat steam systems

These pressure changes are sensed by HP and LP Bypass controllers

Respective bypass valves are opened

Page 12: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

If LP steam- bypass system fails or the condenser cannot

accept LP bypass steam , Safety Valves open and dump

steam to atmosphere

Page 13: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

Hydraulic Mode of Operation

• The controller controls plunger coil of Electro Hydraulic Converter

• With increase in voltage, the jet pipe is deflected towards right

• Converter piston moves downwards leading to generation of LPB signal oil through Follow-up pistons provided in the hydraulic control system

Page 14: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

Hydraulic Mode of Operation

• Two Follow-up Pistons actuate and open first stage of water injection valve

• Remaining two Follow-up Pistons generate signal oil for opening LPBypass stop and control valve

Page 15: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

ADJUSTMENT OF

LPBYPASS CONVERTER

Page 16: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

Design of LPBypass Valves for 210 MW Steam Turbine

• Controlled by 8 bar mineral oil

Page 17: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

Design of LPBypass Valve for 500 MW Steam Turbine

• Controlled by 36 bar FRF

Page 18: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

Protection Devices

Low Vacuum Condensor ProtectionSpray Water Pressure SwitchCondensor Temperature Protection

Page 19: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

Protection Devices cause closure of bypass station in case of following

eventualities

a) Condensor vacuum is low ( > 0.6 bar absolute )

b) Spray water pressure is low (< 8.5 / 9.5 bar )

c) Temperature of condenser body is high (> 90° C )

Page 20: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

Water Injection Valves operate in two stages

• Second stage Water Injection Valves open when steam flow through LPBypass Valves increases more than 45 %

Page 21: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

CURVE FOR LPBYPASS CONTROLLER

Page 22: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.

• Damping device

Page 23: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.
Page 24: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.
Page 25: Design Criteria for LP BYPASS SYSTEM. LP Bypass system provide a very effective means of controlling reheat –steam flow during Startup Low-load / part.