Basic Meter Setup
Training LabLAB Modify the Demand framework of an ION 7650
meterLAB Modify the Demand framework of an ION 7650 meter
Modify the Demand framework of an ION7650 meterThis lab activity
provides a procedure for using Designer to examine and modify the
Demand framework of an ION 7650 meter.ObjectivesUpon completion of
this lab, the student will be able to: Modify the Demand framework
of an ION7650 meterTime
30 Mins
Logon to Designer1. Open the ION Enterprise Tools folder that is
located on the desktop. Double-click on Designer to launch the
application.
2. Enter the following into the logon window that appearsUser
name: supervisorPassword: 03. File ( Open and select the ION7650
and click OK:
Navigate to the Demand Setup diagram1. on the Grouping Object
called Period, # of Sub-periods in the Demand Setup box, as shown
below:
Examine the Demand Setup diagram1. Determine the naming
convention for the modules shown:
QUESTIONS:
Change the Demand Interval1. on the Sliding Window Demand module
called kW sd del to expose its Setup Registers
2. Review the existing Setup Registers
3. Configure the following kW sd del module setup registers, as
shown below:
QUESTIONS:
4. Send & Save
5. Change the remaining 25 Sliding Window Demand modules so they
all calculate an average based on a 10 minute interval (same Setup
Registers as Step 5).6. Send & Save
Add a Text Box to describe the changes made1. a Text Box from
the Toolbox, as shown below:
2. on the Text Box and a description, as shown below: 3. on the
tab called Text and select Custom and on the Font Button: 4.
Configure the Font to be Arial 12 Bold and the OK button: 5. on the
tab called Box and select Show for the Border, as shown below: 6.
For Background Color, select Custom and on the Color button: 7.
Select White and press the OK button
8. When you have finished configuring the Text Box, the OK
button
9. a corner of the Text Box to adjust its size to display the
description and position it neatly on the diagram as shown
below
Examine the Demand Framework diagram1. on the Sliding Window
Demand module icon on the Toolbox.2. In the list of Sliding Window
Demand modules from the Toolbox, on the first module called kW sd
del-rec (= SWinDemand1), as shown below:
QUESTIONS:
3. anywhere on the Toolbox to make the list of modules
disappear:
QUESTIONS:
Copy the description Text Box into the Demand Framework
diagram1. In the Menu Bar, on the word Window. In the list of open
Designer diagrams, on diagram called Demand
Setup[East_Sub.Main].(This will re-open the Demand Setup
diagram).
2. on the custom Text Box created before. This will select
it.
3. With the custom Text Box selected, Copy it using one of three
methods:
Copy icon in the Tool Bar Edit ( Copy + C
4. In the Menu Bar, on the word Window. In the list of open
Designer diagrams, on diagram called Demand
Framework[East_Sub.Main].
(This will re-open the Demand Framework diagram that we left in
Step 31).
5. With the custom Text Box copied to the clipboard, Paste it
using one of three methods:
Paste icon in the Tool Bar Edit ( Paste
+ V
6. on the custom Text Box and position it neatly on the diagram,
as shown below:
QUESTIONS:
Align the row of Convert modules1. Holding down the key, on each
of the Convert modules (Q1 boolean; Q2 boolean; Q3 boolean; Q4
boolean) at the bottom of the diagram to select them:
2. Use the Up Arrow key to position the Convert modules in line
with the And/Or module:
Close the Demand Framework and Demand Setup diagrams
1. the X in the top right-hand corner to close the Demand
Framework diagram.
2. the X in the top right-hand corner to close the Demand Setup
diagram.
