Twa Panel Systems Inc. April 12, 2012 1201 – 4 th St. Nisku, Alberta, Canada P: +1 (780) 955-8757 T9E 7L3 F: +1 (780) 965-8757 www.twapanels.ca
Nov 15, 2014
Twa Panel Systems Inc. April 12, 20121201 – 4th St.Nisku, Alberta, Canada P: +1 (780) 955-8757T9E 7L3 F: +1 (780) 965-8757www.twapanels.ca
Agenda
• Active Beam Origin
• Active Beam Overview
• How A.B.’s Function
• Construction
• System comparisons
• Air-side Information
• Water-side Information
• Capacity
• Benefits & Limitations
• Applications
Active Beam Origin
Passive Chilled Beams(1990’s)
Perimeter Induction Unit
(1950’s)
Modular Active Chilled Beams
(2000’s)
Radiant Panels(1950’s)
Chilled Sails
(1990’s)
•Origins in Europe
Active Beam Overview
• High acceptance rate in Europe• Historically high energy costs
• North American market increasing due largely to: • Green initiatives• Increasing energy costs• Increased installed base (Familiarity & Successful projects)• Lowering cost due to increasingly competitive market
Active Beam Overview
• Hydronic systems use water as the energy transport medium
• Water has many times the thermal capacitance as compared to air
Conduction Convection Radiation
Active Beam Overview
Modes of Heat Transfer
How A.B.’s Function
A – Duct connection S/A (primary Air) from the AHUB – Primary air (P/A) plenum Static Pressure forms and drives P/A through nozzlesC – Perforated grille Room air (Secondary air) is induced, through grille, into coilD – Unit mounted coil 2 or 4 pipe coil, cools/heats the secondary airE – Mixed air P/A and secondary air mixF – Discharge air Mixed discharge air exits the beam, Coanda is induced to throw the air horizontally
How A.B.’s Function
Construction Standard Beam Dimensions:Width: 1’, 2’Length: 2’, 4’, 6’, 8’, 10’
Standard Coil Lengths:2’, 3’, 4’, 5’, 6’, 7’, 8’, 9’, 10’
Various Nozzle Types• Induction Ratio• Acoustics
Discharge Pattern:1, 2, & 4 - way
Other:• Frame for Drywall• Exposed – Coanda
Wings
System comparisonsActive Beams• Low Energy Consumption• Reasonable Acoustics• Low maintenance costs (No moving parts)• Cooling Capacity: ~100 – 394 W/m2 (32 – 125 Btuh/ft2)
Versus
Fan Coil Units (FCU)• Medium/High Energy Consumption• Reasonable/Loud Acoustics• Adaptable Solution• Potential for high maintenance costs• Cooling Capabilities: ~100 – 200 W/m2 (32 – 64 Btuh/ft2)
Variable Air Volume (VAV) System• Low Energy Consumption• Quiet/Reasonable acoustics• Most efficient all air system• Cooling Capabilities: ~100 – 200 W/m2 (32 – 64 Btuh/ft2)
Variable Refrigerant Volume (VRV) System• High Energy Consumption• Reasonable Acoustics• Potential for high installation/maintenance costs• Cooling Capabilities: ~150 – 200 W/m2 (48 – 64 Btuh/ft2)
Air Side Information (Primary Air - Overview)
• Meet all ventilation requirements• Min. Vent. (O/A requirements)• Remove 100% of the latent loads (Psychrometrics)• Induce enough Rm./A to meet sensible loads
**Greatest of these factors sets the minimum air flow rate**
• Higher SAT may be used• May use heat recovery strategies for increased energy savings
• Decreased AHU & Duct size
• Decrease in fan energy
Air Side Information (Primary Air)
• Majority of energy is saved at the FAN
• Air-side Load Fraction (ALF)– The smaller the air-side load fraction, the more energy can be saved by
using a chilled beam system
Office Classroom Lobby
O/A Requirement(cfm/ft2)
0.15 0.5 1
Air Volume (All Air System) (cfm/ft2)
1 1.5 2
Air-side Load Fraction 15% 33% 50%
Air Side Information (Primary Air)
Air Side Information(Psychrometrics)
Psychrometric review required to prevent condensation
Standard Procedure:
• Remove moisture from the P/A at AHU
• Dry P/A lowers the space dew point temperature
• To prevent condensate on the coil:
Space dew point temp. < EWT
Not all spaces are suitable for active beams:
• Suitability engineering check - % of Sensible from
CFMLatent
Air Side Information(Psychrometrics)
Option 1 Option 2
Primary air dew point
48°F 51.5°F
Room air dew point
55°F 57.8°F
Secondary CWT
55°F 58°F
Dehumidification
0.002 lbs/lbDA 0.002 lbs/lbDA
RESET FOR ENERGY SAVINGS!
