CONTENTS PAGE

3.6/6 (7.2) kV XLPE/PVC 1 x (25 ~ 800) mm² A-16/10 (12) kV XLPE/PVC 1 x (25 ~ 800) mm² A-28.7/15 (17.5) kV XLPE/PVC 1 x (25 ~ 630) mm² A-312/20 (24) kV XLPE/PVC 1 x (35 ~ 630) mm² A-418/30 (36) kV XLPE/PVC 1 x (50 ~ 630) mm² A-5

3.6/6 (7.2) kV XLPE/PVC 3 x (25 ~ 300) mm² B-16/10 (12) kV XLPE/PVC 3 x (25 ~ 300) mm² B-28.7/15 (17.5) kV XLPE/PVC 3 x (25 ~ 300) mm² B-312/20 (24) kV XLPE/PVC 3 x (35 ~ 300) mm² B-418/30 (36) kV XLPE/PVC 3 x (50 ~ 240) mm² B-5

3.6/6 (7.2) kV XLPE/AWA/PVC 1 x (25 ~ 630) mm² C-16/10 (12) kV XLPE/AWA/PVC 1 x (25 ~ 630) mm² C-28.7/15 (17.5) kV XLPE/AWA/PVC 1 x (25 ~ 630) mm² C-312/20 (24) kV XLPE/AWA/PVC 1 x (35 ~ 630) mm² C-418/30 (36) kV XLPE/AWA/PVC 1 x (50 ~ 630) mm² C-5

3.6/6 (7.2) kV XLPE/SWA/PVC 3 x (25 ~ 300) mm² D-16/10 (12) kV XLPE/SWA/PVC 3 x (25 ~ 300) mm² D-28.7/15 (17.5) kV XLPE/SWA/PVC 3 x (25 ~ 300) mm² D-312/20 (24) kV XLPE/SWA/PVC 3 x (35 ~ 300) mm² D-418/30 (36) kV XLPE/SWA/PVC 3 x (50 ~ 240) mm² D-5

3.6/6 (7.2) kV XLPE/DATA/PVC 1 x (25 ~ 630) mm² E-16/10 (12) kV XLPE/DATA/PVC 1 x (25 ~ 630) mm² E-28.7/15 (17.5) kV XLPE/DATA/PVC 1 x (25 ~ 630) mm² E-312/20 (24) kV XLPE/DATA/PVC 1 x (35 ~ 630) mm² E-418/30 (36) kV XLPE/DATA/PVC 1 x (50 ~ 630) mm² E-5

3.6/6 (7.2) kV XLPE/DSTA/PVC 3 x (25 ~ 300) mm² F-16/10 (12) kV XLPE/DSTA/PVC 3 x (25 ~ 300) mm² F-28.7/15 (17.5) kV XLPE/DSTA/PVC 3 x (25 ~ 300) mm² F-312/20 (24) kV XLPE/DSTA/PVC 3 x (35 ~ 300) mm² F-418/30 (36) kV XLPE/DSTA/PVC 3 x (50 ~ 240) mm² F-5

3.6/6 (7.2) kV XLPE/FSWA/PVC 3 x (25 ~ 300) mm² G-16/10 (12) kV XLPE/FSWA/PVC 3 x (25 ~ 300) mm² G-28.7/15 (17.5) kV XLPE/FSWA/PVC 3 x (25 ~ 300) mm² G-312/20 (24) kV XLPE/FSWA/PVC 3 x (35 ~ 300) mm² G-418/30 (36) kV XLPE/FSWA/PVC 3 x (50 ~ 240) mm² G-5

Conditions of Current rating calculation HCorrection factor H-1 , H-2Reduction Factors for groups of more than one multi-core cables in air to be appliedto the current-carrying capacity for one multi-core cable in free air I-1Reduction Factors for groups of more than one circuit of single-core cables to be appliedto the current-carrying capacity for one circuit of singlei-core cables in free air I-2Permissible Pulling tension JMinimum Bending radius JPermissible Side Wall pressure KCalculation of Cable Pulling tension during installation KVoltage drop K

Page 3: Catalogue MV 07

According to : IEC 60502-2

Copper Conductor

XLPE Insulation

Conductor Screen

Insulation Screen

Copper Tape Screen

PVC Sheath (Red or Black colour)

BindingTape (manufacturer's option)

XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables (3.6/6 kV ~ 18/30 kV ) XLPE/PVC 1 CORE

AFFILIATE OFSUMITOMO ELECTRIC INDUSTRIES,LTD - JAPAN

PT. SUMI INDO KABEL Tbk.KABELSI

(A)

Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Longitudinally Water blocking characteristic.* Anti termite performance.* Tin coated Copper conductor.* Copper wire screen.* Polyethylene / Low smoke Halogen Free sheath.

Page 4: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 400 500 630 800 No. of Wire - 7 7 19 19 19 37 37 37 37 61 61 61 61 61 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 23.4 26.5 30.3 34.3 Nom. Thick. of Insulation mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.8 3.0 3.2 3.2 3.2 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. Of Outer sheath mm 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.1 2.2 2.3 2.5 Overall Diameter of cable mm 17.5 19.0 20.0 21.5 23.5 24.5 26.0 28.0 30.5 33.5 37.0 40.5 45.0 49.0 Weight of cable, approx. kg/km 503 614 743 962 1235 1480 1763 2113 2678 3305 4153 5235 6705 8410

ELECTRICAL DATA AC Voltage test for 5 min. kV 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5

Partial Discharge test at max. 10ρC kV 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 0.0614 0.0482 0.0376 0.0310 Insulation Resistance at 20°C Μ.Ω.km 2500 2000 2000 2000 1500 1500 1500 1500 1000 1000 1000 1000 1000 1000 Capacitance µF/km 0.258 0.291 0.318 0.361 0.413 0.448 0.485 0.531 0.573 0.596 0.605 0.637 0.715 0.797 Inductance (Trefoil) mH/km 0.406 0.385 0.369 0.348 0.33 0.317 0.308 0.301 0.291 0.285 0.28 0.273 0.268 0.260 Reactance (Trefoil) Ω/km 0.128 0.121 0.116 0.109 0.104 0.100 0.097 0.095 0.091 0.090 0.088 0.086 0.084 0.082 Current Carrying Capacity : - Buried direct in ground at 20°C **) (Trefoil) A 140 166 196 239 285 323 361 406 469 526 590 * 655 * 740 * 840

(Flat spaced) A 144 172 203 246 293 332 366 410 470 524 572 * 650 * 730 * 820 - In Air at 30°C (Trefoil) A 163 198 238 296 361 417 473 543 641 735 845 * 940 * 1080 * 1250

(Flat spaced) A 196 238 286 356 434 500 559 637 745 846 938 * 1075 * 1235 * 1420 (Flat touching) A 167 203 243 303 369 426 481 550 647 739 837 * 945 * 1080 * 1250

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 56.4 70.5 88.8 112.8*) Diameter compacted shape * typical data

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

3.6/6 (7.2) kV XLPE/PVC 1 x (25 - 800) mm²

(A-1)

XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables

Page 5: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 400 500 630 800 No. of Wire - 7 7 19 19 19 37 37 37 37 61 61 61 61 61 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 23.4 26.5 30.3 34.3 Nom. Thick. of Insulation mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. Of Outer sheath mm 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.0 2.2 2.2 2.4 2.5 Overall Diameter of cable mm 19.5 21.0 22.0 23.5 25.5 26.5 28.0 30.0 32.5 34.5 38.0 41.0 45.5 49.5 Weight of cable, approx. kg/km 568 682 815 1038 1315 1565 1853 2207 2784 3382 4217 5261 6734 8442

ELECTRICAL DATA AC Voltage test for 5 min. kV 21 21 21 21 21 21 21 21 21 21 21 21 21 21

Partial Discharge test at max. 10ρC kV 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 0.0614 0.0482 0.0376 0.0310 Insulation Resistance at 20°C Μ.Ω.km 3000 2500 2500 2000 2000 2000 2000 1500 1500 1500 1500 1000 1000 1000 Capacitance µF/km 0.202 0.226 0.246 0.278 0.315 0.341 0.368 0.401 0.446 0.492 0.545 0.605 0.679 0.756 Inductance (Trefoil) mH/km 0.428 0.406 0.388 0.366 0.346 0.333 0.323 0.314 0.303 0.291 0.286 0.276 0.270 0.262 Reactance (Trefoil) Ω/km 0.134 0.127 0.122 0.115 0.109 0.104 0.101 0.099 0.095 0.091 0.090 0.087 0.085 0.082 Current Carrying Capacity : - Buried direct in ground at 20°C **) (Trefoil) A 140 166 196 239 285 323 361 406 469 526 590 * 655 * 740 * 840

(Flat spaced) A 144 172 203 246 293 332 366 410 470 524 572 * 650 * 730 * 820 - In Air at 30°C (Trefoil) A 163 198 238 296 361 417 473 543 641 735 845 * 940 * 1080 * 1250

(Flat spaced) A 196 238 286 356 434 500 559 637 745 846 938 * 1075 * 1235 * 1420 (Flat touching) A 167 203 243 303 369 426 481 550 647 739 837 * 945 * 1080 * 1250

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 56.4 70.5 88.8 112.8*) Diameter compacted shape * typical data

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

6/10 (12) kV XLPE/PVC 1 x (25 - 800) mm²

XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables

(A-2)

Page 6: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 1 1 1 1 1 1 1 1 1 1 1 1 1 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 400 500 630 No. of Wire - 7 7 19 19 19 37 37 37 37 61 61 61 61 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 23.4 26.5 30.3 Nom. Thick. of Insulation mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. Of Outer sheath mm 1.8 1.8 1.8 1.8 1.8 1.9 1.9 2.0 2.1 2.1 2.2 2.3 2.4 Overall Diameter of cable mm 22.0 23.0 24.0 25.5 27.5 29.0 30.5 32.0 34.5 37.0 40.0 43.5 48.0 Weight of cable, approx. kg/km 646 764 900 1128 1412 1665 1958 2332 2918 3525 4355 5427 6896

ELECTRICAL DATA AC Voltage test for 5 min. kV 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5

Partial Discharge test at max. 10ρC kV 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 0.0614 0.0482 0.0376 Insulation Resistance at 20°C Μ.Ω.km 3500 3000 3000 2500 2500 2500 2000 2000 2000 1500 1500 1500 1500 Capacitance µF/km 0.168 0.186 0.202 0.226 0.255 0.275 0.296 0.322 0.356 0.392 0.432 0.478 0.535 Inductance (Trefoil) mH/km 0.452 0.424 0.406 0.382 0.361 0.351 0.340 0.327 0.315 0.305 0.296 0.288 0.281 Reactance (Trefoil) Ω/km 0.142 0.133 0.127 0.120 0.113 0.110 0.107 0.103 0.099 0.096 0.093 0.090 0.088 Current Carrying Capacity : - Buried direct in ground at 20°C **) (Trefoil) A 140 166 196 239 285 323 361 406 469 526 590 * 655 * 740

(Flat spaced) A 144 172 203 246 293 332 366 410 470 524 572 * 650 * 730 - In Air at 30°C (Trefoil) A 163 198 238 296 361 417 473 543 641 735 845 * 940 * 1080

(Flat spaced) A 196 238 286 356 434 500 559 637 745 846 938 * 1075 * 1235 (Flat touching) A 167 203 243 303 369 426 481 550 647 739 837 * 945 * 1080

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 56.4 70.5 88.8*) Diameter compacted shape * typical data

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

8.7/15 (17.5) kV XLPE/PVC 1 x (25 - 630) mm²

XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables

(A-3)

Page 7: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 1 1 1 1 1 1 1 1 1 1 1 1 Nom. Cross-section area mm² 35 50 70 95 120 150 185 240 300 400 500 630 No. of Wire - 7 19 19 19 37 37 37 37 61 61 61 61 Diameter of Conductor, approx. *) mm 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 23.4 26.5 30.3 Nom. Thick. of Insulation mm 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. Of Outer sheath mm 1.8 1.8 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 Overall Diameter of cable mm 25.5 26.5 28.0 30.0 31.0 32.5 34.5 37.0 39.5 42.5 45.5 50.0 Weight of cable, approx. kg/km 853 992 1225 1516 1772 2085 2451 3045 3678 4518 5582 7088

ELECTRICAL DATA AC Voltage test for 5 min. kV 42 42 42 42 42 42 42 42 42 42 42 42

