Armed Forces Retirement Home Design Build Services Request for Proposal Gulfport, Mississippi 21 May 2007 General Services Administration Public Buildings Service Southeast Sunbelt Region Real Estate Design and Construction UNCLASSIFIED APPENDIX A – ROOM DATA SHEETS
311
Embed
APPENDIX A – ROOM DATA SHEETS - USMconstruction.usm.edu/stenningmaterials/AFRH-RFP-Specs/Chapter 8... · APPENDIX A – ROOM DATA SHEETS . Armed Forces Retirement Home Design Build
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Armed Forces Retirement Home Design Build Services Request for Proposal Gulfport, Mississippi 21 May 2007
General Services Administration Public Buildings Service Southeast Sunbelt Region Real Estate Design and Construction
UNCLASSIFIED
APPENDIX A – ROOM DATA SHEETS
Armed Forces Retirement Home Design Build Services Request for Proposal Gulfport, Mississippi 21 May 2007
General Services Administration Public Buildings Service Southeast Sunbelt Region Real Estate Design and Construction
UNCLASSIFIED
BASE CONTRACT
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 101
Room Name Entry
Net Area 100
Quantity 1
Adjacency Locate along public corridor.Adjacent to Secretary.Shared with Business Office.
Equipment AV System.Include ceiling-mounted projector, motorized projection screen, and wall-mounted whiteboard.
Arch Notes Conference room also serves as Emergency Operations Center (EOC).Include board table and seating for 12.Room shall have direct access from corridor and Director's office.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
LAN Fiber / CAT MDF.Provide additional voice and data capacity.
Sprinkler FM 200
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide UPS System with 4-hour battery backup to support IT equipment.Provide standby power for 4-hour IT equipment.Provide standby power for HVAC service.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 118
Room Name IT Distribution Closets
Net Area 25
Quantity 19
Adjacency
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Protect in cabinet Data Switch.
Arch Notes Lockable cabinets for telephone, data, and cable TV.
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 226
Room Name Main Trash Rooms (1 per 150 units)
Net Area 300
Quantity 3
Adjacency Trash Chutes (from above).Easy access to Loading Dock.
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment Trash compactor and trash chute with fire-rated doorsat each level.Include smoke detectors in chute.
Arch Notes 1 Trash Room per 150 Units.The DBC shall describe how trash removal is addressed.May be located at First Floor or Wash-Out Level.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Self-cleaning trash chute will require water supply and drain.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Quick Response Heads
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 227
Room Name Trash Room (Includes all Living Units)
Net Area 50
Quantity 19
Adjacency Elevators, Janitor Closet, and Laundry Room.
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal SGL
Wall Construction CMU
Casework
Equipment Self-cleaning trash chute with fire-rated doors.Recycling bins provided by Housekeeping Contractor.
Arch Notes 1 trash room per 24 residents ( Independent Living).1 trash room per 30 residents (Assisted Living).1 trash room per 12 residents (Memory Support and Long Term Care).
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 228
Room Name Main Recycling Room
Net Area 250
Quantity 1
Adjacency Easy Access to Loading Dock.Adjacent to Trash Room.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment Recycling containers provided by contractor.
Arch Notes Once-a-week service.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 229
Room Name Medical Waste Holding Room
Net Area 100
Quantity 1
Adjacency Easy Access to Loading Dock.Adjacent to Trash Room and Main Recycling Room.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal SGL
Wall Construction CMU
Casework
Equipment Secure containers provided by contractor.
Arch Notes 90-day storage facility.For medical waste disposal.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 230
Room Name Loading Area
Net Area 0
Quantity
Adjacency Locate along service corridor.Adjacent to Kitchen, Trash Room(s), and other service and storage areas.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type OHD
Wall Construction CMU
Casework
Equipment Trash compactor in one dedicated loading space.Dock levelers at other loading spaces.Include space for 30 cubic yard dumpster, screened from view, separated from loading dock (could be in
Arch Notes 4 spaces including trash compactor, food delivery, recycling, and typical deliveries.Prefer recessed location, not enclosed, at Main Floor Level.Provide direct connection from Loading Dock to Kitchen (separate from other delivery paths).
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Include motion detectors.
Sprinkler Dry Pipe System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 231
Room Name Building Engineer's Office
Net Area 120
Quantity 1
Adjacency Mechanical / Electrical Room
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Metal SGL w/Side Lite
Wall Construction CMU w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.Include observation window.Provide acoustical treatment. Provide one door to corridor and one door for Mechanical / Electrical room
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 232
Room Name Engineer's Toilet
Net Area 70
Quantity 1
Adjacency Building Engineer's Office
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction CMU w/GWB
Casework Plam Wall Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 233
Room Name Mechanical / Electrical Room
Net Area 5000
Quantity 1
Adjacency Locate as required.Provide exterior access for maintenance.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment Mechanical and Electrical equipment (see separate description).Emergency Generator with 7-day fuel supply (safety items and emergency items).
Arch Notes 7-day survivability is required.Category 5 Hurricane requirements will influence location and layout of mech/elec equipment.2 independent electrical feeders shall be provided for redundant power.Emergency Generators are required.
Temp F (Winter) 50 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide access to building exterior for removal and replacement of major equipment components.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide multiple floor drains.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 301
Room Name Resident Services Chief
Net Area 224
Quantity 1
Adjacency Director's Office Entry and Admissions Officer.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.Conference table for 4 with storage unit.
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency power.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes: Multiple room uses.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 303
Room Name Reception Room
Net Area 800
Quantity 1
Adjacency Hall of Honor, Security Services, Main Entrance, and Concierge.
Floor Finish Carpet 36 oz
Wall Finish Paint & FWC
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment Memorabilia display area (floor and wall units).
Arch Notes Formal Parlor, always ready for formal events.Contains seating groups for 20 people and a grand piano.Provide separate entrance from exterior.Memorabilia displays included items from past, present, and future conflicts and AFRH history.
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control NoneCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes: Provide lighting for multiple room uses.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 304
Room Name Concierge
Net Area 144
Quantity 1
Adjacency Locate in Main Lobby / Seating Area.
Floor Finish Stone
Wall Finish Paint & FWC
Base Stone
Ceiling Finish Painted GWB
Door Type
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Home-Style desk manned by volunteers with 2 visitor chairs with lockable storage.Assembly point for transportation scheduling.Collect flowers, dry cleaning deliveries, etc.
Drain, water, and power required for vending machines.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 306
Room Name Hall of Honor
Net Area 2500
Quantity 1
Adjacency Main Entrance, Reception Room, Concierge, News & Vending, and Main Street.
Floor Finish TBD
Wall Finish TBD
Base TBD
Ceiling Finish TBD
Door Type
Wall Construction Metal Stud w/GWB
Casework
Equipment Memorabilia display area (floor and wall units).Provide shelf space.Refer to Allowance 3.
Arch Notes Two-story exhibit space with overlook from above.Seating for 20 people.Recessed display cases and wall exhibits (TBD).Intended to display military memorabilia, including flags, uniforms, plaques, medals, photos, and other display materials.
