Chilled Beam OKNI The OKNI chilled beam is a high capacity device designed for venti- lation, cooling and heating of areas with ceiling heights up to 3 metres. The beam has been designed for integration with suspended ceilings with 300, 450 or 600 mm centres. Integration in a sheet metal cassette ceiling is a possibility. Suitable for most suspended ceiling systems employing Tee-bar or lattice supports, the beam can be supplied in any length from 1140 to 2995 mm. Due to its lightweight construction it is possible to mount the type 300 in a Tee-bar ceiling or to suspend each beam on drop rods or wires. We suggest type 600 to be suspended on drop rods or wires. Options: Units can be fitted with a top or side connection The side connection can be oval in the case of height restrictions. The units can be fitted with Flow Pattern Control (FPC). With the FPC air direction can be set from 0 o to 45 o EcoHVAC products Brisbane 07 3808 9400 Sydney 02 9669 4500 www.ecohvac.com.au Solid Air ® International BV OKNI 600 OKNI 300
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Chilled Beam OKNI
The OKNI chilled beam is a highcapacity device designed for venti-lation, cooling and heating of areaswith ceiling heights up to 3 metres.
The beam has been designed for integration withsuspended ceilings with 300, 450 or 600 mm centres. Integration in a sheet metal cassette ceiling is apossibility. Suitable for most suspended ceiling systems employing Tee-bar or lattice supports, the beamcan be supplied in any length from 1140 to 2995mm. Due to its lightweight construction it is possible to mount the type 300 in a Tee-bar ceilingor to suspend each beam on drop rods or wires.We suggest type 600 to be suspended on droprods or wires.
Options:Units can be fitted with a top or side connection The side connection can be oval in the case ofheight restrictions.
The units can be fitted with Flow Pattern Control(FPC). With the FPC air direction can be set from0o to 45o
The “OKNI extravent” chilled beam is an adjustablebeam fitted with extra nozzles. These extra nozzlescan be activated in groups providing the flexibility tochange from small to large nozzles. The adjustmentcan be done from the front of the beam by sliding amagnetic strip. This patented system guarantees100% air tightness and prevents undesirable sound
production. By using the extravents the primary airduty can be significantly adjusted without the
requirement to change the installed product toone of a different size. This provides the possibility
to alter the application of the beam to suit varying application requirements, i.e. additional air (fromordinary office use to meeting room), heating and orcooling.
Options are the same as with the standard OKNI
OKNV Suspended
The OKNV Suspended chilled beam is designed forsuspended mounting. The beam can be supplied inany length from 1140 to 2995 mm.The OKNV is available in two models: 300 and 450.
The OKNB chilled beam is a high capacity device designed for ventilation, cooling and heating in areaswith ceiling heights up to 3 metres.
The unit has been designed for bulkhead installation.To provide a highly efficient low energy solution tocomfort condition rooms.The OKNB is suited to hotel bedroom or hospital bedroom applications.
Options:Single, or double deflection supply grille.High induction grille.
OKNM T-bar mountable unit
The unit is designed as for T-beam mounting in a
ceiling with a module size of 600 mm.
Surface mounting is also possible.
The closed beam supplies air from four sides and due
to its high induction rate can be mounted universally
in an office. In order to obtain an efficient combination
of ventilation and cooling capacity, three different noz-
The variable volume unit VVOO is suitable forroom temperature control in low, medium and highpressure installations. The units are suitable forboth supply and extract systems.
The variable volume unit with induction is suitablefor room temperature control in low, middle and
high pressure installations.The unit has an integrated sound attenuator section.The secondary side be fitted with a rectangularconnection or a 4 x round connection.
Options:Electronic or pneumatic control equipment.Hot water heating coil.
VCMH Round Constant Volume Unit
The VCMH is a mechanical constant volumedamper. The damper is designed to maintain thedesign volume independent of inlet pressure. Thedesign volume is easily set by adjustment of theexternal sliding scale. The operating range of thedamper is 50 - 1000 Pa (±5%)
VCMR Rectangular Constant Volume
The VCMR is a mechanical constant volumedamper. The damper is designed to maintain thedesign volume independent of inlet pressure. Thedesign volume is easily set by adjustment of theexternal sliding scale. The operating range of thedamper is 50 - 1000 Pa (±10%)