Water Arabia 2011 Conference Innovative Water & Wastewater Technologies for A Sustainable Environment Conference Bapco Innovative Waste Water Treatment Plant 2 nd February 2011 Gulf Hotel Kingdom of Bahrain Essa Al-Ansari
34

Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Apr 23, 2018

Download

Documents

vanminh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Water Arabia 2011 Conference

Innovative Water & Wastewater Technologies forA Sustainable Environment Conference

Bapco Innovative Waste Water Treatment Plant

2nd February 2011Gulf Hotel

Kingdom of Bahrain

Essa Al-Ansari

Page 2: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

• 1936 Bahrain Refinery with a capacity of 10,000 BBLD was commissioned. The first unit is still running.

• Environmental concerns only started to develop in the late 60’s and early 70’s within the industrialized world.

• Legislative Decree No. 21, 1996 with respect to the Environment.

• Ministerial Order No. 10, 1999 Environmental Standards (Air & Water).

• Air & Water Standards revised in 2001.• Ministerial Order No. 3, 2006, Management of

Hazardous Wastes.

Background to the Presentation

Page 3: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

• Ministerial Order No. 4, 2006, Management of Hazardous Chemicals.

• Ministerial Order No. 10, 2006, Monitoring of Air Pollutants.

• A detailed gap analysis was carried out to identify non-compliance.

• The following environmental projects with a total anticipated cost > US$ 400 Million were agreed with GDEWP in year 2000 to achieve compliance:

Background to the Presentation .. Cont’d

Page 4: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

(1) Unleaded Gasoline:Completed: 2000.Cost : US$ 7MM

Page 5: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

(2) KERO-MEROX Unit:Completed: 2001Cost : US$ 30MM

Page 6: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

(3) Sitra Effluent Treatment:Completed: 2002Cost : US$ 1.6

Page 7: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

(4) RGDP :Completed: 2008Cost : US$ 150MM

Page 8: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

(5) Hazardous Waste Landfill Project:Completed : 2006Cost : US$ 5.2 MM

Page 9: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

(6) Tank double seals for VOC Control:Completed : 50Outstanding : 5Cost : US$ 6MM

Page 10: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

(7) Sewage Treating PlantEstd. Completion: 4Q2011Cost : US$ 15MM

Page 11: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

(8) FCCU Particulates Study:Being studied under Refinery Master Plan Project

Page 12: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

(9) Waste Water Treatment (WWTP)

Bapco Innovative

Waste Water Treatment Plant

Page 13: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Introduction• Bapco identified a need to install secondary

treatment to improve the quality of the waste water being discharged from the Refinery to the Gulf.

• At present the waste water undergoes primary treatment in a system which consists of American Petroleum Institute (API) oil separators followed by Induced Air Flotation (IAF) units.

• Biological secondary treatment has been common practice for a long time in Oil Refineries because of the high flow rates and the nature and concentration and concentration of the contaminantsof the contaminants.

• Biological secondary treatment was favoured because of its lower cost.

Page 14: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

The range of different wastewater treatment methods

1

10

100

1000

0.1 1 10 100Chemical oxygen demand (COD), g/l

Was

tew

ater

, m3/

h

Wet oxidation

Adsorption Combustion

Biology

Ozone technology

BAPCO

Application of Waste Water Treatment Technologies Based on Flow and COD ConcentrationLARGE REFINERY WW FLOWS WITH RELATIVELY “LOW”CONCENTRATION ORGANIC POLLUTION: “BIOLOGY” IS “WITHOUT COMPETITION” IN THIS RANGE OF FLOW AND CONCENTRATION, IF IT WORKS FOR THE SPECIFIC CASE

Page 15: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Introduction ... Cont’d

• Bapco’s waste water was considered a challenge to treat because of:

– stringent water quality regulations.– high temperature– high and variable salinity

• This presentation describes how and why the biological process technology used in the new plant design was selected.