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.Provide dedicated panel, and sufficient electrical lighting.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes: Provide special lighting for museum-quality display. Provide display lighting for wall-mounted exhibits. Consider UV effects on exhibits.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 307
Room Name Admissions Officer
Net Area 200
Quantity 1
Adjacency Adjacent to Move-In / Admissions Assistant and Resident Services Chief.Easy access to Director's MeetingRoom.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.Conference table with 4 chairs.
Arch Notes Shared among staff and residents.24-hour access for Residents.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Provide additional telephone and data capacity.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 314
Room Name Mail Room / Post Office
Net Area 950
Quantity 1
Adjacency Along public corridor.Adjacent to Shared Work / Copy Room and Bank.Easy access to Loading Dock.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Equipment ADA accessible and casework for full postal operations, including mailboxes.Follow USPS standards.
Arch Notes Manned by Contractor.Include area for USPS vending machines.24-hour access to post office boxes and vending.Include counter with roll-up door for USPS operator.Package drawer below with key."Knees-to-eyebrows" for mailboxes.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Provide special access control per USPS requirements.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 315
Room Name Bank
Net Area 400
Quantity 1
Adjacency Locate along public corridor.Adjacent to Shared Work / Copy Room and Post Office.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Glass DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Equipment and casework provided by Bank Tenant.
Arch Notes Manned by Bank Tenant.2 tellers plus office.ATM located outside the bank. Accessible after hours.The DBC will coordinate installation with Bank Tenant
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Run empty conduit from main telephone room for independent voice and data access.CCTV camera to be located for view of door to Bank.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 316
Room Name Security Counter / Eqpt. Room
Net Area 285
Quantity 1
Adjacency Locate at Main Entrance.Adjacent to Security Office and Interview Room.
Floor Finish Stone
Wall Finish Paint
Base Stone
Ceiling Finish ACT w/GWB Accents
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Security Desk
Equipment Monitors, panels, and CCTV equipment.Include Resident Monitoring System.
Arch Notes Subdivide into 2 rooms with glass partitions.Dedicated HVAC service with UPS system.Work station for 2 behind counter.Include recessed emergency medical cabinet (wired to security).
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Provide additional voice and data capacity.Include Resident Monitoring System.Include AED (electronically monitored by security).
Sprinkler FM 200
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power system as required by users and to support security equipment.Provide UPS system with 4-hour battery backup to support security equipment.Provide standby power for HVAC service
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 317
Room Name Security Office
Net Area 170
Quantity 1
Adjacency Security Counter / Equipment Room
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Wall mounting monitor display system with Flat screens TVs, monitors, and recording devices.No drawers on the base of manning system.
Arch Notes Accommodate "L" shaped furniture arrangements. Standard workstation with 4 chairs.
Voice ( Data ( ) Audio-Video ( ) Access Control Key OnlyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 322
Room Name Janitor's Closet (On Residential Units Levels)
Net Area 30
Quantity 19
Adjacency Trash Room.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood SGL
Wall Construction CMU
Casework Security Desk
Equipment Mop sink and rack.
Arch Notes Provide at least one Janitor's Closet per floor.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 323
Room Name Contractor / Employee Break Area
Net Area 500
Quantity 1
Adjacency Locate along public corridor.Adjacent to Housekeeping Contractor's Office
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Kitchenette equipment, including refrigerator.Employee lockers.
Arch Notes Provide separate Men's and Women's Locker Areas leading to Staff Toilets.Provide full kitchenette and tables with seating for 12.Provide half-height lockers for 24 in each locker area.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Do not locate CCTV cameras in Locker Areas.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 324
Room Name Contractor / Employee Toilets
Net Area 600
Quantity 1
Adjacency Contractor / Employee Break Room
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile Wet Wall
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.Provide 3 water closets (or equivalent) and 2 lavatories in each room.
Arch Notes Provide Men's and Women's Toilet Rooms.Provide 2 accessible showers in each Toilet Room.Provide automatic door openers.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 325
Room Name Public Toilet Rooms (On Main Level)
Net Area 3200
Quantity 1
Adjacency Locate along public corridor near major program areas.
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile Wet Wall
Base Ceramic
Ceiling Finish ACT w/GWB Accents
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Wood Base & Solid Surface Top
Equipment Provide complete stainless steel toilet accessories.Provide at least 32 accessible water closets and 16accessible lavatories.Provide automatic door openers at all Toilet Rooms
Arch Notes Provide Men's and Women's Toilet Rooms.Distribute throughout Mail Level , so that all entrances, exits, and gathering places are no more than 80 ft. from a public toilet room.Toilet rooms shall be ADA-UFAS compliant and accommodate BPV's.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 326
Room Name Ham Radio / Electronic Repair / Computer Shop
Net Area 400
Quantity 1
Adjacency Locate near Main Street.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Base & Top
Equipment Refer to Appendix C - Ham Radio Shop Information.Provide portable antennas and "Man-Pack" radios.
Arch Notes 4 computer workstations with seating and storage units.See Appendix C for more information about antenna requirements.Provide portable antennas and man pack radios to re-establish communication if fixed antennas fail.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Provide additional voice and data capacity.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power to accommodate Ham Radios that can connect to theFederal communication system in an emergency.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide minimal lighting on standby power to allow room to be used in an emergency.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 327
Room Name Wood Shop
Net Area 1500
Quantity 1
Adjacency Locate near Main Street.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Wood DBL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Woodworking benches with stools and storage units.Woodworking equipment to be determined.Include lighting for equipment.Flammable storage cabinet / locker.
Arch Notes Provide special ventilation and acoustical treatment.Include Service desk.Subdivide into small "Amateur " shop (300 - 400 SF with hand tools and benches) and larger "Power Tool"shop.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide exhaust system for collection and removal of saw dust.
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.Address power equipment for woodworking equipment.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 334
Room Name Fitness Equipment Area
Net Area 2500
Quantity 1
Adjacency Locate near Main Street and Vending.Adjacent to Exercise Classroom and Fitness Storage.
Floor Finish Anti Microbial Carpet
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Glass DBL
Wall Construction CMU w/GWB
Casework
Equipment Fitness equipment as required.Refer to Appendix C for a list of Recommended Equipment.Include recessed emergency medical cabinet (wired
Arch Notes Provide special ventilation and acoustical treatment.Rubber floor under major equipment.Provide wall mirrors and balanced bars.Refer to Appendix C for equipment list.Water fountain should be included.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 336
Room Name M & W Shower / Locker Rooms
Net Area 230
Quantity 2
Adjacency Fitness Equipment Room.
Floor Finish Rubber
Wall Finish Sanitary Wainscot
Base Ceramic
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction CMU w/GWB
Casework
Equipment Ceiling lift-track system ("voyager" style).Podiatric sink.Recumbent fast-fill tub, usable from ceiling or hydraulic lift.
Arch Notes No-wall shower (floor drain and rubber walls).Include 20 half-height lockers (no metal), benches, 4 showers (2 showers / gender), toilet, and sink. Showers and toilets should be separate from locker rooms. Showers to include a separate dressing area.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( x ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Emergency phone
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 337
Room Name Assisted Unisex Bathroom
Net Area 160
Quantity 1
Adjacency Fitness Center M & W Shower / Locker Room.