Partial Discharge test at max. 10ρC kV 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 DC Resistance at 20°C Ω/km 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 AC Resistance at 90°C Ω/km 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 0.0614 0.0482 0.0376 Insulation Resistance at 20°C Μ.Ω.km 3500 3500 3000 3000 2500 2500 2500 2000 2000 2000 1500 1500 Capacitance µF/km 0.161 0.174 0.194 0.218 0.234 0.251 0.272 0.300 0.329 0.362 0.399 0.445 Inductance (Trefoil) mH/km 0.444 0.426 0.401 0.379 0.364 0.353 0.342 0.329 0.318 0.308 0.297 0.289 Reactance (Trefoil) Ω/km 0.140 0.134 0.126 0.119 0.114 0.111 0.108 0.103 0.100 0.097 0.093 0.091 Current Carrying Capacity : - Buried direct in ground at 20°C **) (Trefoil) A 166 196 239 285 323 361 406 469 526 590 * 655 * 740

(Flat spaced) A 172 203 246 293 332 366 410 470 524 572 * 650 * 730 - In Air at 30°C (Trefoil) A 198 238 296 361 417 473 543 641 735 845 * 940 * 1080

(Flat spaced) A 238 286 356 434 500 559 637 745 846 938 * 1075 * 1235 (Flat touching) A 203 243 303 369 426 481 550 647 739 837 * 945 * 1080

Short circuit current rating at 1 sec. (approx.) kA 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 56.4 70.5 88.8*) Diameter compacted shape * typical data

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

12/20 (24) kV XLPE/PVC 1 x (35 - 630) mm²

XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables

(A-4)

Page 8: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 1 1 1 1 1 1 1 1 1 1 1 Nom. Cross-section area mm² 50 70 95 120 150 185 240 300 400 500 630 No. of Wire - 19 19 19 37 37 37 37 61 61 61 61 Diameter of Conductor, approx. *) mm 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 23.4 26.5 30.3 Nom. Thick. of Insulation mm 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. Of Outer sheath mm 2.0 2.0 2.1 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 Overall Diameter of cable mm 31.5 33.5 35.5 36.5 38.5 40.0 42.5 45.0 48.0 51.0 55.5 Weight of cable, approx. kg/km 1253 1499 1820 2088 2414 2795 3412 4046 4910 6023 7568

ELECTRICAL DATA AC Voltage test for 5 min. kV 63 63 63 63 63 63 63 63 63 63 63

Partial Discharge test at max. 10ρC kV 31.1 31.1 31.1 31.1 31.1 31.1 31.1 31.1 31.1 31.1 31.1 DC Resistance at 20°C Ω/km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 AC Resistance at 90°C Ω/km 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 0.0614 0.0482 0.0376 Insulation Resistance at 20°C Μ.Ω.km 4500 4000 3500 3500 3000 3000 2500 2500 2500 2000 2000 Capacitance µF/km 0.136 0.151 0.167 0.179 0.191 0.206 0.225 0.246 0.269 0.295 0.327 Inductance (Trefoil) mH/km 0.460 0.437 0.412 0.397 0.387 0.372 0.357 0.344 0.332 0.320 0.310 Reactance (Trefoil) Ω/km 0.145 0.137 0.130 0.125 0.121 0.117 0.112 0.108 0.104 0.100 0.097 Current Carrying Capacity : - Buried direct in ground at 20°C **) (Trefoil) A 196 239 285 323 361 406 469 526 590 * 655 * 740

(Flat spaced) A 203 246 293 332 366 410 470 524 572 * 650 * 730 - In Air at 30°C (Trefoil) A 238 296 361 417 473 543 641 735 845 * 940 * 1080

(Flat spaced) A 286 356 434 500 559 637 745 846 938 * 1075 * 1235 (Flat touching) A 243 303 369 426 481 550 647 739 837 * 945 * 1080

Short circuit current rating at 1 sec. (approx.) kA 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 56.4 70.5 88.8*) Diameter compacted shape * is typical data

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

18/30 (36) kV XLPE/PVC 1 x (50 - 630) mm²

XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables

(A-5)

Page 9: Catalogue MV 07

According to : IEC 60502-2

Copper Conductor

XLPE Insulation

Conductor Screen

Insulation Screen

Copper Tape Screen

Filler (Polyprophylene yarn, or extruded filler upon request)

PVC Sheath (Red or Black colour)

Binding Tape (manufacturer's option)

Identification of core(Red, Yellow, Blue by coloured tape)

XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables (3.6/6 kV ~ 18/30 kV) XLPE/PVC 3 CORE

AFFILIATE OFSUMITOMO ELECTRIC INDUSTRIES,LTD - JAPAN

PT. SUMI INDO KABEL Tbk.KABELSI

(B)

Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Longitudinally Water blocking characteristic.* Anti termite performance.* Tin coated Copper conductor.* Copper wire screen.* Polyethylene / Low smoke Halogen Free sheath.

Page 10: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 3 3 3 3 3 3 3 3 3 3 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 No. of Wire - 7 7 19 19 19 37 37 37 37 61 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 Nom. Thick. of Insulation mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.8 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Outer sheath mm 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 3.0 3.2 Overall Diameter of cable mm 35.0 38.0 40.5 44.0 49.0 51.5 54.5 58.5 64.5 71.0 Weight of cable, approx. kg/km 1613 1992 2418 3133 4036 4832 5759 6900 8790 10829

ELECTRICAL DATA AC Voltage test for 5 min. kV 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5

Partial Discharge test at max. 10ρC kV 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.197 0.160 0.1281 0.0984 0.0799 Insulation Resistance at 20°C Μ.Ω.km 2500 2000 2000 2000 1500 1500 1500 1500 1000 1000 Capacitance µF/km 0.258 0.291 0.318 0.361 0.413 0.448 0.485 0.531 0.573 0.596 Inductance mH/km 0.363 0.342 0.328 0.311 0.296 0.287 0.279 0.271 0.264 0.259 Reactance Ω/km 0.114 0.107 0.103 0.098 0.093 0.090 0.088 0.085 0.083 0.082 Current Carrying Capacity :

- Buried direct **) A 129 153 181 221 262 298 334 377 434 489 in ground at 20°C- In Air at 30°C A 142 170 204 253 304 351 398 455 531 606

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / WDepth of laying = 0.8 m

3.6/6 (7.2) kV XLPE/PVC 3 x (25 - 300)mm²

XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables

(B-1)

Page 11: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 3 3 3 3 3 3 3 3 3 3 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 No. of Wire - 7 7 19 19 19 37 37 37 37 61 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 Nom. Thick. of Insulation mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Outer sheath mm 2.2 2.3 2.4 2.5 2.7 2.8 2.9 3.0 3.1 3.3 Overall Diameter of cable mm 39.5 42.5 45.0 48.5 53.0 56.0 59.0 63.5 68.5 74.0 Weight of cable, approx. kg/km 1864 2260 2696 3433 4387 5203 6150 7350 9173 11160

ELECTRICAL DATA AC Voltage test for 5 min. kV 21 21 21 21 21 21 21 21 21 21

Partial Discharge test at max. 10ρC kV 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.197 0.160 0.1281 0.0984 0.0799 Insulation Resistance at 20°C Μ.Ω.km 3000 2500 2500 2000 2000 2000 2000 1500 1500 1500 Capacitance µF/km 0.202 0.226 0.246 0.278 0.315 0.341 0.368 0.401 0.446 0.492 Inductance mH/km 0.389 0.367 0.352 0.332 0.315 0.305 0.296 0.287 0.277 0.269 Reactance Ω/km 0.122 0.115 0.110 0.104 0.099 0.096 0.093 0.090 0.087 0.084 Current Carrying Capacity :

- Buried direct **) A 129 153 181 221 262 298 334 377 434 489 in ground at 20°C- In Air at 30°C A 142 170 204 253 304 351 398 455 531 606

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / WDepth of laying = 0.8 m

6/10 (12) kV XLPE/PVC 3 x (25 - 300)mm²

XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables

(B-2)

Page 12: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 3 3 3 3 3 3 3 3 3 3 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 No. of Wire - 7 7 19 19 19 37 37 37 37 61 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 Nom. Thick. of Insulation mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Outer sheath mm 2.4 2.5 2.6 2.7 2.8 2.9 3.0 3.1 3.3 3.5 Overall Diameter of cable mm 45.0 47.5 50.0 53.5 58.0 61.0 64.5 68.0 73.5 79.0 Weight of cable, approx. kg/km 2184 2598 3057 3818 4775 5608 6608 7800 9698 11718

ELECTRICAL DATA AC Voltage test for 5 min. kV 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5

Partial Discharge test at max. 10ρC kV 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.197 0.160 0.1281 0.0984 0.0799 Insulation Resistance at 20°C Μ.Ω.km 3500 3000 3000 2500 2500 2500 2000 2000 2000 1500 Capacitance µF/km 0.168 0.186 0.202 0.226 0.255 0.275 0.296 0.322 0.356 0.392 Inductance mH/km 0.415 0.391 0.374 0.353 0.334 0.323 0.314 0.303 0.292 0.283 Reactance Ω/km 0.130 0.123 0.118 0.111 0.105 0.102 0.098 0.095 0.092 0.089 Current Carrying Capacity :

- Buried direct **) A 129 153 181 221 262 298 334 377 434 489 in ground at 20°C- In Air at 30°C A 142 170 204 253 304 351 398 455 531 606

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / WDepth of laying = 0.8 m

8.7/15 (17.5) kV XLPE/PVC 3 x (25 - 300)mm²

XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables

(B-3)

Page 13: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 3 3 3 3 3 3 3 3 3 Nom. Cross-section area mm² 35 50 70 95 120 150 185 240 300 No. of Wire - 7 19 19 19 37 37 37 37 61 Diameter of Conductor, approx. *) mm 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 Nom. Thick. of Insulation mm 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Outer sheath mm 2.6 2.7 2.8 3.0 3.1 3.2 3.3 3.5 3.6 Overall Diameter of cable mm 52.5 55.0 58.5 63.5 66.5 69.5 73.5 78.5 84 Weight of cable, approx. kg/km 2995 3425 4213 5254 6110 7100 8323 10256 12280

ELECTRICAL DATA AC Voltage test for 5 min. kV 42 42 42 42 42 42 42 42 42

Partial Discharge test at max. 10ρC kV 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 DC Resistance at 20°C Ω/km 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 AC Resistance at 90°C Ω/km 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0799 Insulation Resistance at 20°C Μ.Ω.km 3500 3500 3000 3000 2500 2500 2500 2000 2000 Capacitance µF/km 0.161 0.174 0.194 0.218 0.234 0.251 0.272 0.300 0.329 Inductance mH/km 0.412 0.395 0.372 0.352 0.340 0.329 0.318 0.306 0.295 Reactance Ω/km 0.129 0.124 0.117 0.110 0.107 0.103 0.100 0.096 0.093 Current Carrying Capacity :

- Buried direct **) A 153 181 221 262 298 334 377 434 489 in ground at 20°C- In Air at 30°C A 170 204 253 304 351 398 455 531 606

Short circuit current rating at 1 sec. (approx.) kA 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / WDepth of laying = 0.8 m

12/20 (24) kV XLPE/PVC 3 x (35 - 300)mm²

XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables

(B4)

Page 14: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 3 3 3 3 3 3 3 Nom. Cross-section area mm² 50 70 95 120 150 185 240 No. of Wire - 19 19 19 37 37 37 37 Diameter of Conductor, approx. *) mm 8.1 9.7 11.6 12.9 14.3 16.0 18.3 Nom. Thick. of Insulation mm 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Outer sheath mm 3.1 3.2 3.3 3.4 3.6 3.7 3.8 Overall Diameter of cable mm 67.0 71.0 75.0 78 81.5 85.5 90.5 Weight of cable, approx. kg/km 4504 5351 6405 7310 8348 9667 11645

ELECTRICAL DATA AC Voltage test for 5 min. kV 63 63 63 63 63 63 63

Partial Discharge test at max. 10ρC kV 31.1 31.1 31.1 31.1 31.1 31.1 31.1 DC Resistance at 20°C Ω/km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 AC Resistance at 90°C Ω/km 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 Insulation Resistance at 20°C Μ.Ω.km 4500 4000 3500 3500 3000 3000 2500 Capacitance µF/km 0.136 0.151 0.167 0.179 0.191 0.206 0.225 Inductance mH/km 0.436 0.411 0.388 0.375 0.362 0.35 0.335 Reactance Ω/km 0.137 0.129 0.122 0.118 0.114 0.110 0.105 Current Carrying Capacity :

- Buried direct **) A 181 221 262 298 334 377 434 in ground at 20°C- In Air at 30°C A 204 253 304 351 398 455 531

Short circuit current rating at 1 sec. (approx.) kA 7.0 9.8 13.3 16.9 21.1 26.0 33.8 Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / WDepth of laying = 0.8 m

18/30 (36) kV XLPE/PVC 3 x (50 - 240)mm²

XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables

(B5)

Page 15: Catalogue MV 07

According to : IEC 60502-2

XLPE Insulated, Copper Tape Shielded, Round Aluminium Wire Armoured

Copper Conductor

XLPE Insulation

Conductor Screen

Insulation Screen

Copper Tape Screen

PVC Separation Sheath

Round Aluminium Wire Armour

PVC Sheath (Red or Black colour)

Binding Tape (manufacturer's option)

Binding Tape (manufacturer's option)

(3.6/6 kV ~ 18/30 kV) XLPE/AWA/PVC

and PVC Sheathed Cables

AFFILIATE OFSUMITOMO ELECTRIC INDUSTRIES,LTD - JAPAN

PT. SUMI INDO KABEL Tbk.KABELSI

(C)

Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Longitudinally Water blocking characteristic.* Anti termite performance.* Tin coated Copper conductor.* Copper wire screen.* Polyethylene / Low smoke Halogen Free sheath.