Legend:■ Easy , Application of active beam products is natural
■ Medium , Application of active beam products requires some additional design to control building moisture
■ Difficult, Application of active products is more difficult and humidity must be carefully considered
Air Side Information(Psychrometrics & Climate Regions)
Air Side Information(P/A Design Parameters)
Typical Design Conditions (Cooling):
S/A SpaceTDry Bulb: 55 - 65°F TDry Bulb: 75°FTWet Bulb: 53 - 57°F TWet Bulb: 64°FTDew point: 52°F TDew point: 58°F
R.H.: 55% ΔGr = 13.64 Gr/lb
Typical Design Conditions (Heating):
S/A SpaceTDry Bulb: 65°F TDry Bulb: 70°F
R.H.: 50%
QL = 0.68*CFM*ΔGr Qs = 1.08*CFM*ΔT
Air Side Information(Space Over Cooling)
• Maintain reasonable dew point control
• Meet 100% of latent load under Peak Design conditions
• Infiltration
• Maximum occupancy
• Other sources of moisture
• Limit over-cooling
• Keep air-side load fraction low
• Reset air temperature
• CHWS Shut-off control or EWT reset
• VAV for fluctuating occupancy
Air Side Information(Air Velocities & Thermal Comfort)
ASHRAE Std. 55
• Occupied Zone• ΔT and Air velocity
determine Thermal Comfort• 80% Occupancy Satisfaction• Radiant Affect
Active Beams
• Higher discharge air temp.• Highest air velocities are at
the perimeter of the space
Air Side Information(Air Velocities & Thermal Comfort)
Active Beam
Diffuser
Air Side Information(Plenum Air Pressure Drop)
50
70
90
110
130
150
170
190
210
230
250
0 5 10 15 20 25 30 35 40
Primary air [l/s]
Ple
num
Pre
ssur
e [P
a]
K 60A
K 60C
K 60D
K 60B
1.00”
0.93”
0.85”
0.77”
0.69”
0.60”
0.44”
0.36”
0.28”
0.20”
0.52”
10 21 32 42 53 64 74 85CFM
• Fan Static is higher
• Less penalty then high air flow
• Can correlate pressure and air flow
• Air volume is difficult to measure
• Measuring pressure is easy and reliable
• Pressure is the common factor
• Plenum and ducting should be sealed
Air Side Information(Acoustics)
0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.415
20
25
30
35
40
45
Plenum Pressure [“w.c.]
Lw
A [
dB
(A)]
Active beams can be very quiet!
Chart reports acoustic values
without roomattenuation
effect
2’x8’ – Smaller Nozzles
2’x8’ – Larger Nozzles
Air Side Information(Air Side Controls)
Tota
l cap
acity
Static pressure
• CAV primary air flow is typically simple with orifice plate “Iris” type dampers.• Varying the plenum
pressure yields a non-linear capacity response. Tight control with variable plenum pressure is typically impractical.
Air Side Information(Air Side Controls)
Tota
l cap
acity
Primary air volume
• Occupancy Valve may solve the issue of over-cooling a space with un-tempered primary air.
• Plenum static pressure range (0.3”-1.2” w.c. max)
• VAV modulation range is low with active beams
Air Side Information(Possible Dampers)
Iris Dampers – (angled multi-leaf
blades)
Iris Dampers
Pressure independent – butterfly type
Air Side Information(Common Design Pitfalls)
• Two Air-side Design Concerns:
1) Psychrometrics (Cooling only)
2) Preliminary Design based on DOAS system
Water Side Information (Overview)
• Coil responsible for majority of the sensible load• Cooling & Heating
• Design requires:• Water flow rate• Circuit pressure drop• Temperatures (EWT, LWT)
• Increase in pump size and pump energy• Fan Energy vs. Pump Energy = Net energy savings
Water Side Information (Water Design Parameters)
• Active Beam Cooling:• EWT temperature, typically between 56 – 62°F
• Secondary CHWS loop required
• Psychrometrics – (Condensation control)
• Generally EWT = 1 – 2 °F above SPACE dew point temp.