Floor Finish Seamless Vinyl
Wall Finish Sanitary Wainscot
Base Integral Coved Base
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Wood Base & Solid Surface Top
Equipment Accessible bathroom with sink, toilet, and safety tub (similar to Bathease).
Arch Notes Discreet entrance for private access.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide toilet exhaust in accordance with Code.
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( x ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 338
Room Name Exercise Classroom
Net Area 2000
Quantity 1
Adjacency Fitness Equipment Area and Fitness Storage.Near Vending Area.
Floor Finish Sprung Wood
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Glass DBL
Wall Construction CMU w/GWB
Casework
Equipment Exercise Floors Mats.
Arch Notes Low-impact exercises are typical. Provide movable partition to sub-divide classroom.Provide special ventilation and acoustical treatment.Include wall mirrors and balance bars.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 340
Room Name Multi-Purpose Activity Room
Net Area 3400
Quantity 1
Adjacency Located near Main Street.Adjacent to Dining Room.Near Prefunction, Outside Patio, and Exercise Classroom.
Floor Finish Marble Floor
Wall Finish Paint & FWC
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Wood DBL w/Side Lite
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Provide moveable partition between Multi-Purp Activity Room and Dining Room for expansion during major events w/soundproofing.Provide storage for tables, chairs, etc.
Arch Notes Hi-ceiling, square shape, column-free space with flat floor.Provide movable partition to sub-divide room into 2 spaces.Provide special ventilation and acoustical treatment,Small raised stage with ramp.Provide dance floor (size TBD)
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include movie projection system and adequate microphone equipment.Include emergency phone and AED (electronically monitored by security).Include recessed emergency medical cabinet (wired to security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power to allow room to be used in an emergency.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes: Provide lighting on standby power to allow room to be used in an emergency.Provide special theatrical lighting for stage area.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 341
Room Name Lounge
Net Area 1800
Quantity 1
Adjacency Locate along Main Street.Adjacent to Smokehouse / BBQ Equipment Storage , Outside Patio, Bowling, Multi-Purpose Activity Room and Dining Room.
Floor Finish Wood
Wall Finish Paint & FWC
Base Wood
Ceiling Finish ACT w/GWB Accents
Door Type Wood DBL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework Wood Base & Solid Surface Top
Equipment Bar equipment as required.Common kitchen and hood ventilation for grilling.Include recessed emergency medical cabinet (wired to security).
Arch Notes Provide bar tables and seating for 25 people.Provide special ventilation and acoustical treatment.Floor finish should be different at bar area.Include anti-fatigue mats behind bar.Include storage area as required.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Floor Drain and sink placed at bar service area.
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 342
Room Name Smokehouse / BBQ Equipment Storage
Net Area 150
Quantity 1
Adjacency Locate near Lounge, Game Room and Bowling.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Glass SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Include recessed emergency medical cabinet (wired to security).Provide pass-through window from the bar.Not directly attached to building.
Arch Notes Provide tables and seating for 12.Provide separate special ventilation and acoustical treatment.Available for staff and residents.Glass walls and ceiling fan (greenhouse type, outdoorfeeling).Provide fireplace.Exterior access desired.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide confinement ventilation system with 100% exhaust of space.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 344
Room Name Meditation Room
Net Area 600
Quantity 1
Adjacency Locate in quiet area near Main Street.
Floor Finish Carpet 36 oz
Wall Finish Paint & FWC
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood DBL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment 8 pews for 30 to 40 people.Lectern with microphone.
Arch Notes Provide special ventilation and acoustical treatment.Inter-faith services.Multi-purpose room for group settings.Quiet room.Provide "Open-Flame" vitrine.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 354
Room Name Bowling
Net Area 2750
Quantity 1
Adjacency Lounge, Smokehouse / BBQ Equipment Storage and Game Room.Near Vending.
Floor Finish Wood
Wall Finish Paint
Base Wood
Ceiling Finish 2 x 4 ACT
Door Type Glass DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Bowling equipment as required.
Arch Notes 4 lanes.End lane should be accessible for mobility impaired.Fully automatic system and scoring.This space should be isolated for sound control.Special humidity control.Include unisex accessible toilet room.
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 356
Room Name Hair Care / Salon
Net Area 260
Quantity 1
Adjacency Locate along Main Street.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Glass SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Hair Care Salon equipment provided by operator.Include 4 stations.
Arch Notes Space should be divided as follows: 240 SF for 4 stations and 20 SF for locked storage and shelving.Include handwashing station.Include hair washing station.Provide wall mirrors.Provide special ventilation.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.Provide sufficient power for hair dryers and equipment.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 357
Room Name Library + DVD Room
Net Area 2000
Quantity 1
Adjacency Locate along Main Street.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Glass DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment Main Desk
Arch Notes Provide library shelving for books.Tables and seating for 20 to 30.Provide small storage room (lockable) with shelving (10' x 10').
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Provide empty conduit from main switch room for independent voice and data access.CCTV camera to be located for view of door to Exchange PX.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Additional power for tenant equipment.Refrigerator on emergency power.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 359
Room Name Multi-Function Media Room
Net Area 1000
Quantity 1
Adjacency Locate along Main Street and Lounge.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Wood Base & Solid Surface Top
Equipment Projector, projection screen, and AV systems.
Arch Notes Provide offset theater-style seating for up to 100 people to watch movies, etc.Provide special ventilation and acoustical treatment.Wall treatment with wheelchair protection.
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.Provide additional power for AV equipment as required.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 360
Room Name Spiro's Canteen
Net Area 700
Quantity 1
Adjacency Locate along Main Street.
Floor Finish VCT
Wall Finish Sanitary Wainscott
Base Integral Coved Base"
Ceiling Finish 2 x 4 ACT
Door Type
Wall Construction Metal Stud w/Impact Res. GWB
Casework Wood Base & Solid Surface Top
Equipment Provided by vendor.
Arch Notes Provide 6 tables and seating for 20 to 25 people.Provide special ventilation and acoustical treatment.Self-service café.Open area.Late night operation.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Handwashing sink placed on countertop.Drain and water supply to beverage dispensing equipment (approx. 4 machines).
Voice ( x ) Data ( ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Provide additional power for beverage dispensing machines.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc): 10
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 361
Room Name Painting and Ceramics (Wet)
Net Area 600
Quantity 1
Adjacency Locate along Main Street.Adjacent to Crafts (Dry), Sewing Room, and Resident Art Display Room.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood DBL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework Wood Base & Solid Surface Top
Equipment Arts equipment as required.Provide separate room for kilns. (100 SF). Locate with special exhaust ventilation.Include 2 - 3 stations with hoods for localized table-
Arch Notes Provide a door to open directly to Crafts (Dry).Shelving for storing items.Tables and seating for 12.Provide 2 service sinks and worktop.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide 2 sinks with sano-trap.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.Provide additional power for electric kilns.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 362
Room Name Crafts (Dry)
Net Area 600
Quantity 1
Adjacency Locate along Main Street.Adjacent to Painting and Ceramics (Wet), Sewing Room, and Resident Art Display Room.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood DBL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework Wood Base & Solid Surface Top
Equipment Crafts equipment as required.
