BACnet INTERFACE o p e r a t i n g m a n u a l GB

Page 2: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input

2 BACNET Interface - Ref.: OPMBACNE1310-GB_01

1. COM-SLOT INSTALLATION 31. 1. DELPHYS MP/MX 31. 2. DELPHYS BC & GrEEn PowEr 2.0 31. 3. MASTErYS IP+ AnD GP 80 – 120 31. 4. MASTErYS BC 3

2. INTERFACE DEFAULT SETTING 4

2. 1. SErIAL LInk 42. 2. ETHErnET ConnECTIon 4

3. DEVICE CONFIGURATION 43. 1. FInDEr.EXE 43. 2. EXAMPLE oF A BACnET DEvICE PrESEnT In THE nETwork 4

4. WEB SERVER ACCESS 54. 1. LoGIn 54. 2. DEvICE ID 54. 3. BACnET MEnu 54. 4. nETwork MEnu 5

5. LIST OF BACNET OBJECTS FOR SOCOMEC UPS 6

6. DEVICE OBJECT 76. 1. oBjECT ProPErTIES 76. 2. oBjECT_nAME = uPS MoDELS 86. 3. MoDEL_nAME 86. 4. DESCrIPTIon 86. 5. LoCAL_TIME AnD LoCAL_DATE 8

7. MULTI-STATE OBJECT 97. 1. oBjECT ProPErTIES 97. 2. MuLTI-STATE oBjECT DEFInITIon 10

8. BITSTRING OBJECT 118. 1. ProPErTIES 118. 2. oBjECT DESCrIPTIon 12

9. INTEGER VALUE OBJECT 139. 1. ProPErTIES 139. 2. LIST oF MEASurEMEnTS 14

10. REFERENCE 1510. 1. TErMS, DEFInITIonS, ABBrEvIATIonS AnD ACronYMS 15

11. TROUBLESHOOTING 1511. 1. PowEr SuPPLY LED 1511. 2. SErIAL LInk 1511. 3. rESET PHASE 15

12. TESTING TOOL 15

INDEX

Page 3: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input

3

EN

GLS

IH

BACNET Interface - Ref.: OPMBACNE1310-GB_01

Recommendation:

1. Connect the RJ45 on the board

2. Insert the board in the com-slot, power on the UPS

3. Connect the RJ45 to Ethernet Network

1. 1. DELPHYS MP/MXThe board is to install in Com-slot 5 or 6 (upper slots)

1. 2. DELPHYS BC & GrEEn PowEr 2.0The board is to install in Com-slot 2 (upper slot)

1. 3. MASTErYS IP+ AnD GP 80 – 120The board is to install in Com-slot 1 (bottom slot)

1. 4. MASTErYS BCN/A

Warning :

Yellow led on RJ45 is blinking every second in case of RESET phase.

In this case, it’s necessary to follow the procedure bellow:

•DisconnecttheEthernetNetworkcable(onsite),

•Unplugtheboardfromtheslot,orpowerofftheUPS.

•Inserttheboardagaininthecom-slot,powerontheUPS

•ConnecttheRJ45cableontheEthernetNetwork(onsite)

1. COM-SLOT INSTALLATION

Page 4: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input

4 BACNET Interface - Ref.: OPMBACNE1310-GB_01

2. INTERFACE DEFAULT SETTING

3. DEVICE CONFIGURATION

2. 1. SErIAL LInk

The interface uses a serial link as input : 9600,N,8,1 slave 1.

Make sure that the serial link of the slot used for this interface has the same settings.

2 LEDs indicates the serial activity (RX and RT signals). Those LEDs are blinking every 5 seconds.

2. 2. ETHErnET ConnECTIon

DHCP set by default.

It is possible to set a fixed IP address using web interface of the board.

3. 1. FInDEr.EXE

This tool is used to discover all BACnet devices on the network.It’s necessary to check the MAC address of each device having the right IP address of the devices.

3. 2. EXAMPLE oF A BACnET DEvICE PrESEnT In THE nETwork

WARNING

TheIPconfigurationisnotpossibleviathistool.

Page 5: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input

5

EN

GLS

IH

BACNET Interface - Ref.: OPMBACNE1310-GB_01

4. WEB SERVER ACCESS

To change the DEVICE ID and the IP address is necessary to open the embedded web server.After checking the IP address with FINDER tool, enter this address in the web browser.