Page 16: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 1 1 1 1 1 1 1 1 1 1 1 1 1 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 400 500 630 No. of Wire - 7 7 19 19 19 37 37 37 37 61 61 61 91 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 23.4 26.5 30.3 Nom. Thick. of Insulation mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.8 3.0 3.2 3.2 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.3 1.4 Nom. Diameter of Round Aluminium wire mm 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.5 2.5 Nom. Thick. of Outer sheath mm 1.8 1.8 1.8 1.8 1.9 1.9 2.0 2.1 2.1 2.2 2.3 2.5 2.6 Overall Diameter of cable mm 23.5 24.5 25.5 27.5 29.0 30.5 32.0 35.0 37.5 40.5 44.0 48.5 52.5 Weight of cable, approx. kg/km 798 927 1071 1314 1615 1875 2197 2663 3277 3958 4862 6183 7678

ELECTRICAL DATA AC Voltage test for 5 min. kV 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 Partial Discharge test at max. 10ρC kV 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 0.0614 0.0482 0.0376 Insulation Resistance at 20°C Μ.Ω.km 2500 2000 2000 2000 1500 1500 1500 1500 1000 1000 1000 1000 1000 Capacitance µF/km 0.258 0.291 0.318 0.361 0.413 0.448 0.485 0.531 0.573 0.596 0.605 0.637 0.715 Inductance (Trefoil) mH/km 0.465 0.436 0.418 0.397 0.372 0.361 0.350 0.345 0.332 0.323 0.315 0.310 0.299 Reactance (Trefoil) Ω/km 0.146 0.137 0.131 0.125 0.117 0.113 0.110 0.108 0.104 0.101 0.099 0.097 0.094 Current Carrying Capacity : - Buried direct in ground at 20°C **) (Trefoil) A 140 166 196 239 285 323 361 406 469 526 590 * 655 * 740

(Flat spaced) A 144 172 203 246 293 332 366 410 470 524 572 * 650 * 730 - In Air at 30°C (Trefoil) A 163 198 238 296 361 417 473 543 641 735 845 * 940 * 1080

(Flat spaced) A 196 238 286 356 434 500 559 637 745 846 938 * 1075 * 1235 (Flat touching) A 167 203 243 303 369 426 481 550 647 739 837 * 945 * 1080

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 56.4 70.5 88.8*) Diameter compacted shape * typical data

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

3.6/6 (7.2) kV XLPE/AWA/PVC 1 x (25 - 630)mm²

XLPE Insulated, Copper Tape Shielded, Round Aluminium Wire Armoured and PVC Sheathed Cables

(C-1)

Page 17: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 1 1 1 1 1 1 1 1 1 1 1 1 1 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 400 500 630 No. of Wire - 7 7 19 19 19 37 37 37 37 61 61 61 91 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 23.4 26.5 30.3 Nom. Thick. of Insulation mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.3 1.3 1.4 Nom. Diameter of Round Aluminium wire mm 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.5 2.5 2.5 Nom. Thick. of Outer sheath mm 1.8 1.8 1.8 1.9 1.9 2.0 2.1 2.1 2.2 2.3 2.4 2.5 2.6 Overall Diameter of cable mm 25.5 26.5 27.5 29.5 31.0 33.5 35.0 37.0 39.5 42.0 45.5 49.0 53.0 Weight of cable, approx. kg/km 889 1022 1169 1416 1722 2084 2413 2795 3414 4079 5088 6212 7722

ELECTRICAL DATA AC Voltage test for 5 min. kV 21 21 21 21 21 21 21 21 21 21 21 21 21 Partial Discharge test at max. 10ρC kV 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 0.0614 0.0482 0.0376 Insulation Resistance at 20°C Μ.Ω.km 3000 2500 2500 2000 2000 2000 2000 1500 1500 1500 1500 1000 1000 Capacitance µF/km 0.202 0.226 0.246 0.278 0.315 0.341 0.368 0.401 0.446 0.492 0.545 0.605 0.679 Inductance (Trefoil) mH/km 0.481 0.452 0.433 0.411 0.385 0.379 0.368 0.356 0.343 0.330 0.322 0.312 0.300 Reactance (Trefoil) Ω/km 0.151 0.142 0.136 0.129 0.121 0.119 0.115 0.112 0.108 0.104 0.101 0.098 0.094 Current Carrying Capacity : - Buried direct in ground at 20°C **) (Trefoil) A 140 166 196 239 285 323 361 406 469 526 590 * 655 * 740

(Flat spaced) A 144 172 203 246 293 332 366 410 470 524 572 * 650 * 730 - In Air at 30°C (Trefoil) A 163 198 238 296 361 417 473 543 641 735 845 * 940 * 1080

(Flat spaced) A 196 238 286 356 434 500 559 637 745 846 938 * 1075 * 1235 (Flat touching) A 167 203 243 303 369 426 481 550 647 739 837 * 945 * 1080

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 56.4 70.5 88.8*) Diameter compacted shape * typical data

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

6/10 (12) kV XLPE/AWA/PVC 1 x (25 - 630)mm²

XLPE Insulated, Copper Tape Shielded, Round Aluminium Wire Armoured and PVC Sheathed Cables

(C-2)

Page 18: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 1 1 1 1 1 1 1 1 1 1 1 1 1 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 400 500 630 No. of Wire - 7 7 19 19 19 37 37 37 37 61 61 61 91 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 23.4 26.5 30.3 Nom. Thick. of Insulation mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.3 1.4 1.4 Nom. Diameter of Round Aluminium wire mm 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 2.5 Nom. Thick. of Outer sheath mm 1.8 1.9 1.9 2.0 2.0 2.1 2.1 2.2 2.3 2.3 2.5 2.6 2.7 Overall Diameter of cable mm 27.5 29.0 30.0 31.5 34.5 36.0 37.5 39.0 41.5 44.0 48.0 51.5 55.5 Weight of cable, approx. kg/km 1000 1137 1287 1553 1948 2239 2556 2961 3589 4244 5286 6457 7950

ELECTRICAL DATA AC Voltage test for 5 min. kV 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 Partial Discharge test at max. 10ρC kV 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 0.0614 0.0482 0.0376 Insulation Resistance at 20°C Μ.Ω.km 3500 3000 3000 2500 2500 2500 2000 2000 2000 1500 1500 1500 1500 Capacitance µF/km 0.168 0.186 0.202 0.226 0.255 0.275 0.296 0.322 0.356 0.392 0.432 0.478 0.535 Inductance (Trefoil) mH/km 0.496 0.470 0.450 0.424 0.407 0.394 0.381 0.367 0.352 0.339 0.332 0.322 0.310 Reactance (Trefoil) Ω/km 0.156 0.148 0.142 0.133 0.128 0.124 0.120 0.115 0.111 0.107 0.104 0.101 0.097 Current Carrying Capacity : - Buried direct in ground at 20°C **) (Trefoil) A 140 166 196 239 285 323 361 406 469 526 590 * 655 * 740

(Flat spaced) A 144 172 203 246 293 332 366 410 470 524 572 * 650 * 730 - In Air at 30°C (Trefoil) A 163 198 238 296 361 417 473 543 641 735 845 * 940 * 1080

(Flat spaced) A 196 238 286 356 434 500 559 637 745 846 938 * 1075 * 1235 (Flat touching) A 167 203 243 303 369 426 481 550 647 739 837 * 945 * 1080

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 56.4 70.5 88.8*) Diameter compacted shape * typical data

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

8.7/15 (17.5) kV XLPE/AWA/PVC 1 x (25 - 630)mm²

XLPE Insulated, Copper Tape Shielded, Round Aluminium Wire Armoured and PVC Sheathed Cables

(C-3)

Page 19: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 1 1 1 1 1 1 1 1 1 1 1 1 Nom. Cross-section area mm² 35 50 70 95 120 150 185 240 300 400 500 630 No. of Wire - 7 19 19 19 37 37 37 37 61 61 61 91 Diameter of Conductor, approx. *) mm 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 23.4 26.5 30.3 Nom. Thick. of Insulation mm 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.3 1.3 1.4 1.5 Nom. Diameter of Round Aluminium wire mm 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 Nom. Thick. of Outer sheath mm 1.9 2.0 2.1 2.1 2.2 2.2 2.3 2.3 2.5 2.6 2.7 2.8 Overall Diameter of cable mm 31.0 32.5 35.0 37.0 38.5 39.5 41.5 44.0 47.5 51.0 54.0 58.0 Weight of cable, approx. kg/km 1258 1426 1775 2105 2402 2725 3137 3764 4606 5507 6678 8224

ELECTRICAL DATA AC Voltage test for 5 min. kV 42 42 42 42 42 42 42 42 42 42 42 42 Partial Discharge test at max. 10ρC kV 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 DC Resistance at 20°C Ω/km 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 AC Resistance at 90°C Ω/km 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 0.0614 0.0482 0.0376 Insulation Resistance at 20°C Μ.Ω.km 3500 3500 3000 3000 2500 2500 2500 2000 2000 2000 1500 1500 Capacitance µF/km 0.161 0.174 0.194 0.218 0.234 0.251 0.272 0.300 0.329 0.362 0.399 0.445 Inductance (Trefoil) mH/km 0.483 0.467 0.445 0.412 0.407 0.392 0.379 0.364 0.355 0.344 0.331 0.318 Reactance (Trefoil) Ω/km 0.152 0.147 0.140 0.132 0.128 0.123 0.119 0.114 0.111 0.108 0.104 0.100 Current Carrying Capacity : - Buried direct in ground at 20°C **) (Trefoil) A 166 196 239 285 323 361 406 469 526 590 * 655 * 740

(Flat spaced) A 172 203 246 293 332 366 410 470 524 572 * 650 * 730 - In Air at 30°C (Trefoil) A 198 238 296 361 417 473 543 641 735 845 * 940 * 1080

(Flat spaced) A 238 286 356 434 500 559 637 745 846 938 * 1075 * 1235 (Flat touching) A 203 243 303 369 426 481 550 647 739 837 * 945 * 1080

Short circuit current rating at 1 sec. (approx.) kA 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 56.4 70.5 88.8*) Diameter compacted shape * typical data

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

12/20 (24) kV XLPE/AWA/PVC 1 x (35 - 630)mm²

XLPE Insulated, Copper Tape Shielded, Round Aluminium Wire Armoured and PVC Sheathed Cables

(C-4)