Navigate to the Reporting Framework1. With only the main Factory
Configuration diagram open, on the Grouping Object called
Frameworks in a text box labeled Advanced Setup, as shown
below:
2. Navigate to the Revenue Framework and the Reporting
Framework, as shown below:
Examine the Reporting Framework1. To view the source inputs that
are logged for reporting purposes (Energy Demand and Load Profile
reports), on the input arrow of the Data Recorder called EgyDmd
Log, as shown below:
2. Fill in the table below to document the measurements that are
being logged by this meter for reporting purposes:Input to EgyDmd
LogInput Label
Source 1
Source 2
Source 3
Source 4
Source 5
Source 6
Source 7
Source 8
Source 9
Source 10
Source 11
Source 12
Source 13
Source 14
Source 15
Source 16
Enable
Record
Rearm
Change the Logging Interval to match the Demand Interval1. on
the Periodic Timer module called EgyDmd Log Trg, as shown
below:
2. Change the Setup Register called Period so that this Periodic
Timer (which controls the logging interval) now fires at the same
time that the Sliding Window Demand modules in this framework
calculate a new demand value, as shown below:
3. Send & Save
NOTE THE TIME:
Close and Exit Designer1. the X in the top right-hand corner to
close the Reporting Framework diagram.
2. Close all other Designer sub-diagrams, until only the main
Factory Configuration diagram is open.
3. Exit Designer, as shown below:
View Logged Demand Values in VistaLaunch Vista
1. Open the ION Enterprise Taskpad that is located on the
desktop of the ION Enterprise client/server computer. Click on
VISTA to launch the Vista application.
2. Enter the following into the logon window that appearsUser
name: supervisorPassword: 0
3. Create a new Vista diagram. File ( New, as shown below:
4. a Data Log Viewer object from the Toolbox onto the new Vista
diagram, as shown below:
5. on the Data Log Viewer and on the Query Server tab:
6. the radio button beside Custom Query Server and on the Edit
Link button, as shown below: 7. on words Query Modules in the
Managers column and then Query 1 in the Modules column and QM1
Query Register in the Output Registers column and finally on the OK
button, as shown below: 8. Confirm that QM1 Query Register has been
linked
9. on the Query tab and on the Edit Query button, as shown
below:
10. on the ION7650 in your system and click the Add button to
place it into the Selected container. Press the Next button to
proceed, as shown below: 11. on the EgyDmd Log and click on the Add
button to select it and click Next: 12. Select the columns to
display in the data table using the Add button and order them
exactly as shown using the small up/down arrows to the right. Click
Next to proceed.
13. Select timestamp and on the Add button. This selection
causes the data to be displayed sorted by timestamp (i.e.
chronologically). Click Finish.
14. the OK button
15. on the Data Log Viewer to view a data table for the above
query:
16. on vertical line between the timestamp column and the node
column and adjust the timestamp column width so that it shows the
full timestamp:
17. Scroll through the data table and find the point in which
the timestamp intervals change from 15 minutes to 10 minutes:
18. Congratulations, you have just confirmed that your
programming modifications to the Demand Framework of the ION7650
meter are working properly. Additional Resources
The references listed below provide additional information
related to the topics covered in this lab activity
ION Enterprise Client users Guide
here
What do the following labels stand for?
kW sd del rec
____________________________________________________________
kW td del rec
____________________________________________________________
What is the difference between sd and td? Do you need both
calculations?
__________________________________________________________________________
__________________________________________________________________________
Sub Interval: 600
# of Sub Intervals: 1
Predicted Response: 70
Update Rate: End of Sub-Interval
here
here
and adjust column width here
here
here
When was the logging interval changed and saved to the
meter?
_________________________________________________________
What is the name of the diagram that you just navigated to?
_____________________________________________________________
What is the Demand Interval for the Sliding Window Demand
modules in this framework? ____________ seconds= ____________
minutes
anywhere on the Toolbox
When a particular type of module is selected from the Toolbox,
how many modules appear in a full row?
__________________________
How many Sliding Window Demand modules exist in a default
ION7650 meter? ____________________________
1. here
What is the default logging interval for demand measurements in
an ION meter?
5 minutes10 minutes15 minutesI dont know
What happens if the interval for calculating demand does not
match the logging interval for demand?
________________________________________________________________________________________________________________________________________________________
2. here
What is the demand interval now?
_______________ seconds = ______________ minutes
What is the relationship between the Sub Interval and # of Sub
Intervals setup registers? (Use the ION Reference document)
__________________ x __________________ = __________________
________________________________________________________________________________________________________________________________________________________
What would be a benefit of calculating a running average that
updates every second?
________________________________________________________________________________________________________________________________________________________