4. 1. LoGIn

A login page is opened :Login: rootPassword: CemocoS

4. 2. DEvICE ID

By default the device ID is 1338If several devices are connected on the same network, it is necessary to change the ID, on all of them.

4. 3. BACnET MEnu

Change the ID, and Apply

4. 4. nETwork MEnu

After changing parameters, it’s necessary to root the device.

Page 6: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input

6 BACNET Interface - Ref.: OPMBACNE1310-GB_01

Device objectMulti-state value objects :

• LoadStatus • UPSStatus • InverterStatus • RectifierStatus • RectInputStatus • BypassInputStatus • BatteryStatus • UPSAlarms • DeviceStatus

Bit String object :• UPSAlarms

Integer value Objects• UPS load rate L1 • UPS load rate L2 • UPS load rate L3 • UPS load rate • UPS output kW • Output kVA L1 • Output kVA L2 • Output kVA L3 • Output current L1 • Output current L2 • Output current L3 • Output voltage L1 • Output voltage L2 • Output voltage L3 • Output frequency • UPS temperature • Battery voltage + • Battery voltage - • Battery current • Battery capacity % • Battery capacity • Remaining BackupTime • InputVoltage L1 • InputVoltage L2 • InputVoltage L3 • InputFrequency • InputPower L1 • InputPower L2 • InputPower L3 • Bypass voltage L1 • Bypass voltage L2 • Bypass voltage L3 • Bypass frequency

Note:If the Bit String Object is not managed by the system, use the multi-state value Object UPSAlarm

5. LIST OF BACNET OBJECTS FOR SOCOMEC UPS

Page 7: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input

7

EN

GLS

IH

BACNET Interface - Ref.: OPMBACNE1310-GB_01

6. DEVICE OBJECT

6. 1. oBjECT ProPErTIES

PropertyIdentifier Property DatatypeConformance

CodeSupported

Readable(R)Writable(W)

UPS Value

Object_Identifier BACnetObjectIdentifier R √ R

Object_Name CharacterString R √ R UPS model

Object_Type BACnetObjectType R √ R

System_Status BACnetDeviceStatus R √ R

Vendor_Name CharacterString R √ R SOCOMEC UPS

Vendor_Identifier Unsigned16 R √ R 591

Model_Name CharacterString R √ R kVA *10

Firmware_Revision CharacterString R √ R

Application_Software_Version CharacterString R √ R

Location CharacterString O

Description CharacterString O Serial number

Protocol_Version Unsigned R √ R

Protocol_Revision Unsigned R √ R

Protocol_Services_Supported BACnetServicesSupported R √ R

Protocol_Object_Types_Supported BACnetObjectTypesSupported R √ R

Object_List BACnetARRAY[N]of BACnetObjectIdentifier R √ R

Max_APDU_Length_Accepted Unsigned R √ R

Segmentation_Supported BACnetSegmentation R √ R

Max_Segments_Accepted Unsigned O1

VT_Classes_Supported List of BACnetVTClass O2

Active_VT_Sessions List of BACnetVTSession O2

Local_Time Time O √ R UPS time

Local_Date Date O √ R UPS day

UTC_Offset INTEGER O

Daylight_Savings_Status BOOLEAN O

APDU_Segment_Timeout Unsigned O1

APDU_Timeout Unsigned R √ R

Number_Of_APDU_Retries Unsigned R √ R

List_Of_Session_Keys List of BACnetSessionKey O

Time_Synchronization_Recipients List of BACnetRecipient O

Max_Master Unsigned(1..127) O

Max_Info_Frames Unsigned O

Device_Address_Binding List of BACnetAddressBinding R √ R

Database_Revision Unsigned R √ R

Configuration_Files BACnetARRAY[N] of BACnetObjectIdentifier O

Last_Restore_Time BACnetTimeStamp O

Backup_Failure_Timeout Unsigned16 O

Active_COV_Subscriptions List of BACnetCOVSubscription O

Slave_Proxy_Enable BACnetArray[N] of BOOLEAN O

Manual_Slave_Address_Binding List of BACnetAddressBinding O

Auto_Slave_Discovery BACnetArray[N] of BOOLEAN O

Slave_Address_Binding List of BACnetAddressBinding O

Profile_Name CharacterString O

1Requiredifsegmentationofanykindissupported.2 If one of the properties VT_Classes_Supported or Active_VT_Sessions is present, then both of these properties shall be present. Both

Page 8: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input

8 BACNET Interface - Ref.: OPMBACNE1310-GB_01

6. 2. oBjECT_nAME = uPS MoDELS

List of supported UPS MODELS

•MASTERYS GP 80 - 120

•MASTERYS IP+

•DELPHYS GP

•DELPHYS MP & MX

6. 3. MoDEL_nAME

Defines the value of nominal UPS power in kVA * 10.