Page 20: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 1 1 1 1 1 1 1 1 1 1 1 Nom. Cross-section area mm² 50 70 95 120 150 185 240 300 400 500 630 No. of Wire - 19 19 19 37 37 37 37 61 61 61 91 Diameter of Conductor, approx. *) mm 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 23.4 26.5 30.3 Nom. Thick. of Insulation mm 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.2 1.2 1.2 1.2 1.3 1.3 1.3 1.4 1.4 1.5 1.6 Nom. Diameter of Round Aluminium wire mm 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5 Nom. Thick. of Outer sheath mm 2.2 2.2 2.3 2.3 2.4 2.5 2.6 2.6 2.7 2.8 3.0 Overall Diameter of cable mm 38.5 40.5 42.5 43.5 46.0 48.0 50.5 53.0 56.0 59.5 64.0 Weight of cable, approx. kg/km 1878 2151 2506 2797 3287 3727 4402 5114 6040 7243 8854

ELECTRICAL DATA AC Voltage test for 5 min. kV 63 63 63 63 63 63 63 63 63 63 63 Partial Discharge test at max. 10ρC kV 31.1 31.1 31.1 31.1 31.1 31.1 31.1 31.1 31.1 31.1 31.1 DC Resistance at 20°C Ω/km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 AC Resistance at 90°C Ω/km 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 0.0614 0.0482 0.0376 Insulation Resistance at 20°C Μ.Ω.km 4500 4000 3500 3500 3000 3000 2500 2500 2500 2000 2000 Capacitance µF/km 0.136 0.151 0.167 0.179 0.191 0.206 0.225 0.246 0.269 0.295 0.327 Inductance (Trefoil) mH/km 0.500 0.474 0.448 0.432 0.422 0.408 0.392 0.377 0.363 0.350 0.338 Reactance (Trefoil) Ω/km 0.157 0.149 0.141 0.136 0.133 0.128 0.123 0.118 0.114 0.110 0.106 Current Carrying Capacity : - Buried direct in ground at 20°C **) (Trefoil) A 196 239 285 323 361 406 469 526 590 * 655 * 740

(Flat spaced) A 203 246 293 332 366 410 470 524 572 * 650 * 730 - In Air at 30°C (Trefoil) A 238 296 361 417 473 543 641 735 845 * 940 * 1080

(Flat spaced) A 286 356 434 500 559 637 745 846 938 * 1075 * 1235 (Flat touching) A 243 303 369 426 481 550 647 739 837 * 945 * 1080

Short circuit current rating at 1 sec. (approx.) kA 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 56.4 70.5 88.8*) Diameter compacted shape * typical data

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

18/30 (36) kV XLPE/AWA/PVC 1 x (50 - 630)mm²

XLPE Insulated, Copper Tape Shielded, Round Aluminium Wire Armoured and PVC Sheathed Cables

(C-5)

Page 21: Catalogue MV 07

According to : IEC 60502-2

Copper Conductor

XLPE InsulationConductor Screen

Insulation ScreenIdentification tape(Red, Yellow, Blue by coloured tape)

Copper Tape Screen

Separation Sheath

Binding Tape (manufacturer's option)

PVC Sheath (Red or Black colour)

Binding Tape (manufacturer's option)

Galvanized Round Steel Wire Armour

AFFILIATE OFSUMITOMO ELECTRIC INDUSTRIES,LTD - JAPAN

PT. SUMI INDO KABEL Tbk.KABELSI

XLPE Insulated, Copper Tape Shielded, Galvanized Round Steel Wire Armoured and PVC Sheathed Cables

(3.6/6 kV ~ 18/30 kV) XLPE/SWA/PVC

(D)

Filler (Polyprophylene yarn, or extruded filler upon request)

Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Longitudinally Water blocking characteristic.* Anti termite performance.* Tin coated Copper conductor.* Copper wire screen.* Polyethylene / Low smoke Halogen Free sheath.

Page 22: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 3 3 3 3 3 3 3 3 3 3 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 No. of Wire - 7 7 19 19 19 37 37 37 37 61 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 Nom. Thick. of Insulation mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.8 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.2 1.3 1.3 1.4 1.4 1.5 1.6 1.6 1.7 1.8 Nom. Diameter of Round Steel wire mm 2.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3.15 3.15 Nom. Thick. of Outer sheath mm 2.3 2.4 2.5 2.6 2.7 2.9 3.0 3.1 3.3 3.5 Overall Diameter of cable mm 41.5 45.0 47.5 51.5 55.5 59.0 62.5 66.0 73.0 80.0 Weight of cable, approx. kg/km 3018 3870 4386 5334 6414 7432 8521 9814 12718 15198

ELECTRICAL DATA AC Voltage test for 5 min. kV 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5

Partial Discharge test at max. 10ρC kV 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.197 0.160 0.1281 0.0984 0.0799 Insulation Resistance at 20°C Μ.Ω.km 2500 2000 2000 2000 1500 1500 1500 1500 1000 1000 Capacitance µF/km 0.258 0.291 0.318 0.361 0.413 0.448 0.485 0.531 0.573 0.596 Inductance mH/km 0.363 0.342 0.328 0.311 0.296 0.287 0.279 0.271 0.264 0.259 Reactance Ω/km 0.114 0.107 0.103 0.098 0.093 0.090 0.088 0.085 0.083 0.082 Current Carrying Capacity :

- Buried direct **) A 129 154 181 220 263 298 332 374 431 482 in ground at 20°C- In Air at 30°C A 143 172 205 253 307 352 397 453 529 599

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / WDepth of laying = 0.8 m

3.6/6 (7.2) kV XLPE/SWA/PVC 3 x (25 - 300)mm²

XLPE Insulated, Copper Tape Shielded, Galvanized Round Steel Wire Armoured and PVC Sheathed Cables

(D-1)

Page 23: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 3 3 3 3 3 3 3 3 3 3 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 No. of Wire - 7 7 19 19 19 37 37 37 37 61 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 Nom. Thick. of Insulation mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.3 1.3 1.4 1.5 1.5 1.6 1.6 1.7 1.8 1.9 Nom. Diameter of Round Steel wire mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3.15 3.15 Nom. Thick. of Outer sheath mm 2.5 2.6 2.7 2.8 2.9 3.0 3.1 3.2 3.4 3.6 Overall Diameter of cable mm 47.0 50.0 52.5 56.5 60.5 64.0 67.0 70.5 77.5 83.5 Weight of cable, approx. kg/km 3848 4372 4925 5903 7010 8023 9076 10421 13402 15769

ELECTRICAL DATA AC Voltage test for 5 min. kV 21 21 21 21 21 21 21 21 21 21

Partial Discharge test at max. 10ρC kV 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.197 0.160 0.1281 0.0984 0.0799 Insulation Resistance at 20°C Μ.Ω.km 3000 2500 2500 2000 2000 2000 2000 1500 1500 1500 Capacitance µF/km 0.202 0.226 0.246 0.278 0.315 0.341 0.368 0.401 0.446 0.492 Inductance mH/km 0.389 0.367 0.352 0.332 0.315 0.305 0.296 0.287 0.277 0.269 Reactance Ω/km 0.122 0.115 0.110 0.104 0.099 0.096 0.093 0.090 0.087 0.084 Current Carrying Capacity :

- Buried direct **) A 129 154 181 220 263 298 332 374 431 482 in ground at 20°C- In Air at 30°C A 143 172 205 253 307 352 397 453 529 599

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / WDepth of laying = 0.8 m

6/10 (12) kV XLPE/SWA/PVC 3 x (25 - 300)mm²

XLPE Insulated, Copper Tape Shielded, Galvanized Round Steel Wire Armoured and PVC Sheathed Cables

(D-2)

Page 24: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 3 3 3 3 3 3 3 3 3 3 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 No. of Wire - 7 7 19 19 19 37 37 37 37 61 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 Nom. Thick. of Insulation mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.4 1.4 1.5 1.5 1.6 1.7 1.7 1.8 1.9 2.0 Nom. Diameter of Round Steel wire mm 2.5 2.5 2.5 2.5 2.5 2.5 3.15 3.15 3.15 3.15 Nom. Thick. of Outer sheath mm 2.6 2.7 2.8 2.9 3.1 3.2 3.3 3.4 3.6 3.8 Overall Diameter of cable mm 52.0 55.0 57.5 61.0 65.5 68.5 73.0 77.5 83.0 88.5 Weight of cable, approx. kg/km 4388 4937 5546 6484 7687 8656 10533 12027 14242 16607

ELECTRICAL DATA AC Voltage test for 5 min. kV 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5

Partial Discharge test at max. 10ρC kV 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.197 0.160 0.1281 0.0984 0.0799 Insulation Resistance at 20°C Μ.Ω.km 3500 3000 3000 2500 2500 2500 2000 2000 2000 1500 Capacitance µF/km 0.168 0.186 0.202 0.226 0.255 0.275 0.296 0.322 0.356 0.392 Inductance mH/km 0.415 0.391 0.374 0.353 0.334 0.323 0.314 0.303 0.292 0.283 Reactance Ω/km 0.130 0.123 0.118 0.111 0.105 0.102 0.098 0.095 0.092 0.089 Current Carrying Capacity :

- Buried direct **) A 129 154 181 220 263 298 332 374 431 482 in ground at 20°C- In Air at 30°C A 143 172 205 253 307 352 397 453 529 599

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / WDepth of laying = 0.8 m

8.7/15 (17.5) kV XLPE/SWA/PVC 3 x (25 - 300)mm²

XLPE Insulated, Copper Tape Shielded, Galvanized Round Steel Wire Armoured and PVC Sheathed Cables

(D-3)

Page 25: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 3 3 3 3 3 3 3 3 3 Nom. Cross-section area mm² 35 50 70 95 120 150 185 240 300 No. of Wire - 7 19 19 19 37 37 37 37 61 Diameter of Conductor, approx. *) mm 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 Nom. Thick. of Insulation mm 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.5 1.6 1.6 1.7 1.8 1.8 1.9 2.0 2.1 Nom. Diameter of Round Steel wire mm 2.5 2.5 2.5 2.5 3.15 3.15 3.15 3.15 3.15 Nom. Thick. of Outer sheath mm 2.9 3.0 3.1 3.2 3.4 3.6 3.6 3.8 3.9 Overall Diameter of cable mm 60.5 63.0 66.5 70.5 75.5 78.5 82.5 88.0 93.5 Weight of cable, approx. kg/km 5600 6228 7166 8332 10206 11400 12866 15143 17550

ELECTRICAL DATA AC Voltage test for 5 min. kV 42 42 42 42 42 42 42 42 42

Partial Discharge test at max. 10ρC kV 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 DC Resistance at 20°C Ω/km 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 AC Resistance at 90°C Ω/km 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 Insulation Resistance at 20°C Μ.Ω.km 3500 3500 3000 3000 2500 2500 2500 2000 2000 Capacitance µF/km 0.161 0.174 0.194 0.218 0.234 0.251 0.272 0.300 0.329 Inductance mH/km 0.412 0.395 0.372 0.352 0.340 0.329 0.318 0.306 0.295 Reactance Ω/km 0.129 0.124 0.117 0.110 0.107 0.103 0.100 0.096 0.093 Current Carrying Capacity :

- Buried direct **) A 154 181 220 263 298 332 374 431 482 in ground at 20°C- In Air at 30°C A 172 205 253 307 352 397 453 529 599

Short circuit current rating at 1 sec. (approx.) kA 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / WDepth of laying = 0.8 m

12/20 (24) kV XLPE/SWA/PVC 3 x (35 - 300)mm²

XLPE Insulated, Copper Tape Shielded, Galvanized Round Steel Wire Armoured and PVC Sheathed Cables

(D-4)

Page 26: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 3 3 3 3 3 3 3 Nom. Cross-section area mm² 50 70 95 120 150 185 240 No. of Wire - 19 19 19 37 37 37 37 Diameter of Conductor, approx. *) mm 8.1 9.7 11.6 12.9 14.3 16.0 18.3 Nom. Thick. of Insulation mm 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.8 1.8 1.9 2.0 2.0 2.1 2.2 Nom. Diameter of Round Steel wire mm 3.15 3.15 3.15 3.15 3.15 3.15 3.15 Nom. Thick. of Outer sheath mm 3.4 3.5 3.7 3.8 3.9 4.0 4.2 Overall Diameter of cable mm 76.0 80.0 84.5 87.5 91.0 95.0 100.5 Weight of cable, approx. kg/km 8667 9720 11084 12168 13415 15010 17359

ELECTRICAL DATA AC Voltage test for 5 min. kV 63 63 63 63 63 63 63

Partial Discharge test at max. 10ρC kV 31.1 31.1 31.1 31.1 31.1 31.1 31.1 DC Resistance at 20°C Ω/km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 AC Resistance at 90°C Ω/km 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 Insulation Resistance at 20°C Μ.Ω.km 4500 4000 3500 3500 3000 3000 2500 Capacitance µF/km 0.136 0.151 0.167 0.179 0.191 0.206 0.225 Inductance mH/km 0.436 0.411 0.388 0.375 0.362 0.350 0.335 Reactance Ω/km 0.137 0.129 0.122 0.118 0.114 0.110 0.105 Current Carrying Capacity :

- Buried direct **) A 181 220 263 298 332 374 431 in ground at 20°C- In Air at 30°C A 205 253 307 352 397 453 529

Short circuit current rating at 1 sec. (approx.) kA 7.0 9.8 13.3 16.9 21.1 26.0 33.8 Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / WDepth of laying = 0.8 m

18/30 (36) kV XLPE/SWA/PVC 3 x (50 - 240)mm²

XLPE Insulated, Copper Tape Shielded, Galvanized Round Steel Wire Armoured and PVC Sheathed Cables

(D-5)

Page 27: Catalogue MV 07

According to : IEC 60502-2

Copper Conductor

XLPE Insulation

Conductor Screen

Insulation Screen

Copper Tape Screen

PVC Separation Sheath

Double Aluminium Tape Armour

PVC Sheath (Red or Black colour)

Binding Tape (manufacturer's option)

XLPE Insulated, Copper Tape Shielded, Double Aluminium Tape Armoured

(3.6/6 kV ~ 18/30 kV) XLPE/DATA/PVC

and PVC Sheathed Cables

AFFILIATE OFSUMITOMO ELECTRIC INDUSTRIES,LTD - JAPAN

PT. SUMI INDO KABEL Tbk.KABELSI

(E)

Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Longitudinally Water blocking characteristic.* Anti termite performance.* Tin coated Copper conductor.* Copper wire screen.* Polyethylene / Low smoke Halogen Free sheath.

