Top Banner
W:\Permit Center (Rachelle)\Permit Center Handouts\PDF Form Versions Handouts Page 1 of 1 Revised: June 2019 MECHANICAL Commercial Structures City of Tukwila Department of Community Development 6300 Southcenter Boulevard, Suite #100 Tukwila, Washington 98188 Phone: 206-431-3670 Web site: http://www.TukwilaWA.gov DOCUMENTS Complete Mechanical Permit Application Plan Review Fee contact Permit Center for fee estimate 206-431-3670. Washington State Department of Labor and Industries valid contractors license required at time of permit issuance. Current City of Tukwila business license required at time of permit issuance. PLANS 2 sets of working drawings *Minimum sheet size 11x 17”, maximum sheet size 24x 36”. Site plan 1. North arrow and scale 2. Vicinity map 3. Address or parcel number 4. If multiple structures are on site, identify the structure that the mechanical work will be located in. Working drawings 1. Floor plan and system layout 2. Roof plan required to identify individual equipment and the location of each installation 3. Details and elevations and proposed screening for roof mounted equipment, where required. 4. Air distribution systems with a design capacity greater than 2000 cfm shall be equipped with smoke detectors listed and labeled for installation in air distribution systems (International Mechanical Code Section 606). 5. Equipment schedule and specifications must be provided to show that equipment complies with the efficiency ratings and other applicable requirements of the Washington State Non-Residential Energy Code. 6. Structural engineer’s analysis is required for new and the replacement of existing roof top equipment (including commercial kitchen hoods) weighing 400 pounds and greater. Wet stampedand signed by a registered design professional, licensed by the State of Washington.
1

City of Tukwila MECHANICAL

Feb 17, 2022

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: City of Tukwila MECHANICAL

W:\Permit Center (Rachelle)\Permit Center Handouts\PDF Form Versions Handouts Page 1 of 1 Revised: June 2019

MECHANICAL –

Commercial Structures

City of Tukwila Department of Community Development 6300 Southcenter Boulevard, Suite #100

Tukwila, Washington 98188 Phone: 206-431-3670

Web site: http://www.TukwilaWA.gov DOCUMENTS

Complete Mechanical Permit Application

Plan Review Fee – contact Permit Center for fee estimate 206-431-3670.

Washington State Department of Labor and Industries valid contractor’s license required at time of permit issuance.

Current City of Tukwila business license required at time of permit issuance.

PLANS – 2 sets of working drawings

*Minimum sheet size 11” x 17”, maximum sheet size 24” x 36”.

Site plan

1. North arrow and scale

2. Vicinity map

3. Address or parcel number

4. If multiple structures are on site, identify the structure that the mechanical work will be located in.

Working drawings

1. Floor plan and system layout

2. Roof plan required to identify individual equipment and the location of each installation

3. Details and elevations and proposed screening for roof mounted equipment, where required.

4. Air distribution systems with a design capacity greater than 2000 cfm shall be equipped with smoke detectors

listed and labeled for installation in air distribution systems (International Mechanical Code Section 606).

5. Equipment schedule and specifications must be provided to show that equipment complies with the efficiency

ratings and other applicable requirements of the Washington State Non-Residential Energy Code.

6. Structural engineer’s analysis is required for new and the replacement of existing roof top equipment (including

commercial kitchen hoods) weighing 400 pounds and greater. “Wet stamped” and signed by a registered design

professional, licensed by the State of Washington.