Top Banner
BROOK-MTL, 63 Allens Road, East Tamaki, Auckland, New Zealand Tel +64 9 271 6063 - Fax +64 9 271 6020 - www.brookmtl.co.nz - [email protected] Associate company: Rotating Machinery Supplies, 6 Devon Road, Hamilton [email protected] Delta C200 Series AC Drives The VFD-C200 Series is an intelligent vector control micro drive that provides versatile control modes for motors and includes built-in PLC functions with capacity up to 5,000 steps. It is suitable for harsh environment applications with a strengthened thermal and anti-dust design that provides comprehensive protection. Delta C200 Series AC Drives Specifications: Built-in PLC program with 5,000 steps capacity Built-in brake chopper MODBUS RS-485 and CANopen (Slave) The high-brightness LED keypad shares the same extension cable of the VFD-E/M/B Series to maximize operation distance Supports open loop control of permanent motors (PM Sensorless) Two high speed pulse input terminals MI7 and MI8 built-in with maximum speed up to 33kHz Two high speed pulse output terminals DFM1 and DFM2 built-in with maximum speed up to 33kHz New PCB coating for circuit (IEC 60721-3-3 class 3C2) and thermal design suitable for harsh environment applications C200 Series Frame A supports wall mounted installation Part Numbers: SKU KW HP Volts Phase Amps VDEL0.7 3/3 C200 0.7 1 460 3 2.9 VDEL1.5 3/3 C200 1.5 2 460 3 3.8 VDEL2.2 3/3 C200 2.2 3 460 3 5.7 VDEL3.7 3/3 C200 3.7 5 460 3 8.1 VDEL4.0 3/3 C200 4 5 460 3 9.5 VDEL5.5 3/3 C200 5.5 7.5 460 3 11 VDEL7.8 3/3 C200 7.5 10 460 3 17 VDEL0.4 1/3 C200 0.4 1/2 230 1 2.8 VDEL0.7 1/3 C200 0.7 1 230 1 4.8 VDEL1.5 1/3 C200 1.5 2 230 1 7.1 VDEL2.2 1/3 C200 2.2 3 230 1 10 C200 User Manual C200 Catalogue
5

Delta C200 Series AC Drives - Brook MTLbrookmtl.co.nz/.../uploads/2014/12/Delta-C200-Series-AC-Drives.pdf · Delta C200 Series AC Drives ... C200 User Manual ... QUICK SET UP INSTRUCTIONS

Apr 12, 2018

Download

Documents

vuongkhue
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Delta C200 Series AC Drives - Brook MTLbrookmtl.co.nz/.../uploads/2014/12/Delta-C200-Series-AC-Drives.pdf · Delta C200 Series AC Drives ... C200 User Manual ... QUICK SET UP INSTRUCTIONS

BROOK-MTL, 63 Allens Road, East Tamaki, Auckland, New Zealand Tel +64 9 271 6063 - Fax +64 9 271 6020 - www.brookmtl.co.nz - [email protected]

Associate company: Rotating Machinery Supplies, 6 Devon Road, Hamilton [email protected]

Delta C200 Series AC Drives

The VFD-C200 Series is an intelligent vector control micro drive that provides versatile control modes for motors and includes built-in PLC functions with capacity up to 5,000 steps. It is suitable for harsh environment applications with a strengthened thermal and anti-dust design that provides comprehensive protection.

Delta C200 Series AC Drives

Specifications: Built-in PLC program with 5,000 steps capacity Built-in brake chopper MODBUS RS-485 and CANopen (Slave) The high-brightness LED keypad shares the same extension cable of the VFD-E/M/B

Series to maximize operation distance Supports open loop control of permanent motors (PM Sensorless) Two high speed pulse input terminals MI7 and MI8 built-in with maximum speed up to

33kHz Two high speed pulse output terminals DFM1 and DFM2 built-in with maximum speed up

to 33kHz New PCB coating for circuit (IEC 60721-3-3 class 3C2) and thermal design suitable for

harsh environment applications C200 Series Frame A supports wall mounted installation

Part Numbers:

