Conditioning of Moist Air Properties of moist air Equations – Conservation of mass – Conservation of energy Classic moist air processes – Sensible heating and cooling – Cooling and dehumidifying – Adiabatic humidifying – Heating and humidifying – Adiabatic mixing Space conditioning – Sensible heat factor (SHF) – Cooling coil bypass (b) – Evaporative cooling – Economizer cycle – Effect of fans – Designing indoor RH Change using bulk properties at inlet and outlet 2 3 1 1 2 1 2 a T T m 02 . 1 q 1 2 a h h m q W h h w w w h m q W h 3 1 2 3 m m 2 a 1 a 2 1 2 3 m m 3 a 1 a 2 1 3 1 m m 3 a 2 a
18
Embed
Conditioning of Moist Air l Properties of moist air l Equations – Conservation of mass – Conservation of energy l Classic moist air processes – Sensible.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Conditioning of Moist Air Properties of moist air Equations
– Conservation of mass– Conservation of energy
Classic moist air processes– Sensible heating and cooling– Cooling and dehumidifying– Adiabatic humidifying– Heating and humidifying– Adiabatic mixing
Space conditioning– Sensible heat factor (SHF)– Cooling coil bypass (b)– Evaporative cooling– Economizer cycle– Effect of fans– Designing indoor RH
Change using bulk properties at inlet and outlet
23
1 1
2
12a TTm02.1q
12a hhmq
W
hhw
ww
hm
q
W
h
31
23
m
m
2a
1a
21
23
m
m
3a
1a
21
31
m
m
3a
2a
Adiabatic mixing - Example
– Two thousand cubic feet per minute (cfm) of air at 100 F db and 75 F wb (state 1) are mixed with 1000 cfm of air at 60 F db and 50 F wb (state 2). The process is adiabatic at a steady flow rate and at standard sea level pressure. Find the condition of the mixed streams.
– Convert to SI:8.1/)32F(C oo
s/L472cfm1000
C8.37F100 oo
sL4719.0cfm1
C9.23F75 oo C6.15F60 oo C10F50 oo
s/L944cfm2000
3
1
2
kg/m9.0v 31
Adiabatic mixing - Solution
kg/m825.0v 32
s/kg05.19.0/944.0m 1a
s/kg57.0825.0/472.0m 2a
kg/g3.109.123.562.1
57.00.13
C30T o3
123a
2a13 WW
m
mWW
C9.19T o3wb %383
21
32
m
m
3a
1a
510
0
20
30
40
50
units4.31
units5.4862.1
05.132
method graphical partial
method graphicalfully
Typical air handling system
Outdoor air
Exhaust air
filter
heating coil
cooling coil
Return air
energyrecoverysystem
recirculation air
damper
-20°C
22°C
23°C
15°C - 35°C
Supply air
economizer
Sensible heat factor
a2a1a mmm
q
q
qq
q
ferheat trans total
ferheat trans sensibleSHF s
ls
s
1
2
)hh(mq 2zas
)hh(mq z1al
z
sensib
le
laten
t
1 2
coil q 2222a h,W,T,m1111a h,W,T,m
www h,T,m
Sensible heat factor - Example
1
2
kW6.6)3.395.52(5.0
)hh(mq 12a
kW0.2qqq sl
– Conditioned air is supplied to a space at T=15C and Twb=14C at a flow rate of 0.5 kg/s. The sensible heat factor for the space is 0.70 and the space is to be maintained at 24C . Find the sensible and latent cooling loads for the space.
condition lineskg
1 5.0m C15T o
1 C14T o
1wb
1
2
C24T o7.0SHF
kW6.47.06.6SHFqqs
parallel
If the cooling load is 6.6kW,what is m1 if state 1 is here?
(i.e., the supply air is heated and the space air is cooled)
1
3
Cooling coil bypass
2
4
41
34
m
mb
1a
6a
bypass factor
condition line
1 3
333a W,T,m111a W,T,m
www h,T,m55 ,T
5
T4 = apparatus dew point
1 3
333a W,T,m111a W,T,m
www h,T,m
6
4
55 ,T
Evaporative cooling - 1
1 2
1111a h,W,T,m
ww h,m
1
2
– Energy balance
– Given air at outdoorconditions (1) and theSHF of the space we canuse evaporative cooling tocool from state 1 to state 2
– The flow rate of air thatis required to cool thespace depends on cooling load
2aww1a hmhmhm negligible for water
2222a h,W,T,m
21 hh
3
condition line
3
6.0SHF
Is this a more favourable outdoorcondition for evaporative cooling?
sq
lq
Evaporative cooling - 2
OA
OAdesign target
good potential
no potential
– Low cost alternative to refrigerant systems Requires less energy for cooling Requires less capital investment
– Cooling potential (Twb,design – Twb,outdoors) If the cooling potential is small, the air flow rates become very large and
system is not economical because of fan and duct costs If cooling load is large, air flow rates become large
– Evaporative systems are subjectto mold and bacteria growth
– Freezing may be a problemduring swing seasons(spring/fall) in colder climates
Economizer cycle
– Using outdoor air to condition the indoor space
– Can be used during “off-design” conditions to save energy (usually cooling) by increasing the amount of outside (ventilation) air (usually at night-time)
– May be limited in amount of outdoor air if RH must be controlled to a specific value (often RH must remain below some maximum value)
– must measure the enthalpy (T & ) to properly control