Arch Notes Provide a door to open directly to Arts (Wet).Shelving for storing items.Tables and seating for 20.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 363
Room Name Sewing Room
Net Area 600
Quantity 1
Adjacency Locate along Main Street.Adjacent to Painting and Ceramics (Wet), Crafts (Dry), and Resident Art Display Room.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood DBL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework Wood Base & Solid Surface Top
Equipment Sewing equipment as required.
Arch Notes Tables and seating for 12 with storage units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 364
Room Name Puzzle Room
Net Area 180
Quantity 1
Adjacency Assisted Living
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Tables and seating for 12 with storage units.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 369
Room Name Toilet Rooms
Net Area 400
Quantity 1
Adjacency Near to the Volunteer Home Room.
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile Wet Wall
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes Provide Men's and Women's Toilet Rooms.Provide automatic door openers.Provide 3 water closets (or equivalent) and 2 lavatories in each Toilet Room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 370
Room Name Contractor Services Representative / Janitorial Servi
Net Area 120
Quantity 1
Adjacency Housekeeping Contractor's Office
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 372
Room Name Prefunction
Net Area 1000
Quantity 1
Adjacency Locate along public corridor.Adjacent to Service Line.Easy access to Public Toilets.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type
Wall Construction Metal Stud w/GWB
Casework
Equipment Memorabilia display area (floor and wall units).
Arch Notes Provide seating for "people-watching".Open area.20 - 30 seats.Memorabilia displays included items from past, present, and future conflicts and AFRH history.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes: Provide lighting to allow for multiple room uses.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 373
Room Name Dining and Assisted Dining
Net Area 7700
Quantity 1
Adjacency Prefunction, Kitchen, Multi-Purpose Activity Room, Outside Patio, and Public Toilets.
Floor Finish VCT
Wall Finish Wainscott"
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Glass DBL
Wall Construction CMU w/GWB
Casework
Equipment Provide moveable partition between Dining Room and Multi-Purpose Activity Room for expansion during major events.Dining equipment as required.
Arch Notes Provide separate Assisted Dining Area with separate entrance and a separate service line.Estimated seating for 275 (28 SF / person). NO ROUND TABLES.Provide variety of seating (individuals, doubles, and groups of 6-12) with adjustable table heights.
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).Include recessed emergency medical cabinet (wired to security).Provide AV System for major events.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide minimal receptacles on standby power to allow room to be used in an emergency.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes: Provide l lighting on standby power to allow room to be used in an emergency.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 374
Room Name Service Line
Net Area 2000
Quantity 1
Adjacency Kitchen and Dining.
Floor Finish Sheet Vinyl
Wall Finish Paint
Base Integral Coved Base"
Ceiling Finish Painted GWB
Door Type
Wall Construction CMU w/GWB
Casework
Equipment Stainless steel service line equipment.
Arch Notes "Functionally accessible for older people."Secure sanitized areas from Dining Room for after-hours operation.ADA-Compliant.36-foot overall length (approx.).Half-height anti-fungal durable / washable hard surface.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power to allow for fully functional kitchen service.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching:
Lighting Notes: Provide lighting on standby power to allow for fully functional kitchen service.
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 376
Room Name Kitchen
Net Area 8000
Quantity 1
Adjacency Service Lines and Loading Dock.Provide direct connection to MS Service Line (maybe dedicated elevator) for food delivery and scullery service.
Floor Finish Sheet Vinyl
Wall Finish Sanitary Wainscot
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood DBL
Wall Construction CMU w/GWB
Casework Plam Wall Base & Top
Equipment Kitchen equipment as required - refer to Section K - Dining and Food Service.Refer to Appendix C - List of Existing Kitchen Equipment and Plan of Existing Kitchen.
Arch Notes Includes Offices, Cold Stores, Dry Stores, EmergencyStores, and Staff Lockers.Full-service common kitchen menus - refer to Appendix C for examples.Catering (10-300) up to 1 per week.7-10 day food storage.Serves 1,200 meals per day (3 servings).
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide dedicated kitchen make-up air and exhaust systems sized and configured in accordance with Code.
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide hand washing and service sinks as required.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power to allow for fully functional kitchen service.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide lighting on standby power to allow for fully functional kitchen service.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 377
Room Name Kitchen Staff Men's Toilet
Net Area 300
Quantity 1
Adjacency Kitchen
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction CMU w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes Provide 3 water closets (or equivalent) and 2 lavatories in each Toilet Room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 378
Room Name Kitchen Staff Women's Toilet
Net Area 300
Quantity 1
Adjacency Kitchen
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction CMU w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes Provide 3 water closets (or equivalent) and 2 lavatories in each Toilet Room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 379
Room Name Independent Living 1 Units
Net Area 450
Quantity 282
Adjacency See Adjacency Diagram for Typical Independent Living Level.
Floor Finish Anti Microbial Carpet
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Wood Wall Base & Solid Surface Top
Equipment Full kitchenette with sink and area for "mini" refrigerator and microwave oven.Include "lock boxes" for valuables (6" x 12" - Type TBD).
Arch Notes Includes full accessible bath with sink, toilet and shower.Provide rubber floor and "sanitary" walls in bathroom for wash down.Provide pull-down bars at toilet, and standard grab bars elsewhere as required.Provide connecting door for 10% of units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide fully-waterproofed floor in bathroom.Provide separate floor drains in shower and bathroom floor.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Provide 2 telephone outlets (on opposite walls) and 1 data connection with 2 data lines.Provide 1 emergency device in bathroom and 2 devices in living area connected to the Resident Monitoring System (including Wellness Center Check-In Button).
Sprinkler Quick Response Heads
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide one duplex outlet in each room on standby power circuit.Provide circuit for personal battery powered vehicle charging.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide indirect lighting in living area.Provide one permanently installed lighting fixture in the living unit and one permanently installed lighting fixture in the bathroom on standby power.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 380
Room Name IL1 Day Room / Lounge
Net Area 250
Quantity 12
Adjacency Elevator Lobby and Resident Corridor.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment
Arch Notes 1 unit serves 24 residents.Provide TV, couches and chairs, and 2 card tables with 4 chairs each.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Dry Pipe System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 381
Room Name IL1 Laundry Room
Net Area 100
Quantity 12
Adjacency Elevators, Janitor Closet, and Trash Room.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Commercial-grade Washer / Dryer and deep stackable front load. ADA-accessible sink.Provide Industrial-grade solid shelving.Warpool system for drying and "steaming" equipment
Arch Notes 1 Laundry Room per 24 residents.Include table for folding laundry, clothes rod, and 2 chairs.Provide special ventilation and acoustical treatment.Water temperature booster in laundry rooms for one of washer --controlled by staff.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide utility sink.Provide special oversized floor drain with gooseneck faucet to accommodate washer overflow.
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 382
Room Name IL1 Public Toilet Rooms (M & W)
Net Area 70
Quantity 24
Adjacency IL1 Day Room / Lounge and Independent Living Units.