• Active Beam Heating:• EWT temperature, typically between 100 – 120°F
• Secondary HWS loop required
• Minimum flow rate per circuit = 0.45 to 0.65 GPM• Prevent laminar flow (more important for cooling)
Water Side Information (Piping Design)
Water system pressure control
• Variable speed pump and differential pressure sensor
• Reduces energy by lowering pump loading
• Maintain constant pressure
• Can cause imbalances in the system when not at full flow if pressure independent flow control valves are not used
Water Side Information (Piping Design)
Direct return• Length of pipe varies from supply
header to return header for each unit
• Change in pressure drop from one circuit to another, affects flow rates
• Use balancing valves or circuit setters
• Can cause imbalances in the system when not at full flow if pressure independent flow control valves are not used
Water Side Information (Piping Design)
Reverse return
• First supplied, last returned
• Zone or array is self-balancing
• Number of balancing valves can be reduced
• Additional pipe length required
• May require pressure independent flow control valves at mains for zone take off
Water Side Information (Piping Design)
Parallel piping
• Used exclusively for chilled beams
• Reduced pressure loss
• Lower flow rates to achieve ΔT
• Better temperature distribution and response
Water Side Information (Water Side Controls)
On/Off valve
• Inexpensive• Adequate control• Flow remains turbulent• Req’d for mix mode ventilation• Small & large zones
Proportional control valve
• Expensive• Advanced control not required• Flow becomes laminar (cooling)• Potential for searching
0 50 100
Seco
ndar
y Cap
acity
Water gpm
0.22 0.440
Turbulent flow
Laminar flow
Minimum flow rate per circuit = 0.45 to 0.65 GPM
Water Side Information (Common Design Pitfalls)
• Three water-side Design Concerns:1) Use of Glycol as the operating fluid
• Especially in cooling
2) Not considering Pressure independent flow control valves
• Especially with large hydronic systems
• Modulating valves
• Variable frequency drive pumps
3) Valve & Entrapped air noise
Capacity Overview
Air Side:
• 100% Latent energy capacity, increase by:• Increasing ΔGr between P/A & Rm/A• Increasing air flow rate
• Minority of sensible capacity, increase by:• Increasing ΔT between P/A & Rm/A• Increasing air flow rate
Water Side:
• Majority of sensible capacity, increase by:• Increasing ΔT between water & Rm/A• Increasing water flow rate
Total Capacity = Air capacity + Water capacity
5
10
15
20
25
30
35
40
100 200 300 400 500 600 700 800
Air
Vo
lum
e [
l/s]
Secondary Capacity [W]
A-DT 8A-DT 10B-DT 8B-DT 10C-DT 8C-DT 10D-DT 8D-DT 10
Typical sensible range is approx. 250 – 1500 BTUh/Ft
• Increasing air flow rate and pressure:
• Significant Increase in Capacity
• Increasing GPM in turbulent flow:
• Marginal Increase in Capacity
Capacity vs. Air Volume
Capacity(Performance Data)
• Applicable standards:• EN 15116: Chilled Beams• ASHRAE/AHRI - SPC 200
• When choosing a manufacturer, ensure they test to an applicable standard!
Active Beam Benefits• Significant Fan Energy savings
• lower overall S/A
• Increased air circulation with high thermal comfort
• Smaller AHU & Ductwork• Lower floor-floor heights• Good retrofit applications• Significant reduction of riser space
• Low maintenance requirements
• Can be integrated with other energy saving systems• Geothermal, ERV’s, Enthalpy wheel…etc
• Water side free cooling may be an option
Active Beam Benefits
• Spaces may be zoned• Increased Comfort• Reduced energy consumption• Individual space temperature control (LEED Compliant)
• Quick response time
• Low to Reasonable Acoustics
Active Beam Limitations
• Potential for higher first cost• Increase in pump energy
• Small Compared to Fan Energy Savings
• Limited air-side free cooling
• Limited VAV modulating range
• High importance for building humidity control in Cooling• Dehumidification at the AHU is required• May require a building envelope upgrade• May require more sophisticated controls for humidity control• May not be acceptable for all spaces, based on latent loads
ApplicationsCommercialOffice spacesData centersShops/Stores
InstitutionalLabsLecture Theatres*
GovernmentSchoolsHospital**AirportsClinics
OtherChild care facilities
*Occupancy may produce high latent requirements**Some areas such as surgical suites do not allow room air to be induce or circulated through the HVAC equipment
Sensible and Latent energy drive suitability
Higher the sensible - the greater the energy savings
Lower the latent - the easier it is to control the dew point temperature of the space (Required due to no condensate pan)
Spaces with:
• High sensible loads & low latent loads • Ideal
• High sensible loads & high latent loads • May be suitable with careful examination
• Low sensible loads & high latent loads • Would not be recommended for use with chilled beams
Not a silver bullet, each space should be individually reviewed to determine suitability
Applications
Open Office Area
Applications
Individual Office Area
Applications
Child Care Center
Applications
Coffee Shop
Questions