6. 4. DESCrIPTIon

Gives the UPS serial number in 10 characters.

6. 5. LoCAL_TIME AnD LoCAL_DATE

If the Date and Time are not available by the UPS, Local Time and Local Date identifiers are not managed.

Page 9: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input

9

EN

GLS

IH

BACNET Interface - Ref.: OPMBACNE1310-GB_01

7. MULTI-STATE OBJECT

7. 1. oBjECT ProPErTIES

PropertyIdentifier Property Datatype ConformanceCode

Object_Identifier BACnetObjectIdentifier R

Object_Name CharacterString R

Object_Type BACnetObjectType R

Present_Value Unsigned R1

Description CharacterString O

Status_Flags BACnetStatusFlags R

Event_State BACnetEventState R

Reliability BACnetReliability O2

Out_Of_Service BOOLEAN R

Number_Of_States Unsigned R

State_Text BACnetARRAY[N] of CharacterString O

Priority_Array BACnetPriorityArray O3

Relinquish_Default Unsigned O3

Time_Delay Unsigned O4

Notification_Class Unsigned O4

Alarm_Values List of Unsigned O4

Fault_Values List of Unsigned O4

Event_Enable BACnetEventTransitionBits O4

Acked_Transitions BACnetEventTransitionBits O4

Notify_Type BACnetNotifyType O4

Event_Time_Stamps BACnetARRAY[3] of BACnetTimeStamp O4

Profile_Name CharacterString O

1 If Present_Value is commandable, then it is required to be writable. This property is required to be writable

when Out_Of_Service is TRUE.

2 If Present_Value is commandable, then both of these properties shall be present.

3 This property is required if the object supports COV reporting.

4 These properties are required if the object supports intrinsic reporting.

Page 10: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input

10 BACNET Interface - Ref.: OPMBACNE1310-GB_01

7. 2. MuLTI-STATE oBjECT DEFInITIon

BACnet Object Description (state_text) Value

Load Status Load on maintenance Bypass 1Load on automatic bypass 2UPS in eco mode 3Normal mode 4Load on Inverter 5Load OFF 6

UPS Status UPS in maintenance 1UPS on battery 2UPS working 3UPS in standby 4

Inverter Status Inverter OFF 1Inverter ON 2

Rectifier Status Rectifier OFF 1Rectifier ON 2

RectInput Status Absent 1Out of tolerance 2OnGetSet 3OK 4

Bypass Input Status Absent 1Out of tolerance 2Synchro with inverter 3OK 4

Battery Status Disconnected 1BatteryAlarm 2Battery end of BUT / Low 3Discharged 4Discharging 5Test in progress 6Charging 7Battery OK 8

Alarm NO ALARM 1IMMINENT STOP 2OVERLOAD 3TRANSFER IMPOSSIBLE 4BATTERY GENERAL ALARM 5CHARGER / BOOSTER GENERAL ALARM 6INVERTER GENERAL ALARM 7RECTIFIER GENERAL ALARM 8BYPASS GENERAL ALARM 9GENERAL ALARM 10

