Treatment of Small CHP Plant

and Short-term Use Diesel

Generators in the IAQM

Planning Guidance

Dr Ben Marner

Page 2: Ben Marner - AQC -  Treatment of Small CHP Plant and Short-term Use Diesel Generators in the IAQM Planning Guidance

Overview

• Small CHP can have significant impacts

Significant sources are being screened out in the

current guidance

• Diesel generators which aren’t used for long can

have significant impacts

But they are often ignored in assessments

Made using recycled slides

Page 3: Ben Marner - AQC -  Treatment of Small CHP Plant and Short-term Use Diesel Generators in the IAQM Planning Guidance

IAQM Screening Criteria

Page 4: Ben Marner - AQC -  Treatment of Small CHP Plant and Short-term Use Diesel Generators in the IAQM Planning Guidance

Comparison of Some NOx

Emission Sources

Google

Page 5: Ben Marner - AQC -  Treatment of Small CHP Plant and Short-term Use Diesel Generators in the IAQM Planning Guidance

‘Dispersion’ Criterion

Google

Earth

Page 6: Ben Marner - AQC -  Treatment of Small CHP Plant and Short-term Use Diesel Generators in the IAQM Planning Guidance

Micro CHP Case Study

2 x 5.5 kWe (20kW fuel input) CHP

25.5 m tall building

27 m high flue

Modelled using ADMS

CHPs add 0.7 µg/m3 annual NO2

‘Moderate’ Impact

Background NO2 is >40 µg/m3

Page 7: Ben Marner - AQC -  Treatment of Small CHP Plant and Short-term Use Diesel Generators in the IAQM Planning Guidance

Solution for CHP?

• Suggested “precautionary” criterion of 15kWe

• Alternatively tighten up ‘dispersion criterion’

But it would be very difficult to make this sufficiently

definitive

Page 8: Ben Marner - AQC -  Treatment of Small CHP Plant and Short-term Use Diesel Generators in the IAQM Planning Guidance

Short-term Use Diesel Generators

• Short-Term Operating Reserve

• Mobile Plant

e.g. construction sites

Temporary but used intensively

• Backup reserve / life safety

power cuts / fires

Regular routine tests – often 20

mins 1h each month

Page 9: Ben Marner - AQC -  Treatment of Small CHP Plant and Short-term Use Diesel Generators in the IAQM Planning Guidance

Diesel Generators

Page 10: Ben Marner - AQC -  Treatment of Small CHP Plant and Short-term Use Diesel Generators in the IAQM Planning Guidance

Diesel Generators

60 MW (fuel input)

(20 MWe) bank of

generators

60 km of M25

Page 11: Ben Marner - AQC -  Treatment of Small CHP Plant and Short-term Use Diesel Generators in the IAQM Planning Guidance

Generator Case Study

• Bank of 20 x 3MVA backup generators

12 hrs of testing per year (grew to 24 hrs)

IF testing coincided with worst-case met:

PC to 99.79th percentile of 1-h NOx = 4,086 mg/m3

PC to annual mean NOx = 13 mg/m3

Assessed the probability of significant impacts

Could not discount potential for significant impacts

Page 12: Ben Marner - AQC -  Treatment of Small CHP Plant and Short-term Use Diesel Generators in the IAQM Planning Guidance

Solution for Generators?

• Suggested Addition to Paragraph 6.20 J

“Description of construction phase impacts. These impacts will relate

primarily to dust emissions, which give rise to dust soiling and elevated

PM10 concentrations, although construction vehicles and plant and

vehicles may need assessment; particularly if diesel power

generators are to be used.”

• Suggested New Paragraph for Section 6

“When considering standby generators that are present

only in case of power failures or emergencies,

consideration should be given to any routine testing

procedures. Even operation for a few hours per year

can give rise to impacts that should be assessed”

Page 13: Ben Marner - AQC -  Treatment of Small CHP Plant and Short-term Use Diesel Generators in the IAQM Planning Guidance

Summary

• Please can we have more stringent criteria for

CHP?

• Please can we encourage robust assessments of

diesel generators?