Page 16: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Discharge Specifications

•severe specifications on 4 differentnitrogen forms (N-NH4, N-NO3, N-NO2, TKN);

•combined with specifications on organic carbon (COD, BOD , TOC);

Page 17: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

0

10

20

30

40

average values in mg/l

Oil & Grease 39 21 20 20 20 8 8

Hovensa, USA

Valero, USA

Hera Petrochem, Italy

API Ref, Italy

SPM Petro, Italy

Bahrain Govt RC, KSA

Queensland

Refinery,

Notes(1) For the US, the standards specified are load-based (monthly average and daily maximum).(2) For Italian refineries the standards specified are on 3 hours average basis.(3) Bahrain Govt and KSA have specified standards on monthly average and maximum value basis.(4) World Bank have specified standards on maximum value basis.(5) For queensland refinery the values specified are on 75 th percentile and maximum basis.• Hera Petrochem, Ravenna, Italy - Special limit due to discharge into sensitive / naturalistic area (defined by the specific study)

with risk of eutrophication.** SPM Petrochem, Venice - Special limit due to discharge into sensitive / naturalistic area (venice lagoon) issued after detailed

study.

NA

NS -Not specifiedNA -Not available

Comparison of Standards specified by Authorities Worldwide for oil & grease

Page 18: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

0

50

100

average values in mg/l

Amm-N 82 40 11.6 7 2 1 1

Total-N 32 15 10 10

TKN 5 5

Hovensa, USA

Valero, USA

API Ref, Italy

Queensland

SPM Petro,

Hera Petroche

Bahrain Govt

RC, KSA

Notes(1) For the US, the standards specified are load-based (monthly average and daily maximum).(2) For Italian refineries the standards specified are on 3 hours average basis.(3) Bahrain Govt and KSA have specified standards on monthly average and maximum value basis.(4) World Bank have specified standards on maximum value basis.(5) For queensland refinery the values specified are on 75 th percentile and maximum basis.• Hera Petrochem, Ravenna, Italy - Special limit due to discharge into sensitive / naturalistic area (defined by the specific study) with risk of

eutrophication.** SPM Petrochem, Venice - Special limit due to discharge into sensitive / naturalistic area (venice lagoon) issued after detailed study.

NS -Not specifiedNA -Not available

NA NA

NA NA NS NS NS

NS

NS

NS NS

Comparison of Standards Specified by Authorities Worldwide for Ammoniacal-N, Total-N and TKN

Page 19: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

First Steps

• It was necessary to use a fundamental approach since there were no plants working under similar conditions. Bapco decided to start with the basics.

• Samples of waste water were shipped from Bapco to two independent consultants in the UK. These consultants performed bench scale treatability tests on the waste water using live activated sludge.

• The bench scale tests gave a good positive indication that the waste water from the existing primary treatment is biologically treatable.

Page 20: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

First Steps

• The bench scale tests did not provide any firm indication regarding which biological process would be best suited.

• The bench scale tests did not provide enough information to develop a plant design and what information there was, was unlikely to remain valid through scale-up.

• Following the bench scale tests Bapco concluded that the next step would be to conduct pilot scale tests on site in order to increase the level of confidence and provide further insight to the solution.

Page 21: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Pilot Plant

• A pilot plant with anoxic and aerobic biological treatment zones followed by a membrane separation stage was established on site. It was fed with water from the primary treatment.

• The pilot plant was operated on a continuous basis by Bapco for eleven months and then for seven months together with CH2M Hill.

• Pilot plant operation provided a range of fundamental process information. These parameters were used as inputs into process simulation programmes in order to:– Fine tune the configuration of the biological process.– select the most appropriate treatment technology. – prove that the selected technology is effective, applicable and viable.

Page 22: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Waste Water Treatment Pilot PlantPilot Plant

Page 23: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Pilot Plant FlowsheetPilot Plant Flowsheet

Waste Activated

Sludge

Phosphoric Acid

Aerobic

Final Effluent

(permeate)

Membrane Unit

Spent Caustic

Feed Tank 2

Feed Tank 1

Sea Water out

Effluentfrom IAF

Return Activated

Sludge

Heat Exchanger

Caustic Soda

Acetic Acid

Anoxic

Page 24: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Pilot Plant ResultsPilot Plant Results

• The Pilot Plant demonstrated that an MBR can be used to treat Bapco’s waste water and provide as complete a biological treatment as possible, leaving only hard/ non-biodegradable/ recalcitrant COD and TKN un-oxidised.

• Fundamental process information was used as input to process simulations to optimise the design.

• Reference sites were visited. These sites were using similar technology in a tightly controlled discharge environment.

• All of this was translated into a practical design.