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes Fully ADA accessible water closet and sink.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 401
Room Name WC Reception / Check In
Net Area 140
Quantity 1
Adjacency Locate along public corridor on Main Level.Adjacent to Waiting Area and Medical Records.Direct access to emergency vehicle drop-off.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Glass DBL
Wall Construction Metal Stud w/GWB
Casework Reception Desk
Equipment Provide standard hospital floor area wall bumpers with integral corner guards in waiting areas and corridors.Provide publication niche for magazine/brochure
Arch Notes Provide work surface with area to charge PDA's, etc.Accessible for Battery Powered Vehicles (BPV).NOTE: Internal corridors in wellness center are 8' wide typical.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 410
Room Name Exam Room
Net Area 120
Quantity 1
Adjacency WC Waiting Area
Floor Finish Seamless Non Glare
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Ptd Mtl Base & Wall w/solid surface top
Equipment Exam Room equipment (TBD).See Appendix C for Exam Room information.
Arch Notes Provide handwashing station, locked storage units, plus writing desk.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide handwashing sink.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Task lighting.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 411
Room Name Bariatric Exam Room
Net Area 120
Quantity 1
Adjacency Exam Room
Floor Finish Seamless Non Glare
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Ptd Mtl Base & Wall w/solid surface top
Equipment Bariatric Exam Room equipment (TBD).See Appendix C for Exam Room information.
Arch Notes Provide handwashing station, locked storage units, plus writing desk.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide handwashing sink.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Task lighting.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 412
Room Name Triage / Exam Room
Net Area 120
Quantity 1
Adjacency Exam RoomsClose to Waiting Room.
Floor Finish Seamless Non Glare
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Ptd Mtl Base & Wall w/solid surface top
Equipment Exam Room equipment as (TBD).Ceiling-mounted exam light.
Arch Notes Provide handwashing station, locked storage units, plus writing desk.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide handwashing sink.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 413
Room Name Phlebotomy / Exam Room
Net Area 120
Quantity 1
Adjacency WC Waiting Area
Floor Finish Seamless Vinyl
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Ptd Mtl Base & Wall w/solid surface top
Equipment Exam Room equipment (TBD).Special medical-type casework for Phlebotomy equipment.
Arch Notes Includes handwashing station, lockable storage units,plus writing desk.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide handwashing sink.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 414
Room Name Centrifuge Room
Net Area 70
Quantity 1
Adjacency Exam Room
Floor Finish Seamless Vinyl
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Ptd Mtl Base & Wall w/solid surface top
Equipment Undercounter refrigerator and handwashing sink.
Arch Notes Provide lockable door.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide handwashing sink.
Voice ( Data ( ) Audio-Video ( ) Access Control Key OnlyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 415
Room Name Podiatry / Exam Room
Net Area 150
Quantity 1
Adjacency WC Waiting Area
Floor Finish Seamless Non Glare
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Ptd Mtl Base & Wall w/solid surface top
Equipment Exam Room equipment (TBD), including Podiatric sink.
Arch Notes Includes handwashing station, lockable storage units,plus writing desk.Additional casework near Podiatric sink.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Includes handwashing station and podiatric sink with floor drain.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 416
Room Name WC Medication Distribution
Net Area 120
Quantity 1
Adjacency WC ReceptionEasy access from public corridor.
Floor Finish Seamless Vinyl
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Full-size refrigerator.
Arch Notes Locked, secure room.Provide handwashing station and locked storage unitsSpecial locked cabinets for narcotics and drugs.Include drop-off window
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide handwashing sink.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide standby power for refrigerators and freezers.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide standby power for lighting.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 417
Room Name Dental and Eye Clinic Waiting Area
Net Area 200
Quantity 1
Adjacency Reception, Dental Area, and Eye Clinic Area.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 421
Room Name Dental Chairs
Net Area 200
Quantity 3
Adjacency Dentist's Office and Dental Reception.
Floor Finish Seamless Non Glare
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Wood Dental Cabinetry"
Equipment Fixed dental equipment as required.See Appendix C - List of Medical Equipment for Dental Area.
Arch Notes Extra Room for chair, doctor, and BPV.Provide lockable storage cabinets.Provide small handwashing sink with counter space and drawers.Lots of indirect, color corrected lighting.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 422
Room Name Sterilization Room
Net Area 120
Quantity 1
Adjacency Dental Lab and Dentist's Office.
Floor Finish Seamless Non Glare
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Wood Dental Cabinetry"
Equipment
Arch Notes Sink large enough to drain.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 444
Room Name WC Staff Toilet
Net Area 70
Quantity 2
Adjacency WC Staff Offices
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile Wet Wall
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Provide complete stainless steel toilet accessories.
Arch Notes ADA accessible water closet and sink.1 Men assigned.1 Women assigned.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 445
Room Name Rehabilitation Services
Net Area 3000
Quantity 1
Adjacency Locate along public corridor.Adjacent to Wellness Center.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Glass DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment 1 treadmill, 2-3 stationary bikes, 1 parallel bars and steps. Hot pack station, 2 tables with massage mats1 small Jacuzzi (limbs), 1 Aquasizer, Paraffin hot wax, and fluido-therapy equipment.
Arch Notes Sub-divide into 2 Rehab Clinics (PT and OT). Provide one accessible unisex toilet room in each clinic.Provide ADL Bathroom with shower.Include 200 sf locked storage.Provide seating for 6-8.Ceiling lift-track system ("Voyager" style).
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 446
Room Name Rehab Spa / Bathing
Net Area 230
Quantity 1
Adjacency Rehabilitation Services
Floor Finish Rubber
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Ceiling lift-track system ("voyager" style).Podiatric sink.Recumbent, fast-fill tub, usable from ceiling or hydraulic lift.
Arch Notes No-wall shower (floor drain and sanitary walls).Provide pull-down "Lalido" bars at toilet, and standard grab bars elsewhere as required.Provide exterior window and appropriate window treatment for natural light.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( x ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 447
Room Name Rehab Storage
Net Area 200
Quantity 1
Adjacency Rehabilitation Services and Evaluation / Treatment Room.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 476
Room Name Assisted Living Units (AL)
Net Area 450
Quantity 60
Adjacency Refer to Assisted Living Unit Adjacency Diagram.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Full kitchenette with sink and area for "mini" refrigerator and microwave oven.Include "lock boxes" for valuables (6" x 12" - Type TBD).
Arch Notes Includes full accessible bath with sink, toilet and shower.Provide rubber floor and "sanitary" walls in bathroom for wash down.Provide pull-down bars at toilet, and standard grab bars elsewhere as required.Provide connecting door for 10% of units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide fully-waterproofed floor in bathroom.Provide separate floor drains in shower and bathroom floor.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Provide 2 telephone outlets (on opposite walls) and one data connection with 2 data linesProvide one emergency device in bathroom and 2 devices in living area connected to the Resident Monitoring System (including Wellness Center Check-In Button).
Sprinkler Quick Response Heads
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide one duplex outlet in each room on standby power circuit.Provide circuit for personal battery powered vehicle charging.Nurse Call System shall be on standby power.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide one permanently installed lighting fixture in the living unit and one permanently installed lighting fixture in the bathroom on standby power.Provide indirect lighting in living area.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 477
Room Name AL Home Base
Net Area 270
Quantity 2
Adjacency AL Main Entrance and Club Room
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Include copy machine, refrigerator, and Nurse Call System base unit."Home Free" system and other equipment as required by AFRH.