SKU KW HP Volts Phase Amps

VDEL0.7 3/3 C200 0.7 1 460 3 2.9

VDEL1.5 3/3 C200 1.5 2 460 3 3.8

VDEL2.2 3/3 C200 2.2 3 460 3 5.7

VDEL3.7 3/3 C200 3.7 5 460 3 8.1

VDEL4.0 3/3 C200 4 5 460 3 9.5

VDEL5.5 3/3 C200 5.5 7.5 460 3 11

VDEL7.8 3/3 C200 7.5 10 460 3 17

VDEL0.4 1/3 C200 0.4 1/2 230 1 2.8

VDEL0.7 1/3 C200 0.7 1 230 1 4.8

VDEL1.5 1/3 C200 1.5 2 230 1 7.1

VDEL2.2 1/3 C200 2.2 3 230 1 10  

C200 User Manual C200 Catalogue 

Page 2: Delta C200 Series AC Drives - Brook MTLbrookmtl.co.nz/.../uploads/2014/12/Delta-C200-Series-AC-Drives.pdf · Delta C200 Series AC Drives ... C200 User Manual ... QUICK SET UP INSTRUCTIONS

BROOK-MTL, 63 Allens Road, East Tamaki, Auckland, New Zealand

Tel +64 9 271 6063 - Fax +64 9 271 6020 - www.brookmtl.co.nz - [email protected]

Associate companies: Rotating Machinery Supplies, 6 Devon Road, Hamilton [email protected] SOCO ELECTRIC MOTORS, 473 Tremaine ave, Palmerston North [email protected]

All data is subject to confirmation by BROOK-MTL C200 1/3

QUICK SET UP INSTRUCTIONS FOR DELTA VDF-C200 1PHASE

TO 3PHASE VARIABLE SPEED DRIVE

Important Notice

Wiring and connection must be carried out by a registered electrician.

Connection by an unqualified person voids the warranty.

Please check the suitability of the motor before attempting to connect it to the device.

Ensure the motor terminals are connected in a DELTA connection.

Operations panel

Quick Setup for Variable Speed Drive

Turn on power to unit and follow as below:

F60.0 will be displayed on the screen.

Press the enter button.

00. will appear on the screen.

Press enter again.

00.00 will appear on the screen.

Use the up and down keys to change parameters selections to the desired one. Press enter

You will now be able to change the parameter to the desired value or setting. Press enter. End will flash on your screen to indicate that your setting has been saved.

Continue the above steps till all of your parameters have been set.

Once all the parameters have been set press the Mode button till the F60.0 screen comes up again.

Page 3: Delta C200 Series AC Drives - Brook MTLbrookmtl.co.nz/.../uploads/2014/12/Delta-C200-Series-AC-Drives.pdf · Delta C200 Series AC Drives ... C200 User Manual ... QUICK SET UP INSTRUCTIONS

BROOK-MTL, 63 Allens Road, East Tamaki, Auckland, New Zealand

Tel +64 9 271 6063 - Fax +64 9 271 6020 - www.brookmtl.co.nz - [email protected]

Associate companies: Rotating Machinery Supplies, 6 Devon Road, Hamilton [email protected] SOCO ELECTRIC MOTORS, 473 Tremaine ave, Palmerston North [email protected]

All data is subject to confirmation by BROOK-MTL C200 1/3

FOR ADVANCED SET UP REFER TO MANUAL AND CD ROM PROVIDED

OP

TIO

NA

L IF

REQ

UIR

ED

List of quick set parameters

00.20 Source of master Frequency Command. Set to 7 for keypad potentiometer. Factory setting is up and down buttons for speed control.

01.00 Change to the maximum Frequency required.

01.01 Change value to match 01.00

01.02 Change to 230V (Max Voltage output)

01.03 Mid-Point Frequency. Set to half the value of 01.00

01.04 Mid-point Voltage. Set to half the value of 01.02

01.10 Upper limit Frequency.

01.11 Lower limit Frequency.

01.12 Acceleration time.

01.13 Deceleration time.

05.01 Set to Motor Name Plate Current.

05.02 Set to Motor Name Plate KW.

05.03 Set to Motor Name Plate Speed.

05.04 Set as the number of poles of the motor.

Connect Live to R and Neutral to S

And the Motor to U,V and W

Instructions for Remote Setup

(Remote On Off/ Speed Variation)

For remote stop and start connect between DCM

and FWD. (DCM is your common)

For remote Potentiometer connect the pot to

+10V, AVI and ACM (common).