DeviceStatus Running 1Ready 2No Communication with UPS 3Fault 4

Page 11: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input

11

EN

GLS

IH

BACNET Interface - Ref.: OPMBACNE1310-GB_01

8. BITSTRING OBJECT

8. 1. ProPErTIES

Property Identifier Property Datatype Conformance Code

Object_Identifier BACnetObjectIdentifier R

Object_Name CharacterString R

Object_Type BACnetObjectType R

Description CharacterString O

Present_Value BIT STRING R1

Bit_Text BACnetARRAY[N] of CharacterString O

Status_Flags BACnetStatusFlags R

Event_State BACnetEventState O3

Reliability BACnetReliability O

Out_Of_Service BOOLEAN O

Priority_Array BACnetPriorityArray O2

Relinquish_Default BIT STRING O2

Time_Delay Unsigned O3

Notification_Class Unsigned O3

Alarm_Values BACnetARRAY[N] of BIT STRING O3

Bit_Mask BIT STRING O3

Event_Enable BACnetEventTransitionBits O3

Acked_Transitions BACnetEventTransitionBits O3

Notify_Type BACnetNotifyType O3

Event_Time_Stamps BACnetARRAY[3] of BACnetTimeStamp O3

Profile_Name CharacterString O

1 This property is required to be writable when Out_Of_Service is TRUE.

2 If Present_Value is commandable, then both of these properties shall be present.

3 These properties are required if the object supports intrinsic reporting.

Page 12: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input

12 BACNET Interface - Ref.: OPMBACNE1310-GB_01

8. 2. oBjECT DESCrIPTIon

BACnet Object Description Description

UPSAlarms

GeneralAlarm bit0 ImminentStop bit1 UPSOverload bit2 UPSStoppedofrOverload bit3 OverloadTimeout bit4 UPSOverTemperature bit5 RedundancyLost bit6 InsuffisantRessources bit7 TransferImpossible Bit8 MaintenanceBypassAlarm bit9 MaintenanceAlarm bit10 t-Service alarm bit11 General alarm Unit1 bit12 General alarm Unit2 bit13 General alarm Unit3 bit14 General alarm Unit4 bit15 General alarm Unit5 bit 16 General alarm Unit6 bit 17 Battery Alarm bit 18 Battery test alarm bit 19 BatteryCircuitOpen bit 20 BatteryRoomAlarm bit 21 BatteryVoltageAlarm bit 22 Battery Charger Alarm bit 23 Booster Alarm bit 24 Rectifier Alarm bit 25 Inverter Alarm bit 26 OuputVoltage failure bit 27 Bypass Alarm bit 28 PLL fault bit 29 PhaseDetetction Alarm bit 30 Fan failure bit 31 Electronics failure bit 32 PowerSupplyFault bit 33 GenSetAlalrm bit 34 UpsPowerOFF (emergency) bit 35 ImproperConditionOfuse bit 36 ExternalAlarm1 bit 37 ExternalAlarm2 bit 38 ExternalAlarm3 bit 39 ExternalAlarm4 bit 40

BACnet answers ‘True’ if the alarm is set or ‘False’ if the alarm is not active.

The alarm list is managed regarding the kind of UPS. It could be that not all alarms are managed by the UPS con-

cerned.

Page 13: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input

13

EN

GLS

IH

BACNET Interface - Ref.: OPMBACNE1310-GB_01

9. INTEGER VALUE OBJECT

9. 1. ProPErTIES

The properties in green are manage by the interface.Present Value gives the reel time measurement value read from the UPS

PropertyIdentifier Property Datatype ConformanceCode

Object_Identifier BACnetObjectIdentifier R

Object_Name CharacterString R

Object_Type BACnetObjectType R

Description CharacterString O

Present_Value INTEGER R1

Status_Flags BACnetStatusFlags R

Event_State BACnetEventState O4

Reliability BACnetReliability O

Out_Of_Service BOOLEAN O

Units BACnetEngineeringUnits R

Priority_Array BACnetPriorityArray O2

Relinquish_Default INTEGER O2

COV_Increment Unsigned O3

Time_Delay Unsigned O4

Notification_Class Unsigned O4

High_Limit INTEGER O4

Low_Limit INTEGER O4

Deadband Unsigned O4

Limit_Enable BACnetLimitEnable O4

Event_Enable BACnetEventTransitionBits O4

Acked_Transitions BACnetEventTransitionBits O4

Notify_Type BACnetNotifyType O4

Event_Time_Stamps BACnetARRAY[3] of BACnetTimeStamp O4

Profile_Name CharacterString O

1IfPresent_Valueiscommandable,thenitisrequiredtobewritable.Thispropertyisrequiredtobewrit-able when Out_Of_Service is TRUE.

2IfPresent_Valueiscommandable,thenbothofthesepropertiesshallbepresent.