Page 28: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 1 1 1 1 1 1 1 1 1 1 1 1 1 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 400 500 630 No. of Wire - 7 7 19 19 19 37 37 37 37 61 61 61 91 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 23.4 26.5 30.3 Nom. Thick. of Insulation mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.8 3.0 3.2 3.2 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.3 1.4 Nom. Thickness of Aluminium tape mm 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 Nom. Thick. of Outer sheath mm 1.8 1.8 1.8 1.8 1.8 1.9 1.9 2.0 2.1 2.1 2.3 2.4 2.5 Overall Diameter of cable mm 21.5 23.0 24.0 25.5 27.5 28.5 30.0 32.0 34.5 37.5 41.0 45.0 49.5 Weight of cable, approx. kg/km 713 837 978 1214 1507 1766 2065 2448 3058 3720 4608 5734 7282

ELECTRICAL DATA AC Voltage test for 5 min. kV 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 Partial Discharge test at max. 10ρC kV 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 0.0614 0.0482 0.0376 Insulation Resistance at 20°C Μ.Ω.km 2500 2000 2000 2000 1500 1500 1500 1500 1000 1000 1000 1000 1000 Capacitance µF/km 0.258 0.291 0.318 0.361 0.413 0.448 0.485 0.531 0.573 0.596 0.605 0.637 0.715 Inductance (Trefoil) mH/km 0.447 0.424 0.406 0.382 0.361 0.347 0.337 0.327 0.315 0.307 0.301 0.295 0.287 Reactance (Trefoil) Ω/km 0.140 0.133 0.127 0.120 0.113 0.109 0.106 0.103 0.099 0.097 0.095 0.093 0.090 Current Carrying Capacity : - Buried direct in ground at 20°C **) (Trefoil) A 140 166 196 239 285 323 361 406 469 526 590 * 655 * 740

(Flat spaced) A 144 172 203 246 293 332 366 410 470 524 572 * 650 * 730 - In Air at 30°C (Trefoil) A 163 198 238 296 361 417 473 543 641 735 845 * 940 * 1080

(Flat spaced) A 196 238 286 356 434 500 559 637 745 846 938 * 1075 * 1235 (Flat touching) A 167 203 243 303 369 426 481 550 647 739 837 * 945 * 1080

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 56.4 70.5 88.8*) Diameter compacted shape * typical data

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

3.6/6 (7.2) kV XLPE/DATA/PVC 1 x (25 - 630)mm²

XLPE Insulated, Copper Tape Shielded, Double Aluminium Tape Armoured and PVC Sheathed Cables

(E-1)

Page 29: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 1 1 1 1 1 1 1 1 1 1 1 1 1 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 400 500 630 No. of Wire - 7 7 19 19 19 37 37 37 37 61 61 61 91 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 23.4 26.5 30.3 Nom. Thick. of Insulation mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.3 1.3 1.4 Nom. Thickness of Aluminium tape mm 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 Nom. Thick. of Outer sheath mm 1.8 1.8 1.8 1.8 1.9 1.9 2.0 2.1 2.1 2.2 2.3 2.4 2.5 Overall Diameter of cable mm 23.5 25.5 26.0 27.5 29.5 30.5 32.5 34.0 36.5 39 42.0 45.5 50.0 Weight of cable, approx. kg/km 800 927 1070 1310 1610 1874 2191 2581 3170 3813 4685 5765 7315

ELECTRICAL DATA AC Voltage test for 5 min. kV 21 21 21 21 21 21 21 21 21 21 21 21 21 Partial Discharge test at max. 10ρC kV 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 0.0614 0.0482 0.0376 Insulation Resistance at 20°C Μ.Ω.km 3000 2500 2500 2000 2000 2000 2000 1500 1500 1500 1500 1000 1000 Capacitance µF/km 0.202 0.226 0.246 0.278 0.315 0.341 0.368 0.401 0.446 0.492 0.545 0.605 0.679 Inductance (Trefoil) mH/km 0.465 0.444 0.422 0.397 0.375 0.361 0.353 0.339 0.327 0.315 0.306 0.297 0.289 Reactance (Trefoil) Ω/km 0.146 0.140 0.133 0.125 0.118 0.113 0.111 0.107 0.103 0.099 0.096 0.093 0.091 Current Carrying Capacity : - Buried direct in ground at 20°C **) (Trefoil) A 140 166 196 239 285 323 361 406 469 526 590 * 655 * 740

(Flat spaced) A 144 172 203 246 293 332 366 410 470 524 572 * 650 * 730 - In Air at 30°C (Trefoil) A 163 198 238 296 361 417 473 543 641 735 845 * 940 * 1080

(Flat spaced) A 196 238 286 356 434 500 559 637 745 846 938 * 1075 * 1235 (Flat touching) A 167 203 243 303 369 426 481 550 647 739 837 * 945 * 1080

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 56.4 70.5 88.8*) Diameter compacted shape * typical data

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

6/10 (12) kV XLPE/DATA/PVC 1 x (25 - 630)mm²

(E-2)

XLPE Insulated, Copper Tape Shielded, Double Aluminium Tape Armoured and PVC Sheathed Cables

Page 30: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 1 1 1 1 1 1 1 1 1 1 1 1 1 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 400 500 630 No. of Wire - 7 7 19 19 19 37 37 37 37 61 61 61 91 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 23.4 26.5 30.3 Nom. Thick. of Insulation mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.3 1.4 1.4 Nom. Thickness of Aluminium tape mm 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 Nom. Thick. of Outer sheath mm 1.8 1.8 1.9 1.9 2.0 2.0 2.1 2.1 2.2 2.3 2.4 2.5 2.6 Overall Diameter of cable mm 26.0 27.0 28.0 29.5 32.0 33.0 34.5 36.5 39.0 41.5 44.5 48.0 52.5 Weight of cable, approx. kg/km 902 1033 1180 1426 1745 2013 2337 2718 3332 3985 4848 5982 7528

ELECTRICAL DATA AC Voltage test for 5 min. kV 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 Partial Discharge test at max. 10ρC kV 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 0.0614 0.0482 0.0376 Insulation Resistance at 20°C Μ.Ω.km 3500 3000 3000 2500 2500 2500 2000 2000 2000 1500 1500 1500 1500 Capacitance µF/km 0.168 0.186 0.202 0.226 0.255 0.275 0.296 0.322 0.356 0.392 0.432 0.478 0.535 Inductance (Trefoil) mH/km 0.485 0.456 0.437 0.411 0.392 0.376 0.365 0.354 0.340 0.328 0.317 0.307 0.299 Reactance (Trefoil) Ω/km 0.152 0.143 0.137 0.129 0.123 0.118 0.115 0.111 0.107 0.103 0.100 0.097 0.094 Current Carrying Capacity : - Buried direct in ground at 20°C **) (Trefoil) A 140 166 196 239 285 323 361 406 469 526 590 * 655 * 740

(Flat spaced) A 144 172 203 246 293 332 366 410 470 524 572 * 650 * 730 - In Air at 30°C (Trefoil) A 163 198 238 296 361 417 473 543 641 735 845 * 940 * 1080

(Flat spaced) A 196 238 286 356 434 500 559 637 745 846 938 * 1075 * 1235 (Flat touching) A 167 203 243 303 369 426 481 550 647 739 837 * 945 * 1080

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 56.4 70.5 88.8*) Diameter compacted shape * typical data

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

8.7/15 (17.5) kV XLPE/DATA/PVC 1 x (25 - 630)mm²

(E-3)

XLPE Insulated, Copper Tape Shielded, Double Aluminium Tape Armoured and PVC Sheathed Cables

Page 31: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 1 1 1 1 1 1 1 1 1 1 1 1 Nom. Cross-section area mm² 35 50 70 95 120 150 185 240 300 400 500 630 No. of Wire - 7 19 19 19 37 37 37 37 61 61 61 91 Diameter of Conductor, approx. *) mm 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 23.4 26.5 30.3 Nom. Thick. of Insulation mm 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.3 1.3 1.4 1.5 Nom. Thickness of Aluminium tape mm 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 Nom. Thick. of Outer sheath mm 1.9 1.9 2.0 2.0 2.1 2.1 2.2 2.3 2.4 2.5 2.6 2.7 Overall Diameter of cable mm 29.5 30.5 32.0 34.0 35.5 37.0 39.0 41.5 44.0 47.0 50.5 55.0 Weight of cable, approx. kg/km 1146 1296 1562 1874 2162 2475 2878 3502 4165 5040 6187 7776

ELECTRICAL DATA AC Voltage test for 5 min. kV 42 42 42 42 42 42 42 42 42 42 42 42 Partial Discharge test at max. 10ρC kV 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 DC Resistance at 20°C Ω/km 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 AC Resistance at 90°C Ω/km 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 0.0614 0.0482 0.0376 Insulation Resistance at 20°C Μ.Ω.km 3500 3500 3000 3000 2500 2500 2500 2000 2000 2000 1500 1500 Capacitance µF/km 0.161 0.174 0.194 0.218 0.234 0.251 0.272 0.300 0.329 0.362 0.399 0.445 Inductance (Trefoil) mH/km 0.473 0.454 0.427 0.404 0.391 0.379 0.367 0.352 0.339 0.328 0.318 0.308 Reactance (Trefoil) Ω/km 0.149 0.143 0.134 0.127 0.123 0.119 0.115 0.111 0.107 0.103 0.100 0.097 Current Carrying Capacity : - Buried direct in ground at 20°C **) (Trefoil) A 166 196 239 285 323 361 406 469 526 590 * 655 * 740

(Flat spaced) A 172 203 246 293 332 366 410 470 524 572 * 650 * 730 - In Air at 30°C (Trefoil) A 198 238 296 361 417 473 543 641 735 845 * 940 * 1080

(Flat spaced) A 238 286 356 434 500 559 637 745 846 938 * 1075 * 1235 (Flat touching) A 203 243 303 369 426 481 550 647 739 837 * 945 * 1080

Short circuit current rating at 1 sec. (approx.) kA 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 56.4 70.5 88.8*) Diameter compacted shape * typical data

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

12/20 (24) kV XLPE/DATA/PVC 1 x (35 - 630)mm²

(E-4)

XLPE Insulated, Copper Tape Shielded, Double Aluminium Tape Armoured and PVC Sheathed Cables