Arch Notes 1 unit serves 30 residents.Open nurses' station with lockable storage.Includes patient records storage in lateral files.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide handwashing sink.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Nurse call.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide multiple outlets for monitoring equipment.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 478
Room Name AL Club Room
Net Area 1080
Quantity 2
Adjacency AL Home Base
Floor Finish Carpet 36 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Glass DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Include recessed emergency medical cabinet (wired to security).
Arch Notes 1 Club Room per 30 residents.Provide lounge seating for 30 - 40 people.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Include Nurse Call device, emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 479
Room Name AL Activity Room
Net Area 340
Quantity 1
Adjacency AL Club Room, AL Nourishment Center, and AL Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Kitchenette with full-size refrigerator.
Arch Notes 1 Activity Room per 60 residents.Movable wall.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 480
Room Name AL Nourishment Center
Net Area 100
Quantity 1
Adjacency Locate along internal corridor near AL Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Kitchenette with full-size refrigerator and microwave.
Arch Notes 1 Nourishment Center for 30 residents.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 481
Room Name AL Spa / Bathing Room
Net Area 230
Quantity 2
Adjacency AL Home Base and Resident Corridor.
Floor Finish Rubber
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Ceiling lift-track system ("voyager" style).Podiatric sink.Recumbent, fast-fill tub, usable from ceiling or hydraulic lift.
Arch Notes 1 Spa / Bathing Rm per 30 residents.No-wall shower (floor drain and sanitary walls).Provide pull-down "Lalido" bars at toilet, and standard grab bars elsewhere as required.Provide exterior window and appropriate window treatment for natural light.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( x ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include Nurse Call device and emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 482
Room Name AL Public Toilet Room
Net Area 70
Quantity 2
Adjacency AL Home Base and Resident Corridor.
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes 1 Public Toilet Room per 30 residents.Provide accessible water closet and sink.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include Nurse Call device and emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 483
Room Name AL Clean Linen
Net Area 120
Quantity 2
Adjacency AL Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Provide Industrial-grade solid shelving.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 488
Room Name AL Medication Room
Net Area 120
Quantity 2
Adjacency AL Home Base
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Full-size refrigerator.
Arch Notes 1 Medication Room per 30 residents.Includes handwashing station and lockable storage units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Refrigerator and minimal lighting only.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 489
Room Name AL Laundry Room
Net Area 100
Quantity 2
Adjacency AL Home Base
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Base & Top
Equipment Commercial-grade Washer / Dryer and deep stackable front load. ADA-accessible sink.Provide Industrial-grade solid shelving.Warpool system for drying and "steaming" equipment
Arch Notes 1 Laundry Room per 30 residents.Include table for folding laundry, clothes rod, and 2 chairs.Provide special ventilation and acoustical treatment.Water temperature booster in laundry rooms for one of washer --controlled by staff.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide utility sink.Provide special floor drain to accommodate washer overflow.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 490
Room Name AL Staff Break Area
Net Area 150
Quantity 2
Adjacency AL Home Base
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Half-height lockers for 16 employees.Kitchenette with full-size refrigerator.
Arch Notes 1 Staff Break Area per 30 residents.Tables and chairs for 6.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 491
Room Name AL Staff Toilet
Net Area 70
Quantity 2
Adjacency AL Staff Break Area
Floor Finish Seamless Vinyl
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes ADA accessible water closet and sink.1 Men assigned.1 Women assigned.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc): 10
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 492
Room Name AL Clinical Supervisor
Net Area 200
Quantity 1
Adjacency AL Medical Provider, AL Medical Records Technician, AL Recreational Therapist, AL Dietician, and AL Social Worker.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 493
Room Name AL Medical Provider
Net Area 200
Quantity 1
Adjacency AL Clinical Supervisor, AL MedicalRecords Technician, AL Recreational Therapist, and AL Dietician.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Ptd Metal Base w/Solid Surface Top
Equipment
Arch Notes Seamless floor non-glare sheet, pre-finished for one step cleaning process.Conference table with 4 chairs.Serves as Exam Room.Exam Table and workstation.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Include handwashing station.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 494
Room Name AL Medical Records Technician
Net Area 120
Quantity 1
Adjacency Locate along public corridor.Adjacent to Assisted Living Unit Entrance.Close to AL Home Base (2)
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment Medical charts carousel (60 residents).
Arch Notes Secretarial workstation.Functions as reception area for Assisted Living Offices.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 498
Room Name Memory Support Units (MS)
Net Area 350
Quantity 24
Adjacency MS Home Base and Staff Work Areas.
Floor Finish Carpet 36 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Include "lock boxes" for valuables (6" x 12" - Type TBD).Provide Nurse Call device in living area and CCTV in hallways.
Arch Notes Includes full accessible bath with sink, toilet and shower.Provide rubber floor and "sanitary" walls in bathroom for wash down.Provide pull-down bars at toilet, and standard grab bars elsewhere as required.Provide connecting door for 10% of units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide fully-waterproofed floor in bathroom.Provide separate floor drains in shower and bathroom floor.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Provide 2 telephone outlets (on opposite walls) and one data connection with 2 data linesProvide one emergency device in bathroom and 2 devices in living area connected to the Resident Monitoring System (including Wellness Center Check-In Button).
Sprinkler Quick Response Heads
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide one duplex outlet in each room on standby power circuit.Provide circuit for personal battery powered vehicle charging.Nurse Call System shall be on standby power.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide one permanently installed lighting fixture in the living unit and one permanently installed lighting fixture in the bathroom on standby power.Provide indirect lighting in living area.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 499
Room Name MS Day Club
Net Area 5600
Quantity 1
Adjacency Locate on common corridor.Adjacent to MS Dining Room and Country Kitchen.Shared with LTC.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Piano, TV, and games.Provide storage closets for games and supplies.Include recessed emergency medical cabinet (wired to security).
Arch Notes Provide walkable space for MS residents.Include controlled Outside Area on same floor.Tables and chairs for 35 - 40 people seating in groups.Provide unisex toilet room and storage cabinets.Provide "cubby" space for individual storage (24).
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Include Nurse Call device, emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Electric locks to be conduited with emergency power.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 500
Room Name MS Secure Exterior Patio
Net Area 3500
Quantity 1
Adjacency MS Day Club
Floor Finish Stone
Wall Finish Paint
Base Stone
Ceiling Finish No Ceiling
Door Type
Wall Construction
Casework
Equipment Include enclosing fence and motion detection securityfeatures.Gazebo and / or trellis.
Arch Notes Provide level surfaces for group and individual activity with shade.Include edge details that reduce the potential to placea chair or climb the fence.May be used as an emergency exit into a safe area orefuge.Expect pet visitation to this area.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 60%
Special HVAC Requirements
No HVAC service required for this space.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include Motion Detector.Include emergency phone and Home Free system.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching:
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 501
Room Name MS Home Base
Net Area 270
Quantity 2
Adjacency MS Dining Room and Activity Room.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Include copy machine, refrigerator, and Nurse Call System base unit."Home Free" system and other equipment as required by AFRH.