Set 00.20 to 2 (Remote Potentiometer setting)

Set 00.21 to 1 (Remote ON/OFF setting)

Set 04.04 to 0

Page 4: Delta C200 Series AC Drives - Brook MTLbrookmtl.co.nz/.../uploads/2014/12/Delta-C200-Series-AC-Drives.pdf · Delta C200 Series AC Drives ... C200 User Manual ... QUICK SET UP INSTRUCTIONS

BROOK-MTL, 63 Allens Road, East Tamaki, Auckland, New Zealand

Tel +64 9 271 6063 - Fax +64 9 271 6020 - www.brookmtl.co.nz - [email protected]

Associate companies: Rotating Machinery Supplies, 6 Devon Road, Hamilton [email protected] SOCO ELECTRIC MOTORS, 473 Tremaine ave, Palmerston North [email protected]

All data is subject to confirmation by BROOK-MTL C200 3/3

QUICK SET UP INSTRUCTIONS FOR DELTA VDF-C200 3PHASE

TO 3PHASE VARIABLE SPEED DRIVE

Important Notice

Wiring and connection must be carried out by a registered electrician.

Connection by an unqualified person voids the warranty.

Please check the suitability of the motor before attempting to connect it to the device.

Ensure the motor terminals are connected for 400V supply.

Operations panel

Quick Setup for Variable Speed Drive

Turn on power to unit and follow as below:

F60.0 will be displayed on the screen.

Press the enter button.

00. will appear on the screen.

Press enter again.

00.00 will appear on the screen.

Use the up and down keys to change parameters selections to the desired one. Press enter

You will now be able to change the parameter to the desired value or setting. Press enter. End will flash on your screen to indicate that your setting has been saved.

Continue the above steps till all of your parameters have been set.

Once all the parameters have been set press the Mode button till the F60.0 screen comes up again.

Page 5: Delta C200 Series AC Drives - Brook MTLbrookmtl.co.nz/.../uploads/2014/12/Delta-C200-Series-AC-Drives.pdf · Delta C200 Series AC Drives ... C200 User Manual ... QUICK SET UP INSTRUCTIONS

BROOK-MTL, 63 Allens Road, East Tamaki, Auckland, New Zealand

Tel +64 9 271 6063 - Fax +64 9 271 6020 - www.brookmtl.co.nz - [email protected]

Associate companies: Rotating Machinery Supplies, 6 Devon Road, Hamilton [email protected] SOCO ELECTRIC MOTORS, 473 Tremaine ave, Palmerston North [email protected]

All data is subject to confirmation by BROOK-MTL C200 3/3

FOR ADVANCED SET UP REFER TO MANUAL AND CD ROM PROVIDED

OP

TIO

NA

L IF

REQ

UIR

ED

List of quick set parameters

00.20 Source of master Frequency Command. Set to 7 for keypad potentiometer. Factory setting is up and down buttons for speed control.

01.00 Change to the maximum Frequency required.

01.01 Change value to match 01.00

01.02 Change to 415V (Max Voltage output)

01.03 Mid-Point Frequency. Set to half the value of 01.00

01.04 Mid-point Voltage. Set to half the value of 01.02

01.10 Upper limit Frequency.

01.11 Lower limit Frequency.

01.12 Acceleration time.

01.13 Deceleration time.

05.01 Set to Motor Name Plate Current.

05.02 Set to Motor Name Plate KW.

05.03 Set to Motor Name Plate Speed.

05.04 Set as the number of poles of the motor. (3000rpm=2pole; 1500rpm=4pole; 1000rpm=6pole; 750rpm=8pole)

Connect L1-R, L2-S and L3-T

And the Motor to U,V and W

Instructions for Remote Setup

(Remote On Off/ Speed Variation)

For remote stop and start connect between DCM

and FWD. (DCM is your common)

For remote Potentiometer connect the pot to

+10V, AVI and ACM (common).

Set 00.20 to 2 (Remote Potentiometer setting)

Set 00.21 to 1 (Remote ON/OFF setting)

Set 04.04 to 0