Page 32: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 1 1 1 1 1 1 1 1 1 1 1 Nom. Cross-section area mm² 50 70 95 120 150 185 240 300 400 500 630 No. of Wire - 19 19 19 37 37 37 37 61 61 61 91 Diameter of Conductor, approx. *) mm 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 23.4 26.5 30.3 Nom. Thick. of Insulation mm 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.2 1.2 1.2 1.2 1.3 1.3 1.3 1.4 1.4 1.5 1.6 Nom. Thickness of Aluminium tape mm 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 Nom. Thick. of Outer sheath mm 2.1 2.2 2.2 2.3 2.3 2.4 2.5 2.5 2.6 2.7 2.9 Overall Diameter of cable mm 36.0 37.5 39.5 41.0 42.5 44.5 47.0 49.5 52.5 56.0 61.0 Weight of cable, approx. kg/km 1632 1913 2241 2543 2888 3288 3934 4620 5520 6698 8357

ELECTRICAL DATA AC Voltage test for 5 min. kV 63 63 63 63 63 63 63 63 63 63 63 Partial Discharge test at max. 10ρC kV 31.1 31.1 31.1 31.1 31.1 31.1 31.1 31.1 31.1 31.1 31.1 DC Resistance at 20°C Ω/km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 AC Resistance at 90°C Ω/km 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 0.0614 0.0482 0.0376 Insulation Resistance at 20°C Μ.Ω.km 4500 4000 3500 3500 3000 3000 2500 2500 2500 2000 2000 Capacitance µF/km 0.136 0.151 0.167 0.179 0.191 0.206 0.225 0.246 0.269 0.295 0.327 Inductance (Trefoil) mH/km 0.487 0.459 0.434 0.420 0.406 0.393 0.377 0.363 0.350 0.338 0.329 Reactance (Trefoil) Ω/km 0.153 0.144 0.136 0.132 0.128 0.124 0.119 0.114 0.110 0.106 0.103 Current Carrying Capacity : - Buried direct in ground at 20°C **) (Trefoil) A 196 239 285 323 361 406 469 526 590 * 655 * 740

(Flat spaced) A 203 246 293 332 366 410 470 524 572 * 650 * 730 - In Air at 30°C (Trefoil) A 238 296 361 417 473 543 641 735 845 * 940 * 1080

(Flat spaced) A 286 356 434 500 559 637 745 846 938 * 1075 * 1235 (Flat touching) A 243 303 369 426 481 550 647 739 837 * 945 * 1080

Short circuit current rating at 1 sec. (approx.) kA 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 56.4 70.5 88.8*) Diameter compacted shape * typical data

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

18/30 (36) kV XLPE/DATA/PVC 1 x (50 - 630)mm²

(E-5)

XLPE Insulated, Copper Tape Shielded, Double Aluminium Tape Armoured and PVC Sheathed Cables

Page 33: Catalogue MV 07

According to : IEC 60502-2

Identification of core(Red, Yellow, Blue by coloured tape)

Copper Conductor

XLPE Insulation

Conductor Screen

Insulation Screen

Copper Tape Screen

PVC Separation Sheath

Double Galvanized Steel Tape Armour

PVC Sheath (Red or Black colour)

Binding Tape (manufacturer's option)

AFFILIATE OFSUMITOMO ELECTRIC INDUSTRIES,LTD - JAPAN

PT. SUMI INDO KABEL Tbk.KABELSI

XLPE Insulated, Copper Tape Shielded, Double Galvanized Steel Tape Armoured

(3.6/6 kV ~ 18/30 kV) XLPE/DSTA/PVC

and PVC Sheathed Cables

(F)

Filler (Polyprophylene yarn, or extruded filler upon request)

Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Longitudinally Water blocking characteristic.* Anti termite performance.* Tin coated Copper conductor.* Copper wire screen.* Polyethylene / Low smoke Halogen Free sheath.

Page 34: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 3 3 3 3 3 3 3 3 3 3 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 No. of Wire - 7 7 19 19 19 37 37 37 37 61 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 Nom. Thick. of Insulation mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.8 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.2 1.3 1.3 1.4 1.4 1.5 1.6 1.6 1.7 1.8 Nom. Thick. of Steel tape mm 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 Nom. Thick. of Outer sheath mm 2.2 2.3 2.4 2.5 2.6 2.8 2.9 3.0 3.2 3.4 Overall Diameter of cable mm 38.5 41.5 43.5 47.5 52.0 55.5 58.5 62.5 68.0 75.0 Weight of cable, approx. kg/km 2370 2829 3283 4100 5096 6009 7036 8268 10226 12443

ELECTRICAL DATA AC Voltage test for 5 min. kV 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5

Partial Discharge test at max. 10ρC kV 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.197 0.160 0.1281 0.0984 0.0799 Insulation Resistance at 20°C Μ.Ω.km 2500 2000 2000 2000 1500 1500 1500 1500 1000 1000 Capacitance µF/km 0.258 0.291 0.318 0.361 0.413 0.448 0.485 0.531 0.573 0.596 Inductance mH/km 0.363 0.342 0.328 0.311 0.296 0.287 0.279 0.271 0.264 0.259 Reactance Ω/km 0.114 0.107 0.103 0.098 0.093 0.090 0.088 0.085 0.083 0.082 Current Carrying Capacity :

- Buried direct **) A 129 154 181 220 263 298 332 374 431 482 in ground at 20°C- In Air at 30°C A 143 172 205 253 307 352 397 453 529 599

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / WDepth of laying = 0.8 m

3.6/6 (7.2) kV XLPE/DSTA/PVC 3 x (25 - 300)mm²

XLPE Insulated, Copper Tape Shielded, Double Galvanized Steel Tape Armoured and PVC Sheathed Cables

(F-1)

Page 35: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 3 3 3 3 3 3 3 3 3 3 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 No. of Wire - 7 7 19 19 19 37 37 37 37 61 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 Nom. Thick. of Insulation mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.3 1.3 1.4 1.5 1.5 1.6 1.6 1.7 1.8 1.9 Nom. Thick. of Steel tape mm 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 Nom. Thick. of Outer sheath mm 2.4 2.4 2.6 2.7 2.8 2.9 3.0 3.1 3.3 3.5 Overall Diameter of cable mm 43.5 46.0 48.5 52.5 57.0 60.0 63.0 67.0 72.5 78.0 Weight of cable, approx. kg/km 2739 3170 3705 4552 5575 6484 7502 8727 10734 12883

ELECTRICAL DATA AC Voltage test for 5 min. kV 21 21 21 21 21 21 21 21 21 21

Partial Discharge test at max. 10ρC kV 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.197 0.160 0.1281 0.0984 0.0799 Insulation Resistance at 20°C Μ.Ω.km 3000 2500 2500 2000 2000 2000 2000 1500 1500 1500 Capacitance µF/km 0.202 0.226 0.246 0.278 0.315 0.341 0.368 0.401 0.446 0.492 Inductance mH/km 0.389 0.367 0.352 0.332 0.315 0.305 0.296 0.287 0.277 0.269 Reactance Ω/km 0.122 0.115 0.110 0.104 0.099 0.096 0.093 0.090 0.087 0.084 Current Carrying Capacity :

- Buried direct **) A 129 154 181 220 263 298 332 374 431 482 in ground at 20°C- In Air at 30°C A 143 172 205 253 307 352 397 453 529 599

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / WDepth of laying = 0.8 m

6/10 (12) kV XLPE/DSTA/PVC 3 x (25 - 300)mm²

XLPE Insulated, Copper Tape Shielded, Double Galvanized Steel Tape Armoured and PVC Sheathed Cables

(F-2)

Page 36: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 3 3 3 3 3 3 3 3 3 3 Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300 No. of Wire - 7 7 19 19 19 37 37 37 37 61 Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 Nom. Thick. of Insulation mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.4 1.4 1.5 1.5 1.6 1.7 1.7 1.8 1.9 2.0 Nom. Thick. of Steel tape mm 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.8 Nom. Thick. of Outer sheath mm 2.5 2.6 2.7 2.8 3 3.1 3.2 3.3 3.5 3.7 Overall Diameter of cable mm 48.5 51.0 54.0 57.5 62.0 65.0 68.0 72.0 78.0 84.5 Weight of cable, approx. kg/km 3169 3646 4180 5021 6132 7005 8041 9355 11411 14441

ELECTRICAL DATA AC Voltage test for 5 min. kV 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5

Partial Discharge test at max. 10ρC kV 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.197 0.160 0.1281 0.0984 0.0799 Insulation Resistance at 20°C Μ.Ω.km 3500 3000 3000 2500 2500 2500 2000 2000 2000 1500 Capacitance µF/km 0.168 0.186 0.202 0.226 0.255 0.275 0.296 0.322 0.356 0.392 Inductance mH/km 0.415 0.391 0.374 0.353 0.334 0.323 0.314 0.303 0.292 0.283 Reactance Ω/km 0.130 0.123 0.118 0.111 0.105 0.102 0.098 0.095 0.092 0.089 Current Carrying Capacity :

- Buried direct **) A 129 154 181 220 263 298 332 374 431 482 in ground at 20°C- In Air at 30°C A 143 172 205 253 307 352 397 453 529 599

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / WDepth of laying = 0.8 m

8.7/15 (17.5) kV XLPE/DSTA/PVC 3 x (25 - 300)mm²

XLPE Insulated, Copper Tape Shielded, Double Galvanized Steel Tape Armoured and PVC Sheathed Cables

( )

(F-3)

sukarno1
Rectangle
sukarno1
Rectangle
Page 37: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 3 3 3 3 3 3 3 3 3 Nom. Cross-section area mm² 35 50 70 95 120 150 185 240 300 No. of Wire - 7 19 19 19 37 37 37 37 61 Diameter of Conductor, approx. *) mm 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7 Nom. Thick. of Insulation mm 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.5 1.6 1.6 1.7 1.8 1.8 1.9 2.0 2.1 Nom. Thick. of Steel tape mm 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.8 0.8 Nom. Thick. of Outer sheath mm 2.8 2.9 3.0 3.1 3.2 3.3 3.5 3.7 3.8 Overall Diameter of cable mm 56.5 59.0 63.0 67.0 70.0 73.5 77.5 84.0 90.0 Weight of cable, approx. kg/km 4161 4712 5585 6637 7591 8650 10030 12964 15217

ELECTRICAL DATA AC Voltage test for 5 min. kV 42 42 42 42 42 42 42 42 42

Partial Discharge test at max. 10ρC kV 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 DC Resistance at 20°C Ω/km 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 AC Resistance at 90°C Ω/km 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0779 Insulation Resistance at 20°C Μ.Ω.km 3500 3500 3000 3000 2500 2500 2500 2000 2000 Capacitance µF/km 0.161 0.174 0.194 0.218 0.234 0.251 0.272 0.300 0.329 Inductance mH/km 0.412 0.395 0.372 0.352 0.340 0.329 0.318 0.306 0.295 Reactance Ω/km 0.129 0.124 0.117 0.110 0.107 0.103 0.100 0.096 0.093 Current Carrying Capacity :

- Buried direct **) A 154 181 220 263 298 332 374 431 482 in ground at 20°C- In Air at 30°C A 172 205 253 307 352 397 453 529 599

Short circuit current rating at 1 sec. (approx.) kA 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3 Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / WDepth of laying = 0.8 m

12/20 (24) kV XLPE/DSTA/PVC 3 x (35 - 300)mm²

XLPE Insulated, Copper Tape Shielded, Double Galvanized Steel Tape Armoured and PVC Sheathed Cables

(F-4)

Page 38: Catalogue MV 07

CONSTRUCTION DATA No. of Core - 3 3 3 3 3 3 3 Nom. Cross-section area mm² 50 70 95 120 150 185 240 No. of Wire - 19 19 19 37 37 37 37 Diameter of Conductor, approx. *) mm 8.1 9.7 11.6 12.9 14.3 16.0 18.3 Nom. Thick. of Insulation mm 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Nom. Thick. of Separation sheath mm 1.8 1.8 1.9 2.0 2.0 2.1 2.2 Nom. Thick. of Steel tape mm 0.5 0.5 0.5 0.8 0.8 0.8 0.8 Nom. Thick. of Outer sheath mm 3.3 3.4 3.5 3.7 3.8 3.9 4.1 Overall Diameter of cable mm 71.0 75.0 79.5 83.5 87.0 91.0 96.5 Weight of cable, approx. kg/km 6037 6965 8156 10040 11186 12643 14891