3 This property is required if the object supports COV reporting.

4 These properties are required if the object supports intrinsic reporting.

Page 14: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input

14 BACNET Interface - Ref.: OPMBACNE1310-GB_01

9. 2. LIST oF MEASurEMEnTS

Unit Format UPS COMPATIBILITY

UPSOutputMeasuements UPS load rate L1 %

UPSOutputMeasuements UPS load rate L2 % -1 for 1 phase UPS

UPSOutputMeasuements UPS load rate L3 % -1 for 1 phase UPS

UPSOutputMeasuements UPS load rate %

UPSOutputMeasuements UPS output kW kW (*10)

UPSOutputMeasuements Output kVA L1 kVA (*10)

UPSOutputMeasuements Output kVA L2 kVA (*10) -1 for 1 phase UPS

UPSOutputMeasuements Output kVA L3 kVA (*10) -1 for 1 phase UPS

UPSOutputMeasuements Output current L1 A (*10)

UPSOutputMeasuements Output current L2 A (*10) -1 for 1 phase UPS

UPSOutputMeasuements Output current L3 A (*10) -1 for 1 phase UPS

UPSOutputMeasuements Output voltage L1 V

UPSOutputMeasuements Output voltage L2 V -1 for 1 phase UPS

UPSOutputMeasuements Output voltage L3 V -1 for 1 phase UPS

UPSOutputMeasuements Output frequency Hz (*10)

UPSOutputMeasuements UPS temperature °C (*10)

BatteryMeasurements Battery voltage + V (*10)

BatteryMeasurements Battery voltage - V (*10) Set to 0 for DELPHYS range

BatteryMeasurements Battery current A (*10) Signed value

BatteryMeasurements Battery capacity % %

BatteryMeasurements Battery capacity Ah (*10)

BatteryMeasurements Remaining BackupTime Mn

RectifierMeasurements InputVoltage L1 V

RectifierMeasurements InputVoltage L2 V -1 for 1 phase UPS

RectifierMeasurements InputVoltage L3 V -1 for 1 phase UPS

RectifierMeasurements InputFrequency Hz (*10) Not available for DELPHYS MP/MX

RectifierMeasurements InputPower L1 kVA (*10)

RectifierMeasurements InputPower L2 kVA (*10) -1 for 1 phase UPS

RectifierMeasurements InputPower L3 kVA (*10) -1 for 1 phase UPS

BypassMeasurements Bypass voltage L1 V

BypassMeasurements Bypass voltage L2 V -1 for 1 phase UPS

BypassMeasurements Bypass voltage L3 V -1 for 1 phase UPS

BypassMeasurements Bypass frequency Hz (*10)

Page 15: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input

15

EN

GLS

IH

BACNET Interface - Ref.: OPMBACNE1310-GB_01

Référence Document Version Date

[1] ANSI/ASHRAE Standard 135-2004 2004

[2]ANSI/ASHRAE Addendum wANSI/ASHRAE Standard 135-2008(Integer Value & BitString Value Objects Types)

Jan 2010

10. 1. TErMS, DEFInITIonS, ABBrEvIATIonS AnD ACronYMS

Abréviation Nom complet

ASHRAEAmerican Society of Heating,Refrigerating and Air-Conditioning Engineers, Inc.

BACnet Building Automation and Control Networks

UPS Uninterruptible Power Supply

11. TROUBLESHOOTING

11. 1. PowEr SuPPLY LEDIf the LED 5V_ISO is not ON, the board is not power supplied.

11. 2. SErIAL LInk

Rx/Tx blinking means that the board dials with the UPS, and update the BACnet data base managed by the DEVICE.No blinking means the serial link is not set according the values needed for the DEVICE:9600 baud, no parity, 1 stop bit, slave 1.

11. 3. rESET PHASE

Yellow led flashing every seconds.Disconnect the Ethernet Cable (on site)Remove the board from the slotInsert again the boardReconnect the Ethernet Network cable (on site)

12. TESTING TOOL

The EPICS file can be used with VTS tools for example to test the BACnet interface.This kind of tool can browse all BACnet UPS object.