Arch Notes 1 Home Base per 12 residents.Locate to maintain visual connection to all resident units.Included patient records storage in lateral files.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Nurse call.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide multiple outlets for monitoring equipment.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 502
Room Name MS Work Space
Net Area 45
Quantity 4
Adjacency Resident Corridor
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Base & Top
Equipment
Arch Notes 1 Work Space per 6 residents.Locate on resident corridor (no door).Include patient record storage (stand alone and movable).Lockable storage units.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Nurse call.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 508
Room Name MS Spa / Bathing Room
Net Area 230
Quantity 2
Adjacency MS Home Base and Resident Corridor.
Floor Finish Rubber
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish 2 x 2 ACT
Door Type Wood DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment Ceiling lift-track system ("voyager" style).Podiatric sink.Recumbent, fast-fill tub, usable from ceiling or hydraulic lift.
Arch Notes 1 Spa / Bathing Rm per 12 residents.No-wall shower (floor drain and sanitary walls).Provide pull-down "Lalido" bars at toilet, and standard grab bars elsewhere as required.Provide exterior window and appropriate window treatment for natural light.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( x ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include Nurse Call device and emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 509
Room Name MS Public Toilet Room
Net Area 70
Quantity 2
Adjacency MS Home Base and Resident Corridor.
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes 1 Public Toilet Room per 12 residents.Provide accessible water closet and sink.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include Nurse Call device and emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 510
Room Name MS Clean Linen
Net Area 120
Quantity 2
Adjacency MS Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Provide Industrial-grade solid shelving.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc): 10
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 514
Room Name MS Medication Room
Net Area 110
Quantity 2
Adjacency MS Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Full-size refrigerator.
Arch Notes 1 Medication Room per 12 residents.Includes handwashing station and lockable storage units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Refrigerator for medications.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Minimal lighting for emergency access to refrigerator.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 515
Room Name MS Laundry Room
Net Area 100
Quantity 2
Adjacency MS Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Commercial-grade Washer / Dryer and deep stackable front load. ADA-accessible sink.Provide Industrial-grade solid shelving.Warpool system for drying and "steaming" equipment
Arch Notes 1 Laundry Room per 12 residents.Include table for folding laundry, clothes rod, and 2 chairs.Provide special ventilation and acoustical treatment.Water temperature booster in laundry rooms for one of washer --controlled by staff.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide utility sink.Provide special floor drain to accommodate washer overflow.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 516
Room Name MS Staff Break Area
Net Area 150
Quantity 2
Adjacency MS Home Base
Floor Finish VCT
Wall Finish Sanitary Wainscot
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Half-height lockers for 16 employees.Kitchenette with full-size refrigerator.
Arch Notes 1 Staff Break Area per 30 residents.Tables and chairs for 6.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 601
Room Name Security Gate House
Net Area 150
Quantity 1
Adjacency Main Vehicular Site Entrance
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Metal SGL
Wall Construction CMU w/GWB
Casework Security Desk
Equipment Gates and retractable bollards at entrance roadways.Security equipment as required.
Arch Notes Includes accessible toilet room with toilet and sink.Provide glazing to control all security barriers.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 602
Room Name Exterior Recreational Terrace
Net Area 3000
Quantity 1
Adjacency Dining Room
Floor Finish Stone
Wall Finish Paint
Base Stone
Ceiling Finish No Ceiling
Door Type
Wall Construction
Casework
Equipment Grilles, serving line equipment, and work tables for outside events.
Arch Notes Moveable tables, chairs, benches, etc. to accommodate 100 to 350 people.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 60%
Special HVAC Requirements
No HVAC service required for this space.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide floor drains as required.
Voice ( x ) Data ( ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Provide emergency phone.Provide capacity for portable outdoor telephone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.Provide power for portable outdoor electrical appliances and equipment.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Armed Forces Retirement Home Design Build Services Request for Proposal Gulfport, Mississippi 21 May 2007
General Services Administration Public Buildings Service Southeast Sunbelt Region Real Estate Design and Construction
UNCLASSIFIED
OPTION 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 226
Room Name Main Trash Rooms
Net Area 300
Quantity 1
Adjacency Trash Chutes (from above).Easy access to Loading Dock.
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment Trash compactor and trash chute with fire-rated doorsat each level.Include smoke detectors in chute.
Arch Notes 1 Trash Room per 150 Units.The DBC shall describe how trash removal is addressed.May be located at First Floor or Wash-Out Level.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Self-cleaning trash chute will require water supply and drain.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Quick Response Heads
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 227
Room Name Trash Room (Includes all Living Units)
Net Area 50
Quantity 9
Adjacency Elevators, Janitor Closet, and Laundry Room.
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal SGL
Wall Construction CMU
Casework
Equipment Self-cleaning trash chute with fire-rated doors.Recycling bins provided by Housekeeping Contractor.
Arch Notes 1 trash room per 24 residents ( Independent Living).1 trash room per 30 residents (Assisted Living).1 trash room per 12 residents (Memory Support and Long Term Care).
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 322
Room Name Janitor's Closet (On Residential Units Levels)
Net Area 30
Quantity 9
Adjacency Trash Room.
Floor Finish
Wall Finish
Base
Ceiling Finish
Door Type
Wall Construction
Casework
Equipment Mop sink and rack.
Arch Notes Provide at least one Janitor's Closet per floor.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 379
Room Name IL1Independent Living Units
Net Area 450
Quantity 170
Adjacency See Adjacency Diagram for Typical Independent Living Level.
Floor Finish Anti Microbial Carpet
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Wood Wall Base & Solid Surface Top
Equipment Full kitchenette with sink and area for "mini" refrigerator and microwave oven.Include "lock boxes" for valuables (6" x 12" - Type TBD).
Arch Notes Includes full accessible bath with sink, toilet and shower.Provide rubber floor and "sanitary" walls in bathroom for wash down.Provide pull-down bars at toilet, and standard grab bars elsewhere as required.Provide connecting door for 10% of units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide fully-waterproofed floor in bathroom.Provide separate floor drains in shower and bathroom floor.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Provide 2 telephone outlets (on opposite walls) and 1 data connection with 2 data lines.Provide 1 emergency device in bathroom and 2 devices in living area connected to the Resident Monitoring System (including Wellness Center Check-In Button).
Sprinkler Quick Response Heads
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide one duplex outlet in each room on standby power circuit.Provide circuit for personal battery powered vehicle charging.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide indirect lighting in living area.Provide one permanently installed lighting fixture in the living unit and one permanently installed lighting fixture in the bathroom on standby power.
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 380
Room Name IL1 Day Room / Lounge
Net Area 250
Quantity 7
Adjacency Elevator Lobby and Resident Corridor.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment
Arch Notes 1 unit serves 24 residents.Provide TV, couches and chairs, and 2 card tables with 4 chairs each.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED.