ELECTRICAL DATA AC Voltage test for 5 min. kV 63 63 63 63 63 63 63

Partial Discharge test at max. 10ρC kV 31.1 31.1 31.1 31.1 31.1 31.1 31.1 DC Resistance at 20°C Ω/km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 AC Resistance at 90°C Ω/km 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 Insulation Resistance at 20°C Μ.Ω.km 4500 4000 3500 3500 3000 3000 2500 Capacitance µF/km 0.136 0.151 0.167 0.179 0.191 0.206 0.225 Inductance mH/km 0.436 0.411 0.388 0.375 0.362 0.350 0.335 Reactance Ω/km 0.137 0.129 0.122 0.118 0.114 0.110 0.105 Current Carrying Capacity :

- Buried direct **) A 181 220 263 298 332 374 431 in ground at 20°C- In Air at 30°C A 205 253 307 352 397 453 529

Short circuit current rating at 1 sec. (approx.) kA 7.0 9.8 13.3 16.9 21.1 26.0 33.8 Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / WDepth of laying = 0.8 m

18/30 (36) kV XLPE/DSTA/PVC 3 x (50 - 240)mm²

XLPE Insulated, Copper Tape Shielded, Double Galvanized Steel Tape Armoured and PVC Sheathed Cables

( )

(F-5)

sukarno1
Rectangle
Page 39: Catalogue MV 07

According to : IEC 60502-2

Copper Conductor

XLPE InsulationConductor Screen

Insulation Screen

Copper Tape Screen

PVC Separation Sheath

Galvanized Steel Tape binding

Binding Tape (manufacturer's option)

Galvanized Flat Steel Wire Armour

Identification of core(Red, Yellow, Blue by coloured tape)

PVC Sheath (Red or Black colour)

AFFILIATE OFSUMITOMO ELECTRIC INDUSTRIES,LTD - JAPAN

PT. SUMI INDO KABEL Tbk.KABELSI

XLPE Insulated, Copper Tape Shielded, Galvanized Flat Steel Wire Armoured

(3.6/6 kV ~ 18/30 kV) XLPE/FSWA/PVC and PVC Sheathed Cables

(G)

Filler (Polyprophylene yarn, or extruded filler upon request)

Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Longitudinally Water blocking characteristic.* Anti termite performance.* Tin coated Copper conductor.* Copper wire screen.* Polyethylene / Low smoke Halogen Free sheath.

Page 40: Catalogue MV 07

CONSTRUCTION DATA

No. of Core - 3 3 3 3 3 3 3 3 3 3

Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300

No. of Wire - 7 7 19 19 19 37 37 37 37 61

Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7

Nom. Thick. of Insulation mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.8

Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1

Nom. Thick. of Separation sheath mm 1.2 1.3 1.3 1.4 1.4 1.5 1.6 1.6 1.7 1.8

Nom. Thick. of Flat Steel wire mm 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8

Nom. Thick. of Steel tape mm 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3

Nom. Thick. of Outer sheath mm 2.2 2.3 2.4 2.5 2.6 2.7 2.9 3.0 3.2 3.3

Overall Diameter of cable mm 39.0 42.0 44.0 48.0 52.0 55.5 59.0 63.0 68.5 75.0

Weight of cable, approx. kg/km 2549 3003 3455 4277 5292 6188 7247 8503 10463 12685

ELECTRICAL DATA

AC Voltage test for 5 min. kV 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5

Partial Discharge test at max. 10ρC kV 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23

DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601

AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.197 0.160 0.1281 0.0984 0.0799

Insulation Resistance at 20°C Μ.Ω.km 2500 2000 2000 2000 1500 1500 1500 1500 1000 1000

Capacitance µF/km 0.258 0.291 0.318 0.361 0.413 0.448 0.485 0.531 0.573 0.596

Inductance mH/km 0.363 0.342 0.328 0.311 0.296 0.287 0.279 0.271 0.264 0.259

Reactance Ω/km 0.114 0.107 0.103 0.098 0.093 0.090 0.088 0.085 0.083 0.082

Current Carrying Capacity :

- Buried direct **) A 129 154 181 220 263 298 332 374 431 482

in ground at 20°C

- In Air at 30°C A 143 172 205 253 307 352 397 453 529 599

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3

Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

3.6/6 (7.2) kV XLPE/FSWA/PVC 3 x (25 - 300)mm²

XLPE Insulated, Copper Tape Shielded, Galvanized Flat Steel Wire Armoured and PVC Sheathed Cables

(G-1)

Page 41: Catalogue MV 07

CONSTRUCTION DATA

No. of Core - 3 3 3 3 3 3 3 3 3 3

Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300

No. of Wire - 7 7 19 19 19 37 37 37 37 61

Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7

Nom. Thick. of Insulation mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1

Nom. Thick. of Separation sheath mm 1.3 1.3 1.4 1.5 1.5 1.6 1.6 1.7 1.8 1.9

Nom. Thick. of Flat Steel wire mm 0.8 0.8 0.8 0.8 0.8 0.8 0.8 1.8 0.8 0.8

Nom. Thick. of Steel tape mm 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3

Nom. Thick. of Outer sheath mm 2.3 2.4 2.5 2.7 2.8 2.9 3.0 3.1 3.3 3.4

Overall Diameter of cable mm 43.5 46.5 48.5 52.5 57.0 60.0 63.5 67.0 72.5 78.0

Weight of cable, approx. kg/km 2915 3362 3848 4742 5784 6702 7729 8978 10990 13130

ELECTRICAL DATA

AC Voltage test for 5 min. kV 21 21 21 21 21 21 21 21 21 21

Partial Discharge test at max. 10ρC kV 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38

DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601

AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.197 0.160 0.1281 0.0984 0.0799

Insulation Resistance at 20°C Μ.Ω.km 3000 2500 2500 2000 2000 2000 2000 1500 1500 1500

Capacitance µF/km 0.202 0.226 0.246 0.278 0.315 0.341 0.368 0.401 0.446 0.492

Inductance mH/km 0.389 0.367 0.352 0.332 0.315 0.305 0.296 0.287 0.277 0.269

Reactance Ω/km 0.122 0.115 0.110 0.104 0.099 0.096 0.093 0.090 0.087 0.084

Current Carrying Capacity :

- Buried direct **) A 129 154 181 220 263 298 332 374 431 482

in ground at 20°C

- In Air at 30°C A 143 172 205 253 307 352 397 453 529 599

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3

Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

6/10 (12) kV XLPE/FSWA/PVC 3 x (25 - 300)mm²

XLPE Insulated, Copper Tape Shielded, Galvanized Flat Steel Wire Armoured and PVC Sheathed Cables

(G-2)

Page 42: Catalogue MV 07

CONSTRUCTION DATA

No. of Core - 3 3 3 3 3 3 3 3 3 3

Nom. Cross-section area mm² 25 35 50 70 95 120 150 185 240 300

No. of Wire - 7 7 19 19 19 37 37 37 37 61

Diameter of Conductor, approx. *) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7

Nom. Thick. of Insulation mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1

Nom. Thick. of Separation sheath mm 1.4 1.4 1.5 1.5 1.6 1.7 1.7 1.8 1.9 2.0

Nom. Thick. of Flat Steel wire mm 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8

Nom. Thick. of Steel tape mm 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3

Nom. Thick. of Outer sheath mm 2.5 2.6 2.7 2.8 2.9 3.1 3.2 3.3 3.5 3.6

Overall Diameter of cable mm 48.5 51.5 54.0 57.5 62.0 65.0 68.5 72.5 78.0 83.5

Weight of cable, approx. kg/km 3334 3826 4377 5221 6320 7233 8278 9614 11699 13875

ELECTRICAL DATA

AC Voltage test for 5 min. kV 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5

Partial Discharge test at max. 10ρC kV 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1

DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601

AC Resistance at 90°C Ω/km 0.927 0.669 0.494 0.343 0.247 0.197 0.160 0.1281 0.0984 0.0799

Insulation Resistance at 20°C Μ.Ω.km 3500 3000 3000 2500 2500 2500 2000 2000 2000 1500

Capacitance µF/km 0.168 0.186 0.202 0.226 0.255 0.275 0.296 0.322 0.356 0.392

Inductance mH/km 0.415 0.391 0.374 0.353 0.334 0.323 0.314 0.303 0.292 0.283

Reactance Ω/km 0.130 0.123 0.118 0.111 0.105 0.102 0.098 0.095 0.092 0.089

Current Carrying Capacity :

- Buried direct **) A 129 154 181 220 263 298 332 374 431 482

in ground at 20°C

- In Air at 30°C A 143 172 205 253 307 352 397 453 529 599

Short circuit current rating at 1 sec. (approx.) kA 3.5 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3

Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

8.7/15 (17.5) kV XLPE/FSWA/PVC 3 x (25 - 300)mm²

XLPE Insulated, Copper Tape Shielded, Galvanized Flat Steel Wire Armoured and PVC Sheathed Cables

(G-3)

Page 43: Catalogue MV 07

CONSTRUCTION DATA

No. of Core - 3 3 3 3 3 3 3 3 3

Nom. Cross-section area mm² 35 50 70 95 120 150 185 240 300

No. of Wire - 7 19 19 19 37 37 37 37 61

Diameter of Conductor, approx. *) mm 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7

Nom. Thick. of Insulation mm 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1

Nom. Thick. of Separation sheath mm 1.5 1.6 1.6 1.7 1.8 1.8 1.9 2.0 2.1

Nom. Thick. of Flat Steel wire mm 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8

Nom. Thick. of Steel tape mm 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3

Nom. Thick. of Outer sheath mm 2.8 2.9 3.0 3.1 3.2 3.3 3.4 3.6 3.8

Overall Diameter of cable mm 57.0 59.5 63.0 67.0 70.5 73.5 77.5 83.0 88.5

Weight of cable, approx. kg/km 4373 4917 5817 6889 7852 8919 10287 12383 14601

ELECTRICAL DATA

AC Voltage test for 5 min. kV 42 42 42 42 42 42 42 42 42

Partial Discharge test at max. 10ρC kV 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76

DC Resistance at 20°C Ω/km 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601

AC Resistance at 90°C Ω/km 0.669 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972 0.0799

Insulation Resistance at 20°C Μ.Ω.km 3500 3500 3000 3000 2500 2500 2500 2000 2000

Capacitance µF/km 0.161 0.174 0.194 0.218 0.234 0.251 0.272 0.300 0.329

Inductance mH/km 0.412 0.395 0.372 0.352 0.340 0.329 0.318 0.306 0.295

Reactance Ω/km 0.129 0.124 0.117 0.110 0.107 0.103 0.100 0.096 0.093

Current Carrying Capacity :

- Buried direct **) A 154 181 220 263 298 332 374 431 482

in ground at 20°C

- In Air at 30°C A 172 205 253 307 352 397 453 529 599

Short circuit current rating at 1 sec. (approx.) kA 4.9 7.0 9.8 13.3 16.9 21.1 26.0 33.8 42.3

Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

12/20 (24) kV XLPE/FSWA/PVC 3 x (35 - 300)mm²

XLPE Insulated, Copper Tape Shielded, Galvanized Flat Steel Wire Armoured and PVC Sheathed Cables

(G-4)

Page 44: Catalogue MV 07

CONSTRUCTION DATA

No. of Core - 3 3 3 3 3 3 3

Nom. Cross-section area mm² 50 70 95 120 150 185 240

No. of Wire - 19 19 19 37 37 37 37

Diameter of Conductor, approx. *) mm 8.1 9.7 11.6 12.9 14.3 16.0 18.3

Nom. Thick. of Insulation mm 8.0 8.0 8.0 8.0 8.0 8.0 8.0

Nom. Thick. of Copper tape mm 0.1 0.1 0.1 0.1 0.1 0.1 0.1

Nom. Thick. of Separation sheath mm 1.8 1.8 1.9 2.0 2.0 2.1 2.2

Nom. Thick. of Flat Steel wire mm 0.8 0.8 0.8 0.8 0.8 0.8 0.8

Nom. Thick. of Steel tape mm 0.3 0.3 0.3 0.3 0.3 0.3 0.3

Nom. Thick. of Outer sheath mm 3.3 3.4 3.5 3.6 3.7 3.8 4.0

Overall Diameter of cable mm 71.5 75.0 79.5 82.5 85.5 89.5 95.5

Weight of cable, approx. kg/km 6286 7241 8448 9469 10551 11986 14176

ELECTRICAL DATA

AC Voltage test for 5 min. kV 63 63 63 63 63 63 63

Partial Discharge test at max. 10ρC kV 31.1 31.1 31.1 31.1 31.1 31.1 31.1

DC Resistance at 20°C Ω/km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754