10. REFERENCE

Page 16: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input
Page 17: BACnet INTERFACE - Socomec BACNET Interface - Ref.: OPMBACNE1310-GB_01 2. INTERFACE DEFAULT SETTING 3. DEVICE CONFIGURATION 2. 1. SErIAL LInk The interface uses a serial link as input

www.socomec.com

heaD oFFice

SOCOMEC GROUPS.A. SOCOMEC capital 10 816 800€ R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse F-67235 Benfeld Cedex - FRANCE Tel. +33 3 88 57 41 41 Fax +33 3 88 74 08 00 [email protected]

Socomec worldwide

BELGIUMUPS / Power Control & Energy Efficiency / SolarTel. +32 2 340 02 30 Fax +32 2 346 28 99 [email protected]

FRANCEUPS / Power Control & Energy Efficiency / SolarTel. +33 1 45 14 63 00 Fax +33 1 48 67 31 12 [email protected]

GERMANYPower Control & Energy EfficiencyTel. +49 7243 65292 0 Fax +49 7243 65292 13 [email protected]. +49 621 71 68 40 Fax +49 621 71 68 444 [email protected]

ITALYPower Control & Energy EfficiencyTel.+39 02 98 49 821 Fax +39 02 98 24 33 10 [email protected]. +39 0444 598611 Fax +39 0444 598627 [email protected] Tel.+39 02 98 242 942 Fax +39 02 98 240 723 [email protected]

NETHERLANDSUPS / Power Control & Energy Efficiency / SolarTel. +31 30 760 0900 Fax +31 30 637 2166 [email protected]

POLANDPower Control & Energy EfficiencyTel. +48 91 442 64 11 Fax +48 91 442 64 19 [email protected]. +48 22 825 73 60 Fax. +48 22 825 73 60 [email protected]

PORTUGALUPS / SolarTel.+351 261 812 599 Fax +351 261 812 570 [email protected]

ROMANIAUPS / Power Control & Energy Efficiency / SolarTel. +40 21 319 36 88 Fax +40 21 319 36 89 [email protected]

RUSSIAUPS / Power Control & Energy Efficiency / SolarTel. +7 495 775 19 85 Fax +7 495 775 19 85 [email protected]

SLOVENIAUPS / Power Control & Energy Efficiency / SolarTel. +386 1 5807 860 Fax +386 1 561 11 73 [email protected]

SPAINUPS / Power Control & Energy Efficiency / SolarTel. +34 93 540 75 75 Fax +34 93 540 75 76 [email protected]

UNITED KINGDOMPower Control & Energy EfficiencyTel. +44 1462 440 033 Fax +44 1462 431 143 [email protected].+44 1285 863 300 Fax+44 1285 862 304 [email protected]

TURKEYUPS / Power Control & Energy Efficiency / SolarTel. +90 216 540 71 20-21-22 Fax +90 216 540 71 27 [email protected]

non

con

trac

tual

doc

umen

t. ©

201

3, s

ocom

ec s

a. a

ll rig

hts

rese

rved

. - T

o he

lp p

rote

ct th

e en

viro

nmen

t, th

is d

ocum

ent h

as b

een

prin

ted

on P

eFc

pap

er (P

rogr

amm

e fo

r th

e e

ndor

sem

ent o

f For

est c

ertif

icat

ion)

.

YoUr DisTriBUTor

in asia PaciFic

AUSTRALIAUPSTel. +61 2 9325 3900 Fax +61 2 9888 9544 [email protected]

CHINAUPS / Power Control & Energy EfficiencyTel. +86 21 52 98 95 55 Fax +86 21 62 28 34 68 [email protected]

INDIAPower Control & Energy EfficiencyTel. +91 124 4027210 Fax +91 124 4562738 [email protected] / SolarTel. +91 44 39215400 Fax +91 44 39215450 & 51 [email protected] [email protected]

SINGAPORE UPS / Power Control & Energy EfficiencyTel.+65 6506 7600 Fax +65 64 58 7377 [email protected]

THAILANDUPSTel. +66 2 941 1644 7 Fax +66 2 941 1650 [email protected]

VIETNAMUPSTel. +84 8 3559 1220 Fax +84 8 3559 1221 [email protected]

in MiDDle easT

UNITED ARAB EMIRATESUPS / Power Control & Energy Efficiency / SolarTel.+971 4 29 98 441 Fax +971 4 29 98 449 [email protected]

in aMerica

USA, CANADA & MEXICOPower Control & Energy EfficiencyTel. +1 617 245 0447 Fax +1 617 245 0437 [email protected]

oTher coUnTries

NORTH AFRICAAlgeria / Morocco / [email protected]

AFRICAOther [email protected]

SOUTH EUROPECyprus / Greece / Israel / [email protected]

SOUTH AMERICATel. +34 93 540 75 75 [email protected]

MORE DETAILSwww.socomec.com/worldwide

in eUroPe