Sprinkler Dry Pipe System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 381
Room Name IL1 Laundry Room
Net Area 100
Quantity 7
Adjacency Elevators, Janitor Closet, and Trash Room.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Commercial-grade Washer / Dryer and deep stockable front load. ADA-accessible sink.Provide Industrial-grade solid shelving.Warpool system for drying and "steaming" equipment
Arch Notes 1 Laundry Room per 24 residents.Include table for folding laundry, clothes rod, and 2 chairs.Provide special ventilation and acoustical treatment.Water temperature booster in laundry rooms for one of washer --controlled by staff.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide utility sink.Provide special oversized floor drain with gooseneck faucet to accommodate washer overflow.
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 382
Room Name IL1 Public Toilet Rooms (M & W)
Net Area 70
Quantity 14
Adjacency Day Room / Lounge and Independent Living Units.
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes Fully ADA accessible water closet and sink.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 523
Room Name Long-Term Care Units
Net Area 350
Quantity 24
Adjacency LTC Home Base and Staff Work Areas
Floor Finish Carpet 36 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Same as Memory Support Unit.Not Kitchenette.
Arch Notes Provide at least one Bariatric room with larger bed, ceiling lift track, and larger entry and bathroom doors.Provide connecting door between units for 10% of rooms.Ceiling structure in unit shall support ceiling lifts ("Voyage" style).
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Medical gases are not required in the Long Term Units.Provide fully-waterproofed floor in bathroom.Provide separate floor drains in shower and bathroom floor.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Provide 2 telephone outlets (on opposite walls) and one data connection with 2 data linesProvide one emergency device in bathroom and 2 devices in living area connected to the Resident Monitoring System (including Wellness Center Check-In Button).
Sprinkler Quick Response Heads
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide one duplex outlet in each room on standby power circuit.Provide circuit for personal battery powered vehicle charging.Nurse Call System shall be on standby power.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide one permanently installed lighting fixture in the living unit and one permanently installed lighting fixture in the bathroom on standby power.Provide indirect lighting in living area.
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 524
Room Name LTC Secure Exterior Patio
Net Area 3500
Quantity 1
Adjacency LTC Home Base and LTC Day / Visitor Room.
Floor Finish Stone
Wall Finish Paint
Base Stone
Ceiling Finish No Ceiling
Door Type
Wall Construction
Casework
Equipment Include enclosing fence and motion detection securityfeatures.Gazebo and / or trellis.
Arch Notes Provide level surfaces for group and individual activity with shade.Include edge details that reduce the potential to placea chair or climb the fence.May be used as an emergency exit into a safe area orefugeExpect pet visitation to this area.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 532
Room Name LTC Spa / Bathing Room
Net Area 230
Quantity 2
Adjacency LTC Home Base and Resident Corridor.
Floor Finish Rubber
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish 2 x 2 ACT
Door Type Wood DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment Ceiling lift-track system ("voyager" style).Podiatric sink.Recumbent, fast-fill tub, usable from ceiling or hydraulic lift.
Arch Notes 1 Spa / Bathing Rm per 12 residents.No-wall shower (floor drain and sanitary walls).Provide pull-down "Lalido" bars at toilet, and standard grab bars elsewhere as required.Provide exterior window and appropriate window treatment for natural light.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( x ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include Nurse Call device and emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 533
Room Name LTC Nourishment Center
Net Area 100
Quantity 1
Adjacency LTC Home Base
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Kitchenette with full-size refrigerator, microwave, and ice machine.
Arch Notes Tables and seating for 4.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power for refrigerator and kitchenette.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide lighting on standby power.
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 534
Room Name LTC Workstation
Net Area 80
Quantity 1
Adjacency Locate along public corridor near Long Term Care Unit Entrance.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Secretarial workstation.Functions as reception area for Long Term Care Offices.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 534
Room Name LTC Public Toilet Room
Net Area 70
Quantity 2
Adjacency
Floor Finish Seamless Vinyl
Wall Finish Paint
Base Integral Coved Base"
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes 1 Public Toilet Room per 12 residents.Provide accessible water closet and sink.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include Nurse Call device and emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 535
Room Name LTC Clean Linen
Net Area 120
Quantity 2
Adjacency LTC Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Provide Industrial-grade solid shelving.
Arch Notes 1 Clean Supply Room per 12 residents.Storage for "full" and "empty" containers, 8-12 "E" tanks.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 539
Room Name LTC Medication Room
Net Area 110
Quantity 2
Adjacency LTC Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Base & Top
Equipment Full-size refrigerator.
Arch Notes 1 Medication Room per 12 Residents.Includes handwashing station and lockable storage units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Refrigerator for medications.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Minimal lighting for emergency access to refrigerator.
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 540
Room Name LTC Laundry Room
Net Area 100
Quantity 2
Adjacency LTC Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Commercial-grade Washer / Dryer and deep stockable front load. ADA-accessible sink.Provide Industrial-grade solid shelving.Warpool system for drying and "steaming" equipment
Arch Notes 1 Laundry Room per 24 residents.Include table for folding laundry, clothes rod, and 2 chairs.Provide special ventilation and acoustical treatment.Water temperature booster in laundry rooms for one of washer --controlled by staff.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide utility sink.Provide special floor drain to accommodate washer overflow.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 541
Room Name LTC Lift Storage
Net Area 100
Quantity 1
Adjacency Internal corridor.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Provide Industrial-grade solid shelving.
Arch Notes Provide storage for five wheelchairs, two lifts (3' x 3'), and general storage for other equipment.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Armed Forces Retirement Home Design Build Services Request for Proposal Gulfport, Mississippi 21 May 2007
General Services Administration Public Buildings Service Southeast Sunbelt Region Real Estate Design and Construction
UNCLASSIFIED
OPTION 2
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 701
Room Name Pool(s) and Deck
Net Area
Quantity 1
Adjacency General Swimming Area.
Floor Finish TBD
Wall Finish
Base None
Ceiling Finish No Ceiling
Door Type
Wall Construction
Casework
Equipment Standard pool equipment including ladders, ropes, and life guard station.
Arch Notes Provide 25 meter lap pool with 8 lanes.Chaise lounges, tables, and chairs for 40-50 people.Provide "Cool Deck" finish surrounding pool.
Temp F (Winter)
Temp F (Summer)
% R Humidity (Winter)
% R Humidity (Summer)
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Provide emergency phone.
Sprinkler
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.Provide connections for food service equipment.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Underwater pool lighting and decorative fixtures for nighttime use.
Per IESNA
May 21, 2007AFRH Gulport RFP Option 2
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 702
Room Name Dressing Area
Net Area 750
Quantity 2
Adjacency Pool(s) and Deck
Floor Finish Rubber
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Metal SGL
Wall Construction CMU
Casework
Equipment
Arch Notes Provide Men's and Women's locker / toilet rooms.Provide 40 -50 half-height lockers (no metal) and benches.Include 2 showers, 3 water closets (or equivalent) and2 sinks in each room.Provide direct outside access to pool.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 60%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Provide dry pipe system if located in outbuilding.
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 2
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 703
Room Name Sunning Area / Outdoor Terrace
Net Area
Quantity 1
Adjacency Pool(s) and Deck
Floor Finish TBD
Wall Finish
Base TBD
Ceiling Finish
Door Type
Wall Construction
Casework
Equipment
Arch Notes Provide "Cool Deck" floor finish.Chaise lounges, tables, and chairs for 20-25 people.