  • Switch Disconnector

    Fuse Units

  • Indo Asian presents the widest range of world-class Switch Disconnector Fuse units and Switch Disconnectors. The

    complete range conforms to IS 13947-3/IEC 947-3 rated for AC-23A duty and most suited for Indian conditions.

    The design of SDF units type ITF is based on the innovative `QUAD BREAK' principle. This design enables a drastic

    reduction in the intensity of arc, which is produced at the time of breaking. During breaking the current path is broken at four

    places in series, thus the arc is reduced. This leads to less strain on the contacts and the life of the switch is increased.

    The moving contacts are designed to make two parallel current paths, which produce high electro-magnetic attraction

    forces during high faults and increase the contact pressure, this eliminates chance of arcing at the contacts and allows the

    fuse to safely clear the fault. The self-cleaning contacts ensure wiping of deposits during each operation and increase the

    life of the contacts.

    The fuses in SDF units' type ITF are stationary and are isolated at both the incoming and outgoing ends, this offers complete

    safety for fuse replacement in OFF condition.

    The switch mechanism is quick-make quick-break i.e. independent of operating speed. Positive ON/OFF indication is

    provided at the switch handle and mechanism assembly; however, clear physical contact position can be seen through

    inspection windows on the housing of the switch.

    The complete range from 32A to 800A is offered in TPN and 4-pole (TPSN) versions. The neutral is rated for 100% of the

    switch rating. Incase of switched neutral (TPSN) version, the neutral is advance i.e. makes before and breaks later than the

    main poles and is housed in the same housing without any ADD-ON attachment.

    Phase barriers are provided as a standard feature to prevent any accidental fault between the fuses.

    Rated insulation voltage 1000V AC and 1500V DC

    High Breaking capacity (AC23A IEC 947-3 / IS 13947-3)

    Contact position clearly visible through inspection windows

    ON/OFF position clearly indicated on handle and on switch mechanism

    Neutral rated for full rated current

    Independent manual operation

    Front operated rotary handle with door interlock

    Padlockable with up to 3 locks

    O O

    Storage ambient temp. -25 C to 55 C

    O O

    Working ambient temp. -20 C to 45 C

    Relative humidity max. 95%

    Rated frequency 50-60Hz

    - Auxiliary Contacts

    1NO + 1NC

    2NO + 2NC

    Switch Disconnector Fuse

    Innovative Design :

    Complete Safety :

    General Characteristics :

    l

    l

    l

    l

    l

    l

    l

    l

    Normal Service Conditions :

    l

    l

    l

    l

    Accessories Available:

  • Switch Disconnector Fuse Units

    Technical data Switch Disconnector Fuse type - ITF IS 13947-3 / IEC 947-3

    IT10A032

    IT10B032

    IT1SA032

    1.1

    IT10A063

    IT10B063

    IT1SA063

    1.1

    IT20A125

    IT20B125

    IT2SA125

    2

    IT20A160

    IT20B160

    IT2SA160

    2

    IT30A200

    IT30B200

    IT3SA200

    5.3

    IT30A250

    IT30B250

    IT3SA250

    5.3

    IT40A315

    IT40B315

    IT4SA315

    7.4

    IT40A400

    IT40B400

    IT4SA400

    7.4

    IT50A630

    IT50B630

    IT5SA630

    14.5 14

    IT50A800

    IT50B800

    ORDER REFERENCE

    Interior TPN

    Interior 4 Pole (TPSN)

    In sheet steel enclosure TPN

    Weight (Interior) kg

    IT1F

    32A 63A 125A 160A 200A 250A 315A 400A 630A 800A

    IT2F IT3F IT4F IT5F

    Type Designation IT1F

    TPN/4P TPN/4P TPN/4P TPN/4P TPN/4P

    100%

    32

    32

    415

    1000

    8

    50-60

    63

    63

    415

    1000

    8

    50-60

    125

    125

    415

    1000

    12

    50-60

    160

    160

    415

    1000

    12

    50-60

    200

    200

    415

    1000

    12

    50-60

    250

    250

    415

    1000

    12

    50-60

    315

    315

    415

    1000

    12

    50-60

    400

    400

    415

    1000

    12

    50-60

    630

    630

    415

    1000

    12

    50-60

    800

    800

    415

    1000

    12

    50-60

    100% 100% 100% 100%

    IT2F IT3F IT4F IT5F

    No. of poles

    Neutral rating

    Rated thermal current (Ith)

    Rated operational voltage (Ue)

    Rated insulation voltage (Ui)

    Rated impulse withstand voltage (Uimp)

    Rated frequency

    Conventional enclosed thermal current at 45C (Ithe)