AC Resistance at 90°C Ω/km 0.494 0.343 0.247 0.196 0.159 0.1272 0.0972

Insulation Resistance at 20°C Μ.Ω.km 4500 4000 3500 3500 3000 3000 2500

Capacitance µF/km 0.136 0.151 0.167 0.179 0.191 0.206 0.225

Inductance mH/km 0.436 0.411 0.388 0.375 0.362 0.350 0.335

Reactance Ω/km 0.137 0.129 0.122 0.118 0.114 0.110 0.105

Current Carrying Capacity :

- Buried direct **) A 181 220 263 298 332 374 431

in ground at 20°C

- In Air at 30°C A 205 253 307 352 397 453 529

Short circuit current rating at 1 sec. (approx.) kA 7.0 9.8 13.3 16.9 21.1 26.0 33.8

Note : *) Diameter compacted shape

**) Thermal resistivity of soil : 1.5°K.m / W

Depth of laying = 0.8 m

18/30 (36) kV XLPE/FSWA/PVC 3 x (50 - 240)mm²

XLPE Insulated, Copper Tape Shielded, Galvanized Flat Steel Wire Armoured and PVC Sheathed Cables

(G-5)

Page 45: Catalogue MV 07

CURRENT CARRYING CAPACITY ACCORDING TO IEC 60502-2 : 2005

Current rating of cable is calculated under the following conditions :

Maximum conductor

temperature

Basic ambient

temperature

Thermal resistivity of soil

Depth of laying, underground

Trefoil

In Air

Flat

Cable Trefoil

arrangement

( D : Overall dia.) Under-

ground

Flat

80 cm

Three single-core cable

One three-core cable

In Air

In Air

Underground

90°C

30°C

20°C

1.5 K.m/W

Underground

Dx3.0≥

D D

Dx5.0≥

Dx5.0≥

D

(H)

Dx5.0≥Flat spaced Flat touching

Page 46: Catalogue MV 07

CORRECTION FACTOR

20 25 30 35 40 45 50 55 60

1.08 1.04 1 0.96 0.91 0.87 0.82 0.76 0.71

10 15 20 25 30 35 40 45 50

1.07 1.04 1 0.96 0.93 0.89 0.85 0.80 0.76

Correction factors for depths of laying for direct buried cables

0.94

0.93

0.91

0.90

0.88

0.86

1.04

1.03

1

0.98

0.96

0.950.93

0.91

0.90

1

0.97

0.95

0.94

0.93

0.91

0.90

2.5

3

1.04

1.02

1

0.98

0.96

0.951.5

1.75

2

0.8

1

1.25

Three-core

cables

0.5

0.6

1.06

1.04

≥ 185 mm²≤ 185 mm²

mm²

Nominal conductor size

90

m

Depth of laying

Single-core cables

Correction factors for ambient Air temperatures

°C

Max.conductor

temperature

90

Ambient air temperature

°C

Correction factors for ambient Ground temperatures

Max.conductor Ambient Ground temperature

temperature °C

°C

( H-1 )

Page 47: Catalogue MV 07

CORRECTION FACTOR

Correction factors for soil thermal resistivities for Direct buried Single-core cables

0.7 0.8 0.9 1 1.5 2 2.5 3

1.29 1.24 1.19 1.15 1 0.89 0.82 0.75

1.30 1.25 1.20 1.16 1 0.89 0.81 0.75

1.30 1.25 1.21 1.16 1 0.89 0.81 0.75

1.32 1.26 1.21 1.16 1 0.89 0.81 0.74

1.33 1.27 1.22 1.17 1 0.89 0.81 0.74

1.34 1.28 1.22 1.18 1 0.89 0.80 0.74

1.34 1.28 1.22 1.18 1 0.88 0.80 0.74

1.35 1.28 1.23 1.18 1 0.88 0.80 0.74

1.35 1.29 1.23 1.18 1 0.88 0.80 0.74

1.36 1.29 1.23 1.18 1 0.88 0.80 0.73

1.36 1.30 1.24 1.19 1 0.88 0.80 0.73

1.37 1.30 1.24 1.19 1 0.88 0.79 0.73

Correction factors for soil thermal resistivities for Direct buried Three-core cables

0.7 0.8 0.9 1 1.5 2 2.5 3

1.23 1.19 1.16 1.12 1 0.91 0.84 0.78

1.24 1.20 1.16 1.13 1 0.91 0.84 0.78

1.25 1.21 1.17 1.13 1 0.91 0.83 0.78

1.25 1.21 1.17 1.14 1 0.91 0.83 0.77

1.26 1.21 1.18 1.14 1 0.90 0.83 0.77

1.26 1.22 1.18 1.14 1 0.90 0.83 0.77

1.26 1.22 1.18 1.14 1 0.90 0.83 0.77

1.27 1.22 1.18 1.15 1 0.90 0.83 0.77

1.27 1.23 1.18 1.15 1 0.90 0.83 0.77

1.28 1.23 1.19 1.15 1 0.90 0.83 0.77

1.28 1.23 1.19 1.15 1 0.90 0.82 0.77

1.28 1.23 1.19 1.15 1 0.90 0.82 0.76400

240

300

50

185

70

95

120

150

25

35

of conductor K.m/W

mm²

16

400

Values of soil thermal resistivity

K.m/W

Nominal area Values of soil thermal resistivity

185

240

300

70

95

120

150

25

35

50

Nominal area

of conductor

mm²

16

( H-2 )

Page 48: Catalogue MV 07

Reduction factors for groups of more than one multi-core cables in air to be applied tothe current -carrying capacity for one multi-core cable in free air

Number Number of cables

of trays 1 2 3 4 6 9

1 1.00 0.88 0.82 0.79 0.76 0.73

2 1.00 0.87 0.80 0.77 0.73 0.68

3 1.00 0.86 0.79 0.76 0.71 0.66

1 1.00 1.00 0.98 0.95 0.91 -

2 1.00 0.99 0.96 0.92 0.87 -

3 1.00 0.98 0.95 0.91 0.85 -

1 1.00 0.88 0.82 0.78 0.73 0.72

2 1.00 0.88 0.81 0.76 0.71 0.70

1 1.00 0.91 0.89 0.88 0.87 -

2 1.00 0.91 0.88 0.87 0.85 -

1 1.00 0.87 0.82 0.80 0.79 0.78

2 1.00 0.86 0.80 0.78 0.76 0.73

3 1.00 0.85 0.79 0.76 0.73 0.70

1 1.00 1.00 1.00 1.00 1.00 -

2 1.00 0.99 0.98 0.97 0.96 -

3 1.00 0.98 0.97 0.96 0.93 - NOTE 1 Value given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than 5 %

NOTE 2 Factors apply to single layer groups of cables as shown above and do not apply when cables are installed in more than one layer touching each other. Values for such installations may be significantly lower and must be determined by an appropriate method.

NOTE 3 Values are given for vertical spacings between trays of 300 mm and at least 20 mm between trays and wall. For closer spacing, the factors should be reduced.

NOTE 4 Values are given for horizontal spacings between trays of 225 mm with trays mounted back to back. For closer spacing, the factors should be reduced.

perforated trays

Cables on ladder

supports,cleats,

etc.

Method of installation

Cables on

perforated trays

Cables on vertical

( I-1 )

Touching

Spaced

≥ 20 mm

≥ 20 mm

D

Touching

Spaced

Touching

Spaced

≥ 20 mm

≥ 20 mm

D

≥225 mm

≥225 mm

D

Page 49: Catalogue MV 07

Reduction factors for groups of more than one circuit of single-core cables (Note 2) - To be applied tothe current -carrying capacity for one circuit of single-core cables in free air

Number of

trays 1 2 3

1 0.98 0.91 0.87

2 0.96 0.87 0.81

3 0.95 0.85 0.78

1 1.00 0.97 0.96

2 0.98 0.93 0.89

3 0.97 0.90 0.86

1 1.00 0.98 0.96

2 0.97 0.93 0.89

3 0.96 0.92 0.86

1 1.00 0.91 0.89

2 1.00 0.90 0.86

1 1.00 1.00 1.00

2 0.97 0.95 0.93

3 0.96 0.94 0.90 NOTE 1 Value given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than 5 %

NOTE 2 Factors are given for single layers of cables (or trefoil groups) as shown in the table and do not apply when cables are installed in more than one layer touching each other. Values for such installations may be significantly lower and should be determined by an appropriate method

NOTE 3 Values are given for vertical spacings between trays of 300 mm.For closer spacing, the factors should be reduced.

NOTE 4 Values are given for horizontal spacings between trays of 225 mm with trays mounted back to back. For closer spacing, the factors should be reduced

NOTE 5 For circuits having more than one cable in parallel per phase, each three phase set of conductors should be considered as a circuit for the purpose of this table

Three cables in

trefoil formation

formation

Three cables in

horizontal

formation

Use as a multiplier to

rating for

Perforated

trays

Three cables in

horizontal

Method of installation

supports,cleats etc.

(Note 3)

Vertical

perforated trays

(Note 4)

Ladder

(Note 3)

Ladder

supports,cleats etc.

(Note 3)

Perforated

trays

( I-2 )

Touching

≥ 20 mm

Spaced

Touching

≥ 20 mm

≥ 20 mm

≥ 2 D D

225 mm

D

≥ 2 D

≥ 20 mm

≥ 2 D D

Page 50: Catalogue MV 07

PERMISSIBLE PULLING TENSION

Pulling equipment Permissible pulling tension (kg) PULLING EYE 7 x (Number of core) x (Cross section area of conductor) CABLE NET About 500 kg, but the maximum tension shall not be more than one of

conductor (same calculation as using PULLING EYE)

Reference data on Aluminium conductor Pulling equipment Permissible pulling tension (kg) PULLING EYE 4 x (Number of core) x (Cross section area of conductor) CABLE NET About 500 kg, but the maximum tension shall not be more than one of

conductor (same calculation as using PULLING EYE)Note) Cable net shall be covered more than 500 mm in length

MINIMUM BENDING RADIUS

Reference data on other types of POWER cables

Sheild cable 10D Non sheild cable 8D Triplex type cable - Wire armored cable 10D Tape armored cable 10D Flat wire armoured cable 10D

Reference data on other types of INSTRUMENT cables

Note) Sheild tape shall be AL mylar tape

3.6/6kV and above

Type of cable Single core cable Multi core cable

12D 8D Round/Compacted

6D6D

Multi core cableMinimum bending radius

Sector conductor10D

Minimum bending radius

Type of cable

Non sheild cable Sheild cable

D : Diameter of cable

12D 8D12D 6D

Minimum bending radius

Round/CompactedMulti core cable

Sector conductorSingle core cable

-12D12D12D

8D10D10D10D

Type of cable

Medium voltage cable

( J )

Page 51: Catalogue MV 07

PERMISSIBLE SIDE WALL PRESSURE

300kg/m is suggested as permissible side wall pressure to the cable during installation.

Side wall pressure (T1) can be calculated with below formula.

T1 =

T = Pulling tension r = Bending radius

CALCULATION OF CABLE PULLING TENSION DURING INSTRALLATION

The cable pulling tension (T2) during installation can be calculated with below formula.

1) Horizontal straight part : T2 =2) Horizontal curve part : T3 = T4

µ : Friction factor

underground

W : Weight of cable (kg/m)L : Length of cable with straight part (m)θ : Angle of curve part (rad)

T2 : Pulling tension (kg)T3 : Pulling tension before curve part (kg)T4 : Pulling tension after curve part (kg)

VOLTAGE DROP

I : Current of Conductor (A)

K : Coefficient

- Single phase system = 2

- Three phase system =

: AC Conductor resistance (Ohm/km)

: Reactance (Ohm/km)

0.2 - 0.30.5 - 0.7

Friction factor0.2on pulley

in pipe

T kg

r

LxWxµ( )µθ∧ex

( K )

rT

( )θθ sincos XRxIxKV acd +=

1sincos 22 =+ θθ

3

acR

X

Page 52: Catalogue MV 07

NOTES

Page 53: Catalogue MV 07
Page 54: Catalogue MV 07

Head Office/Factory :Jl. Gatot Subroto Km 7,8 Kel Pasir Jaya, Kec. Jati Uwung, Tangerang 15135-IndonesiaPhone : (62-21) 5922404, 5928066 (Hunting) Fax. : (62-21) 59301979,5922576, 5901469