Page 25: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Reasons for Selecting MBR Technology • An MBR process, as the Best Available Technology (BAT),

was considered because:Low TSS limit Low TKN limitLow sludge growth rateLow contaminant loading Poor floc settling properties resulting from the high salinity.Will retain all the bugs in the systemLower Cost

• It was considered unlikely to meet the specs with anything other than an MBR.

• Despite rapid growth in MBR installations they have not been used in Refinery because of the perceived risk of membrane fouling by oil. The pilot plant demonstrated the manageability of this risk.

Page 26: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Process Configuration • Currently the Best Available Technology (BAT) for the

secondary biological treatment of refinery waste water would be an MBR; a biological plant (anoxic and aerobic zones) followed by a membrane separation stage.

• This process offers the most complete biological treatment possible including nitrogen removal. The specification from the GDEWP is stringent on all forms of nitrogen.

• 4 biological stages (anoxic/ aerobic/ anoxic/ aerobic) are necessary to meet the stringent specifications.

• Further biological treatment is not possible and as a result of this the polluting nature of the treated water is at an absoluteminimum. This was also supported by toxicity testing.

• No problems with oil on the membrane or other issues concerning the membrane material were encountered.

Page 27: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Final Process Configuration

• The final process configuration is:

– Max capacity 5000 USgpm– Unit feed pit– Equalization system– Cooling system– Integrated 4-stage flexible biological system

(organics removal, nitrification and denitrification)– Membrane tanks for liquid/solid separation

system– Sludge treatment (storage and dewatering

system)– Chemical storage and dosing systems.

Page 28: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Spent Caustic

• Bapco has a waste stream of spent caustic, and ways of handling it in an environmentally acceptable way were being investigated.

• Following experiments on the pilot plant it was demonstrated that the spent caustic, when added in a controlled manner could be processed without a problem.

• The Pilot Plant mass balance showed a COD shortfall as required by the de-nitrification reaction. As an additional benefit, the spent caustic could help reduce the shortage by providing COD. This saves acetic acid addition as COD source.

• As another benefit, the alkalinity provided by the spent causticreduces the alkalinity required for nitrification. This saves fresh caustic addition.

Page 29: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Process FlowsheetProcess Flowsheet

Acetic acid or other carbon source

Return Activated Sludge Waste Activated

Sludge

AerobicAnoxic

Equalised Effluentfrom IAF

Aerobic

Final Effluent (permeate)

Membrane Unit

Spent Caustic

Nitrate Recycle

Page 30: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Project Status• The Engineering Design Package EDP was

completed in December 2008.

• Front End Engineering Design (FEED) was completed in December 2009.

• EPC was awarded to GS E&C through Tender Board competitive bidding.

• Project was kicked off in November 2010.

• Project completion is scheduled for June 2012.

Page 31: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Waste Water Treatment PlantPlant

Page 32: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Summary

• From a position of no one knowing anything about the best process, if any at all, to treat its problematic waste water and spent caustic, Bapco first established a knowledge base and then developed that further to a practical design based on an MBR, a state of the art technology.

Page 33: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

Thank You

Page 34: Bapco Innovative Waste Water Treatment Plant - SAWEA · Bapco Innovative Waste Water Treatment Plant 2nd February 2011 Gulf Hotel Kingdom of Bahrain ... Petroleum Institute (API)

THE FINAL DESIGN DECISION PROCESSWHAT IS THE APPROPRIATE WW TREATMENT PROCESS?

Wastewater

Organics? HeavyMetals?

Refractory ortoxic organics?

Inorganic salt Load too high?

Recoveryfeasible?

BiologicalTreatment?

More biologicalTreatment?

HeavyMetals?

Inorganic salt Load too high?

BAT forheavy metaltreatment

BAT forsalt (chloride,

sulphate)treatment(option)

BAT* forcentral

biologicaltreatment

BAT fordecentralized

biologicaltreatment

BAT recovery techniquesNF/RO, Adsorption

Extraction/DistribtutionEvaporation

Stripping/gas treatment

BAT abatement techniqueschem reactions (oxidationreduction, hydrolysis, airoxidation), incineration

BAT forheavy metaltreatment

BAT forsalt (chloride,

sulphate)treatment(option)

Balancetank

Discharge

Y

Y

Y

YY

Y

Y

Y

Y

Y

Y

N

N

N

N

N

N

N

N

Y

N

N

N

Y

*BAT = Best Available Technology