    A

    V

    V

    kV

    Hz

    A

    32

    32

    32

    320*

    256*

    80

    15

    10000

    1500

    12x2

    25

    A2

    Bolted

    6-32

    63

    63

    63

    630*

    504*

    80

    30

    10000

    1500

    12x2

    25

    A2/A3

    Bolted

    6-63

    125

    125

    125

    1250

    1000

    80

    50

    8000

    1000

    16x4

    70

    SIZE 00SIZE 00SIZE 00 SIZE 00 SIZE 1 SIZE 1 SIZE 2 SIZE 2 SIZE 3

    6-125

    160

    160

    160

    1600

    1280

    80

    70

    8000

    1000

    16x4

    95

    6-160

    200

    200

    200

    2000

    1600

    80

    90

    7000

    1000

    25x4

    185

    32-200

    250

    250

    250

    2500

    2000

    80

    110

    7000

    1000

    25x4

    185

    32-250

    315

    315

    315

    3150

    2520

    80

    140

    7000

    1000

    30x5

    2x300

    250-400

    400

    400

    400

    4000

    3200

    80

    180

    7000

    1000

    30x5

    2x300

    250-400

    630

    630

    630

    6300

    5040

    80

    300

    4000

    1000

    40x7

    2x400

    Bolted C3

    315-630

    800

    800

    800

    8000

    6400

    80

    380

    4000

    1000

    40x7

    2x400

    Rated operational current (Ie) (A) AC-21A utilization category

    at 415V

    AC-22A utilization category

    at 415V

    AC-23A utilization category

    at 415V

    Rated making capacity (415V, Cosf=0.35) (0.45*)

    Rated breaking capacity (415V, Cosf=0.35) (0.45*)

    Rated fused short circuit current

    Capacitor duty at 415V, 50-60Hz

    Mechanical life (Operating cycles)

    Electrical life (Operating cycles)

    Terminal size

    Terminal capacity

    Size of fuse as per IS-13703 (Part I & II)

    Ratings of Indo Asian make fuses available

    A

    A

    A

    A

    A

    kA

    kVAR

    mm

    2

    mm

    A

    Type designation of fuse

    Details of IA Fuses Suitable for Switch Disconnector Fuse Unit

    SIZE 00 SIZE 00 SIZE 1 SIZE 1 SIZE 2 SIZE 2 SIZE 3

  • INDO ASIAN offers you a range of state of the art 4-Pole Switch Disconnectors type ITI.

    The Switch Disconnectors are designed for optimum performance. Compact in size, these switch dicconnectors are rated

    for AC23A as per IS 13947-3/ IEC 947-3. The quick make - quick break switch mechanism is independent of the operating

    speed. The self - wiping contact system allows cleaning of contacts during each operation, calling for lesser maintenance

    and higher life. The terminals are staggered allowing easy termination of aluminium conductors with adequate clearances.

    The neutral is advance and is rated for 100% of the switch rating*.

    General Characteristics :

    l Rated insulation voltage 1000V AC and 1500V DC

    l High Electrical & Mechanical endurance

    l Double break self wiping contacts

    l Contact position clearly visible through inspection windows

    l Staggered terminals facilitate easy termination and increased clearances

    l Advance neutral closes earlier and opens later than the main poles

    l Neutral rated for full rated current

    l Front operated rotary handle with door interlock

    l Padlockable with up to 3 locks

    Normal Service Conditions :

    O O

    l Storage ambient temp. -25 C to 55 C

    O O

    l Working ambient temp. -20 C to 45 C

    l Relative humidity max. 95%

    l Rated frequency 50-60Hz

    Accessories Available :

    - Auxiliary Contacts

    1NO + 1NC

    2NO + 2NC

    Switch Disconnector

  • Switch Disconnector

    Switch Disconnectors Conforms to IEC 947-3 / IS 13947-3

    TECHNICAL DATA

    Rated insulation voltage

    Rated impulse withstand voltage (Uimp) kV

    Rated thermal current (lth) A

    63A

    1000

    1500

    63

    125A

    1000

    1500

    88

    125

    200A

    1000

    1500

    12

    200

    250A

    1000

    1500

    12

    250

    315A

    1000

    1500

    12

    315

    400A

    1000

    1500

    12

    400

    630A

    1000

    1500

    12

    630

    Rated operational

    current (A) (le) AC-23A

    Short withstand current 1 sec. kA

    Making capacity in short circuit kA

    Back-up fuse A

    A

    A

    kVAR

    mm

    2

    mm

    Rated making capacity

    415V AC cos = 0.35(0.45*)

    Rated breaking capacity

    415V AC cos = 0.35(0.45*)

    Capacitor duty 415V AC

    Mechanical endurance (Operating Cycles)

    Electrical endurance (Operating Cycles)

    Terminal size

    Terminal Capacity

    Ordering Code

    5

    7.5

    63

    630*

    504*

    30

    12000

    3000

    15x3

    70

    IT1SD063 IT1SD125 IT2SD200 IT2SD250 IT3SD315 IT3SD400 IT4SD630

    5

    7.5

    125

    1250

    1000

    50

    10000

    2000

    15x3

    70

    8

    13.5

    200

    2000

    1600

    90

    10000

    2000

    20x4

    185

    8

    13.5

    250

    2500

    2000

    110

    10000

    2000

    20x4

    185

    13

    26

    315

    3150

    2520

    140

    8000

    1500

    28x4

    300

    13

    26

    400

    4000

    3200

    180

    8000

    1500

    28x4

    300

    15

    30

    630

    6300

    5040

    300

    8000

    1500

    40x6

    400

    240V

    415V

    500V

    690V

    63

    63

    45

    35

    125

    125

    100

    80

    200

    200

    160

    125

    250

    250

    200

    160

    315

    315

    250

    200

    400

    400

    315

    250

    630

    630

    500

    400

    IT1I IT2I IT3I IT4I

    (Ui) VAC

    VDC

    Ratings available upto 3150A, kindly contact us for other ratings / technical details.

    800A

    1000

    1500

    12

    800

    IT5SD800

    35

    73.5

    800

    8000

    6400

    370

    7000

    1000

    50x6

    --

    800

    800

    630

    500

    IT5I

    5

  • Dimensional Drawing

    DIMENSIONAL DRAWING

    245.5

    DOOR DRILLING DETAILS

    34

    O

    45

    O

    45

    IT5F-800A

    30

    6

    50

    40

    29

    Switch Disconnector Fuse (TPN)

    16

    04

    0

    All dimensions are in mm

    Switch Disconnector Fuse (TPN)

    245.5

    DOOR DRILLING DETAILS

    34

    O

    45

    O

    45

    SR

    1.5 - 3

    B

    C

    D

    IT1F-32A, 63A IT2F-125A, 160A, IT3F-200A, 250A IT4F-315A, 400A IT5F-630A

    36.5 25 70 8 41 172 36.5

    31 25 70 8 41 170.5 31

    D E F G H J K

    60.5 40 160 12 71 265 80

    52 40 120 12 71 225.5 68

    IT1F

    IT2F

    SIZE

    IT5F

    IT4F

    IT3F

    70.5

    74

    A

    93

    75

    75

    101.5

    96.5

    B

    172

    150.5

    121

    4

    2

    C

    7

    5

    4 41 40 120 10 71 199 56

    168 22.5 37.5 39 30 162 146.5 37.5 40.5 78 49.5 16 14.5 8.5 9.5 106 118 146.5 162 16X4 16X4

    142 19 33 33 24 105 95 23 35.5 66 40.5 12 14 5.5 9.5 77 88 95 105 12X2 12X2

    L M N O P R S T U V W X Y Z AA AB AC AD AEPHASE NEUTRAL

    TERMINAL SIZE

    356 37 85 85 64 306 256 60 79.5 170 106.5 40 29 12.5 16.5 200 228 246 286 40X7 50X7

    280 31.5 66.5 68 46 270 205 51 64 136 80 30 24 12.5 14.5 160 180 205 210 30X5 30X5

    235 29 56 56 38 207 177.5 40 53 114 68 25 21 10.5 12 140 157 177.5 207 25X4 25X4

    All dimensions are in mm

  • Switch Disconnector Fuse Units

    C

    A

    BD

    F EE

    JH

    J

    S

    K

    FLANGE PLATE

    L

    M

    245.5

    DOOR DRILLING DETAILS

    34

    O

    45

    O

    45

    DIMENSIONAL DRAWING

    Switch Disconnector Fuse in Sheet Steel enclosure

    IT2FS 224 183 41 292 44 204 300 215 43 4-6.5 4-38 8-26

    IT1FS 224 183 41 262 44 174 300 215 43 4-6.5 4-38 8-26

    SIZE A B C D E F G H J K L M

    IT5FS 351 280 71 480 43.5 393 600 515 42.5 4-6.5 4-78 8-70

    IT4FS 306 235 71 385 43.5 298 450 365 42.5 4-6.5 4-68 8-63

    IT3FS 280 209 71 347 43.5 260 400 315 42.5 4-6.5 4-52 8-48

    IT1FS-32A, 63A IT2FS-125A, 160A, IT3FS-200A, 250A IT4FS-315A, 400A IT5FS-630A All dimensions are in mm.

    DIMENSIONAL DRAWING

    Switch Disconnectors

    All dimensions are in mm.IT1I-63A, 125A IT2I-200A, 250A IT3I-315A, 400A IT4I-630A, IT5I-800A

    IT2I 42.5 94 4 41 25 70 41 136.5 67 8 168 22.5 37.5 39 30 37.5 40.5 78 49.5 20 14.5 10.5 9.5 4.5 107 118 158

    IT5I

    IT1I 43 86 3 33 25 70 41 129 56 8 142 19 33 33 24 23 35.5 66 40.5 15 14 8.5 9.5 4.5 77 88 118

    IT3I 55 114 4 49 40 120 71 169 85 10 235 29 56 56 38 47 53 114 68 28 21 16 12 6 140 157 217

    IT4I 53.5 140.5 6 58 40 120 71 194 98 12 280 31.5 66.5 68 46 51 64 136 80 40 24 16.5 15 7 160 180 244

    SIZE A B C D E F G H J K L M N O P R S T U V W X Y Z AA AB AC

    190

    138

    265.5

    300

    AD

    63 - 6 - 40 120 71 - - 12 356 37 85 85 64 60 79.5 170 106.5 50 29 16.5 16 7 200 228 256 390